HomeMy WebLinkAbout5857 OWENS AVE; ; FA990014; Permit7/30/25, 7:32 AM
Job Address:
Permit Type:
Parcel No:
Lot#:
Reference No.:
PC#:
Project Title:
Applicant:
about blank
Fees($)
183
FA990014 Permit Data
City of Carlsbad
Fire Alarm Permit
Permit No: FA990014
5857 OWENS AV Status:
FALARM Applied
2120923200 Approved:
0
Issued:
Inspector:
CARLSBAD AIRPORT CTR #1
Add'I Fees ($)
0
Owner:
Total($)
183
ISSUED
10/27/1999
Balance($)
0
1/1
City of Carlsbad 98302
Fire Depanment • Bureau of Prevention
Plan Review: Requirements Category: Alarm System
Date of Report: Wednesday, November 3, 1999 Reviewed by:. __ {;_.;M~_~ __ l_--__
Contact Name JJJ Enterprises
Address 533 Vinewood ------------------
City, State Escondido CA 92025
Bldg. Dept No. CB98-2739 Planning No.
Job Name Carlsbad Airport Ctr
Job Address 5857 Owens ~~~~--------------Ste. or Bldg. No. ____ _
~ Approved • The item you have submitted for review has been approved. The approval is
based on plans; information and/or specifications provided in your submittal;
therefore any changes to these items after this date, including field modifica-
tions, must be reviewed by this office to insure continued conformance with
applicable codes. Please review carefully all comments attached, as failure
to comply with instructions in this report can result in suspension of permit to
construct or install improvements.
D Disapproved -Please see the attached report of deficiencies. Please make corrections to
plans or specifications necessary to indicate compliance with applicable
codes and standards. Submit corrected plans and/or specifications to this
office for review.
For Fire Department Use Only
Review 1st. __ _ 2ndc._ __ 3rd, __ _
Other Agency ID
CFD Job#_--=-98=3=0=2 __ File# ___ _
2560 Orion Way • Carlsbad, California 92008 • (619} 931-2121
FIRE ALARM • SECURITY • LOW VOLTAGE SYSTEMS
CARLSBAD AIRPORT CENTER #1
5857 OWENS A VENUE, CARLSBAD, CA 92008
FIRE ALARM SYSTEM
(_
CARLSBAD AIRPORT CENTER #1
5857 OWENS A VENUE, CARLSBAD, CA 92008
FIRE ALARM SYSTEM
BILL OF MATERIALS
NOTIFIER AFP-200 FIRE ALARM CONTROL PANEL
CSFM# 7165-0028:164
NOTIFIER LCD-80 ANNUNCIATOR PANEL
CSFM# 7120-0028: 156
NOTIFIER BGX-I0lL MANUAL PULL STATION
CSFM# 7150-0028:003
NOTIFIER NBG-IOW MANUAL PULL STATION
CSFM# 7150-0028:139
NOTIFIER CPX-551 INTELLIGENT SMOKE DETECTOR/BX-SOI BASE
CSFM# 7271-0028: 149/7300-0028: 173
NOTIFIER SDX-551 INTELLIGENT PHOTO. SMOKE DET./BX-501 BASE
CSFM# 7172-0028: 148/7300-0028: I 73
SYSTEM SENSOR P2415/75K IScd. WEATHERPROOF HORN/STROBE
SYSTEM SENSOR P2475K 75cd. WEATHERPROOF HORN/STROBE
SYSTEM SENSOR P24 l IOK I IOcd. WEATHERPROOF HORN/STROBE
CSFM# 7125-1209:182
SYSTEM SENSORP2415 IScd. HORN/STROBE
CSFM# 7135-1209:173
SYSTEM SENSOR S2415 IScd. STROBE
CSFM# 7125-1209:174
SYSTEM SENSOR DH400ACDCP DUCT DETECTORS BY OTHERS
CSFM# 3240-1209: 155
* ONLY cur SHEETS ARE PROVIDED BY JJJ ENTERPRISES.
(._
GENERAL
The AFP-200 is a compact, cost-effective, intelligent fire
alarm control with a capacity of 301 individually identified
and controlled points and an extensive list of powerful
features. The AFP-200 provides capabilities that exceed
most large intelligent systems, at a cost comparable to
conventional control panels.
FEATURES
198 intelligent device capacity (99 analog detectors and
99 monitor/control modules). Style 4, 6, or 7.
Overall 301 point capability (198 intelligent points, 4
programmable NAC circuits, 99 programmable relays).
Network ready (reference NOTI •FIRE• NET-and NAM-
232 catalog sheets for more information).
Intelligent features:
v' Manual sensitivity adjustment.
v' Day/Night automatic sensitivity adjustment.
v' Drift compensation (U.S. Patent Pending) meets UL
requirements as a calibrated test instrument.
v' Auto detector test (meets NFPA 72).
v' Maintenance alert (two separate algorithms).
v' Pre-alarm (AWACS™ U. S. Patent Pending).
v' Activate local sounder base on pre-alarm.
v' LED blink control for sleeping areas.
v' Automatic device type check.
Releasing features:
v' Four independent hazards.
v' Sophisticated cross-zone (three options)
v' Delay timer and Discharge timers (adjustable).
v' Abort (four options).
Optional DACT, with AC fail delay.
LCD-80 remote display/control.
ACS annunciators (EIA-485), including LDM custom.
Printer interface (80 column and 40 column printers).
5.0 A usable regulated output power, plus 3.0 A expander.
80 character LCD display, backlit.
Real time clock, with European format option.
History file with 650 event capacity in nonvolatile memory.
Includes non-erasable shadow history.
Waterflow or supervisory selection per point.
Alarm Verification selection per point, with tally.
Walk Test reports 2 devices set to same address.
Positive Alarm Sequence (PAS) Presignal per NFPA 72.
Silence inhibit and Auto Silence timer options.
March time/temporal/California code for bell circuits.
Field-programmable on panel or on PC, with user-defined
passwords, plus Autoprogram feature.
UL-listed modem interface allows remote/off-site system
integration.
NOTl•FIRE•NET™ is a trademark of NOTIFIER, 1994.
August 13, 1997
AFP-200
Analog Fire Panel
Software Release 2
A-102
Section: Intelligent Fire Alarm Control Panels
®@19,.~~-~
S635 CS 118 for secunty) •
U.S. Coast Guard
161.002/23/1 I California State Fire Marshal
7165-0028:164
The AFP-200
16.125" H x 14.5" W X 5.5" D
94/00004
MMX-2 two-wire detector interface provides compatibility
with many non-NOTIFIER detectors for retrofit applica-
tions (consult factory for latest compatibility listings).
Dual rate charger for up to 90 hours of standby power.
Two-Stage option for bell circuits (Canada).
Tornado Warning activates different Notification Circuit
code.
Non-alarm points for lower priority functions.
Remote ACK/Silence/Reset/Drill via MMX modules.
Automatic time control functions, with holiday exceptions.
Rapid poll algorithm for manual stations. Responds in < 2
seconds.
Operates with untwisted, unshielded wire (up to 1000 feet)
for retrofit applications (U. S. Patent 5, 210, 523).
UL listed for Fire Signaling per Standard 864 & NFPA 72.
UL listed for Burglary applications per Standard 1076.
UL listed for Releasing perNFPA 12, 12A, 128, 13, 15, 16.
UL listed for Critical Process Monitoring.
FM approved for Agent Release and Preaction/Deluge.
Approved for marine applications by U.S. Coast Guard
and Lloyd's Register of shipping.
This document is not intended to be used for installation purposes. We try to keep our
product information up•lo-date and accurate. We cannot cover all specific applications or
anticipate all requirements. A11 specifications are subject to change without notice. For
more information, contact NOTIFIER. Phone: (203) 484•7161 FAX: (203) 484•7118
IS0-9001
Engineering and Manufacturing
Quality System Certified to
International Standard ISO-900t @) N OTI Fl ER• 12 Clintonville Road, Northrord, Connecticut 06472 Made In the U.S.A.
ON•3783 -Page 1 of 4
SYSTEM BLOCK DIAGRAM
NOTl•FIRE•NET
Optional Network Interface via the NAM-232
SLC Intelligent Loop
_ __ 198 devices
SDX-551 CPX-551 FDX-551 --------------BGX-101L
EIA-485 99 software zones
MMX-1 t
IDC
AFP-200
Four standard
Notification or
Releasing
circuits.
Full Alpha
keyboard for
menu-driven
programming.
5 ampere
regulated
power supply.
Voltmeter/
Ammeter
Option.
Page 2 of 4 -DN-3783
===
RS-232 1 ■1111~
4 Notification or
Release Circuits
PRN-4 Printer
EIA-232 Interface for CRT,
printer, or PC computer.
ACM--SR
Relay
Control
CRT-2
12 AH batteries.
Up to 90 hours standby power.
ACM/AEM-16AT
LED Annunciator
LDM--32
Custom Graphics
EtA-485 loop for
LCD or LED
annunciators.
SLC loop.
Up to 198 devices
on a single pair
of wires.
Slot for
optional
module.
80 character backlit
LCD display.
{'•
CMX-2
+ IAC
' ·, ' ' ""}'
9
(_
l.
AWACS TM Advance Warning Addressable Combustion Sensing (U.S. Patent Pending)
SMOKE OBSCURATION
% per foot
3% ACTION
Shut off power
ALERT
Warning at panel
of possible fire to equipment monitored
by this detector
ALARM
Evacuate building
and call fire department
2%
1%
PREAlM SMOKE(PHOTOJ
FLOOR 3 EQUIP RACK 5
AlERT: 0.22'11, 1.40%
11 :25 P 12/25/93 D66
TIME
PREAlM SMOKE( PHOTO)
FlOOR 3 EQUIP RACK 5
ACTION: 0.51'11, 1.40'11,
11:36 P 12/25/93 066
AlARM: SMOKE(PHOTOJ
FLOOR 3 EQUIP RACK
FIRE DEPT CAlLEO
11 :59 P 12/25/93
ALERT and ACTION levels are completely adjustable in the field to suit the cleanliness and stability of the environment.
ALARM levels are field adjustable to one of 3 levels within the UL permitted range. ACTION levels latch and may be
used to perform control functions. ALERT levels self-restore and may be used to activate a local sounder base before
general ALARM evacuation.
FIELD PROGRAMMING -3 WAYS
1. AUTO-PROGRAM
The AFP-200 identifies all devices that are connected,
determines the type of device, and loads default values
(general alarm) into non-volatile memory. This is com-
pleted in less than 30 seconds.
2. ON-LINE EDIT
While still providing fire protection, the AFP-200 program
may be completely edited from the front keypad. Menu
trees permit easy change of any parameter without refer-
ral to the programming manual. Recall, increment and edit
function speeds entry of alphanumeric labels. New pro-
gram check routine catches common errors.
3. OFF-LINE PC
The complete AFP-200 program may be created in
an off-line PC compatible computer, then loaded
into the AFP-200 EIA-232 port. The program may
also be off-loaded to a PC at any time. High speed
data transfer completes upload or download in less
than 1 minute. The PC program may also be used
to access remote AFP-200 systems over dial-up
phone lines, providing detail status information and
history file search/sort.
AUTOPROGRAM
PLEASE WAIT
0= CLR 1 =AUTO 2 = POINT
3 = PASSWD 4 = MESSAGE
5 = ZONES 6 = SPL ZONES
7 = SYS 8 = CHECK
ON-3783 -Page 3 of 4
c..
(.
(_
AGENCY LISTINGS AND APPROVALS
See page 1 for listing agencies and file numbers. These
listings and approvals apply to the basic AFP-200 control
panel. In some cases, certain modules may not be listed
by certain approval agencies, or listing may be in process.
Consult factory for latest listing status.
SPECIFICATIONS
Primary Input power, 120 VAC, 50/60 Hz, 3.0 Amps.
Total Internal 24 VDC Power-5.0 A (total shared power).
o' High Ripple Regulated Power -1.5 A (suitable for
EIA-485 devices, except ACM-SR) -1.0 A max.
standby.
o' Non-resettable Power -500 mA.
o' 4-wire Smoke Detector Power -500 mA.
o' Four built-In Notification Circuits
• NAC Circuit 1 -2.25 A
• NAC Circuits 2-4 -2.25 A (shared total)
Note: with optional AVPS Power Supply NAC circuits 3 &
4 are expanded to 3.0 A (8.(J A total power).
Battery charger range: 7 AH -17 AH.
Charge high rate: 29.1 V. Float Rate: 27.0 V.
• Relay contact rating: 2.0 A @ 30 VDC.
SYSTEM CAPACITY
Total programmable Input/output points: 301
Intelligent Detectors: 99
Addressable monitor/control modules: 99
Programmable NAG (bell) circuits In panel: 4
Programmable software zones: 99
Programmable remote relay/annunciator points: 99
LCD-80 annunciators per system: 4
ACS annunciators per system: 10
CONTROLS AND INDICATORS
6 LED Indicators: AC Power; Fire Alarm; Pre-Alarm; Su-
pervisory/Security; Alarm Silenced; System Trouble.
21 Membrane Switch Controls: Acknowledge/Step; Si-
lence; Evacuate; System Reset; 12 key Alpha pad; 4
cursor keys; Enter.
LCD Display: 80 characters (4 X 20) with long-life LED
backlight.
COMPATIBLE INTELLIGENT DEVICES
Model
CPX-551
CPX-751
SDX-551
SDX-751
SDX-551TH
FDX-551
FDX-551R
BX-501
B710LP
B501BH
DHX-501
DHX-502
MMX•1
MMX-2
MMX-101
CMX-2
BGX-101L
IS0-X
Description
Ionization Smoke Detector.
Low Profile Ionization Detector.
Photoelectric Smoke Detector.
low Profile Photoelectric detector.
Photoelectric with thermal element.
Fixed Thermal (Heat) Sensor.
Fixed and Rate-of-Rise thermal sensor.
Detector Base, high profile.
Detector Base, low profile.
Sounder Base.
Duct Housing with Alarm relay.
Duct Housing without Alarm relay.
Monitor Module.
Two wire detector monitor module.
Miniature Monitor Module.
Control Module
Manual Fire Alarm Station, Addressable.
Isolator Module.
Page 4 of 4 -DN-3783
WonlPerfecte Is a registered trademark
of Won!Perfect Corporation.
COMPATIBLE DEVICES, EIA-232 Port
Model
PRN-4
VS4095IS2
CRT-2
NAM-232
DescrlpUon
80 column printer.
Printer, 40 column, 24 V. Mounted In exter-
nal backbox (Order from Keltron, Inc.).
Video display terminal.
Network Interface Module to NOTI •FIRE•
NET wire or fiber models.
COMPATIBLE DEVICES, RS-485 Port
Model DescrlpUon (see catalog sheets)
ACS Serles Remote Serial Annunciator/Control systems.
LCD-80 Remote LCD display.
LDM Serles Remote custom graphic driver modules.
ACM-SR Remote relay module. 8 Form-C relays.
NIB-96 Network Interface Board.
RPT -485 Series Repeater, Isolator and/or fiber optic
modem.
UDACT Universal Digital Communicator.
PRODUCT LINE INFORMATION
Model DescrlpUon
BEAFP-200G -Basic AFP-200 equipment kit. Includes
main board with display and keypad, door, hardware
and manual. Backbox (SBB-4X or SBB-4XR) ordered
separately.
BEAFP-200R -Same as BEAFP-200G, but Includes a red
door.
BEAFP-200GE -Same as BEAFP-200G but 230 VAC.
BEAFP-200RE -Same as BEAFP-200R but 230 VAC.
SBB-4X -AFP-200 Backbox (no door), gray.
SBB-4XR -AFP-200 Backbox (no door), red.
CAB-AM -Heavy duty outer enclosure. Required for ma-
rine agency approved applications.
4XTM -Plug-In Transmitter Module. Provides municipal
box & remote station connection.
RTM-8 -Plug-in Relay Transmitter Module. Provides 8
Form-C relays, plus transmitter.
4XMM -AmmeterNoltrneter.
TR-4XG -Gray Trim Ring for semi-flush mounting (TR-
4XR for red).
DP-AFP200 -Full length dead front panel (required for
Canadian Applications).
PS-1270 -Battery, 12 volt, 7.0 AH, {two required).
PS-12120 -Battery, 12 volt, 12.0 AH, (two required).
PS-12170 -Battery, 12 volt, 17.0 AH (two required).
AVPS-24 -3.0 A Expansion supply (requires BB-17).
BB-17 -Battery box, required for PS-12170, or If AVPS-24
Is used.
911AC -Digital Alarm Communicator/Transmitter.
PK-200 -Programming kit for PC. Includes diskette,
cable, and Instructions.
ROM-AFP200SP -Spanish language kit. Includes soft-
ware IC, manual and labels.
ARCHITECTURAL/
ENGINEERING SPECIFICATIONS
Complete specifications are available on 3.5" (1.44 mbyte)
IBM compatible diskette, In WordPerfect & ASCII formats.
(_
LISTING No.
CATEGORY:
US,EE:
DESIGN:
INSTALLATION:
MARKING:
APPROVAL:
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING DIVISION
LISTING SERVICE
7165-0028:164
Control Units (Non High-Rise)
Notifier, 12 Clintonville Road, Northford CT 06472-1001
Contact: Larry Flood (203) 484-1200
LISTING EXPIRES
JUNE 30, 1999
Page 1 of 1
Model AFP-200 fire alarm control unit. Local, auxiliary, remote station (PPUJ,
proprietary (PPUJ and central station (PPUJ. Also suitable for releasing device
service. Refer to listee's data sheet for additional detailed product description
and operational considerations. System components:
4XTM
RTM-8
DP-AFP200
TR-4XG
MMX-1, -101
ISO-X
N-ELR
CRT-2
VS4095/5
CMX-1
BB-17
AVPS-24
NAM-232
4XMM
Transmitter Module
Relay Module
Dress Panel
Trim Ring
Monitor Module
Loop Isolator Module
EOL Resistors
Terminal with Keyboard
Printer
Control Module
Battery Box
Power Supply
Network Adapter Module
Meter Module
In accordance with listee's printed installation instructions, NFPA 72, applicable
codes & ordinances and in a manner acceptable to the authority having
jurisdiction.
Listec's name, model number, electrical rating and UL label.
Listed as fire alarm control unit for use with separately listed compatible
initiating and indicating devices. Suitable for central station (PPUJ service
when used with separately listed compatible DACT.
*This control unit can generate the distinctive three-pulse Temporal Pattern Fire
Alarm Evacuation Signal (for total evacuation) in accordance with NFPA 72,
1993 Edition. Refer to manufacturer's Installation Manual for details.
THIS LISTING IS BASED UPON TECHNICAL DATA SUBMnTEO BY THE APPLIC"A.NT. CSFM FIRE ENG!NEERING STAFF HAS REVIEWED
THE TEST RESULT!t AND/OR OTHER DATA BUT DOES NOT MAKE AN IN0.5:PENDENT VERIRCATION OF ANY CL.AIMS. THIS LISTING Ito NOT
AN EtlOORSEMENl' OR RECOMME'.NDATION OF THE ITEM U~. THIS LISTING SHOULD NOT BE USED TO VERIFY CORRECT OPERATIONAL
REQUIREMENTS OR INSTALLATION CRrT£RIA. REFER TO USTEE'S DATA SHEE''f, INSTALLATION INSTRUCTIONS AND/OR OTHER
SUIT ABLE INFORMATION SOURCES.
(_ DATEfssuED:MAY12,1998 APPROVED BY:
EFFECTIVE ISSUE DATE TO EXPIRATION DATE
PROGRAM COORDINATOR
(_
l.
GENERAL
The LCD-80 is an BO-character, backlit LCD display annuncia-
tor for the NOTIFIERAM2020, AFP1010, AFP-400, AFP-300,
AFP-200, System 5000, and System 500 fire alarm control
panels. Up to 32 LCD-80s may be connected onto the two-
wire EIA-4B5 port. The LCD-80 has two basic modes of op-
eration, "Terminal" and "ACS" mode.
COMMON FEATURES
BO-character Liquid Crystal Display (20 characters x 4 lines),
backlighted.
Control switches for System Acknowledge, Signal Silence
and System Reset.
Time and date display field.
Enable Key switch and phone Jack options.
Can be remotely located up to 6,000 feet from the control
panel.
Local piezo sounder with alarm/trouble resound.
Flush/surface/panel mount option.
Optional RPT -485 repeater increases the distance and num-
ber of LCD-80s in a system (see RPT-485 catalog sheet).
Optional transmission over fiber optics (see RPT-485 cata-
log sheet).
ACS MODE
When operated in "ACS" mode, the LCD-BO provides a re-
mote or local digital display and printer interface for the Sys-
tem 5000 and System 500. For the AM2020, AFP1010, AFP-
400, AFP-300, and AFP-200, the LCD-80 provides a vectored
annunciation capability. Individual devices/zones can be in-
staller-defined to only display and print at specific locations
(EXAMPLE: A maintenance office receives only non-alarm
point activations. These inputs could be sump pump on, high
water, backup AHU on, low temperature in freezer, etc.).
Alarm/trouble count.
Custom "normal" message.
European option: first alarm/last alarm/alarm count.
Field-programmable messages from CRT or PC-compatible
computer (PK-LCD-BO Programming Kil required).
EIA-4B5 interface: up to 32 per system.
Printer output port: RS-232, compatible with PRN Series
printers.
Field-programmable messages in nonvolatile memory in two
options: 128 points, 40 character labels; or 256 points, 20
character labels.
Internal nonvolatile clock for time and date.
AM2020, AFP1010, AFP-400, and AFP-300 "vectored"
printer capability.
Can be mounted in a System 5000 cabinet module position.
TERMINAL MODE
(AM2020, AFP1010, AFP-400, AFP-300,
and AFP-200 ONL )')
In Terminal Mode, the LCD-80 mimics the AM2020, AFP1010,
AFP-400, AFP-300 and AFP-200 displays. Up to 32 LCD-80s
May 1, 1998 D-120
LCD-80
Liquid Crystal Display
Section: Annunciator Control Systems
@@<&> MEA
S635 CS100 QV7A0.AY
290-91-E
289-91-E
I California
State Fire Marshal
7120-0028:156
LCD-BO
(shown with ABF-1 flush backbox)
can annunciate and provide remote reset, acknowledge, and
silence of the control panel from remote locations. The DIA-
1010 and DIA-2020 (Display Interface) include a terminal mode
driver port for LCD-B0s In terminal mode. The Terminal mode
port is standard on the AFP-400, AFP-300, and AFP-200 main
PC/CPU boards.
