HomeMy WebLinkAbout3258 GREY HAWK CT; ; FA060034; Permit7/15/24, 4:51 PM FA060034 Permit Data
City of Carlsbad
Fire Alarm Permit
Job Address: 3258 GREY HAWK CT
Permit Type: FALARM
Parcel No: 2210150200
Lot #: 0
Reference No.:
Permit No: FA060034
Status: ISSUED
Applied 6/8/2006
Approved: 6/8/2006
Issued: 6/8/2006
PC #: Inspector:
Project Title: GREY HAWK BUSINESS CTR FIRE ALARM PLAN CHECK &
INSPECTIONS
Applicant:
JMG SECURITY
17150 NEWHOPE
SUITE 109
800-900-4564 EXT.316
Owner:
GREYHAWK ASSOCIATES
C/O RUDY BALDONI
949 S COAST DR #600
COSTA MESA CA
Fees ($) Add'I Fees ($) Total ($) Balance ($)
60 0 60 0
about:blank 1/1
Fire Alarm System
Record of Completion
OF
Name of Protected Property: Greyhawk Business Park, Lot 5 Building "W-X-Y"
Address: 3254, 3256 & 3258 Greyhawk Court, Carsibad, CA. 92009.
Representative of Protected Property. (name! telephone):
Authority Having Jurisdiction: CARLSBAD SAFETY CENTER
Address/Phone Number: 2560 Orion Way, Carslbad, CA. 92010, tel 760) 931-2141.
1. Types of System or Service
NFPA 72, Chapter 3 Local
If alarm is transmitted to location(s) off premises, list where received:
Q NFPA 72, Chapter 3 Emergency Voice/Alarm Service
Quantity of voice/alarm channels: Single: Multiple:
Quantity of speakers installed: Quantity of speaker zones:
Quantity of telephones or telephone jacks included in system:
NFPA 72 Chapter 4 Auxiliary
Indicate type of connection:
Local energy: Shunt: Parallel telephone:
Location and telephone number for receipt of signals:
Q NFPA 72 Chapter 4 Remote Station
Alarm:
Supervisory:
NFPA 72, Chapter 4 Proprietary
If alarms are retransmitted to public fire service communications center or others, indicate location and
telephone number
Of the organization receiving alarm:
Indicate how alarm is retransmitted:
NFPA 72, Chapter 4- Central Station
The Prime Contractor: DBA National Monitoring Center (NMC).
Central Station Location: 26800 Laguna Hills Drive, Suite 250. Aliso Viejo, CA. 92656
Means of transmission of signals from the protected premises to the central station:
Digital alarm communicator
Means of transmission of alarms to the public fire service communications center:
Central Station Operators telephone call
System location: 26800 Laguna Hills Drive, Suite 250. Aliso Viejo, CA. 92656
Organization Name Representative Name Telephone
Installer JMG SECURITY SYSTEMS Mike Trenblay 714-545-8882
Supplier JMG SECURITY SYSTEMS Mike Trenblay 714-545-8882
Service Organization .JMG SECURITY SYSTEMS Mike Trenblay 714-545-8882
Location of Record (As-Built) Drawings: At Premises
Location of Owners Manuals: At Premises
Location of Test Reports: At Premises
0 0' i A contract dated '1 , for test and inspection n accordance with NFPA standard(s) No.(s) NFPA 72, dated
1999, is in effect.
2. Record of System Installation
(Fill out after installation is complete and wiring checked for opens, shorts, ground faults, and improper
branching, but prior to conducting operational acceptance tests.)