Displays device type Identifiers.
Device and zone custom alpha labels.
Time/date and Device address.
May operate in addition lo CRT.
No programming necessary. LCD-80 displays time, date,
and custom messages received from AM2020, AFP1010,
AFP-400, AFP-300, or AFP-200.
This document Is not Intended to be used for installation purposes. We try to keep our
product lnfonnation up-~ate and accurate. We cannot cover all specific applications or
anticipate all requirements. All specifications are subject to change without noUce. For
more Information, contact NOTIFIER. Phone: (203) 484-7161 FAX; (203) 484-7118
ISO-9001
Engineering and Manufacturing
Quality System Certified to
lntematlonal Standard IS0-9001 @) N OTI Fl ER• 12 Clintonville Road, Northford, Connecticut 06472 Made tn the U.S.A.
DN-3198 -Page 1 of2
(_
L
The LCD-80 in ACS Mode LCD-80 is 8-1/4"(20.96cm) high, 4-3/8" (11.11
cm) wide, and 1-3/4" (4.45 cm) deep.
EIA-232, 4 wires
50 feet maximum
PRN Printer
Up to 32 LCD-80s may be used on one EIA-
485 circuit.
NOTE: Must have sufficient regulated 24 volt
power. Certain NOTIFIER systems may have
limits to the amount ofLCD-80s with ACK/STEP,
Signal Silence, and Reset switches.
----------
LCD-80 mounts with any CHS-4 chassis slot.
The LCD-80 may display all System 5000 cir-
cuits. Alternately, It may display up to 192
AIM-200 points and two rows of modules. r. "o"''""
System 5000 with
panel-mounted LDC-80 6,000 feet maximum total wire length.
EIA-485 EIA-485 EIA-485 (2 wires) (2 wires) (2 wires)
24VDC 24VDC 24VDC
(2 wires) (2 wires) (2 wires)
CJ CJ CJ
DD DD DD
DD DD DD
DD DD DD TO TO TO =□ PRN LCD-80 PRN LCD-80 PRN LCD-80 =□ PRINTER PRINTER PRINTER =□
System 5000, System 500, AM2020,
AFP1010, AFP-400, or AFP-300
=□ =□ =□
The LCD-80 in Terminal Mode
Tenninal Mode
EIA-485
(2 wires)
24VDC (2 wires)
6,000 feet maximum wire length
between each LCD-80
D CJ D
DD DD DD
DD DD DD
DD DD DD
LCD-80 LCD-80 LCD-BO
ABF-1 D -The ABF-1D is a
semi-flush-mount backbox for
the NOTIFIER LCD-80 Series
Annunciator. The ABF-1D
mounts one LCD-80. It in-
cludes an attractive smoked-
glass door with NOTIFIER
keylock.
EIA-232 ! AM2020, Terminal Mode EIA-485 return (2 wires)
PrinterPort AFP1010, ~---------------~
Dimensions, BOX only:
9-15/16" (25.24 cm) high,
4-5/8" (11.75 cm) wide,
2-1/2" (6.35 cm) deep.
Dimensions, DOOR only:
10.713" (27.21 cm) high,
AFP-400, AFP-300, Up to 32 LCD-80s may be used in a continuous 4·
or AFP-200 wire loop (verify sufficient 24 VDC available). .
PRN Printer Each may have ACK/STEP, SIGNAL SILENCE,
and SYSTEM RESET switches.
Displays all analog, addressable points.
No programming required for LCD-80s.
6" (15.24 cm) wide,
0.75" (1.9 cm) deep.
RELATED OPTIONS
PK-LCD-110
CCM-1
ABF-1D
ADP-4
ABF-1
ABS-1T
AKS-1
APJ-1
PRN Serles
RPT-485W
RPT-485F
Off-Line Programming Kil for LCD-80. Allows PC programming messages when the LCD-80 Is used in the ACS
mode.
Converter Module. Requined for tenminal mode operation on older AM2020s or AFP1010s that do not Include
the DIA-2020 or DIA-1010 Display Interlaces. Also required for AM2020 and AFP1010 systems which require
a CRT with keyboard. Uses one ICA-4 chassis slot or two CHS-4 chassis slots.
Semi-flush box with alternative smoked11lass door, any keylock.
Annunciator Dress Plate. Allows panel mounting of up to four LCD-80 modules In a CAB-X3 Series cabinet.
Annunciator Flush Box. 9-15/16" (25.24 cm) high, 4-5/8" (11.75 cm) wide, and 2-1/2" (6.35 cm) deep. Order
AKS-1 key-switch and APJ-1 phone Jack If desired. Can also be mounted In ABF-2 or ABF-4 annunciator
backboxes.
Deep Surface Backbox (mounts one LCD-80).
Keyswllch lo enable/disable controls when mounted In ABF or ABS-1T.
Annunciator Phone Jack. Mounts to ABF flush box or ABS-1T.
BO-Column Serial Printer.
EIA-485 Wire Repeater. Increases wire distance between LCD-IIOs.
EIA-485 Fiber-Optics Repeater. Increases distance and converts EIA-485 wire lo fiber-optics.
Page2of2 -Dlh'l198
(
l
L
L
LISTING No.
CATEGORY:
LISTEE:
DESIGN:
INSTALLATION:
MARKING:
APPROVAL:
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING DIVISION
LISTING SERVICE
LISTING EXPIRES
JUNE 30, 1999
7120-0028: 156 Page 1 of 1
Annunciators
Notifier, 12 Clintonville Rd., Northford CT 06472-1653
Contact: Larry Flood (203) 484-1200
Model ACS annunciator control system. Refer to listee's data sheet for
additional detailed product description and operational considerations. Unit
consists of the following modules:
ACM-16AT
AEM-16AT
AEM-32A, ACM-32A
AFM-16AT, AFM-32A, AFM-16A
ABM-16AT, ABM-32A
ABS-1, ABS-2
ABF-1, -10•, -2, -20•, -4
ADP-4
AKS-1
LCD-80, -80TM •
LDM-32
LDM-E32
LDM-R32
ACM-8R
Control Module
Expander Module
Control Module
Fixed Module
Blank Module
Enclosures (Surfoce)
Enclosures (Flush)
Dress Panel
Key Switch
Control Panel
Lamp Driver Module
Lamp Driver Expander
Lamp Driver Expander (Relay)
Mappable Relay Control Module
In accordance with listee's printed installation instructions, applicable codes &
ordinances and in manner acceptable to the authority having jurisdiction.
Listee's name, product number, electrical rating and UL label.
Listed as an annunciator system when used in conjunction with separatelr listed
compatible fire alarm control units.
•Rov. 02-13-96
THIS LISTING IS BASED UPON TECHNICAL DATA SUBMITrED BY THE APPLICANT. CSFM FIRE ENGINEERING STAFF HAS
R~VIEWED TH!:: TEST RESULTS AND/OR OTHER DAT.4. BUT DOES NOT MAKE AN INDEPENDENT VERIFiCAT,ON OF ANY CLAIMS.
THIS LISTING 10 NOT AN ENDORSEMENT OR RECOMMENDATION OF THE ITEM LISTED. THIS LISTING SHOULD NOT BE USED TO
VERIFY CORRECT OPERATIONAL REQUIREMENTS OR INSTALLATION CRITERIA. REFER TO USTEE'S DATA SHEET, INSTALLATION
INSTRUCTIONS ANO/OR OTHER SUITABLE INFORMATION SOURCES.
(._ DATE lssuc:D: APRIL 24, 1998 A!"PROVED BY: ~ EFFECTIVE ISSUE DATE TO EXPIRATION 0.A.TE
PROGRAM COORDINATOR
L
l.
L
GENERAL
The BGX-101 L is an addressable manual pull station with a
key-lock reset feature. It provides the AM2020, AFP1010,
AFP-400, AFP-200, and System 5000 (equipped with an
AIM-200 module) with one addressable alarm initiating in-
put.
FEATURES
Within ADA 5 lb. pull force when used without break-tube
(models manufactured after 10-1-96, identified by an ®
under station spring).
Highly visible.
Easily operated (dual-action).
Attractive shape and textured finish.
Semi-flush, mounts to a standard single-gang (2.125" mini-
mum depth), double-gang, or 4" square electrical box.
Operates with or without a crush tube.
Handle latches in down position to clearly indicate the
station has been operated.
Key reset.
Screw terminals for easy connection to SLC Loop Channel.
Optional trim ring.
Meets UL 38, Standard for Manually Actuated Signaling
Boxes.
CONSTRUCTION
Shell, door, and handle are molded of durable LEXAN® (or
polycarbonate equivalent) with a textured finish.
16 gauge steel back plate.
OPERATION
Pulling the handle down causes it to latch in the down posi-
tion. The handle is restored manually by using a mechani-
cal key which allows the top of the case to pivot forward and
the spring-loaded handle to return to its normal position.
The case can then be pivoted back to its normal position
and secured with the key.
Each manual station, on command from the control panel,
sends data to the panel representing the state of the manual
switch. Two rotary decimal switches allow two-digit address
setting.
LEXAN® is a registered trademark of GE Plastics, a subsidiary of
General Electric Company.
November 14, 1996 H-130
BGX-101L
Addressable Manual Pull Station
Section: lntelligenVAddressable Devices
m.\ -\!.Y 0V4A5.AY
S692 (AFP-200)
ADA
0W6A2.AY
(AM-2020/AFP1010)
I California
State Fire
Marshal
7150-0028:003
93/00141
The BGX-101L
Addressable Manual Pull Station
PRODUCT LINE INFORMATION
Model Description
BGX-101L Standard unit. Dual action. Works with, or
without, a fiber crush-tube. Includes key
locking feature.
BG-TR Optional trim ring. 6-1/2" High, 5-1/8" Wide,
5/32" Deep.
SB-10 Surface backbox.
This document is not intended to be used for installation purposes. We try to keep our
product information up-to-date and accurate. We cannot cover all specific applications
or anticipate all requirements. All specifications are subject to change without notice.
For more information, contact NOTIFIER. Phone: (203) 484•7161 FAX: (203) 484-7118
@) N OTI Fl ER• 12 Clintonville Road, Northford, Connecticut 06472
ISO-9001
Engineering and Manufacturing
Quality System Certified to
International Standard IS0-9001 Made in the U.S.A.
DN-3189 -Page 1 of 2
(.
L
INSTALLATION
The BGX-101L will mount semi-flush into a single-gang,
double-gang, or standard 4" square electrical outlet box,
or will surface mount Into the Model SB-1 0 surface backbox.
If the BGX-101l Is being semi-flush mounted, then the
optional trim ring (BG-TR) may be used. The BG-TR Is
usually needed for semi-flush mounting with 4" or double-
gang boxes (not with single-gang boxes).
ELECTRICAL SPECIFICATIONS
Normal operating voltage: 24 voe.
Maximum SLC loop voltage: 28.0 VDC.
Maximum SLC loop current 230 µA.
ARCHITECTURAL/
ENGINEERINGSPECIFICATIONS
Manual Fire Alarm Stations shall be addressable, fiber
break-tube (or-non-fiber break-tube) type, equipment with
a key operated test-reset lock In order that they may be
tested, and so designed that after emergency operation,
they cannot be restored to normal except by using a key.
An operated station shall automatically cond"rtion Itself so
as to be visually detected, as operated, at a minimum
distance of one hundred feet, front or side.
Manual stations shall connect with two wires to one of the
control panel SLC loops. The manual station shall, on
command from the control panel, send data to the panel
representing the state of the manual switch. Manual sta-
tions shall provide two-digit address setting by use of ro-
tary decimal switches.
Manual stations shall be constructed of LEXAN® (or poly-
carbonate equivalent) with clearly visible operating Instruc-
tions provided on the cover. The word FIRE shall appear
on the front of the stations in raised letters, 1.75 Inches or
larger. Stations shall be suitable for surface mounting on
matching backbox, or semi-flush mounting on a standard
single-gang, double-gang box, or 4 inch square box, and
shall be installed within the limits defined by the Ameri-
cans with Disabilities Act (ADA) dependent on manual
station accessibility or per local requirements. Manual
stations shall be Underwriters Laboratories Inc. listed.
Page 2 of2 -DN-3189
• •
Rotary
Decimal
Switches
The SLC Loop Channel ~
• • • r
The BGX-101L (back view)
View from
TOP
View from
SIDE
L
l.
L
LISTING No.
CATEGORY:
LISTEE:
DESIGN:
INSTALLATION:
MARKING:
APPROVAL:
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTlbN
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING DIVISION
LISTING SERVICE
7150-0028:003
Boxes/Pull Stations
Notifier, 12 Clintonville Rd·., Northford CT 06472-1653
Contact: Lawrence Flood (203) 484-1200
LISTING EXPIRES
JUNE 30, 1999
Page 1 of 1
Models BG, BG-1-2W, BGX-101L, BNG, BNGl-SP, BRG, MG and MS series.
Models BG-1-2W and BG-1-2-WTS are suitable for outdoor use. Refer to listee's
data sheet for detailed product description and operational considerations.
In accordance with listee's printed installation instructions, applicable codes
and ordinances and in a manner acceptable to the authority having
jurisdiction.
Listee's name, model number, electrical rating anc;f UL label.
Listed as manual pull stations for use with separately listed compatible control
units.
Rev. 11-30-93
THIS LISTING IS BASED UPON TECHNICAL DATA SUBM!TTED BY THE APPLICANT. CSFM FIRE ENGINEERING STAFF HAS
Re:VJEWED THE T~T RESULTS AND/OR OlHER DATA BUT DOES NOT MAKE AN INDEPENDENT VERIFICATION OF ANY CLAIMS.
THIS USl"ING IS NOT 4.N EHDORSE::MENT OR RECOMMENDATION OF THE' ITEM LISTED, THIS LISTING SHOULD NOT BE USED TO
VERIFY CORRECT OPERATIONAL REQUIREMENTS OR INSTALLATION CRITERIA. REFER TO USTEE'.'S DATA SHEET. INSTALLATION
INSTRUCTIONS ANO/OR OTHER SUITABLE INFORMATION SOURCES.
DATE ISSUED: APRIL 23, 1998
EFFECTIVE ISSUE DA':E TO EXPIRATION DATE
APPROVED By:
DEPUTY BEN HO
PROGRAM COORDINATOR
(_
(_
(__
GENERAL
The NOTIFIER model NBG-10 is a non-coded, dual action,
manual alarm station.
FEATURES
Within ADA 5 lb. pull force when used without break-tube
(models manufactured after 10-1-96, identified by an@
under station spring).
Highly visible (red color with white lettering).
Easily operated.
Attractive shape and textured finish.
Semi-flush mounting on a standard single-gang electrical
box.
Operates with or without a break tube.
Handle latches in down position to clearly indicate that
the station has been operated.
Optional lock with key.
Optional N.O. contact for auxiliary functions.
Optional pre-signal circuit may be used for pre-signal or
Institutional Applications.
Spanish (FUEGO) version.
Meets UL 38, Standard for Manually Activated Signaling
Boxes.
APPLICATIONS
Use to provide a convenient means to manually initiate a fire
alarm.
CONSTRUCTION
Shell, door, and handle are molded of red colored LEXAN®
(or polycarbonate equivalent) with a textured finish and
white lettering.
Back plate made of 16 gauge steel.
Switch contacts are normally open.
INSTALLATION
For semi-flush mounting, attach directly to a standard single-
gang electrical box. Terminal block with screws allows quick
installation.
OPERATION
Pulling the handle down causes it to latch in the down posi-
tion and to close the normally-open switch. The handle is
restored manually by unscrewing the alien-head screw so
the top of the case can pivot forward, allowing the spring-
loaded handle to return to its normal position. The case can
then be pivoted back to its normal position and secured with
the alien-head screw.
The NBG-10L utilizes a mechanical key instead of the alien-
head screw.
The NBG-10 PfT has a normally-open auxiliary switch which
is closed by rotating a key clockwise {the key is non-remov-
able in this position).
March 30, 1998 1-420
NBG-10 Series
Non-Coded
Manual Fire Alarm Station
Section: Conventional Initiating Devices
®<8>1 S635 1 R0A0.AY
(except NBG-10SP)
ADA
SPECIFICATIONS
Physical:
NB!:MO SB.:10
Height: 5.50" 5.50"
Width: 4.13" 4.13"
Depth: 1.38" 1.38"
California State Fire Marshal
7150-0028:139
WE'.,10
6.00"
4.69"
2.00"
Electrical: Current Capacity: 3 Amps@ 125 VAC.
LEXAN® is a registered trademark. of GE Plastics, a subsidiary
of General Electric Company.
This document is not intended to be used for installation purposes. We try to keep our
product information up-lo-date and accurate. We cannot cover all specific applications or
anticipate all requirements. All specifications are subject to change without notice. For
more information, contact NOTIFIER. Phone: (203) 484-7161 FAX: (203) 484-7118
1SO-9001
Engineering and Manufacturing
Quality System Certified to
International Standard 1S0-9001 ~ N OTI Fl ER• 12 Clintonville Road, Northford, Connecticut 06472 Made in the U.S.A.
DN-1668 -Page 1 of 2
L
L
c..
WIRING OF
STANDARD
UNIT:
NBG-10
TO
CONTROL PANEL +---1---_J
DETECTOR
LOOP OUTPUT
TO NEXT DEVICE
ORE.LR.
Additional Switch
Included With Models:
NBG-10A
NBG-10T
TO
TERMINAL BLOCK
FOR N.O. CONTACT +------'
FOR AUXILIARY
FUNCTIONS
Additional Switch (Key Operated)
Included With Model:
NBG-10P
TO
TERMINAL BLOCK
FOR TEST, OR TO
PRESIGNAL CIRCUIT....._ ___ _,
(KEY OPERATED)
Paga2of2 -DN-1668
PRODUCT LINE INFORMATION
Model
NBG-10
Description
Standard unit. Dual action. Works with, or without,
a crush tube. Includes a terminal block with screws
for fast and easy wiring.
NBG-10A Standard unit plus an auxiliary N.O. switch to pro-
vide annunciator contacts.
NBG-10T Standard unit (NBG-10) with key test features.
NBG-10P Standard unit plus N.O. switch for pre-signal opera-
tion.
NBG-10L Standard unit plus key-Jocking feature.
NBG-10WP Standard unit plus weatherproofing. Includes sur-
face weatherproof box (NWP-10).
NBG-10S P Spanish version of standard unit Dual action. Works
with or without crush tube. Includes terminal block.
WP-10 Weatherproof surface backbox for NBG-10WP.
SB-10
BG-TR
Surface backbox for all NBG-10 models.
Optional trim ring.
ARCHITECTURAL/
ENGINEERING SPECIFICATIONS
Manual Are Alarm Stations shall be non-code, break-tube ( or non-
crush tube) type, with a key-operated test-reset Jock in order that
they may be tested, and so designed that after actual Emergency
Operation, they cannot be restored to normal except by use of a
key. An operated station shall automatically condition itself so as
to be visually detected, as operated, at a minimum distance of
one hundred feet, front or side. Manual stations shall be con-
structed of red colored LEXAN® with clearly visible operating in-
structions provided on the cover. The word FIRE shall appear on
the front of the stations In raised white letters, 1. 75 inches or larger.
Stations shall be suitable for surface mounting on matching
backbox, or semi-flush mounting on a standard single-gang box,
and shall be Installed within the limits defined by the Americans
with Disabilities Act (ADA) dependent on manual station accessi-
bility or per local requirements. Manual Stations shall be Under-
writers Laboratories listed.
F RE'
'j I ruSHl'J lj 1 THE rJ
I --I
I PULL V oo:.r.
foOTlrn:n
4-1/B"
L(104.8l mm} v;e;!,;,m
i.-.-...-., -----------' 1.3f8• , 1·1/8· ,
' (34.ll} i (28.6) ' "-lfonal
: 1-318" • s""r1 '1349) i / u ace ~-r
I ,
i..... 2-314•--
I (69.9mm} :
5-1/2" View from
(139.7 mm} SIDE _l
(
(
l
(_
LISTING No.
CATEGORY:
LISTEE:
DESIGN:
INSTALLATION:
MARKING:
APPROVAL:
XLF:
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING -BUILDING MATERIALS LISTING PROGRAM
LISTI NG SERVICE
7150-0028:139
Pull Station/Boxes
listing Expires
June 30, 2000
Page 1 of 1
Notifier, A Pittway Company, One Fire-Lite Place, Northford CT 06472-1653
Contact: Larry Flood (203) 484-1200
Models NBG-10, NBG-10A, NBG-10N, NBG-10L, NBG-10P, NBG-10T, NBG-
10WP, NBG-10SP, NAR-10 AND N-ARA-10 manual pull stations. Units are
intended for indoor use and are intended to be mounted to a listed •outlet box or
Model SB-10 surface back boxes. Model NBG-1 OWP is suitable for outdoor use.
Refer to listee's data sheet for additional detailed product description and
operational considerations.
In accordance with listee's printed installation instructions, applicable codes &
ordinances and in a manner acceptable to the authority having jurisdiction.
Listee's name, model number and UL label.
Listed as manual pull stations for use with separately listed compatible fire -alarm
control units.
7150-0075:103
"Rev. 04-03-97
This listing is based upon ll!chnlcal data submitted by the applicant CSFM Fire Engineering staff has reviewed the test results and/or
other data but does not make an independent verifocation cl any claims. This listing Is not an enclonement or recommendation of the
item listed. This listing should not be used to verify correct operational requirements or installation aiteria. Refer to listee's data sheet,
installation Instructions and/or other suitable Information sources. •
(_ Date Issued: JULY 1, 1999
Effective Issue date to expiration date
Authorized By:
BEN HO, Deputy State Fire Marshal Ill
Program Manager
L
L
l.
GENERAL
The CPX-551 Intelligent Ionization Detector is used with
the AM2020 Advanced Multiplex System, AFP1010, AFP-
400, AFP-300, AFP-200, and System 5000 (with AIM-200
module) to sense products-of-combustion and report the
measured level of such products in analog form to the
control panel. The use of analog information provides sig-
nificant benefits to the end user, installer and service per-
sonnel in ways not possible with a conventional-type sys-
tem. Since the CPX-551 is also addressable, it will help
firefighters to more quickly locate a fire during its early
stages.
FEATURES
Unique unipolar dual chamber provides exceptional sta-
bility.
Factory preset at 1.06% nominal sensitivity for panel
alarm threshold level.
Fully coated circuit boards and superior RF/transient
protection.
Addressable by device.
Rotary DECADE 01-99 address switches.
Two-wire loop connection.
Visible LEDs "blink" when the unit is addressed:
-Optional with AM2020 software release 5 (or higher).
-Optional with AFP1010.
-Optional with AFP-200.
-Optional with AFP-300.
-Optional with AFP-400.
360'-field viewing angle of the visual alarm indicators
(two LEDs). LEDs illuminate steady during alarm.
Integral communications and built-in type identification.
Compact, stylish design.
Remote test feature from the panel.
Built-in functional test switch activated by external mag-
net.
Low standby current.
Listed to UL-268.
Built-in tamper-resistant feature.
Sounder base option.
Designed for direct surface or electrical box mounting.
Sealed against back pressure.
Plugs into separate base for ease of installation and
maintenance.
Separate base allows interchange of photoelectric, ion-
ization and thermal detectors.
94-5V plastic flammability rating.
Removable cover and insect-resistant screen for field
cleaning.
Remote LED annunciator output connection.
Optional relay, isolator, or sounder bases.
April 6, 1998 H-100
CPX-551
Intelligent Ionization Detector
Section: lntelligenVAddressable Devices
S1115
MEA
104-93-E
289-91-E
290-91-E
17-96-E
CS308
(CPX-551A)
BSA
578-81-SA
~
I California State Fire
Marshal
7271-0028:149
<8>
OW6A2.AY, OQ1A8.AY
(AM2020/AFP1010)
OV4A5AY (AFP-200)
0B1AO.AY (AFP-400)
OV2A3.AY
f:!ases 93/00141 ltsted US Coast Guard
separately ...
CONTACT FACTORY.
APPLICATIONS
161•002/27/1 (AFP1010/AM2020)
161 •002/23/1 (AFP-200)
Use ionization detectors in life-safety applications to pro-
vide a broad range fire-sensing capability, especially fast,
flaming fires. Where smoldering fires are anticipated, a
photoelectric sensor may provide faster response.
CONSTRUCTION
These detectors are constructed of LEXAN® In an off-white
color.
The CPX-551 plug-in series of smoke detectors are de-
signed to commercial standards and offer an attractive
appearance.
LEXAN® is a registered trademark of GE Plastics, a subsidiary of
General Electric Company.
This document Is not intended to be used for Installation purposes. We by to keep our
product information up.to-date and accurate. We cannot cover all specific applications or
anticipate all requirements. All specifications are subject to change without notice. For
more Information, contact NOTIFIER. Phone: (203) 484-7161 FAX: (203) 484-7118
ISO-9001
Engineering and Manufacturing
Quality System Certified to
International Standard IS0-9001 ~ @) N OTI Fl ER' 12 Clintonville Road, Northford, Connecticut 06472 Made In the U.S.A.
ON-1451 -Page 1 of2
(_
(_
INSTALLATION
Location of holes
to access and release
locking prongs.
HEAD COVER
Cover and screen
are removable
for cleaning.
Locking prongs.
The CPX-551 Plug-In Detectors use a separate base to
simplify installation, service and maintenance. A specially
designed tool allows maintenance personnel to plug in and
remove the sensors without using a ladder.
Mount base (all base types) on box which is at least 1.5"
(38.1 mm) deep. Suitable boxes include:
4" (101.6 mm) square box
3-112" (88.9 mm) or 4" (101.6 mm) octagonal box.
Singleijang box.
When using the CPX with the B501 BH sounder base: use
a 4" (101.6 mni) square (1.5" [38.1 mm] deep) box.
When using e B524RB or B524BI base: use a 3-112"
(88.9 mm) octagonal, 4" (101.6 mm) octagonal, or 4"
(101.6 mm) square base.
NOTE: Because of the inherent supervision provided by
the SLC loop, end-of-line resistors are not required. Wir-
ing "T-taps• or branches are permitted for Style 4 (Class
·a, wiring.
OPERATION
Each CPX-551 uses one of 99 possible addresses on a
System 5000 (with AIM-200 module), AFP-200, AFP-300,
AFP-400, AM2020 Advanced Multiplex System, and
AFP1010 SLC loop. It responds to regular polls from the
system and reports Its type and status, including the ana-
log level of Its unipolar chamber. If It receives a test com-
mand from the panel (or a local magnet test) It simulates
Its chamber and reports the analog level. It blinks Its LEDs
when polled, and turns the LEDs on steady when com-
manded (LED blink Is optional on the AFP-200, AFP-300,
AFP-400, AFP1010 and AM2020).
The CPX-551 Intelligent Ionization Senso(s unique unipo-
lar chamber responds quickly and uniformly to a broad
range of smoke conditions and can withstand wind gusts
up to 1,500 feet-per-minute without sending an alarm level
signal. Because of the unipolar chamber, the CPX-551 Is
approxlmately two times more responsive than most Ion-
ization sensors. This makes It a more stable detector.
Page2of2 -DN-1451
SPECIFICATIONS
• Operating voltage: 15 -28 V (Peak DC).
• Current range: 6.5 mA current for visible LEDs latched
"'ON".
• Standby current: 200 µA maximum (without communi-
cation); 300 µA maximum ( communication with LED blink
enaj)led).
• Detector standby current B524RB or B524BI: < 700
µA @ 24 VDC (includes detector).
• Sensitivity: 1.5% nominal.
• Sensor: Unipolar, dual-chamber.
• Ambient temperature: o•c to 49"C (32"F to 120"F).
• Relative humidity: 10% to 93%.
• Maximum alrveloclty: 1,500 feet-per-minute maximum
(without triggering a false alarm).
• Weight: 5.3 ounces (160 grams).
• BX-501 base diameter: 6.1 inches (15.5 cm).
B501 base diameter: 4.0 inches (10.2 cm) .
. • B524RB relay base:
Screw terminals: Up to 14 AWG (2.0 mm2).
Relay type: Form-C.
Contact Rating: 2.0 A @ 30 VDC resistive.
0.3 A@ 120 VDC inductive.
1.0 A @ 30 VDC inductive.
Dimensions: 6.2" (157 mm) x 1.4" (36 mm).
Standby: < 700 µA @ 24 VDC.
B524BI: Dimensions: 6.2" (157 mm) x 1.4" (36 mm).
Maximum: 25 devices between isolator bases.
PRODUCT LINE INFORMATION
Model
CPX-551
CPX-551A
Bases ...
BX-501
B501
B501BH
B524RB
B524BI
Description
Intelligent Ionization Sensor.
Intelligent Ionization Sensor.
Canadian (ULC) approved.
Standard U.S. Base
(a base is required for each CPX-551 ).
Base, flangeless European style.
Sounder base assembly
(includes a B501 mounting base)
Intelligent relay base.
Intelligent isolator base.
Other Accessories ...
RMK400 Recessed Mounting Kit for 500 Series
detectors.
XRS Removal Tool.
XP-4 Extension Pole for Removal Tool.
RA400Z* Remote LED. Mounts to a slngl8ijang box.
•supported by BX-501 and 8501 bases only.
ARCHITECTURAL/ENGINEERING
SPECIFICATIONS
For specifications, request a copy of the Architect/Engi-
neer Specification Disk, available from NOTIFIER Utera-
ture Services, on IBM format 3.5" 1.44 Mbyte magnetic disk.
This disk Includes files In both ASCII and WordPerfect®
5.1 formats.
WordPeffocte Is a registered trademark of the WordPerfect
Corporation.
l
l
L
l.
(_
LISTING No.
CATEGORY:
LISTEE:
DESIGN:
INSTALLATION:
MARKING:
APPROVAL:
NOTE:
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTEC1'1ON
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING DIVISION
LISTING SERVICE
7271-0028:149
Ionization Smoke Detector
Notifier, 12 Clintonville Rd., Northford CT 06472-1653
Contact: Larry Flood (203) 484-1200
LISTING EXPIRES
JUNE 30, 1999
Page 1 of 1
Model CPX-551 smoke detector. Refer to listee's data sheet for detailed
product description and operational considerations.
In accordance with listee's printed installation instructions, applicable codes
and ordinances and in a manner acceptable to the authority having
jurisdiction.
listee's name, product number, electrical rating and UL label.
listed as an ionization smoke detector when used in conjunction with Model
BX-501 base (CSFM listing No. 7300-0028:173*) and separately listed
compatible fire alarm control units.
Formerly 7256-0028:149
•corrected 05-14-98
TH:S LISTING IS BASED UPON TECHNICAL DATA SUBMrTTED BY n-tE APPLICANT. CSFM FIRE ENGINEERING STAFF HAS REVIEWED
THE TEST RESULTS AND/OR OTHER DATA BUT DOES NOT MAKE AN INDEPENDENT VERIFICATION OF ANY CLAIMS. TrllS LISTING IS NOT
AN ENDORSEMENT OR RECOMMENDATION OF THE ITEM USTEll. THIS USTING SHOULD NOT BE USED TO VERIFY CORRECT OPE.RATIONAL
REQUIREMENTS OR INSTALLATION CRITERIA. REFER TO USTEE'S DATA SHEET, INSTALLATION INSTPUCTIONS AND/OR OTHER
SUfTABL.£ INFORM.li..TION SOURCES.
DATE ISSUED: MAY 14, 1998 APPROVED BY:
EFFECTIVE ISSUE DATE TO EXPIRATION DATE
PROGRAM COORDINATOR
(_
L
(._
GENERAL
The SDX-551 and SDX-551TH Analog Photoelectric Detec-
tors are used with the NOTIFIER AM2020, AFP1010, AFP-
400, AFP-300, AFP-200, and System 5000 (when equipped
with AIM-200 module) Advanced Multiplex Systems to mea-
sure the analog level of smoke and report this analog level to
the control panel. The use of analog data provides signifi-
cant benefits to the end user, installer, and service personnel
in ways not possible with a conventional-type system. Since
this detector is also addressable, It will help firefighters to more
quickly locate a fire during Its earty stages. The SDX-551TH
offers the same features as the SDX-551 with the addition of
a 135"F (57"C) Internal thermal element.
FEATURES
Unique optical sensing chamber.
Optional integral 135"F (57°C) fixed-temperature element.
Superior signal-to-noise ratio (2.0).
Stable photoelectric operation.
1.6% nominal sensitivity for panel alarm threshold level.
Fully coated circuit boards and superior RF/transient pro-
tection.
Addressable by device.
Rotary DECADE 01-99 address switches.
Two-wire loop connection.
Visible LEDs "blink" every time the unit is addressed, and
illuminate steadily on alarm (this feature may be deselected
on the AM2020, AFP1010, AFP-400, AFP-300, and AFP-
200).
360"-field viewing angle of visual alarm indicators (2 LEDs).
Integral communications, built-in device type identification.
Compact, stylish design.
Remote test feature from the panel.
Built-in functional test switch activated by external magnet.
Low standby current.
Listed to UL-268.
Built-in tamper-resistant feature.
Designed for direct-surface or electrical-box mounting.
Sealed against back pressure.
Optional sounder, relay or isolator bases.
Plugs Into separate base for ease of installation and main-
tenance.
Separate base allows Interchange of photoelectric, Ioniza-
tion and thermal elements.
94-V0 plastic flammability rating.
Removable cover and insect screen for field cleaning.
Remote LED annunciator output connection.
June 18, 1998 H-105
SDX-551 and SDX-551 TH
Intelligent Photoelectric Detectors
Section: lntelligenUAddressable Devices
® ~ ~ ~~:::~~! ~ ~ 7272--0028:148
S1115 CS308 <S>
CS118/CS733 F M
~ (SDX-551A)
~ US Coast Guard 0O4AO.AY
151-002,21,1 MEA 93/00141
(SDX-551) 161•002/23/1 (SDX-551)
BASES LISTED SEPARATELY.
CONTACT FACTORY.
Cover
Screen
Detector
Base
(order
separately)
460-92-E
290-91-E
BSA
578-81-SA
(SDX-551)
This document Is not Intended to be used for Installation purposes. We try to keep our
product Information up-to.date and accurate. We cannot cover all specific applications or
anticipate an requirements. A.II 1pecffications are subject to change without notice. For
more lnfonnallon, contact NOTIFIER. Phone: (203) 484-7161 FAX: (203) 484-7118
ISO-9001
Engineering and Manufac:lurlng
Quality System Certified to
lntematlonal Stendard IS0.9001 @) N OTI Fl ER" 12 Clintonville Road, Northford, Connecticut 06472 Made In lhe U.S.A.
DN-1884 -Page 1 of 2
L
APPLICATIONS
Photoelectric detectors are often faster than Ionization de-
tectors In sensing smoke from slow, smoldering fires. Ion-
ization detectors are often better than photoelectric detec-
tors at sensing fast, flaming fires.
CONSTRUCTION
These detectors are constructed of LEXAN® In an off-white
color. The SDX-551 plug-in series of smoke detectors Is
designed to commercial standards and offers an attractive
appearance.
LEXAN® Is a registered trademar1< of GE Plastics, a subsidiary of
General Electric Company.
INSTALLATION
The SOX Series Plug-In Detectors use a separate base to
simplify Installation, service and maintenance. A specially
designed tool allows maintenance personnel to plug-in and
remove the sensors without using a ladder.
Mount base (all base types) on a box which Is at least 1.5
inches deep. Suitable boxes Include:
4" (101.6 mm) square box with, or without, plaster ring.
3-1/2" (88.9 mm) or 4" (101.6 mm) octagonal box.
Single-gang box.
For the B524RB or 852481 base: use a 3-1/2" (88.9 mm)
or4" (101.6 mm) octagonal box; or4" (101.6 mm) square
box.
When using the SDX with the 85018H sounder base:
use a 4" square box (1.5" [38.1 mm] deep).
NOTE: Because of the inherent supervision provided by
the SLC loop, end-of-line resistors are not required. Wir-
ing "T-taps" or branches are permitted for Style 4 {Class
"B"} circuits.
OPERATION
Each SDX-551/SDX-551TH uses one of 99 possible ad-
dresses on a SLC loop. It responds to regular polls from
the control panel and reports Its type and status, Including
the analog level of its smoke-sensing chamber. If it re-
ceives a TEST command from the panel (or a local magnet
test), it stimulates its chamber electronics and reports an
alarm analog level. It blinks its LEDs when polled, and
turns the LEDs on when commanded by the panel.
The SOX detector uses the 1/ght-scattertng principle, rep-
resenting the latest In smoke-sensing technology.
ARCHITECTURAL/ENGINEERING
SPECIFICATIONS
For specifications request a copy of the Architect/Engineer
Specification Disk, available from NOTIFIER Literature Ser-
vices, on IBM format 3.5" 1.44 Mbyte magnetic disk. This
disk Includes files In both ASCII and WordPerfecl® 5.1
formats.
WordPerfect® Is a registered trademar1< of the WordPerfect
ColporaUon.
Paoe2of2 -DN-1884
COMMON SPECIFICATIONS
Operating voltage: 15 -28 V (peak DC).
Current range: 6.5 mA current for visible LEDs latched
•oN".
Detector standby current: 230 µA maximum (no com-
munication); 330 µA maximum (with LED blink).
Standby current for B524RB or 852481: < 700 µA@
24 voe (includes detector).
Sensitivity: 1.6% nominal.
Sensor: Photoelectric (light-scattering principle).
• Ambient temperature: SDX-551: o•c to 49"C (32"F
to 120"F). SDX-551TH: o·c to 38°C (32"F to 100"F).
• Relative humidity: 10% to 93%.
• Air velocity: 3,000 feet/minute maximum.
Weight: 6 oz. (170 gm.).
BX-501 Base diameter: 6.2" (15.8 cm).
8524RB Relay Base:
Screw terminals: Up to 14 AWG (2.0 mm').
Relay type: Form-C.
Contact rating: 2.0 A @ 30 voe resistive.
0.3 A@ 120 voe Inductive.
1.0 A @ 30 voe Inductive.
Dimensions: 6.2" (157 mm) x 1.4" (36 mm).
• 852481: Dimensions: 6.2" (157 mm) x 1.4" (36 mm).
Maximum: 25 devices between Isolator bases.
SDX-551TH SPECIFICATIONS
Includes 135"F (57°e) fixed-temperature thermal element.
PRODUCT LINE INFORMATION
Model
SDX-551*
Description
Intelligent Photoelectric Sensor
(base ordered separately).
SDX-551TH' Intelligent Photoelectric Sensor with
built-in 135"F (57°e) fixed-temperature
thermal element (base ordered
separately).
• Order suffix "A· for Canadian (ULC) approved devices.
Bases ...
BX-501
8501
Standard U.S. 6.2" diameter mounting base.
European style 4" diameter mounting base
(without flange).
8501 BH Sounder base assembly (Includes B501
base).
8524RB Intelligent relay base.
852481 Intelligent Isolator base.
Optional Accessories ...
RA400Z** Remote LED. Mounts to a single-gang box.
XR5 Removal Tool.
XP-4 Extension Pole for Removal Tool.
•• Supported by BX-501 and 8501 bases only.
(
(
l
C.
L
LISTING No.
CATEGORY:
LISTEE:
DESIGN:
INSTALLATION:
MARKING:
APPROVAL:
NOTE:
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING -BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
7272-0028: 148
Photoelectric Smoke Detector
Usting Expires
June 30, 2000
Page 1 of 1
Notifier, A Pittway Company, One Rre-Lite Place, Northford CT 06472-1653
Contact: Larry. Flood (203) 484-1200
Models SDX-551 and SDX-551T. Refer to listee's data sheet for detailed
product description and operational considerations.
In accordance with listee's printed installation instructions, applicable codes
and ordinances and in a manner acceptable to the authority having
jurisdiction.
Listee's name, product number, electrical rating and UL label.
Listed as photoelectric smoke detectors when used in conjunction with
Model BX-501 base (CSFM Listing No. 7300-0028:173*) and separately
listed compatible control units.
Formerly 7257-0028:148
• Corrected 05-14-98
This listing Is based upon technical data submitted by the applicant CSFM Fire Engineering staff has reviewed the test results and/or
other data but does not make an Independent llerif,cation of any claims. This listing Is not an endor.ement or recommendation of the
item listed. This listing should not be used to verify axrect operational requirements or installation criteria. Refer to listee's data sheet,
Installation instructions and/or other suitable Information sources.
C Datelssued:)ULY 1, 1999
Effective issue date to expiration date
Authorized By:
BEN HO, Deputy State Fire Marshal Ill
Program Manager
J-89
,TM Series
d C 11/Strobes
sual Devices
512 (P1215, P121575, P2415,
'5, P24110). S5512 (S1215,
15, S241575, S2475, S24110).
124).
SA, P241575A, P2475A, P24110A,
;75A, S2475A, S24110A).
14A, HC12/24A).
121575, ► ~
,,P24110, ~
,, S241575,
). 0D4A7.AY(HC12/24).
173 (P1215, P121575, P2415,
75, P24110).
174 (S1215, S121575,
75, S2475, S24110).
143 (H12/24, HC12/24).
◄ 319-96-E (P1215, P121575,
P2415, P241575, P2475,
P24110, S1215, S121575,
S2415, S241575, S2475,
sco, H12/24, HC12/24).
"', and Multl-Alert'" are trade-
livislon of Pittway Corporation.
;-c
1ufacturing
,rtifiedto
; 1S0-9001 ~
Made in the U.S.A.
ON-5939 -Page 1 of 6
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTl<IN
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING DIVISION
LISTING SERVICE
7300-0028:173
Misc. Devices/Control Unit Accessories
Notifier, 12 Clintonville Road, Northford, CT 06472-1653
Contact: Lawrence Flood (203) 484-7161
LISTING EXPIRES
JUNE 30, 1999
Page 1 of 1
Models BX501, 8610LP, 8612LP, 8614LP, B616LP and B710LP detector
bases. Refer to fistee's data sheet for additional detailed product description
and operational considerations.
In accordance with listee's printed installation instructions, applicable codes
and ordinances and in a manner acceptable to the authority having
jurisdiction.
listee's name, product designation, electrical rating and UL label.
Listed as detector bases for use with separately listed compatible detectors.
7300-1209:128
07-29-94
TECHNICAL DATA SUBMl1TED BY THE APPLICANT. CSFM FIRE ENGINEERING STAFF HAS
ANO/OR OTHER DATA B:JT DOES NOT MAKE A"' INDEPENDENT •/ERIFICATION OF ANY CLAIMS.
lSEMEHT OR RECOMMEHCtATION OF THE ITEM LISTED. THIS USTiNC: SHOULD N'=>T BE USED TO
-REQUJREMEtUS OR INSTALLATION CRITERIA. REFER TO USTEE'S DATA SHEET, INSTALLATION
l SUITABLE INFORMATION SOURCES.
, 1998
,TIONOATE
APPROVED BY: ~~
PP.OGRAM COORDINATOR
L
C.
LISTING No.
CATEGORY:
LISTEE:
DESIGN:
INSTALLATION:
MARKING:
APPROVAL:
XLF:
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECT!GN
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING DIVISION
LISTING SERVICE
7300-0028:173
Misc. Devices/Control Unit Accessories
Notifier, 12 Clintonville Road, Northford, CT 06472-1653
Contact: Lawrence Flood (203) 484-7161
LISTING EXPIRES
JUNE 30, 1999
Page 1 of 1
Models BX501, 8610LP, B612LP, 8614LP, 8616LP and 8710LP detector
bases. Refer to listee's data sheet for additional detailed product description
and operational considerations.
In accordance with listee's printed installation instructions. applicable codes
and ordinances and in a manner acceptable to the authority having
jurisdiction.
Listee's name, product designation, electrical rating and UL label.
Listed as detector bases for use with separately listed compatible detectors.
7300-1209:128
07-29-94
THIS LISTING IS BASED UPON TECHNICAL DATA SUBMIITED BY THE APPLICANT. CSFM FIRE ENGINEERING STA.FF HAS
REVIEWED THE TEST RESliLTS A.ND/.:>" OTHER DA.TA B:JT DOES NOT MAKE AN INDEPEtlDENT "IERIFICATION OF ANY CLAIMS.
THIS USTING IS NOT AN ENDORSEMENT OR RECOMMEHCIATION OF THE ITEM LISTED. THIS USTiNG SHOULD Nl)T BE USED TO
VERIFY CORR~CT QPERA.TIONA.L REQUIREMEtHS OR INSTALLATION CRITERIA. REFER TO USTEE"S OA.TA SHEET, INSTALLATION
INSTRUCYIONS AND/OR OTHER SUITABLE INFORMATION SOURCES.