This system has been installed in accordance with the NFPA standards as listed below, was inspected by
r on / 1- I - -' includes the devices listed below and has been in service
since
E1 NFPA 72, Chapters ® 6 ® (circle all that apply)
[l NFPA 70, National Electrical Code, Article 760
I1 Manufacturer's Instructions
Other (specify):
Signed: Date:_________________________________
Organization:
3. Record of System Operation
All operational features and functions of this system were tested by _r Ak on
/1 I- O , and found to be operating properly in accordance with the requirements of
E?l NFPA 72, Chapters ® t2 6 ® (circle all that apply)
l?.l NFPA 70, National Electrical Code, Article 760
El Manufacturer's Instructions
o Other (specify):
Signed: Date:________________________________
Organization:
4. Alarm-Initiating Devices and Circuits (use blanks to indicate quantity of devices)
MANUAL
1 Manual Station 0 Non-coded Q Coded, Activating I Transmitters
Combination Manual Fire Alarm and Guard's Tour Coded Stations.
AUTOMATIC
Coverage: Minimum Code Required
LSmoke Detector 0 Ion 0 Photo
- Duct Detector 0 Ion 0 Photo
- Heat Detector 0 FT 0 RR FT/RR RC
1 Sprinkler Waterflow Switch Z Noncoded U Coded, Activating 2 Transmitter
- other (list):
5. Supervisory Signal Initiating Devices and Circuits (use blanks to indicate quantity of devices.)
GUARD'S TOUR
N/A Coded Stations
NIA Non-coded Stations, Activating Transmitters
2
3
11
(C) NIA Compulsory Guard Tour System Comprised of Transmitter Stations and Intermediate Stations
NOTE: Combination devices recorded under 4(b) and 5(a).
SPRINKLER SYSTEM
- Coded Valve Supervisory Signaling Attachments
1 Valve Supervisory Switch, Activating I Transmitter
El Building Temperature Points
(C) El Site Water Temperature Points
Site Water Supply Level Points
ELECTRIC FIRE PUMP
Q Fire Pump Power
Fire Pump Running
El Phase Reversal
ENGINE-DRIVEN FIRE PUMP
El Selector in Auto Position
(I) U Engine or Control Panel Trouble
Ci) El Fire Pump running
ENGINE-DRIVEN GENERATOR
(k) El Selector in Auto Position
(I) El Control Panel Trouble
El Transfer Switches
El Engine Running
Other Supervisory function(s) (specify):
6. ALARM NOTIFICATION APPLIANCES AND CIRCUITS
Quantity of indicating appliances connected to the systems: 1
Types and quantities of alarm indicating appliances installed:
_Bell 10 Inch
- Speakers
IHorns
_Chimes
- Other:
(t) P Visual Signals Type::STROBE El with audible El w/o audible
(g) 1 Local Annunciator
7. SIGNALING LINE CIRCUITS
Quantity and Style (see NFPA 72, Table 3-6) of signaling line circuits connected to a system:
Quantity: 1 Style: 4
8. SYSTEM POWER SUPPLIES
(a) Primary (Main): Nominal Voltage: 120 VAC Current Rating: 20 AMPS
Overcurrent Protection: Type: BREAKER , Current Rating: 20 AMPS
Location: AT MAIN ELECTRICAL BREAKER PANEL
(b) Secondary (Standby):
Storage Battery Amp-Hour Rating: 7 A
v' Calculated capacity to drive system, in hours 24 Hrs. [:1 60 Hrs.
N/A Engine-driven generator dedicated to fire alarm systems
Location of fuel storage: N/A
(c) Emergency or Stand-by System used as a backup to Primary Power Supply, instead of using a Secondary
Power Supply:
N/A Emergency System described in NFPA 70, Article 700
N/A Legally Required Standby System described in NFPA 70, Article 701
N/A Optional Standby System described in NFPA 70, Article 702, which also meets the performance
requirements of Article 700 or 701
9. SYSTEM SOFTWARE
Operating System Software Revision Level(s) NIA
Application Software Revision Level(s) N/A
Revision Completed by: N/A
10. COMMENTS:
(signed) for the Central Station or Alarm Company
(title) (date)
Frequency of routine tests and inspections, if other than in accordance with the referenced NFPA standard(s)
System deviations from the referenced NFPA standard(s) are: NONE
(signed) for Cdntral Station orfPiService Company (title) (date)
(signed) Representative o Atfth9(kty-h1&ing Jurisdiction ( (title) (d te)
4