DATE ISSUED: APRIL 24, 1998
EFFECTIVE ISSUE OAT£ TO EXPIRATION DATE
APPROVED BY: ~~
PP.OGRAM COORDINATOR
C
(_
September 16, 1998 J-89
GENERAL
System Sensor SpectrAlert Serles strobes, horns, and combina-
tion horn/strobes are UL listed for primary signaling in life safety
systems and meet ADA public mode visible signaling requirements.
SpectrAlert products can be connected to the alarm indicating cir-
cuit of a fire alarm control panel and are compatible with DC line
supervision. The SpectrAlert product line mounts to standard
backboxes using a universal mounting plate included with each unit.
An optional small footprint mounting plate fits to a single-gang box.
An accessory backbox skirt gives a cosmetic finish to a 4" x 4" x
1-1/2" or a 2" x 4" x 1-7/8" surface-mounted backbox. All strobe
and horn/strobe mounting options require only one screw attach-
ment of product to plate.
These products are designed for 12 and 24 VDC and full-wave rec-
tified unfiltered power. Full-wave rectified operation requires-more
current than DC operation. For detailed current draw information,
consult the Current Draw Tables (page 2). The horn/strobe com-
bination products are factory-assembled with jumper wires for in-
tandem operation. For independent wiring of horn and strobe, re-
move jumper wires. When wired for independent operation, the
strobe will continue to run while the horn can be silenced. How-
ever, the strobe must be running for horn to operate.
Horns -The SpectrAlert Series horns and horn/strobes pro-
vide two different field-selectable/reversible tones, a high-low field-
selectable/reversible sound output setting (low setting on 24-volt
models only) and a field-selectable/reversible temp 3 pattern or
non-temporal continuous pattern. These field-selectable features
are accomplished using pins and jumpers located on the back of
each SpectrAlert horn and horn/strobe. An accessory module is
not needed to make these field selections. The horn on horn/strobe
models will operate on a coded power supply. Those horn-only
models with "HC" In their part numbers will also operate on a
coded power supply. The horn and horn/strobe series includes
weatherproof models.
Strobes -The ADA-compliant SpectrAlert strobes are elec-
tronic visible warning signals that flash at 1 Hz over their operating
voltage range. These products are available in 24-volt models at
15, 15/75, 75 and 110 candela intensities and in 12-volt models at
15 and 15/75 candela intensities. The strobe series includes weath-
erproof models. SpectrAlert products feature dramatic reductions
in current requirements.
Sync•Circuit Module (MDL)-The Sync•Circuit Module
is available for synchronization of strobes and horns and can syn-
chronize two Style Y (class B) circuits or one Style Z (class A)
circuit. The module can also generate a synchronized temp 3 tone
for System Sensor's Multi-Alert"' and PA400 horn products.* The
synchronization module allows the SpectrAlert horns on combina-
tion horn/strobes to be silenced on two-wire systems. SpectrAlerl's
Sync•Circuit Module can be daisy-chained for multiple zone syn-
chronization. The module does not operate on a coded power sup-
ply.
*For Multi-Alert and PA400: Strobes must be wired to a continuous
source of power (non-coded power supply}.
SpectrAlert ™ Series
Horns, Strobes, and Horn/Strobes
Section: AudioMsual Devices
® ◄ S4011 & S5512 (P1215, P121575, P2415,
P241575, P2475, P24110). S5512 (S1215,
S121575, S2415, S241575, S2475, S24110).
S4011 (HC12/24).
@ ◄ CS549 (P2415A, P241575A, P2475A, P24110A,
S2415A, S241575A, S2475A, S24110A).
CS548 (H12/24A, HC12/24A).
0B8A4.AY(P1215,P121575, ► ~
P2415,P241575,P2475,P24110, ~
S1215,S121575,S2415,S241575,
S24 75, S24110, H12/24). 0D4A7 .A Y (HC12/24).
California
State Fire
Marshal
7135-1209:173 (P1215, P121575, P2415,
P241575, P2475, P24110).
7125-1209:174 (S1215, S121575,
S2415, S241575, S2475, S24110).
7135-1209:143 (H12/24, HC12/24).
M EA ◄ 319-96-E (P1215, P121575,
P2415,P241575,P2475,
P24110,S1215,S121575,
S2415,S241575,S2475,
S24110, H12/24, HC12/24).
SpectrAlertTM, Sync•ClrcultTM, and Multl-AlertTM are trade-
marks of System Sensor, a division of Pittway Corporation.
This document is not intended to be used for installation purposes. We try lo keep our
product infonnation up-to-date and accurate. We cannot cover all specific applications or
anticipate all requirements. All specifecations are subject to change without notice. For
more information, contact NOTIFIER. Phone: (203) 484-7161 FAX: (203) 484-7118
~ N OTI Fl ER* One Fire-Lite Place, Northford, Connecticut 06472
IS0-9001
Engineering and Manufacturing
Quality System Certified lo
lntemational Slandard 1S0-9001 Made In lhe U.S.A.
DN-5939 -Page 1 of 6
(_
L
(_
FEATURES
24-volt strobe models: 15, 15/75, 75 and 110 candela.
12-volt strobe models: 15 and 15/75 candela.
Hom models operate on 12 and 24 volts.
Low current draw: reductlons as high as 45%.
Two field-selectable/reversible horn tones:
-3000 Hz Interrupted -electromechanical
Field-selectable/reversible high-low dBA output on horn
(low output on 24-volt models only):
-101 peak dBA@ 10 fl. high output.•
-96 peak dBA @ 10 It. low output•
Field-selectable/reversible temp 3 pattern or non-temp 3 con-
tinuous pattern on horn.
Hom/strobe can be wired either in tandem or independently.
Weatherproof strobes, horns, and horn/strobes available.
Homs for use with coded power supply available.
Universal mounting plate included with each unit.
One-screw mounting of strobe and horn/strobe to mounting
plate. •
SpeclrAlert strobe and horn/strobe take up no room In the
backbox.
CURRENT DRAW TABLES
Strobe Only
Single-gang mounting without the use of a mounting plate
(horn model only).
Self-contained screw covers.
Aesthetically pleasing design.
Synchronize horn and strobe with Sync•Circuit™ module
(MDL).
Silence horn on horn/strobe over a single pair of wires using
a Sync-Circuit module (MDL).
•sound output varies with tone and output options selected; sound
levels based upon anechoic room measurements.
SPECIFICATIONS
Input tennlnals: 12 to 18 AWG (3.25 mm• to 0.51 mm').
Dimensions: see diagrams page 3.
Weight, hom only: 7.2 oz. (204 g).
Weight, strobe and horn/strobe: 8.8 oz. (250 g).
Mounting: see diagrams page 4.
Operating temperature: 32°F to 12o•F (0"C to 49•cJ.
Operating voltage range: .. 12 V: 10.5-17 V. 24 V: 20 -30
V.
•• These products should be operated within their rated voltage
range. UL does, however, test functional Integrity to -20¾ and
+10¾ of manufacturer's stated ranges.
______ AVERAGE CURRENT (mA) PEAK CURRENT (mA) _ _ IN RUSH CURRENT(~ ... ~ ·-··· 10.SV 12V 17V 20V 2CV 30V 10.SV 12V 17V 20V 2CV ,ov 10.5V Candela ., ... ., ... ., -., ... ., ... ., ... ., -., ... ., ... ., ... ., -., ... ., -15 133 1 .. "' "' " 128 .. 120 " .. .. ,. , .. ... "" ... ... 1,0 "' 1,0 270 1<0 "" ., 108 15"5 "' "' "' "' .. 1 .. " .. " .. "' , .. 520 ... ... ... 170 ... 170 270 100 270 " "" 75 NA NA NA NA NA NA 1'5 "" 123 "' 102 "' NA NA NA NA NA NA 5SO ... ... "" 330 ... NA NA 110 NA NA NA NA NA NA "' ... , .. '" 11' "' NA NA NA NA NA NA <00 ... ... 570 ... ... NA NA
Horn Only
AVERAGE CURRENT(~--~-, • ........ T-10.5.Y 12V 17V 20V HV 30V T-.,._ -., ... ., .... ., ... ., ... ., ... ., --High • 10 " 10 10 " 1 " 21 " " 29 ,_ Non 10 ,. 10 .. " 17 .. .. " .,
Low • NA NA NA NA NA NA " " 13 13 17 1 -~ NA NA NA NA NA NA " " " 19 17 • 3000Hi. High r-• " 13 " " " 1 " " " 23 " ·-Non " " " " " .. " 27 .. " . Low T-• NA NA NA NA NA NA " " 17 " 21 " Non NA NA NA NA NA NA 13 " " 21 "
Hom/Strobe -15 cd Hom/Strobe -75 cd
·-· .. AVERAGE CURRENT (IIIA)
llgh/LGWT-,, 10.SV 12V IJY 20V 24V T-VOiume INon ,_ ... ., ... ., ... ., -., ... -.... • ,a 110 "' 107 1 71 1111 ,. " --Non 10 110 "' "' " ' .. " .. ,oo
I.ow • NA NA NA NA NA NA ,. " .. " Non NA NA NA NA NA NA ., .. " 3000H, .... 144 172 1 .. ' 101 1 10, ·-Non H4 173 115 , .. " 1 71 102 101
I.ow .. NA NA .. NA NA " " " Non NA NA NA NA NA NA " 12 .. ..
Hom/Strobe -15n5 cd
AVERAGE CURRENT (MAJ
Low
3000H, .... -I.ow
Page 2 of 6 -DN-5939
10.SV 12V 1TV 20V •••
30V Kghllow Temp 10.SV .,,_
7S 141 ---"'-., ... -.... • = NA .. , .. --Non NA NA
" 1 I.ow • NA NA
" 1
Non NA NA .. "' 3000H, .... t .. NA
at ,a --NA NA ., ' I.ow • .. .. .. "' Non NA NA
Hom/Strobe-110 cd --TOM --.... --I.ow
3000H, .... -I.ow
12V 17V 20V 2CV 30V ., ... ., ... ., ... ., ... ., ! " "' 1<0 10> 1 "' ... ,., .. "' 10) "' 170 230 210 ... 270
NA NA NA NA tta 240 230 ... 280
NA NA NA NA "' "' ... 280 280 ,-
AVERACE CURRENT(~
' 12V 17V 20V ... ""' ., ... ., ,_ ... " ... ., ...
NA NA NA •• ,. ~., ua 111 ,s, 187
NA NA NA NA 1t3 181 141 ,. 1:12 ,.
NA NA NA NA 158 112 ,. 112 . .. "' NA NA NA NA 157 112 137 112 111 1
N' ' ' .. , 1
NA NA NA NA 164 112 150 111 "' 1 NA NA NA .. 151 1114 1 , .. ,., 1
NA NA NA NA 158 , .. ,. 11:!1 114 112
AVERAGE CURRENT (11\A)
(
(
(,.
(_
ENGINEERING SPECIFICATIONS
General -SpectrAlert hams, strobes and horn/strobes
shall be capable of mounting to a standard 4" x 4" x 1-1/2"
(10.16 x 10.16 x 3.81 cm) backbox or a single-gang 2" x 4" x
1-1/2" (5.08 x 10.16 x 3.81 cm) backbox using the universal
mounting plate included with each SpedrAlerl product. Also,
SpectrAlert products, when used in conjunction with the ac-
cessory Sync•Circuit Module, shall be powered from a non-
coded power supply and shall operate on 12 or 24 volts. 12-
volt rated devices shall have an operating voltage range of
10.5 -17 volts. 24-volt rated devices shall have an operating
voltage range of 20 -30 volts. SpectrAJert products shall have
an operating temperature of 32'F to 120'F (0'C to 49'C) and
operate from a regulated DC or full-wave rectified, unfiltered
power supply.
Horn -Hom shall be a System Sensor SpectrAlert model
----capable of operating at 12 and 24 volts. Horn shall
be listed to UL 464 for fire protective signaling systems. The
horn shall have two tone options, two audibility options (at 24
volts) and the option to switch between a temporal 3 pattern
and a non-temporal continuous pattern. The horn-only model
shall NOT operate on a coded power supply except those
models (model numbers contain "HC") designed to do so.
Strobe -Strobe shall be a System Sensor SpectrAlert
model ____ listed to UL 1971 and be approved for fire
protective service. The strobe shall be wired as a primary
signaling notification appliance and comply with the Americans
with Disabilities Act requirements for visible signaling appli-
ances, flashing at 1 Hz over the strobe's entire operating volt-
age range. The strobe light shall consist of a xenon flash tube
and associated lens/reflector system.
DIMENSIONS
5-518"
(142.875 mm)
l4--2-5/16"
(58.7375 mm)
ITT
OUTER: 5-518"
(142.875 mm)
Hom/Strobe Combination -Horn/strobe shall be a
System Sensor SpectrAJert model ____ listed to UL 1971
and UL 464 and shall be approved for fire protective service.
Horn/strobe shall be wired as a primary signaling notification
appliance and comply with the Americans with Disabilities Act
requirements for visible signaling appliances, flashing at 1 Hz
over its entire operating voltage range. The strobe light shall
consist of a xenon flash tube and associated lens/reflector
system. The ham shall have two tone options, two audibility
options (at 24 volts) and the option to switch between a tem-
poral 3 pattern and a non-temporal continuous pattern. Strobes
shall be powered independently of the sounder with the re-
moval of factory-Installed jumper wires. The horn on horn/
strobe models shall operate on a coded or non-coded power
supply.
Module -Module shall be a System Sensor Sync•Circuit
model ____ listed to UL 464 and shall be approved for
fire protective service. The module shall synchronize
SpectrAlert strobes at 1 Hz and hams at temporal 3. Also, the
module shall silence the hams on horn/strobe models, while
operating the strobes, over a single pair of wires. The module
shall be capable of mounting to a 4-11/16" (119.0625 mm)
square x 2-1/8" (53.975 mm) deep backbox and shall control
two Style Y (class B) or one Style Z (class A) circuit. Module
shall be capable of multiple zone synchronization by daisy-
chaining multiple modules together and resynchronizing each
other along the chain. The Module shall NOT operate on a
coded power supply.
)<--2-15116" -+I I (74.6125 mm} ]
@T
5-5116"
(134.9375 mm)
1
1-5116" /
(33.3375 mm)
UPPER LEFT: Hom/Strobe with Small Footprint Mounting
Plate (same dimensions for strobe only).
LOWER LEFT: Hom/Strobe with Universal Mounting Plate
(same dimensions for strobe only).
UPPER RIGHT: Hom only (may be mounted with effher Small
Footprint or Universal Mounting Plate).
LOWER RIGHT: Sync-Circuit Module (MDL).
2" r--5-1/4" (133.35 mm) ----+j
T 0
0 0
j'j
~ (i)
0 0
ON-5939 -Page 3 of 6
(_
(_
(_
MOUNTING DIAGRAMS
2" x4" x 1-7/8" backbox Hom
r---~n°i===:+i◄ Direct Mount ...
0-MP
"
Hom with Universal Mounting Plate
(included with each product)
4" x4" 1-1/2" backbox I
.....
4-11/16" X 4-11/16" X 2-1/8"
(119.0625 x 119.0625 x 53.975 mm)
backbox
\i='.::::§~~~ --...
--
T
...
...
Strobe or Horn/Strobe with
Universal Mounting Plate
(included with each product)
4" x 4" x 1-1/2" backbox
I.,,,,
Hom Surface Mount
with accessory
Backbox Skirt
--
...
Strobe or Hom/Strobe
with accessory
Small Footprint
Mounting Plate
-
Sync•Circuit Module Direct Mount Strobe or Hom/Strobe Surface Mount
with accessory Backbox Skirt
SOUND OUTPUT GUIDE (dBA)
UL Reverberant Room dBA @ Volts DC Anechoic Room Peak dBA@ 10 ft.NOC
10.5 12 17 20 24 30 10.5 12 17 20 24 30
LOW Eleclromechanical NA NA NA 75 75 79 NA NA NA 94 96 98
TONE 3000 Hz lnfenupted NA NA NA 75 79 79 NA NA NA 94 96 98 Temporal
HIGH Eleclromechanical 75 75 79 82 82 82 94 95 98 100 101 102
TONE 3000 Hz lntenupted 75 75 79 82 85 85 94 95 98 100 101 102
LOW Eleclromechanical NA NA NA 79 82 85 NA NA NA 94 96 98
TONE 3000 Hz lntenup1ed NA NA NA 82 82 85 NA NA NA 94 96 98
~on-Eleclromecharical 79 emporal HIGH 79 85 85 88 88 94 95 98 100 101 102
TONE 3000 Hz lntenupted 79 82 85 88 88 90 93 95 98 100 101 102
Page• of 6 -DN-5939
(
(_
c.. _/
WIRING DIAGRAMS
NOTE: Do NOT loop wires under terminal screws.
(-)
Tandem Operation
HORN/STROBE COMBO
FACTORY
INSTALLED
JUMPERS H
HORN/STROBE STROBE ONLY
~----(+)
Two-wire system, any mix of models,
wired for TANDEM OPERATION.
T Horns silenced over two-wire circuit.
Any mix of horn/strobes or strobe-only devices is
acceptable.
Horn control connects to interruptible power
source.
MODULE 1
FACP ,1
MODULE2
FACPH
1::}=-.
NAC(;) _+-+++++-o'} ::-' (-)
NAC(;>_+--l+H~~} ::""' H
TEWJUMHIIIOff
DIAGRAM NOTES:
AH SpectrA/ert
homs, homlstrobes,
and strobes wlN
operate In sync.
1) Any mix of SpectrAlert horn/strobe, strobe-only, or horn-
only devices is allowable for Zone 1.
2) No devices or horn-only are allowed on Zone 2. If no de-
vices are installed on Zone 2, terminate EOL resistor at
ham control terminal.
Independent Operation
FACTORY
INSTALLED
JUMPER WIRES
REMOVED
HORN AND STROBE
HORNS
(-)
NOTE: Strobes must be
power8d for hom operation.
STROBES Il1NEXT{ STROBE <S
OR EOL <SS-----\,~. cc-'
\
(-1 fBS2M. FACP,
>,.----<cc<~•) ~~~~tfR
NOTE: Breakwi,easshown \
for supervision of connection.
DO NOT allow stripped wire
leads to extend beyond switch
housing. DO NOT loop wires.
H
0 R
N
(-)
:c :0 (M
(+)
,.
:o
s T R
0
B
(-) E
H 0
R N
s T
R
0
B E
DEVICE
Four-wire system, combo models,
wired for INDEPENDENT OPERATION.
(Hom can be turned off at the panel
whlle strobes continue to operate.)
T Temp 3 coding of Multi-Alert
and PA400 sounders.
NOTE: Strobes must be powered from non-coded
supply.
MODULE 1
-· -FACP
o}~~
o"""""' TO NEXT
DEVICE
d}:,o-" OREOL
NAC• ,.. .. ->
~}~!I > NACZ ......... 9 TO NEXT
DEVICE o}..,.. .,,.{o OREOL
9 --~ > ~ Homs wlllbe
TEMP. JUMPER OH temporal-coded
and In sync.
ON-5939 -Page 5 of 6
(_
(_
z
0 -RED WllTE voltage candela avg. mA·@ avg. mA'@
nom. voe nom.F\\R
P1215 P1215W 12 15 124 167
i
0 u. z -
Horn/Strobes P121575 P121575W 12 15175 152 181
P2415 P2415W 24 15 78 98
P241575 P241575W 24 15175 91 111
P2475 P2475W 24 75 148 167
P24110 P24110W 24 110 165 209
P241575K (wealherprooQ -24 15175 91 111
P2475K (wealherprooQ -24 75 148 167
P24110K (wealherprooQ -24 110 165 209
Ill z -.. P2415A P2415WA 24 15 78 98
P241575A P241575WA 24 15175 91 111
P2475A P2475WA 24 75 148 167 Canadian Models, P24110A P24110WA 24 110 165 "lfJ7 Hom/Strobes ..
" ::,
0
0 ai= a.
P241575KA (wealherprooQ -24 15175 91 111
. P2475KA (wealherprooQ -24 75 148 167
P24110KA (wealherprooQ -24 110 165 209
Spanish Labeling, HIS P241575F (FUEGO) 24 15175 91 111
S1215 S1215W 12 15 114 157
Strobes S121575 S121575W 12 15175 142 171
S2415 S2415W 24 15 53 80
S241575 S241575W 24 15175 66 93
S2475 S2475W 24 75 123 149
S24110 S24110W 24 110 140 191
S2415751< (wealherprooQ -24 15175 66 93
S24751< (wealherprooQ -24 75 123 159
S24110K (wealherprooQ -24 110 140 191
S2415A S2415WA 24 15 53 80
S241575A S241575WA 24 15175 66 93
S2475A S2475WA 24 75 123 149 Canadian Models, S24110A S24110WA 24 110 140 191 Strobes
S241575KA (wealherprooQ -24 15175 66 93
S2475KA (wealherprooQ -24 75 123 149
S24110KA (wealherprooQ -24 110 140 191
Spanish Labeling, Strobes S241575F (FUEGO) 24 15175 66 93
H12/24 H12/24W 12/24 NA 12/23-12 / 21
Horns H12/24K (wealherprooQ -12/24 NA 12 / 23 12 / 21
HC12/24 (coded power} HC12/24W (coded power} 12/24 NA 12 / 23 12 / 21
HC12/24K (wealherproo( br coded power} -12/24 NA 12 / 23 12 / 21
H12/24A H12/24WA 12/24 NA 12/ 23 12 / 21
Accessories H12/24KA (wealherprooQ -12/24 NA 12 / 23 12 / 21 ...... HC12/24A (coded power} HC12/24WA (coded power} 12/24 NA 12 / 23 12 / 21
Mill MDLW 12/24 NA 16 24 Sync•Clrcult Module MDI.A MDI.WA 12/24 NA 16 24
Small Footprint Mountln:/: Plate for Single-Gang OM Y ~p -NA NA NA NA
Surface-Mount Backbox Skirt BBS BBSW NA NA NA NA
Universal Mounting Plate
(replacement) DMP DMPW NA NA NA NA
Weatherproof Backbox wee -NA NA NA NA
NOTES: 1) Canadian model numbe!s end In "A". 2) Latin American model numbers end In "P. 3) All weatherproof models must
use wea1herproof backbox model WBB. 4) All SpectrAlert products are designed for wall-mount only. 5) lnstellaUon of less 1han 75
candela s1robes may be pennlsslble under 1he equivalent facllltaUon clause of 1he ADAAG (Sec. 2.2). However, It Is 1he responslbHlty
of 1he person or enUty designing 1he fire etarm system to determine 1he acceptability of less 1han 75 candela s1robes. 6) All 1 sns
candeta s1robes or horn/strobes are recommended for 20' x 20' rooms or less. •For a complete IIBt/ng of SpactrA/ert current requ/n,.
ments, please n,fer to the CUtr8nf Draw tables on page 2 of this document or the lnstllJcllon Manual. Hom and horn/strobe CU"8nt
draws assume the hom Is set at Temp 3, electromechanlcal tone, and high audlbllty.
Page 6 of 6 -DN-5939
(
(
l.
(_
06-01-99 11:43:21
US11NG No.
CATEGORY:
USTEE:
DESIGN:
RATING:
INSTALLATION:
MARKING:
APPROVAL:
NOTE:
FROM: SYSTEM SENSOR FAX TO: 777
CALIFORNIA DEPARTMENT OF FORESTRY• FIRE PROTECTION
OFFICE: OF THE STATE FIRE MARSHAL
FJRE ENGINEERING DMSION
LISTING SERVICE
7135-1209:173
Audible Devices
System Sensor, 3825 Ohio Ava, St Charles IL 60174
Contact: Adam Kozlowski (630) 377-6680
PAGE
l.JsTING EXPIRES
JUN£30, 1999
Page 1 of 1
Models P1215, P121676, P2416, P241576, P241576F, P241575EV,
P2430, P2460, P2475, P2495 and P24110 horn/strobes with or without
suffix -W (white color}. Suffix F Is for fuego design and suffix EV Indicating
the lens has the word "EVAC" on h. Refer to llstee'a data sheet for
additional detailed product description and operational considerations.
Electrical: -12: 10.5 -17 VDC
-24: 20 -30 voe
candela: -15: 16cd
• 1676: 16cd. 76cd on axis
-30: 30cd0
-60: 60cd"
-95: 96cd•
-75: 76cd
-110: 110cd
In accordance with listee's printed Installation Instructions, approcabla codes.&
ordinances and In a manner acceptable to the authority having jurisdiction.
These sounder/strobe coniblnation units are not Intended for field assembly.
Ustae's name. moder number. rating and UL label.
Listed as hom strobes for use with s-,,taly listed compatible fire alarm control
units. Suitable for the hearing Impaired application. For wan mount and Indoor
use only.
Units can generate the distinctive three-pulse Temporal Pattern Fire Alarm
Evacuation Signal (for total evacuation) In accordance with NFPA 72, 1993
Edition. Refer to manufacturer's Installation Manual for details.
Models P1 216 and P121576 are ffl2I Intended for Publlc Mode Fire Alarm
Service when used on 12 V contf91 panel at low volume.
•Conectec107-21•98
THls LaTINCI. IMSED UPONTECHNICAL DATA SIJIIMITTEDBYTHEAPPUCANT. C5FN PIM: ENCANEEIIINCJSTAPl"HAS RalllEWED
THETDrllESIADAlrim/ORancmt DATA.,.. DOD NOTNAICE All ■ IDIINT YEIIIFICATION OIi' AHY CI..Alla.. TMIS USl'INCl a NOT
ANDttl A DIDll'Olllll!00MMDIDATIONOP'nll:ffDILISl'IED. Tlal.lSIINCIIIH0ULDNO'l'•uaDTOYDlll'YCGlllm'CTOPPA'l10NAL
111:QUUIICNDffll OR INSTAl.l.A'TlON CIU1'ERIA. REPER TO LISTl:E"a DATA SHEET. INSTALLA'l'ION IINS1"RUC110N9 Ml,D/OR ontalt
MJl'l'A-..: INl"OIIIIA1ION SOURcaS.
DATEISsUEO:JULY21, 1998 APPROVED Br.
EFFEcltYEISSUEDATETO ElCPIRATION DATE
PROGRAM COORDINATOR
Jlli-01-1999 10:15 SYSTEM SEN5ffi FAX 89'/. P.05
5
(._
(_
c..
06-01-99 11:43:21
USTINGNo.
CATEGORY:
USTEE:
DESIGN:
RATING:
INSTALLATION:
MARKING:
APPROVAL:
FROM: SYSTEM SENSOR FAX TO: 777
CALIFORNIA. DEPAln'MENTOF ll'ORESTRV a FIRE PR0TECTJON
OFFlCEOFTMESTATEFIREMARIIHAL
FIRE ENGINl!ERING DIVISION
LISTING SERVICE
7125-1209:174
Fire Alarm Devices for ijearing Impaired
SySlem Sensor, 3825 Ohio Avenue, St. Chartes IL 60174
Contact: Adam Kozlowakl (6301 377-8580
PAGE
I LISnNG El<PIRES JUNa30,I-
Page 1 of 1
Models S1215, S2415, S2476, S24110, S121675 and S241575 strobe liohta.
Model number may be followed by 8Uffix -W indicating color white. Refer to
listee'1 data sheet for detaled product description end operational considerations.
Electrical: -12: 10.5-17VDC
-24: 20 -30 voe
Candela: -15: 15cd
-1575: 15cd, 75cd on a><is
-75: 75cd
-110: 110cd
In accordance with listee' s printed installation instructions, applicable codes &
otdinancea and in a manner acceptable to the authotity having jurisdiction.
Llstee's name. model number, electrical and candela rating and UL label.
Listed as hearing i"-'8ired strobe lights for use with separately listed compatible
fire alarm control unit. For waif mount and Indoor use only.
02-03-97
THlaUST1NG1&1M.SEDUPONTECHNICALDATASUBMf'n1EDaYTHEAPPUCANT. CSFMF111EENOINICDIINGffAl'PKUIIEVIEWED
THETDT ltDULTa AND/01111 OTNUt DATA aft'DOal NOr MAKE AH INDCrDCDDffvalll'ICATIOM CW ANTa.AIM&. t'Na &atlNG m NO'I"
Nf DMl C#d!IMFHl'OIII M ltafCIATION fW'TttEft'DI uan:D,, THIii usnt«1 SHOUI.DfllOT-UR:DTOYDIII'• COIIM.Ci OPDIA110NAL
REQUIREMUfT'a OIi .,.,-AU.ATION Clffl'DIIA.. RIEPmt TO LSTD'S DATA ........ Nft'AU.ATION INS1'RUC"l'ION AND✓OII OT14at
SUITAa.E INPOIIMA.TION SOURCD.
DATE l8$UED: MAY 15, 1998 APPROVED BV:
EFFECTIVE ISSUE DAT£ TO EXPIRATION DATE
6
I
~1-1999 10:15 SYSTEM SENSCR FAX 89¼ P.06
l.
L
LISTING No.
CATEGORY:
LISTEE:
DESIGN:
RATING:
INSTALLATION:
MARKING:
APPROVAL:
. • ··-.·-··---·-------~ .. -.
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING -BUILDING MATERIALS LISTING PROGRAM .• .
LISTI NG SERVICE
7125-1209: 182
Fire Alarm Devices for the Hearing Impaired
System Sensor, 3825 Ohio Avenue, St. Charles IL 60174
Contact: Adam Kozlowski (630) 377-6580
,,
Listing Expires
June 30, 2000
Page 1 of 1
Models P2475K, P241575K and P24110K horn/strobes. Suffix "K" indicating
extended indoor operating temperature range of 32° F to 150° F and a NEMA
3R enclosure rating. Refer to listee's data sheet for additional detailed product
description and operational considerations. •
20 -30 voe
In accordance with listee's printed installation instructions, NFPA 72, applicable
codes & ordinances and in a manner acceptable to the authority having
jurisdiction.
listee's name, model number, electrical rating and UL label.
listed as horn strobes suitable for the hearing impaired application when used
with separately listed compatible fire alarm control units. For indoor use and
wall mount only.
If these units are required to produce a distinctive three-pulse Temporal
Pattern Fire Alarm Evacuation Signal (for total evacuation) in accordance with
NFPA 72, 1993 Edition, they must be used with a fire alarm control unit that
can generate the temporal pattern signal. Refer to manufacturer's Installation
Manual for details.
07-14-98
This listing is based upon technical data submitted by the applican~ CSFM Fire Engineering staff has reviewed the test results ancVor
other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation or the
item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet,
installation instructions and/or other suitable information sources.
Datelssued:JULY 1, 1999
.Effective issue date to expiration date Authorized By: ~ ~ Deputy State Fire Marshal Ill
C.
(_
GENERAL
The System Sensor DH400ACDC samples air currents
passing through a duct. It gives dependable performance
for management of fans, blowers and air conditioning sys-
tems, preventing the spread of toxic smoke and fire gases
through the protected area.
System Sensor's DH400ACDC 4-wire duct detector hous-
ing will accommodate either the 1451 DH ionization sensor
or the 2451 photoelectric sensor. The twist-in, twist-out
detector heads allow easy removal for quick cleaning and
maintenance, or a change in application without removing
the duct housing.
NOTE: The System Sensor DH400ACDC Duct Detector
Housing is supplied with either the 1451DH Sensor (order
DH400ACDC/) or the 2451 Photoelectric Sensor (order
DH400ACOCP).
FEATURES
24 voe operation.
Accommodates ionization or photoelectric heads.
Simple change-out of detector heads: twist in, twist out.
Easy to maintain.
Powered outputs for remote LED and Sounder/Strobe.
Air velocity rating from 500 to 4,000 feet per minute (3.175
to 25.4 m./sec.).
UL 268A listed.
Reset time: 0.3 seconds (maximum).
Clear polycarbonate cover for convenient visual inspec-
tion of sampling tube filters.
Rugged plastic housing (mounting portion).
Remote test station option.
Easy and quick mounting to round or rectangular ducts
from 1' to 12' (0.305 to 3.66 m) wide.
Three-year limited warranty.
APPLICATIONS
DH400ACDC detectors are designed to operate on 24 VDC,
24 VAC, 120 VAC, or 240 VAC. Alarm and supervisory
relay contacts are available for control panel interface
(alarm initiation), HVAC control, and other auxiliary func-
tions. These detectors are NOT designed for 2-wire appli-
cations.
Duct detectors are:
NOT a substitute for open area smoke detectors.
NOT a substitute for early warning detection.
NOT a replacement for a building's regular fire detection
system.
Refer to NFPA 90A for additional duct detector application
information.
June 18, 1998 1-352
DH400ACDC Series
4-Wire Duct Detector Housings for
Ionization and Photoelectric Sensors
Section: Conventional Initiating Devices
S911 CS308
MEA
427-91-E
I California State Fire Marshal
3240-1209:155
<8>
0V3A0.AY
DH400ACDCP Duct Detector Housing
with 2451 Photoelectric Sensor
CONSTRUCTION AND INSTALLATION
The twist-in, twist-out detector and base allow the removal
of detectors easily and quickly for cleaning and mainte-
nance. In addition, detector heads can be changed to fit
the application without removing the duct housing. The
DH400ACDC comes with built-in exhaust tube. Sampling
tubes are available to fit ducts from 1 to 12 feet (0.305 to
3.66 meters) wide.
ENVIRONMENTAL LIMITS
Temperature: 32°F to 120°F (0°C to 49°C).
DO NOT INSTALL where normal ambient temperatures
exceed 120"F (50"C).
Relative humidity: 10% to 93%.
Air velocity: 500 to 4,000 f!./min. (3.175 to 25.4 m./sec.).
MECHANICAL SPECIFICATIONS
Width: 14.5 inches (36.83 cm).
Height: 5 inches (12. 70 cm).
Depth (installed): 4 inches (10.16 cm).
Weight: 4.5 pounds (2.041 kg).
This document is not intended to be used for installation purposes. We try to keep our
product infonnation up-lo-date and accurate. We cannot cover all specific applications or
anticipate all requirements. All specifications are subject to change without notice. For
more information, contact NOTIFIER. Phone: (203) 484-7161 FAX: (203) 484-7118
@) N OTI Fl ER" 12 Clintonville Road, Northford, Connecticut 06472
150-9001
Engineering and Manufacturing
Quality System Certified to
lntemaUonal Standard ISO-9001 Made in the U.S.A.
ON-3251 -Page 1 of2
L
(_
ELECTRICAL CHARACTERISTICS
Power supply voltage: 20-29 voe 24 VAC, 50-60 Hz 120 VAC, 50-60 Hz 220/240 VAC,
50-60 Hz
Ripple voltage: 4Vpp NIA NIA NIA
Input capacitance: 270 µF max. 270 µF max. NIA NIA
Reset voltage: 3 VDCmln. 2VAC min. 10 VAC min. 20VAC min.
Reset time with RTS451 ): 0.03 kl 0.30 sec. 0.03 kl 0.30 sec. 0.03 kl 0.30 sec. 0.03 kl 0.30 sec.
Reset time (by power down): 0.6 sec. max. 0.6 sec. max. 0.6 sec. max. 0.6 sec. max.
Power up time: 34 sec. max. 34 sec. max. 34 sec. max. 34 sec. max.
Alann response time: 2 kl 17 sec. 2 kl 17 sec. 2 kl 17 sec. 2 kl 17 sec.
CURRENT & POWER REQUIREMENTS (using no accessories)
Maximum standby current: 25mA 35 mARMS 20 mARMS 20 mARMS
Maximum standby power: 1 Watt • 1 Watt avg. 3 Watts avg . 3 Watts avg.
Maximum alann current: 95mA 55 mARMS 55 mARMS 30 mARMS
Maximum alann power: 4 Watts 4 Watts avg. 4 Watts avg. 4 Watts avg.
CONTACT RATINGS
Alann lnttlatlon contacts (SPST): 2.0 A @ 30 VAC/OC (0.6 power lack>r).
Alann auxlllaiy contacts (DPDT): 10A@30VDC.
10 A@ 277 VAC (0.75 power lack>r).
240 VA @ 240 VAC (0.4 power facklr).
1/8 HP @ 120 VAC.
1/4 HP @ 240 VAC.
Trouble contacts (SPST): 0.3 A @ 32 VDC (resistive).
PRODUCT LINE INFORMATION
Model No. Description
DH400ACDCI DH400ACDC duct detector housing with ST-10
1451DH ionization sensor.
Metal sampling tube, duct widths 8' (1.2192
m) to 12' to (3.6576 m).
DH400ACDCP DH400ACDC duct detector housing with APA451
2451 photoelectric sensor.
1451DH Replacement ionization smoke detector RA400Z
head. PA400
2451 Replacement photoelectric smoke detector
head. M02-04-00
ST-1.5 Metal sampling tube, duct widths 1' (0.3048 RTS451 m) to 2' (0.6096 m). M0D400R ST-3 Metal sampling tube, duct widths 2' (0.6096 CRT-400 m) to 4 (1.2192 m).
ST-5 Metal sampling tube, duct widths 4' (1.2192
m) to 8' (2.4384 m).
Annunciator with piezo, alarm, and power
LEDs.
Remote annunciator alarm LED.
Piezo alert sounder ( offered in red [R], white
[W], or beige [BJ).
Test magnet.
Remote test station.
Sensitivity test kit.
Ionization cover removal tool.
ACCESSORY CURRENT LOADS AT 24 VDC
Any combination ot accessories may be used such that
the given current loads total:
• 100 mA or less In the Standby state.
• 15 mA or less In the Alann state.
*Note: When lnlUatlng en a/arm using the test magnet. The
RTS451 requires 11 mA maximum In pm-alarm and 18 mA In alarm.
Normal standby cu,rent Is O mA. The a/arm cum,nt drops to 7 mA
when the test magnet Is removed from the RTS451.
Pago 2 ol 2 -DN-3251
DEVICE
APA451
PA400
RA400Z
RTS451
STANDBY ALARM
12 mAmax. 30mAmax.
OmA 15mAmax.
OmA 7mAmax.
OmA* 7mAmax.*
(
(_
(_
(._ LISTING No.
CATEGORY:
LISTEE:
DESIGN:
INSTALLATION:
MARKING:
APPROVAL:
NOTE:
CALIFORNIA DEPAR'Tf,IENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STA TE FIRE MARSHAL
FIRE ENGINEERING DMSION
LISTING SERVICE
3240-1209: 155
Duct Detector Housing/Base
System Sensor, 3825 Ohio Avenue, St. Charles, IL 60174
Contact: Adam Kozlowksi (630} 377-6580
LIST1NG ExPIRES
J_UNE 30, 1999
Page 1 of 1
Duct smoke detector units, Models DH400, DH400ACDC, DH400ACDCIR,
DH400ACDCP5V, DH400ACDCl5V, DH400ACDCIHT•, DH400REL, DH500,
DH500ACDC, P270-1 OOOI and P270-1 OOOP. Unit consists of a housing, relay,
electrical components, sampling and exhaust tubes and a listed detector head.
Series DH400 and P270 are intended for use with Models 1451 DH (CSFM Listing
No. 7271-1209:126) and 2451 (CSFM Listing No. 7272-1209:131) detector heads
for open area protection which have been tested for duct applications. •Model
DH400ACDCIHT is intended for use with Model 1451 DHHT smoke detector
(CSFM Listing No. 7271-1209:126)
Series DH500 are intended for use with Models 1551 (CSFM Listing No. 7271-
1209:106) and 2551 (CSFM Listing No. 7272-1209:107) detector heads for open
area which have been tested for duct applications.
Refer to listee's data sheet for additional detailed product description and
operational considerations.
In accordance with listee's printed installation instruction, applicable codes and
ordinances and in a manner acceptable to the authority having jurisdiction.
Listee's name, model designation, air velocity rating and UL label.
Listed as duct detector units when used with listee's separately listed compatible
control units. Intended for use in HVAC systems having air velocities between
300 to 4000 ft/min.
Formerly 3240-1209: 137 & 139
THIS LISTING rs BASED UPON TECHNICAL DATA SUBMITTED BY THE APPLICANT. CSFM FIRE ENGINEERING STAFF HAS REVIEWED
THE TEST RESULTS AND/OR OTHER DATA BUT DOES NOT MAKE AN JNDEPENDENTVERIFlCATION OF AMY CL.AIMS. THIS USTING IS NOT
AN ENDORSEMENT OR RECOMMENDATION OF THE rrEM LISTED. THIS LISTING SHOULD NOT BE usmTOVERIFYCORREcrDPERATIONAL r "'EQUIREMENTS OR INSTA\.l..ATION CRITERIA. REFER TO USTEE'S DATA SHEET, INSTALLATION INSTRUCTIONS AND/OR OTHER
\..., JrTABLE INFORMATION SOURCES.
DATE ISSUED: MAY 15, 1998
EFFECTIVE ISSUE DATE TO EXPIRATION DATE
APPROVED BY:
PROGRAM COORDINATOR
FIRE ALARM • SECURITY • LOW VOLTAGE SYSTEMS
CARLSBAD AIRPORT CENTER #1
5857 OWENS A VENUE, CARLSBAD, CA 92008
FIRE ALARM SYSTEM
AB
Job 83o,:Q
8'/11/77
(_
(_
CARLSBAD AIRPORT CENTER #1
5857 OWENS A VENUE, CARLSBAD, CA 92008
FIRE ALARM SYSTEM
BILL OF MATERIALS
I NOTIFIER AFP-200 FIRE ALARM CONTROL PANEL
CSFM# 7165-0028:164
I NOTIFIER LCD-80 ANNUNCIATOR PANEL
CSFM# 7120-0028:156
I NOTIFIERBGX-I0IL MANUAL PULL STATION
CSFM# 7150-0028:003
6 NOTIFIER NBG-I0W MANUAL PULL STATION
CSFM# 7150-0028:139
7 NOTIFIER CPX-551 INTELLIGENT SMOKE DETECTOR/BX-SOI BASE
CSFM# 7271-0028: 149/7300-0028: 173
2 NOTIFIER SDX-551 INTELLIGENT PHOTO. SMOKE DET./BX-501 BASE
CSFM# 7172-0028: 148/7300-0028: 173
13 SYSTEM SENSOR P24 l 5/75K l Scd. WEATHERPROOF HORN/STROBE
2 SYSTEM SENSOR P2475K 75cd. WEATHERPROOF HORN/STROBE
1 SYSTEM SENSOR P24110K 1 !Ocd. WEATHERPROOF HORN/STROBE
CSFM# 7125-1209:182
2 SYSTEM SENSOR P2415 15cd. HORN/STROBE
CSFM# 7135-1209:173
6 SYSTEM SENSOR S2415 15cd. STROBE
CSFM# 7125-1209: 174
6* SYSTEM SENSOR DH400ACDCP DUCT DETECTORS BY OTHERS
CSFM# 3240-1209: 155
c.. * ONLY Cllf SHEETS ARE PROVIDED BY JJJ ENTERPRISES.
C.
-L
GENERAL
The AFP-200 is a compact, cost-effective, intelligent fire
alarm control with a capacity of 301 individually identified
and controlled points and an extensive 11st of powerful
features. The AFP-200 provides capabilities that exceed
most large intelligent systems, at a cost comparable to
conventional control panels.
FEATURES
198 intelligent device capacity (99 analog detectors and
99 monitor/control modules). Style 4, 6, or 7.
Overall 301 point capability (198 intelligent points, 4
programmable NAC circuits, 99 programmable relays).
Network ready (reference NOTI • FIRE• NET-and NAM-
232 catalog sheets for more information).
Intelligent features:
,/ Manual sensitivity adjustment.
,/ Day/Night automatic sensitivity adjustment.
,/ Drift compensation (U.S. Patent Pending) meets UL
requirements as a calibrated test instrument.
,/ Auto detector test (meets NFPA 72).
,/ Maintenance alert (two separate algorithms).
,/ Pre-alarm (AWACS"' U. S. Patent Pending).
,/ Activate local sounder base on pre-alarm.
,/ LED blink control for sleeping areas.
,/ Automatic device type check.
Releasing features:
,/ Four independent hazards.
,/ Sophisticated cross-zone (three options)
,/ Delay timer and Discharge timers (adjustable}.
,/ Abort (four options).
Optional DACT, with AC fail delay.
LCD-80 remote display/control.
ACS annunciators (EIA-485), including LDM custom.
Printer interface (80 column and 40 column printers).
5.0 A usable regulated output power, plus 3.0 A expander.
80 character LCD display, backlit.
Real lime clock, with European format option.
History file with 650 event capacity in nonvolatile memory.
Includes non-erasable shadow history.
Waterflow or supervisory selection per point.
Alarm Verification selection per point, with tally.
Walk Test reports 2 devices set to same address.
Positive Alarm Sequence (PAS) Presignal per NFPA 72.
Silence inhibit and Auto Silence timer options.
March time/temporal/California code for bell circuits.
Field-programmable on panel or on PC, with user-defined
passwords, plus Autoprogram feature.
UL-listed modem interface allows remote/off-site system
integration.
NOTl•FIRE•NET™ Is a trademark of NOTIFIER, 1994.
August 13, 1997
AFP-200
Analog Fire Panel
Software Release 2
A-102
Section: Intelligent Fire Alarm Control Panels
®@,~<§?
S635 CS118 for security)
~ I Califor~la U.S. Coast Guard State Fore 161 00212311 Marshal •
7165-0028:164 94/00004
TheAFP-200
16.125" H x 14.5" W X 5.5" D
MMX-2 two-wire detector interface provides compatibility
with many non-NOTIFIER detectors for retrofit applica-
tions ( consult factory for latest compatibility listings).
Dual rate charger for up to 90 hours of standby power.
Two-Stage option for bell circuits (Canada).
Tornado Warning activates different Notification Circuit
code.
Non-alarm points for lower priority functions.
Remote ACK/Silence/Reset/Drill via MMX modules.
Automatic time control functions, with holiday exceptions.
Rapid poll algorithm for manual stations. Responds in < 2
seconds.
Operates with untwisted, unshielded wire (up to 1000 feet)
for retrofit applications (U.S. Patent 5, 210, 523).
UL listed for Fire Signaling per Standard 864 & NFPA 72.
UL listed for Burglary applications per Standard 1076.
ULlistedforReleaslngperNFPA12, 12A, 12B, 13, 15, 16.
UL listed for Critical Process Monitoring.
FM approved for Agent Release and Preaction/Deluge.
Approved for marine applications by U.S. Coast Guard
and Lloyd's Register of shipping.
This document is not intended to be used for installation purposes. We t,y to keep our
product information up-to-date and accurate. We cannot cover all specific apprtcations or
anticipate ad requirements. All apecmcations are subject to change without notice. For
more Information, contact NOTIFIER. Phone: (203) 484-7161 FAX: (203) 484-7118
1S0-9001
Engineering and Manufacturing
Quality System Certified to
International Standard IS0-9001 @) N OTI Fl ER" 12 Clintonville Road, Northford, Connecticut 06472 Made In the U.S.A.
DN-3783 -Page 1 of 4
SYSTEM BLOCK DIAGRAM
NOTl•FIRE•NET Optional Network Interface
via the NAM-232
SLC Intelligent Loop
198 devices
SDX-551 CPX-551 FDX-551 --------------BGX-101L
EIA-485 99 software zones
X
MMX-1 t
IDC
AFP-200
Four standard
Notification or
Releasing
circuits.
Full Alpha
keyboard for
menu-driven
programming.
5 ampere
regulated
power supply.
Voltmeter/
Ammeter
Option.
Page 2 of 4 -DN-3783
4 Notification or
Release Circuits
RS-232
PRN-4 Printer
EIA-232 Interface for CRT,
printer, or PC computer.
ACM-SR
Relay
Control
CRT-2
12 AH batteries.
Up to 90 hours standby power_
ACM/AEM-16AT
LED Annunciator
LDM-32 Custom Graphics
EIA-485 loop for
LCD or LED
annunciators.
SLC loop.
Up to 198 devices
on a single pair
of wires.
Slot for
optional
module.
80 character backlit
LCD display.
CMX-2
!
IAC
C
(_
C
AWACS™ Advance Warning Addressable Combustion Sensing (U.S. Patent Pending)
SMOKE OBSCURATION
% per foot
3% ALERT ACTION
Shut off power Warning at panel
of possible fire to equipment monitored
by this detector
ALARM
Evacuate building
and call fire department
2%
1%
PREALM SMOKE(PHOTOI
FLOOR 3 EQUIP RACK 6
ALERT: 0.22% 1.40%
II :26 P 12/26193 066
TIME
PREALM SMOKE(PHOTOI
FLOOR 3 EQUIP RACK 6
ACTION: 0.61% 1.40%
11:36 P 12/26193 066
ALARM: SMOKE(PHOTOI
FLOOR 3 EQUIP RACK
FIRE DEPT CALLED
11 :69 P 12/26193
ALERT and ACTION levels are completely adjustable in the field to suit the cleanliness and stability of the environment.
ALARM levels are field adjustable to one of 3 levels within the UL permitted range. ACTION levels latch and may be
used to perform control functions. ALERT levels self-restore and may be used to activate a local sounder base before
general ALARM evacuation.
FIELD PROGRAMMING -3 WAYS
1. AUTO-PROGRAM
The AFP-200 identifies all devices that are connected,
determines the type of device, and loads default values
(general alarm) into non-volatile memory. This is com-
pleted in less than 30 seconds.
2. ON-LINE EDIT
While still providing fire protection, the AFP-200 program
may be completely edited from the front keypad. Menu
trees permit easy change of any parameter without refer-
ral to the programming manual. Recall, increment and edit
function speeds entry of alphanumeric labels. New pro-
gram check routine catches common errors.
3. OFF-LINE PC
The complete AFP-200 program may be created in
an off-line PC compatible computer, then loaded
into the AFP-200 EIA-232 port. The program may
also be off-loaded to a PC at any time. High speed
data transfer completes upload or download In less
than 1 minute. The PC program may also be used
to access remote AFP-200 systems over dial-up
phone lines, providing detail status information and
history file search/sort.
AUTOPROGRAM
PLEASE WAIT
0= CLR 1 =AUTO 2= POINT
3 = PASSWD 4 = MESSAGE
5 = ZONES 6 = SPL ZONES
7 = SYS 8 = CHECK
DN-3783 -Page 3 of 4
AGENCY LISTINGS AND APPROVALS
See page 1 for listing agencies and file numbers. These
listings and approvals apply to the basic AFP-200 control
panel. In some cases, certain modules may not be listed
by certain approval agencies, or listing may be in process.
Consult factory for latest listing status.
SPECIFICATIONS
Primary input power, 120 VAC, 50/60 Hz, 3.0 Amps.
Total Internal 24 VDC Power-5.0 A (total shared power).
ti' High Ripple Regulated Power -1.5 A (suitable for
EIA-485 devices, except ACM-8R) -1.0 A max.
standby.
ti' Non-resettable Power -500 mA.
ti' 4-wlre Smoke Detector Power • 500 mA.
ti' Four built-in Notification Circuits
• NAC Circuit 1 -2.25 A
• NAC Circuits 2-4 -2.25 A (shared total)
Note: with optional AVPS Power Supply NAG circuits 3 &
4 are expanded to 3.0 A (8.0 A total power).
Battery charger range: 7 AH -17 AH.
Charge high rate: 29.1 V. Float Rate: 27.0 V.
Relay contact rating: 2.0 A @ 30 VDC.
SYSTEM CAPACITY
Total programmable input/output points: 301
Intelligent Detectors: 99
Addressable monitor/control modules: 99
Programmable NAC (bell) circuits in panel: 4
Programmable software zones: 99
Programmable remote relay/annunciator points: 99
LCD-80 annunciators per system: 4
ACS annunciators per system: 10
CONTROLS AND INDICATORS
6 LED Indicators: AC Power; Fire Alarm; Pre-Alarm; Su-
pervisory/Security; Alarm Silenced; System Trouble.
21 Membrane Switch Controls: Acknowledge/Step; Si-
lence; Evacuate; System Reset; 12 key Alpha pad; 4
cursor keys; Enter.
LCD Display: 80 characters (4 X 20) with long-life LED
backlight.
COMPATIBLE INTELLIGENT DEVICES
Model
CPX-551
CPX-751
SDX-551
SDX-751
SDX-551TH
FDX-551
FDX-551R
BX-501
B710LP
B501BH
DHX-501
DHX-502
MMX-1
MMX-2
MMX-101
CMX-2
BGX-101L
ISO-X
Description
Ionization Smoke Detector.
Low Profile Ionization Detector.
Photoelectric Smoke Detector.
Low Profile Photoelectric detector.
Photoelectric with thermal element.
Fixed Thermal (Heat) Sensor.
Fixed and Rate-of-Rise thermal sensor.
Detector Base, high profile.
Detector Base, low profile.
Sounder Base.
Duct Housing with Alarm relay.
Duct Housing without Alarm relay.
Monitor Module.
Two wire detector monitor module.
Miniature Monitor Module.
Control Module
Manual Fire Alarm Station, Addressable.
Isolator Module.
WordPerfect® is a registered trademark
of WordPerfect Corporation.
Page 4 of 4 -DN-3783
COMPATIBLE DEVICES, EIA-232 Port
Model
PRN-4
VS4095/S2
CRT-2
NAM-232
Description
80 column printer.
Printer, 40 column, 24 V. Mounted in exter-
nal backbox (Order from Keltron, Inc.).
Video display terminal.
Network Interface Module to NOTl •FIRE•
NET wire or fiber models.
COMPATIBLE DEVICES, RS-485 Port
Model Description (see catalog sheets)
ACS Serles Remote Serial Annunciator/Control systems.
LCD-80 Remote LCD display.
LDM Serles Remote custom graphic driver modules.
ACM-BR Remote relay module. 8 Form-C relays.
NIB-96 Network Interface Board.
RPT-485 Serles Repeater, Isolator and/or fiber optic
modem.
UDACT Universal Digital Communicator.
PRODUCT LINE INFORMATION
Model Description
BEAFP-200G -Basic AFP-200 equipment kit. Includes
main board with display and keypad, door, hardware
and manual. Backbox (SBB-4X or SBB-4XR) ordered
separately.
BEAFP-200R -Same as BEAFP-200G, but includes a red
door.
BEAFP-200GE -Same as BEAFP-200G but 230 VAC.
BEAFP-200RE • Same as BEAFP-200R but 230 VAC.
SBB-4X -AFP-200 Backbox (no door), gray.
SBB-4XR • AFP-200 Backbox (no door), red.
CAB-AM -Heavy duty outer enclosure. Required for ma-
rine agency approved applications.
4XTM • Plug-in Transmitter Module. Provides municipal
box & remote station connection.
RTM-8 • Plug-in Relay Transmitter Module. Provides 8
Form-C relays, plus transmitter.
4XMM • AmmeterNoltmeter.
TR-4XG • Gray Trim Ring for semi-flush mounting (TR-
4XR for red).
DP-AFP200 -Full length dead front panel (required for
Canadian Applications).
PS-1270 -Battery, 12 volt, 7.0 AH, (two required).
PS-12120 • Battery, 12 volt, 12.0 AH, (two required).
PS-12170 • Battery, 12 volt, 17 .0 AH (two required).
AVPS-24 • 3.0 A Expansion supply (requires BB-17).
BB-17 -Battery box, required for PS-12170, or if AVPS-24
Is used.
911AC • Digital Alarm Communicator!Transmitter.
PK-200 • Programming kit for PC. Includes diskette,
cable, and instructions.
ROM-AFP200SP • Spanish language kit. Includes soft-
ware IC, manual and labels.
ARCHITECTURAL/
ENGINEERING SPECIFICATIONS
Complete specifications are available on 3.5" (1.44 mbyte)
IBM compatible diskette, in WordPerfect & ASCII formats.
C
L
LISTING No.
CATEGORY:
LISTEE:
DESIGN:
INSTALLATION:
MARKING:
APPROVAL:
LALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING DIVISION
LISTING SERVICE
7165-0028: 164
Control Units (Non High-Rise)
Notifier, 12 Clintonville Road, Northford CT 06472-1001
Contact: Larry Flood (203) 484-1200
LISTING EXPIRES
JUNE 30, 1999
Page 1 of 1
Model AFP-200 fire alarm control unit. Local, auxiliary, remote station (PPU),
proprietary (PPU) and central station (PPU). Also suitable for releasing device
service. Refer to listee's data sheet for additional detailed product description
and operational considerations. System components:
4XTM
RTM-8
DP-AFP200
TR-4XG
MMX-1, -101
ISO-X
N-ELR
CRT-2
VS4095/5
CMX-1
BB-17
AVPS-24
NAM-232
4XMM
Transmitter Module
Relay Module
Dress Panel
Trim Ring
Monitor Module
Loop Isolator Module
EOL Resistors
Terminal with Keyboard
Printer
Control Module
Battery Box
Power Supply
Network Adapter Module
Meter Module
In accordance with listee's printed installation instructions, NFPA 72, applicable
codes & ordinances and in a manner acceptable to the authority having
jurisdiction.
Listec's name, model number, electrical rating and UL label.
Listed as fire alarm control unit for use with separately listed compatible
initiating and indicating devices. Suitable for central station (PPU) service
when used with separately listed compatible DACT.
*This control unit can generate the distinctive three-pulse Temporal Pattern Fire
Alarm Evacuation Signal (for total evacuation) in accordance with NFPA 72,
1993 Edition. Refer to manufacturer's Installation Manual for details.
• Corrected 05-12-98
THIS LISTING IS BASED UPON TECHNICAL DATA SUBMITTED BY THE APPLICANT. CSFM FIRE ENG!NEERING STAFF HAS REVIEWED
THE TI$T RESULTS AND/OR OTHER DATA BUT DOES No·r MAKE AN IND:!::PENDENT VERIFICATION OF ANY CLAIMS. THIS LISTING IS NOT
AN EHOORSEMENT OR RECOMME'NDATION OF THE ITEM UaTED. THIS LISTING SHOULD NOT BE USED TO VERlrY CORRECT OPERATIONAL
REQUIREMENTS OR INSTALLATION CRITERIA. REFER TO USTEE'S DATA SHEEl", INSTALLATION INSTRUCTIONS AND/OR OTHER
SUIT ABLE INFORMATION SOURCES.
C DATE ISSUED: MAY 12, 1998
EFFECTIVE ISSUE DATE TO EXPIRATION DATE
APPROVED BY:
PROGRAM COORDINATOR
C
C
c..
GENERAL
The LCD-80 is an BO-character, backlit LCD display annuncia-
tor for the NOTIFIER AM2020, AFP1010, AFP-400, AFP-300,
AFP-200, System 5000, and System 500 fire alarm control
panels. Up to 32 LCD-80s may be connected onto the two-
wire EIA-485 port. The LCD-80 has two basic modes of op-
eration, "Terminal" and "Acs· mode.
COMMON FEATURES
BO-character Liquid Crystal Display (20 characters x 4 lines),
backlighted.
Control switches for System Acknowledge, Signal Silence
and System Reset.
Time and date display field.
Enable Key switch and phone jack options.
Can be remotely located up to 6,000 feet from the control
panel.
Local piezo sounder with alarm/trouble resound.
Flush/surface/panel mount option.
Optional RPT-485 repeater increases the distance and num-
ber of LCD-80s in a system (see RPT-485 catalog sheet).
Optional transmission over fiber optics (see RPT-485 cata-
log sheet).
ACS MODE
When operated in "ACS" mode, the LCD-80 provides a re-
mote or local digital display and printer interface for the Sys-
tem 5000 and System 500. For the AM2020, AFP1010, AFP-
400, AFP-300, and AFP-200, the LCD-80 provides a vectored
annunciation capability. Individual devices/zones can be in-
staller-defined to only display and print at specific locations
(EXAMPLE: A maintenance office receives only non-alarm
point activations. These inputs could be sump pump on, high
water, backup AHU on, low temperature in freezer, etc.).
Alarm/trouble count.
Custom "normal" message.
European option: first alarm/last alarm/alarm count.
Field-programmable messages from CRT or PC-compatible
computer (PK-LCD-80 Programming Kit required).
EIA-485 interface: up to 32 per system.
Printer output port: RS-232, compatible with PRN Series
printers.
Field-programmable messages in nonvolatile memory In two
options: 128 points, 40 character labels; or 256 points, 20
character labels.
Internal nonvolatile clock for time and date.
AM2020, AFP1010, AFP-400, and AFP-300 "vectored"
printer capability.
Can be mounted in a System 5000 cabinet module position.
TERMINAL MODE
(AM2020, AFP1010, AFP-400, AFP-300,
and AFP-200 ONLY)
In Terminal Mode, the LCD-80 mimics the AM2020, AFP1010,
AFP-400, AFP-300 and AFP-200 displays. Up to 32 LCD-80s
May 1, 1998 D-120
LCD-80
Liquid Crystal Display
Section: Annunciator Control Systems
®@<8>
QV7AO.AY
MEA
290-91-E
289-g1-E
S635 CS100
LCD-BO
California
State Fire Marshal
7120-0028:156
(shown with ABF-1 flush backbox)
can annunciate and provide remote reset, acknowledge, and
silence of the control panel from remote locations. The DIA-
1010 and DIA-2020 (Display Interface) include a terminal mode
driver port for LCD-80s in terminal mode. The Terminal mode
port is standard on the AFP-400, AFP-300, and AFP-200 main
PC/CPU boards.
Displays device type Identifiers.
Device and zone custom alpha labels.
Time/date and Device address.
May operate in addition to CRT.
No programming necessary. LCD-80 displays lime, date,
and custom messages received from AM2020, AFP1010,
AFP-400, AFP-300, or AFP-200.
This document is not intended to be used for installation purposes. We try to keep our
product information up-to-date and accurate. We cannot cover all specific applications or
anticipate all requirements. All specifications are subject to change without notice. For
more information, contact NOTIFIER Phone: (203) 484-7161 FAX: (203) 484-7118
ISO-9001
Engineering and Manufacturing
Quality System Certified to
lnternellonal Standard 150-9001 (ffi} N OTI Fl ER" 12 Clintonville Road, Nor1hford, Connecticut 06472 Made in the U.S.A.
ON-3198 -Page 1 of 2
The LCD-BO in ACS Mode LCD-80 is 8-1/4" (20.96 cm) high, 4-3/8" (11.11
cm) wide, and 1-3/4" (4.45 cm) deep.
EIA-232, 4 wires
50 feet maximum
PRN Printer
Up to 32 LCD-80s may be used on one EIA-
485 circuit.
NOTE: Must have sufficient regulated 24 volt
power. Certain NOTIFIER systems may have
limits to the amount of LCD-B0s with ACK/STEP.
Signal Silence, and Reset switches.
--·-------------
LCD-80 mounts with any CHS-4 chassis slot.
The LCD-80 may display all System 5000 cir-
cuits. Alternately, it may display up to 192
AIM-200 points and two rows of modules. , .... 0~"'"'
System 5000 with
panel-mounted LDC-BO
---------
CJ •0«~0,1>
System 5000, System 500, AM2020,
AFP1010, AFP-400, or AFP-300
6,000 feet maximum total wire length.
EIA-4B5 (2 wires)
24VDC
(2 wires) -~-
CJ
DD
DD
TO DD
PRN LCD-BO PRINTER
EIA-4B5
(2 wires)
24VDC
(2 wires)
TO
PRN
PRINTER
CJ
DD
DD
DD
LCD-BO
EIA-4B5
(2 wires)
24VDC
(2 wires)
TO
PRN
PRINTER
The LCD-BO in Terminal Mode
6,000 feet maximum wire length
Tenninal Mode between each LCD-BO EIA-4B5
(2 wires) CJ CJ CJ
24VDC DD DD DD
(2 wires) DD DD DD
DD DD DD
LCD-80 LCD-BO LCD-BO
EIA-232 ! AM2020, Terminal Mode EIA-4B5 return (2 wires) Printer Port AFP1010, L...---------------~
AFP-400, AFP-300, Up to 32 LCD-80s may be used in a continuous 4-
or AFP-200 wire loop (verify sufficient 24 voe available).
Each may have ACK/STEP, SIGNAL SILENCE,
PRN Printer and SYSTEM RESET switches.
RELATED OPTIONS
Displays all analog, addressable points.
No programming required for LCD-80s.
CJ
DD
DD
DD
=□ LCD-BO =□ =□ =□ =□ =□
ABF-1D -The ABF-10 is a
semi-flush-mount backbox for
the NOTIFIER LCD-80 Series
Annunciator. The ABF-10
mounts one LCD-80. It in-
cludes an attractive smoked-
glass door with NOTIFIER
keylock.
Dimensions, BOX only:
9-15/16" (25.24 cm) high,
4-5/8" (11.75 cm) wide,
2-1/2" (6.35 cm) deep.
Dimensions, DOOR only:
10.713" (27.21 cm) high,
6" (15.24 cm) wide,
0.75" (1.9 cm) deep.
PK-LCD-BO
CCM-1
Off-Line Programming Kit for LCD-80. Allows PC programming messages when the LCD-80 is used in the ACS
mode.
ABF-1D
ADP-4
ABF-1
ABS-1T
AKS-1
APJ-1
PRN Serles
RPT-4B5W
RPT-4B5F
Converter Module. Required for tenminal mode operation on older AM2020s or AFP1010s that do not include
the DIA-2020 or DIA-1010 Display Interlaces. Also required for AM2020 and AFP1010 systems which require
a CRT with keyboard. Uses one ICA-4 chassis slot or two CHS-4 chassis slots.
Semi-flush box with alternative smoked-glass door, any keylock.
Annunciator Dress Plate. Allows panel mounting of up to four LCD-80 modules in a CAB-X3 Series cabinet.
Annunciator Flush Box, 9-15/16" (25.24 cm) high, 4-5/8" (11.75 cm) wide, and 2-1/2" (6.35 cm) deep. Order
AKS-1 key-switch and APJ-1 phone Jack if desired. Can also be mounted in ABF-2 or ABF-4 annunciator
backboxes.
Deep Surface Backbox (mounts one LCD-80).
Keyswitch to enable/disable controls when mounted in ABF or ABS-1T.
Annunciator Phone Jack. Mounts to ABF flush box or ABS-1T.
BO-Column Serial Printer.
EIA-485 Wire Repeater. Increases wire distance between LCD-80s.
EIA-485 Fiber-Optics Repeater. Increases distance and converts EIA-485 wire to fiber-optics.
Page 2 of 2 -DN-3198
L LISTING No.
CATEGORY:
LISTEE:
DESIGN:
INSTALLATION:
MARKING:
APPROVAL:
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING DIVISION
LISTING SERVICE
LISTING EXPIRES
JUNE 30, 1999
71 20-0028: 1 56 Page 1 of 1
Annunciators
Notifier, 12 Clintonville Rd., Northford CT 06472-1653
Contact: Larry Flood (203) 484-1200
Model ACS annunciator control system. Refer to listee's data sheet for
additional detailed product description and operational considerations. Unit
consists of the following modules:
ACM-16AT
AEM-16AT
AEM-32A, ACM-32A
AFM-16AT, AFM-32A, AFM-16A
ABM-1 6A T, ABM-32A
ABS-1, ABS-2
ABF-1, -1D•, -2, -2D•, -4
ADP-4
AKS-1
LCD-80, -80TM•
LDM-32
LDM-E32
LDM-R32
ACM-8R
Control Module
Expander Module
Control Module
Fixed Module
Blank Module
Enclosures (Surfoce)
Enclosures (Flush)
Dress Panel
Key Switch
Control Panel
Lamp Driver Module
Lamp Driver Expander
Lamp Driver Expander (Relay)
Mappable Relay Control Module
In accordance with listee's printed installation instructions. applicable codes &
ordinances and in manner acceptable to the authority having jurisdiction.
Listee's name, product number, electrical rating and UL label.
Listed as an annunciator system when used in conjunction with separately listed
compatible fire alarm control units.
• Rev. 02-1 3-96
THIS LISTING IS BASED UPON TECHNICAL DATA SUBMITTED BY THE APPLICANT. CSFM FIRE ENGINEERING STAFF HAS
R5:VIEWED TH!!: TEST RESULTS AND/OR OTHER DAT.-' BUT DOES NOT MAKE AN INDEPENDENT VERIFICATION OF ANY CLAIMS.
THIS LISTING I!. NOT AN ENDORSEMENT OR RECOMMENDATION OF THE ITEM LISTED, THIS LISTINC'i SHOULD NOT BE USED TO
VERIFY CORRECT OPERATIONAL REQUIREMENTS OR INSTALLATION CRITERIA. REFER TO USTEE'S DATA SHEET, INSTALLATION
INSTRUCTIONS ANO/OR OTHER SUITABLE INFORMATION SOURCES.
C..JATE lssuc:o: APRIL 24, 1998 A!"PROVED BY: ~ EFFECTIVE ISSUE OATC TO EXPIRATION D.A.TE
PROGRAM COORDINATOR
(_
(.
C
GENERAL
The BGX-101L is an addressable manual pull station with a
key-lock reset feature. It provides the AM2020, AFP1010,
AFP-400, AFP-200, and System 5000 (equipped with an
AIM-200 module) with one addressable alarm initiating in-
put.
FEATURES
Within ADA 5 lb. pull force when used without break-tube
(models manufactured after 10-1-96, identified by an 0
under station spring).
Highly visible.
Easily operated (dual-action).
Attractive shape and textured finish.
Semi-flush, mounts to a standard single-gang (2.125" mini-
mum depth), double-gang, or 4" square electrical box.
Operates with or without a crush tube.
Handle latches in down position to clearly indicate the
station has been operated.
Key reset.
Screw terminals for easy connection to SLC Loop Channel.
Optional trim ring.
Meets UL 38, Standard for Manually Actuated Signaling
Boxes.
CONSTRUCTION
Shell, door, and handle are molded of durable LEXAN® (or
polycarbonate equivalent) with a textured finish.
16 gauge steel back plate.
OPERATION
Pulling the handle down causes it to latch in the down posi-
tion. The handle is restored manually by using a mechani-
cal key which allows the top of the case to pivot forward and
the spring-loaded handle to return to its normal position.
The case can then be pivoted back to its normal position
and secured with the key.
Each manual station, on command from the control panel,
sends data to the panel representing the state of the manual
switch. Two rotary decimal switches allow two-digit address
setting.
LEXAN® is a registered lrademark of GE Plastics, a subsidiary of
General Electric Company.
November 14, 1996 H-130
BGX-101L
Addressable Manual Pull Station
Section: Intelligent/Addressable Devices
Iii:\ -\!.!,I 0V4A5.AY
S692 (AFP-200)
0W6A2.AY
(AM-2020/AFP1010)
ADA
I Calffomla
State Fire
Marshal
7150-0028:003
~
93/00141
The BGX-101L
Addressable Manual Pull Station
PRODUCT LINE INFORMATION
Model Description
BGX-101L Standard unit. Dual action. Works with, or
without, a fiber crush-tube. Includes key
locking feature.
BG-TR Optional trim ring. 6-1/2" High, 5-1/8" Wide,
5/32" Deep.
SB-10 Surface backbox.
This document Is not Intended to be used for Installation purposes. We try to keep our
product Information up-to-date and accurate. We cannot cover all specific applJcations
or anticipate all requirements. All spadftcatlons are subject to change without notice.
For more infonnation, contact NOTIFIER. Phone: (203) 484-7161 FAX: (203) 484•7118
@) N OTI Fl ER" 12 Clintonville Road, Northford, Connacticut 06472
ISO-9001
Engineering and Manufacturing
Qualily Syslem Certified lo
lnlemalional Slendard 150-9001 Made In the U.S.A.
DN-3189 -Page 1 of 2
INSTALLATION
The BGX-101L will mount semi-flush into a single-gang,
double-gang, or standard 4• square electrical outlet box,
or will surface mount into the Model SB-1 0 surface backbox.
If the BGX-101L is being semi-flush mounted, then the
optional trim ring (BG-TR) may be used. The BG-TR is
usually needed for semi-flush mounting with 4" or double-
gang boxes (not with single-gang boxes).
ELECTRICAL SPECIFICATIONS
Normal operating voltage: 24 VDC.
Maximum SLC loop voltage: 28.0 VDC.
Maximum SLC loop current: 230 µA.
ARCHITECTURAL/
ENGINEERING SPECIFICATIONS
Manual Fire Alarm Stations shall be addressable, fiber
break-tube (or non-fiber break-tube) type, equipment with
a key operated test-reset lock in order that they may be
tested, and so designed that after emergency operation,
they cannot be restored to normal except by using a key.
An operated station shall automatically condition itself so
as to be visually detected, as operated, at a minimum
distance of one hundred feet, front or side.
Manual stations shall connect with two wires to one of the
control panel SLC loops. The manual station shall, on
command from the control panel, send data to the panel
representing the state of the manual switch. Manual sta-
tions shall provide two-digit address setting by use of ro-
tary decimal switches.
Manual stations shall be constructed of LEXAN® (or poly-
carbonate equivalent) with clearly visible operating instruc-
tions provided on the cover. The word FIRE shall appear
on the front of the stations in raised letters, 1.75 inches or
larger. Stations shall be suitable for surface mounting on
matching backbox, or semi-flush mounting on a standard
single-gang, double-gang box, or 4 inch square box, and
shall be installed within the limits defined by the Ameri-
cans with Disabilities Act (ADA) dependent on manual
station accessibility or per local requirements. Manual
stations shall be Underwriters Laboratories Inc. listed.
1,1 .~." '" '117 I Tli[N I
--'
IPULLYDOWNI
, NOTIJ'U:n
Page 2 of2 -DN-3189
•
The SLC Loop Channel ---
The BGX-101 L (back view)
--------. r
View from
TOP
View from
SIDE 5-1/2"
j
(_
(_
LISTING No.
CATEGORY:
LISTEE:
DESIGN:
INSTALLATION:
MARKING:
APPROVAL:
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING DIVISION
LISTING SERVICE
7150-0028:003
Boxes/Pull Stations
Notifier, 12 Clintonville Rd·., Northford CT 06472-1653
Contact: Lawrence Flood (203) 484-1200
LISTING EXPIRES
JUNE 30, 1999
Page 1 of 1
Models BG, BG-1-2W, BGX-101L, BNG, BNG1-SP, BRG, MG and MS series.
Models BG-1-2W and BG-1-2-WTS are suitable for outdoor use. Refer to listee's
data sheet for detailed product description and operational considerations.
In accordance with listee's printed installation instructions, applicable codes
and ordinances and in a manner acceptable to the authority having
jurisdiction.
Listee's name, model number, electrical rating and UL label.
Listed as manual pull stations for use with separately listed compatible control
units.
Rev. 11-30-93
THIS LISTING IS BASED UPON TECHNICAL DATA SUBMITTED BY THE APPLICANT. CSFM FIRE ENGINEERING STAFF HAS
RIEVIEWED THE T~ST RESULTS AND/OR OlHER DATA BUT DOES NOT MAKE AN INDEPENDENT VERIFICATION OF ANY CLAIMS.
THIS LISl ING IS NOT 4.N F-HDORSE::MENT OR RECOMMENDATION OF THF ITEM LISTED. THIS LISTING SHOULD NOT BE USED TO
VERIFY CORRECT OPERATIONAL REQUIREMENTS OR INSTALLATION CRITERIA. REFER TO USTEF.'S DATA SHEET, INSTALLATION
INSTRUCTIONS AND/OR OTHER SUITABLE INFORMATION SOURCES.
(.. DATE ISSUED: APRIL 23, 1998 APPROVED BY:
EFFECTIVE ISSUE OA:t TO EXPIRATION DATE
DEPUTY BEN HO
PROGRAM COORDINATOR
C.
(_
GENERAL
The NOTIFIER model NBG-10 is a non-coded, dual action,
manual alarm station.
FEATURES
Within ADA 5 lb. pull force when used without break-tube
(models manufactured after 10-1-96, identified by an ®
under station spring).
Highly visible (red color with white lettering).
Easily operated.
Attractive shape and textured finish.
Semi-flush mounting on a standard single-gang electrical
box.
Operates with or without a break tube.
Handle latches in down position to clearly indicate that
the station has been operated.
Optional lock with key.
Optional N.O. contact for auxiliary functions.
Optional pre-signal circuit may be used for pre-signal or
Institutional Applications.
Spanish (FUEGO) version.
Meets UL 38, Standard for Manually Activated Signaling
Boxes.
APPLICATIONS
Use to provide a convenient means to manually initiate a fire
alarm.
CONSTRUCTION
Shell, door, and handle are molded of red colored LEXAN®
(or polycarbonate equivalent) with a textured finish and
white lettering.
Back plate made of 16 gauge steel.
Switch contacts are normally open.
INSTALLATION
For semi-flush mounting, attach directly to a standard single-
gang electrical box. Terminal block with screws allows quick
installation.
OPERATION
Pulling the handle down causes it to latch in the down posi-
tion and to close the normally-open switch. The handle is
restored manually by unscrewing the alien-head screw so
the top of the case can pivot forward, allowing the spring-
loaded handle to return to its normal position. The case can
then be pivoted back to its normal position and secured with
the alien-head screw.
The NBG-10L utilizes a mechanical key instead of the alien-
head screw.
The NBG-10 PfT has a normally-open auxiliary switch which
is closed by rotating a key clockwise (the key Is non-remov-
able in this position).
March 30, 1998
NBG-10 Series
Non-Coded
Manual Fire Alarm Station
Section: Conventional Initiating Devices
1-420
® <8> I California
F M ill ~t:::h~\re
7150-0028:139
1R0A0.AY s535 (except NBG-10SP)
ADA
SPECIFICATIONS
Physical:
IIBG-10 s.B:.1JI we:1.0.
Height: 5.50" 5.50" 6.00"
Width: 4.13" 4.13" 4.69"
Depth: 1.38" 1.38" 2.00·
Electrlcal: Current Capacity: 3 Amps@ 125 VAC.
LEXAN® is a registered trademark of GE Plastics, a subsidiary
of General Electric Company.
This document is not intendad to be used for installatk>n purposes. We by to keep our
product information up-to-date and accurate. We cannot cover all specific applications or
anticipate all requirements. All specifications are subject to change without notice. For
more information, contact NOTIFIER. Phone: (203) 484-7161 FAX: (203) 484-7118
150-9001
Engineering and Manufacturing
Quality System Certified to
International Standard IS0-9001 ~ N OTI Fl En· 12 Clintonville Road. Northtord, Connecticut 06472 Made In the U.SA.
DN-1668 -Page 1 of2
WIRING OF
STANDARD
UNIT:
NBG-10
TO
CONTROL PANEL +----+-~
DETECTOR
LOOP OUTPUT
TO NEXT DEVICE
OR E.L.R.
Additional Switch
Included With Models:
NBG-10A
NBG-10T
TO
TERMINAL BLOCK
FOR N.O. CONTACT +--~
FOR AUXILIARY
FUNCTIONS
Additional Switch (Key Operated)
Included With Model:
NBG-10P
TO
TERMINAL BLOCK
FOR TEST, OR TO
PRESIGNAL CIRCUIT+----~
(KEY OPERATED)
Page2of2 -DN-1668
PRODUCT LINE INFORMATION
Model
NBG-10
NBG-10A
Description
Standard unit. Dual action. Works with, or without,
a crush tube. Includes a terminal block with screws
for fast and easy wiring.
Standard unit plus an auxiliary N.O. switch to pro-
vide annunciator contacts.
NBG-10T Standard unit (NBG-10) with key test features.
NBG-10P Standard unit plus N.O. switch for pre-signal opera-
tion.
NBG-10L Standard unit plus key-locking feature.
NBG-10WP Standard unit plus weatherproofing. Includes sur-
face weatherproof box (NWP-10).
NBG-1 0SP Spanish version of standard unit. Dual action. Works
with or without crush tube. Includes terminal block.
WP-10 Weatherproof surface backbox for NBG-10WP.
SB-10
BG-TR
Surface backbox for all NBG-10 models.
Optional trim ring.
ARCHITECTURAL/
ENGINEERING SPECIFICATIONS
Manual Fire Alarm Stations shall be non-code, break-tube (or non-
crush tube) type, with a key-operated test-reset lock in order that
they may be tested, and so designed that after actual Emergency
Operation, they cannot be restored to normal except by use of a
key. An operated station shall automatically condition itself so as
to be visually detected, as operated, at a minimum distance of
one hundred feet, front or side. Manual stations shall be con-
structed of red colored LEXAN® with clearly visible operating in-
structions provided on the cover. The word FIRE shall appear on
the front of the stations in raised white letters, 1.75 inches or larger.
Stations shall be suitable for surface mounting on matching
backbox, or semi-flush mounting on a standard single-gang box,
and shall be installed within the limits defined by the Americans
with Disabilities Act (ADA) dependent on manual station accessi-
bility or per local requirements. Manual Stations shall be Under-
writers Laboratories listed.
'I f-'U"I l'J I I T,IIIJ
f'Ul I V DO,' tJ
.. OT1ru::r.t
4-1/&·
(lD4.B mm) View from
\ l TOP
: ______ __! ------..
: 1-319• : 1-1/8· Jc--
(34.9) l <28.6( Qptlonal
: 1-3/8 : Surface : (34.9) : Backbox -l
:
5-112" View from
] .. SIDE
1.-2-3/4· -....l
: (69.9 mm) :
(_ LISTING No.
CATEGORY:
LISTEE:
DESIGN:
INSTALLATION:
MARKING:
APPROVAL:
XLF:
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFla OF THE STATE FIRE MARSHAL
FIRE ENGINEERING -BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
7150-0028: 139
Pull Station/Boxes
listing Expires
June 30, 2000
Page 1 of 1
Notifier, A Pittway Company, One Fire-Lite Place, Northford CT 06472-1653
Contact: Larry Flood (203) 484-1200
Models NBG-10, NBG-10A, NBG-10N, NBG-10L, NBG-10P, NBG-10T, NBG-
10WP, NBG-10SP, NAR-10 AND N-ARA-10 manual pull stations. Units are
intended for indoor use and are intended to be mounted to a listed •outlet box or
Model SB-1 0 surface back boxes. Model NBG-1 0WP is suitable for outdoor use.
Refer to listee's data sheet for additional detailed product description and
operational considerations.
In accordance with listee's printed installation instructions, applicable codes &
ordinances and in a manner acceptable to the authority having jurisdiction.
Listee's name, model number and UL label.
Listed as manual pull stations for use with separately listed compatible fire alarm
control units.
7150-0075:103
•Rov. 04-03-97
This listing is based upon technical data submitted by the applicant CSFM Fire Engineering staff has reviewed the test results and/or
other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the
item listed. This listing should not be used to verify correct operational requirements or installation aiteria. Refer to listee's data sheet,
installation instructions and/or other suitable Information sources. •
C"latelssued: JULY 1, 1999
fective Issue date to expiration date
Authorized By:
BEN HO, Deputy State Fire Marshal Ill
Program Manager
(_
GENERAL
The CPX-551 Intelligent Ionization Detector is used with
the AM2020 Advanced Multiplex System, AFP1010, AFP-
400, AFP-300, AFP-200, and System 5000 (with AIM-200
module) to sense products-of-combustion and report the
measured level of such products in analog form to the
control panel. The use of analog information provides sig-
nificant benefits to the end user, installer and service per-
sonnel in ways not possible with a conventional-type sys-
tem. Since the CPX-551 is also addressable, it will help
firefighters to more quickly locate a fire during its early
stages.
FEATURES
Unique unipolar dual chamber provides exceptional sta-
bility.
Factory preset at 1.06% nominal sensitivity for panel
alarm threshold level.
Fully coated circuit boards and superior RF/transient
protection.
Addressable by device.
Rotary DECADE 01-99 address switches.
Two-wire loop connection.
Visible LEDs "blink" when the unit is addressed:
-Optional with AM2020 software release 5 (or higher).
-Optional with AFP1010.
-Optional with AFP-200.
-Optional with AFP-300.
-Optional with AFP-400.
360' -field viewing angle of the visual alarm indicators
(two LEDs). LEDs illuminate steady during alarm.
Integral communications and built-in type identification.
Compact, stylish design.
Remote test feature from the panel.
Built-in functional test switch activated by external mag-
net.
Low standby current.
Listed to UL-268.
Built-in tamper-resistant feature.
Sounder base option.
Designed for direct surface or electrical box mounting.
Sealed against back pressure.
Plugs into separate base for ease of installation and
maintenance.
Separate base allows interchange of photoelectric, ion-
ization and thermal detectors.
94-5V plastic flammability rating.
Removable cover and insect-resistant screen for field
cleaning.
Remote LED annunciator output connection.
Optional relay, isolator, or sounder bases.
April 6, 1998 H-100
CPX-551
Intelligent Ionization Detector
Section: lntelligenVAddressable Devices
®
S1115
MEA
104-93-E
289-91-E
290-91-E
17-96-E
CS308
(CPX-551A)
BSA
578-81-SA
~
California
State Fire
Marshal
7271--0028:149
<8>
0W6A2.AY, 0Q1A8.AY
(AM2020/AFP1010)
0V4A5.AY (AFP-200)
0B1A0.AY (AFP-400)
0V2A3.AY
~ases 93/00141 listed US Coast Guard
separately ...
CONTACT FACTORY.
APPLICATIONS
161 •002/27/1 (AFP1010/AM2020)
161 •002/23/1 (AFP-200)
Use ionization detectors in life-safety applications to pro-
vide a broad range fire-sensing capability, especially fast,
flaming fires. Where smoldering fires are anticipated, a
photoelectric sensor may provide faster response.
CONSTRUCTION
These detectors are constructed of LEXAN® in an off-white
color.
The CPX-551 plug-in series of smoke detectors are de-
signed to commercial standards and offer an attractive
appearance.
LEXAN® is a registered trademark of GE Plastics, a subsidiary of
General Electric Company.
This document is not intended to be used for installation purposes. We try to keep our
product information up-to-date and accurate. We cannot cover all specific applications or
anticipate all requirements. All specifications are subject to change without notice. For
more information, contact NOTIFIER. Phone: (203} 484-7161 FAX: (203) 484-7118
1SO-9001
Engineering and Manufacturing
Quality System Certified to
International Standard IS0-9001 (ffi) N OTI Fl ER• 12 Clintonville Road, Northford, Connecticut 06472 Made in the U.S.A.
DN-1451 -Page 1 of 2
INSTALLATION
Location of holes
to access and release
locking prongs.
HEAD COVER
Cover and screen
are removable
for cleaning.
SCREEN
Locking prongs.
The CPX-551 Plug-In Detectors use a separate base to
simplify installation, service and maintenance. A specially
designed tool allows maintenance personnel to plug in and
remove the sensors without using a ladder.
Mount base (all base types) on box which is at least 1.5"
(38.1 mm) deep. Suitable boxes include:
4" (101.6 mm) square box
3-1/2" (88.9 mm) or 4" (101.6 mm) octagonal box.
Single-gang box.
When using the CPX with the B501 BH sounder base: use
a 4" (101.6 mm) square (1.5" [38.1 mm] deep) box.
When using a B524RB or B524BI base: use a 3-1/2"
(88.9 mm) octagonal, 4" (101.6 mm) octagonal, or 4"
(101.6 mm) square base.
NOTE: Because of the inherent supervision provided by
the SLC loop, end-of-line resistors are not required. Wir-
ing "T-taps" or branches are pennitted for Style 4 (Class
"B") wiring.
OPERATION
Each CPX-551 uses one of 99 possible addresses on a
System 5000 (with AIM-200 module), AFP-200, AFP-300,
AFP-400, AM2020 Advanced Multiplex System, and
AFP1010 SLC loop. It responds to regular polls from the
system and reports its type and status, including the ana-
log level of its unipolar chamber. If it receives a test com-
mand from the panel (or a local magnet test) it simulates
its chamber and reports the analog level. It blinks its LEDs
when polled, and turns the LEDs on steady when com-
manded (LED blink is optional on the AFP-200, AFP-300,
AFP-400, AFP1010 and AM2020).
The CPX-551 Intelligent Ionization Sensor's unique unipo-
lar chamber responds quickly and uniformly to a broad
range of smoke conditions and can withstand wind gusts
up to 1,500 feet-per-minute without sending an alarm level
signal. Because of the unipolar chamber, the CPX-551 is
approximately two times more responsive than most ion-
ization sensors. This makes it a more stable detector.
Page2of2 -DN-1451
SPECIFICATIONS
Operating voltage: 15 -28 V (Peak DC).
Current range: 6.5 mA current for visible LEDs latched
.. ON".
Standby current: 200 µA maximum (without communi-
cation); 300 µA maximum (communication with LED blink
enabled).
• Detector standby current B524RB or B524BI: < 700
µA @ 24 voe (includes detector).
• Sensitivity: 1.5% nominal.
Sensor: Unipolar, dual-chamber.
• Ambient temperature: o•c to 49•c (32"F to 120"F).
• Relative humidity: 10% to 93%.
Maximum alrveloclty: 1,500 feet-per-minute maximum
(without triggering a false alarm).
• Weight: 5.3 ounces (160 grams).
BX-501 base diameter: 6.1 inches (15.5 cm).
B501 base diameter: 4.0 inches (10.2 cm) .
. • B524RB relay base:
Screw tenninals: Up to 14 AWG (2.0 mm').
Relay type: Forrn-C.
Contact Rating: 2.0 A @ 30 voe resistive.
0.3 A @ 120 voe inductive.
1.0 A @ 30 voe inductive.
Dimensions: 6.2" (157 mm) x 1.4" (36 mm).
Standby: < 100 µA @ 24 voe.
B524B1: Dimensions: 6.2" (157 mm) x 1.4" (36 mm).
Maximum: 25 devices between isolator bases.
PRODUCT LINE INFORMATION
Model Description
CPX-551 Intelligent Ionization Sensor.
CPX-551A Intelligent Ionization Sensor.
Bases ...
BX-501
B501
B501BH
B524RB
B524BI
Canadian (ULC) approved.
Standard U.S. Base
(a base is required for each CPX-551 ).
Base, flangeless European style.
Sounder base assembly
(includes a B501 mounting base)
Intelligent relay base.
Intelligent isolator base.
Other Accessories ...
RMK400 Recessed Mounting Kit for 500 Series
detectors.
XR5
XP-4
RA400Z•
Removal Tool.
Extension Pole for Removal Tool.
Remote LED. Mounts to a single-gang box.
•supported by BX-501 and B501 bases only.
ARCHITECTURAL/ENGINEERING
SPECIFICATIONS
For specifications, request a copy of the Architect/Engi-
neer Specification Disk, available from NOTIFIER Litera-
ture Services, on IBM format 3.5" 1.44 Mbyte magnetic disk.
This disk includes files in both ASCII and WordPerfect®
5.1 formats.
WordPerfect® Is a registered trademark of the WordPerfect
Corporation.
(_
(_
LISTING No.
CATEGORY:
LISTEE:
DESIGN:
INSTALLATION:
MARKING:
APPROVAL:
NOTE:
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING DIVISION
LISTING SERVICE
7271-0028:149
Ionization Smoke Detector
Notifier, 12 Clintonville Rd., Northford CT 06472-1653
Contact: Larry Flood (203) 484-1200
LISTING EXPIRES
JUNE 30, 1999
Page 1 of 1
Model CPX-551 smoke detector. Refer to listee's data sheet for detailed
product description and operational considerations.
In accordance with listee's printed installation instructions, applicable codes
and ordinances and in a manner acceptable to the authority having
jurisdiction.
Listee·s name, product number, electrical rating and UL label.
Listed as an ionization smoke detector when used in conjunction with Model
BX-501 base (CSFM Listing No. 7300-0028:173*) and separately listed
compatible fire alarm control units.
Formerly 7256-0028:149
•corrected 05-14-98
TH:S LISTING IS BASED U~N TECHNICAL DATA SUBMITTED BY THE APPLICANT. CSFM FIRE ENGINEERING STAFF HAS REVIEWED
THE TEST RESULTS ANO/OR OTHER DATA BllT DOES NOT MAKE AN INDEPENDENT VERIFICATION OF ANY CLAIMS. THIS LISTING IS NOT
AN ENDORSEMENT OR RECOMMENDATION OF THE ITEM USTFJJ. "T}t15 LISTING SHOULD NOT BE USED TO VERIFY C:ORRECT OPF.RA TIONAL
REQUIREMENTS OR INSTALLATION CRrTERIA. REFER TO USTEE'S DATA SHEET, INSTALLATION INSTPUCTIONS AND/OR OTHER
surrABLE INFORM" TION SOURCES.
L DATEISSUEO: MAY 14, 1998 APPROVED BY:
EFFECTIVE ISSUE DATE TO EXPIRATION DATE
PROGRAM COORDINATOR
(_ LISTING No.
CATEGORY:
LISTEE:
DESIGN:
INSTALLATION:
MARKING:
APPROVAL:
XLF:
I CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTIGN
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING DIVISION
LISTING SERVICE
7300-0028:173
Misc. Devices/Control Unit Accessories
Notifier, 12 Clintonville Road, Northford, CT 06472-1653
Contact: Lawrence Flood (203) 484-7161
LISTING EXPIRES
JUNE 30, 1999
Page 1 of 1
Models BX501, B610LP, B612LP, B614LP, B616LP and B710LP detector
bases. Refer to listee's data sheet for additional detailed product description
and operational considerations.
In accordance with listee's printed installation instructions, applicable codes
and ordinances and in a manner acceptable to the authority having
jurisdiction.
Listee's name, product designation, electrical rating and UL label.
Listed as detector bases for use with separately listed compatible detectors.
7300-1209: 128
07-29-94
THIS LISTING IS BASED UPON TECHNICAL DATA SUBMITTED BY THE APPLICANT. CSFM FIRE ENGINEERING STAFF HAS
REVIEWED THE TEST RESULTS AND/O" OTHER DATA BUT DOES NOT MAKE AN INDEPEtlDENT 'l'ERIFICATION OF ANY CLAIMS.
THIS LISTING JS NOT AN ENDORSF.MENT OR RECOMMEHC,ATJON OF THE ITEM LISTED. THIS USTiNG SHOULD NOT BE USED TO
VER0FY CORRl:'.CT OPERATIONAL REQUIREMEtHS OR INSTALLATION CRITERIA. REFER TO USTEE'S OATA SHEET, INSTALLATION
INSTRUCTIO!'-1S AND/OR OTHER SUITABLE INFORMATION SOURCES.
(_ DATE ISSUED: APRIL 24, 1998 APPROVED BY: ~~ EFFECTIVE ISSUE DATE TO EXPIRATION DATE
PP.OGRAM COORDINATOR
I (_
(_
C
June 18, 1998 H-105
GENERAL
The SDX-551 and SDX-551TH Analog Photoelectric Detec-
tors are used with the NOTIFIER AM2020, AFP1010, AFP-
400, AFP-300, AFP-200, and System 5000 (when equipped
with AIM-200 module) Advanced Multiplex Systems to mea-
sure the analog level of smoke and report this analog level to
the control panel. The use of analog data provides signifi-
cant benefits to the end user, installer, and service personnel
in ways not possible with a conventional-type system. Since
this detector is also addressable, It will help firefighters to more
quickly locate a fire during its early stages. The SDX-551TH
offers the same features as the SDX-551 with the addition of
a 135'F (57'C) internal thermal element.
FEATURES
Unique optical sensing chamber.
SDX-551 and SDX-551TH
Intelligent Photoelectric Detectors
Section: Intelligent/Addressable Devices
® @ I California U IC ~ ~':::h~\re
I.:: 7272-0028:148
S1115 CS308 <8>
CS118/CS733 FM
~ (SDX-551A)
~ US Coast Guard 0O4Ao.Av
161•00212111 MEA 93/00141
(SDX-551) 161•002/23/1 (SDX-551)
BASES LISTED SEPARATELY.
CONTACT FACTORY.
460-92-E
290-91-E
BSA
Optional integral 135'F (57"C) fixed-temperature element. I{
Superior signal-to-noise ratio (2.0). .
Stable photoelectric operation.
578-81-SA
(SDX-551)
1.6% nominal sensitivity for panel alarm threshold level.
Fully coated circuit boards and superior RF/transient pro-
tection.
Addressable by device.
Rotary DECADE 01-99 address switches.
Two-wire loop connection.
Visible LEDs "blink" every time the unit is addressed, and
illuminate steadily on alarm (this feature may be deselected
on the AM2020, AFP1010, AFP-400, AFP-300, and AFP-
200).
360'-field viewing angle of visual alarm indicators (2 LEDs).
Integral communications, built-in device type identification.
Compact, stylish design.
Remote test feature from the panel.
Built-in functional test switch activated by external magnet.
Low standby current.
Listed to UL-268.
Built-in tamper-resistant feature.
Designed for direct-surface or electrical-box mounting.
Sealed against back pressure.
Optional sounder, relay or isolator bases.
Plugs into separate base for ease of installation and main-
tenance.
Separate base allows Interchange of photoelectric, ioniza-
tion and thermal elements.
94-VO plastic flammability rating.
Removable cover and Insect screen for field cleaning.
Remote LED annunciator output connection.
This document is not intended to be used for installation purposes. We try to keep our
product Information up-to-date and accurate. We cannot cover all specific applications or
anticipate aH requirements. All specifications are subject to change without notice. For
more Information, contact NOTIFIER. Phone: (203) 484-7161 FAX: (203) 484-7118
(@N OTI Fl E R 0 12 Clintonville Road, Norlhford, Connecticut 06472
Cover
Screen
Detector
Base
{order
separately)
ISO-9001
Engineering and Manufacturing
Quality System Certified lo
International Standard IS0.9001 Made In the U.S.A.
DN-1884 -Page 1 of2
APPLICATIONS
Photoelectric detectors are often faster than ionization de-
tectors In sensing smoke from slow, smoldering fires. Ion-
ization detectors are often better than photoelectric detec-
tors at sensing fast, flaming fires.
CONSTRUCTION
These detectors are constructed of LEXAN® in an off-white
color. The SDX-551 plug-in series of smoke detectors is
designed to commercial standards and offers an attractive
appearance.
LEXAN® Is a registered trademark of GE Plastics, a subsidiary of
General Electric Company.
INSTALLATION
The SOX Series Plug-In Detectors use a separate base to
simplify installation, service and maintenance. A specially
designed tool allows maintenance personnel to plug-in and
remove the sensors without using a ladder.
Mount base (all base types) on a box which is at least 1.5
inches deep. Suitable boxes include:
4" (101.6 mm) square box with, or without, plaster ring.
3-1/2" (88.9 mm) or 4" (101.6 mm) octagonal box.
Single-gang box.
For the B524RB orB524BI base: use a 3-1/2" (88.9 mm)
or4" (101.6 mm) octagonal box; or4" (101.6 mm) square
box.
When using the SDX with the B501BH sounder base:
use a 4" square box (1.5" [38.1 mm] deep).
NOTE: Because of the inherent supervision provided by
the SLC loop, end-of-line resistors are not required. Wir-
ing "T-taps" or branches are permitted for Style 4 (Class
"B") circuits.
OPERATION
Each SDX-551/SDX-551TH uses one of 99 possible ad-
dresses on a SLC loop. It responds to regular polls from
the control panel and reports its type and status, including
the analog level of its smoke-sensing chamber. If it re-
ceives a TEST command from the panel (or a local magnet
test), it stimulates its chamber electronics and reports an
alarm analog level. It blinks its LEDs when polled, and
turns the LEDs on when commanded by the panel.
The SOX detector uses the fight-scattering principle, rep-
resenting the latest in smoke-sensing technology.
ARCHITECTURAL/ENGINEERING
SPECIFICATIONS
For specifications request a copy of the ArchitecVEngineer
Specification Disk, available from NOTIFIER Literature Ser-
vices, on IBM format 3.5" 1.44 Mbyte magnetic disk. This
disk Includes files in both ASCII and WordPerfect® 5.1
formats.
WordPerfect® Is a registered trademark of the WordPerfect
Corporation.
Page 2 of2 -DN-1884
COMMON SPECIFICATIONS
Operating voltage: 15 -28 V (peak DC).
Current range: 6.5 mA current for visible LEDs latched
"ON".
Detector standby current: 230 µA maximum (no com-
munication); 330 µA maximum (with LED blink).
Standby current for B524RB or 852481: < 700 µA @
24 VDC (includes detector).
Sensitivity: 1.6% nominal.
Sensor: Photoelectric (light-scattering principle).
Ambient temperature: SDX-551: o•c to 49•c (32"F
to 120"F). SDX-551TH: o·c to 38"C (32"F to 1 OO"F).
Relative humidity: 10% to 93%.
Air velocity: 3,000 feeVminute maximum.
Weight: 6 oz. (170 gm.).
BX-501 Base diameter: 6.2" (15.8 cm).
B524RB Relay Base:
Screw terminals: Up to 14 AWG (2.0 mm').
Relay type: Form-C.
Contact rating: 2.0 A @ 30 VDC resistive.
0.3 A@ 120 voe inductive.
1.0 A@ 30 voe inductive.
Dimensions: 6.2" (157 mm) x 1.4" (36 mm).
852481: Dimensions: 6.2" (157 mm) x 1.4" (36 mm).
Maximum: 25 devices between isolator bases.
SDX-551TH SPECIFICATIONS
Includes 135"F (57°C) fixed-temperature thermal element.
PRODUCT LINE INFORMATION
Model
SDX-551*
Description
Intelligent Photoelectric Sensor
(base ordered separately).
SDX-551TH* Intelligent Photoelectric Sensor with
built-in 135"F (57"C) fixed-temperature
thermal element (base ordered
separately).
• Order suffix "A" for Canadian (ULC) approved devices.
Bases ...
BX-501
8501
Standard U.S. 6.2" diameter mounting base.
European style 4" diameter mounting base
(without flange).
B501BH Sounder base assembly (includes B501
base).
B524RB Intelligent relay base.
852481 Intelligent isolator base.
Optional Accessories ...
RA4ooz-Remote LED. Mounts to a single-gang box.
XR5 Removal Tool.
XP-4 Extension Pole for Removal Tool.
•• Supported by BX-501 and B501 bases only.
(_
LISTING No.
CATEGORY:
LISTEE:
DESIGN:
INSTALLATION:
MARKING:
APPROVAL:
NOTE:
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING -BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
Listing Expires
June 30, 2000
7272-0028: 148 Page 1 of 1
Photoelectric Smoke Detector
Notifier, A Pittway Company, One Fire-Ute Place, Northford CT 06472-1653
Contact: Larry. Flood (203) 484-1200
Models SDX-551 and SDX-551T. Refer to listee's data sheet for detailed
product description and operational considerations.
In accordance with listee's printed installation instructions, applicable codes
and ordinances and in a manner acceptable to the authority having
jurisdiction.
Ustee's name, product number, electrical rating and UL label.
Listed as photoelectric smoke detectors when used in conjunction with
Model BX-501 base (CSFM Listing No. 7300-0028: 173 *) and separately
listed compatible control units.
Formerly 7257-0028: 148
• Corrected 05-14-98
-, ..
'
This listing is based upon lechnical data submitted by the applicant CSFM Fire Engineering staff has reviewed the test results and/or.
other data but does not make an independent verification d any claims. This listing Is not an endonement or recommendation d the
item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data shee~
installation instructions and/or other suitable Information sources.
,...Date Issued: JULY 1, 1999 L fective issue date to expiration date
Authorized By:
BEN HO, Deputy State Fire Marshal Ill
Program Manager
L LISTING No.
CATEGORY:
LISTEE:
DESIGN:
INSTALLATION:
MARKING:
APPROVAL:
XLF:
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTIGN
OFFICE OF THE STATE FIRE MARSHAL •
FIRE ENGINEERING DIVISION
LISTING SERVICE
7300-0028: 173
Misc. Devices/Control Unit Accessories
Notifier, 12 Clintonville Road, Northford, CT 064 72-1653
Contact: Lawrence Flood (203) 484-7161
LISTING EXPIRES
JUNE 30, 1999
Page 1 of 1
Models BX501, B610LP, B612LP, B614LP, B616LP and B710LP detector
bases. Refer to listee's data sheet for additional detailed product description
and operational considerations.
In accordance with listee's printed installation instructions, applicable codes
and ordinances and in a manner acceptable to the authority having
jurisdicti'ln.
Listee's name, product designation, electrical rating and UL label.
Listed as detector bases for use with separately listed compatible detectors.
7300-1209: 128
07-29-94
THIS LISTING IS BASE'D UPON TECHNICAL DATA SUBMITTED BY THE APPLICANT. CSFM FIRE ENGINEERING STAFF HAS
REVIEWED THE TEST RESULTS AND/0~ OTHER DATA BUT DOES NOT MAKE AN INDEPEtlOENT "/ERIFICATION OF ANY CLAIMS.
THIS lJSTING IS NOT AN ENDORSF.MEHT OR RECOMMEHOATION OF THE ITEM LISTED. THIS LISTiNG-SHOULD NOT BE USED TO
VERiFY CORR~CTQPERATIONAL REQUIREMEt•fr5 OR INSTALLATION CRITERIA. REFER TO USTEE'S DATA SHEET, INSTALLATION
INSTRUCTIONS AND/OR OTHER SUITABLE INFORMATION SOURCES.
(._ DATE ISSUED: APRIL 24, 1998 APPROVED BY: ~~ EFFECTIVE ISSUE DATE TO EXPIRATION DATE
PP.OGRAM COORDINATOR
(_
C
~NOTIFIER®
WFIRE sy;_~J:,!!Y.!§
September 16, 1998 J-89
GENERAL
System Sensor SpectrAlert Series strobes, horns, and combina-
tion horn/strobes are UL listed for primary signaling in life safety
systems and meet ADA public mode visible signaling requirements.
SpectrAlert products can be connected to the alarm indicating cir-
cuit of a fire alarm control panel and are compatible with DC line
supervision. The SpectrAlert product line mounts to standard
backboxes using a universal mounting plate included with each unit.
An optional small footprint mounting plate fits to a single-gang box.
An accessory backbox skirt gives a cosmetic finish to a 4" x 4" x
1-1/2" or a 2" x 4" x 1-7/8" surface-mounted backbox. All strobe
and horn/strobe mounting options require only one screw attach-
ment of product to plate.
These products are designed for 12 and 24 VDC and full-wave rec-
tified unfiltered power. Full-wave rectified operation requires more
current than DC operation. For detailed current draw information,
consult the Current Draw Tables (page 2). The horn/strobe com-
bination products are factory-assembled with jumper wires for in-
tandem operation. For independent wiring of horn and strobe, re-
move jumper wires. When wired for independent operation, the
strobe will continue to run while the horn can be silenced. How-
ever, the strobe must be running for horn to operate.
Homs -The SpectrAlert Series horns and horn/strobes pro-
vide two different field-selectable/reversible tones, a high-low field-
selectable/reversible sound output setting (low setting on 24-volt
models only) and a field-selectable/reversible temp 3 pattern or
non-temporal continuous pattern. These field-selectable features
are accomplished using pins and jumpers located on the back of
each SpedrAlert horn and ham/strobe. An accessory module is
not needed to make these field selections. The horn on horn/strobe
models will operate on a coded power supply. Those horn-only
models with "HC" In their part numbers will also operate on a
coded power supply. The horn and horn/strobe series includes
weatherproof models.
Strobes -The ADA-compliant SpectrAlert strobes are elec-
tronic visible warning signals that flash at 1 Hz over their operating
voltage range. These products are available in 24-volt models at
15, 15/75, 75 and 110 candela intensities and in 12-volt models at
15 and 15/75 candela intensities. The strobe series includes weath-
erproof models. SpectrAlert products feature dramatic reductions
in current requirements.
Sync•Circuit Module (MDL)-The Sync•Circuit Module
is available for synchronization of strobes and horns and can syn-
chronize two Style Y (class B) circuits or one Style Z (class A)
circuit. The module can also generate a synchronized temp 3 tone
for System Sensor's Multi-Alert"' and PA400 horn products.• The
synchronization module allows the SpectrAlert horns on combina-
tion horn/strobes to be silenced on two-wire systems. SpectrAlert's
Sync•Clrcult Module can be daisy-chained for multiple zone syn-
chronization. The module does not operate on a coded power sup-
ply.
*For Multi-Alert and PA400: Strobes must be wired to a continuous
source of power (non-coded power supply).
SpectrAlert TM Series
Horns, Strobes, and Horn/Strobes
Section: AudioNisual Devices
® ◄ S4011 & S5512 (P1215, P121575, P2415,
P241575, P2475, P24110). S5512 (S1215,
S121575, S2415, S241575, S2475, S24110).
54011 (HC12/24).
@ ◄ CS549 (P2415A, P241575A, P2475A, P24110A,
S2415A, S241575A, S2475A, S24110A).
CS548 (H12/24A, HC12/24A).
0B8A4.AY (P1215, P121575, ► ~
P2415, P241575, P2475, P24110, ~
S1215, S121575, S2415, S241575,
S2475, S24110, H12/24). 0D4A7.AY(HC12/24).
California
State Fire
Marshal
7135-1209:173 (P1215, P121575, P2415,
P241575, P2475, P24110).
7125-1209:174 (S1215, S121575,
S2415, S241575, S2475, S24110).
7135-1209:143 (H12/24, HC12/24).
M EA ◄ 319-96-E (P1215, P121575,
P2415, P241575, P2475,
P24110,S1215,S121575,
S2415,S241575,S2475,
S24110, H12/24, HC12/24).
SpectrAlert™, Sync•Clrcult™, and Multl-Alert"" are trade-
marks of System Sensor, a division of Pittway Corporation.
This document is not intended to be used for installation purposes. We try to keep our
product information up-to-date and accurate. We cannot cover all specific applications or
anticipate all requirements. All specifications are subject to change without notice. For
1SO-9001
Engineering and Manufacturing
Quality System Cel!ilied to
lntemational Standard IS0-9001
more information, contact NOTIFIER. Phone: (203) 484-7161 FAX: (203) 484-7118
@) N OTI Fl ER" One Fire-Lite Place, Northford, Connecticut 06472 Made In the U.S.A.
DN-5939 -Page 1 of 6
FEATURES
24-volt strobe models: 15, 15/75, 75 and 110 candela.
12-volt strobe models: 15 and 15/75 candela.
Horn models operate on 12 and 24 volts.
Low current draw: reductions as high as 45%.
Two field-selectable/reversible horn tones:
-3000 Hz interrupted -electromechanical
Field-selectable/reversible high-low dBA output on horn
(low output on 24-volt models only):
-101 peak dBA@ 10 ft. high output.•
-96 peak dBA@ 10 ft. low output.•
Field-selectable/reversible temp 3 pattern or non-temp 3 con-
tinuous pattern on horn.
Hom/strobe can be wired either in tandem or independently.
Weatherproof strobes, horns, and horn/strobes available.
Horns for use with coded power supply available.
Universal mounting plate included with each unit.
One-screw mounting of strobe and horn/strobe to mounting
plate.
SpectrAlert strobe and horn/strobe take up no room in the
backbox.
CURRENT DRAW TABLES
Strobe Only
Single-gang mounting without the use of a mounting plate
(horn model only).
Self-contained screw covers.
Aesthetically pleasing design.
Synchronize horn and strobe with Sync•Circuit™ module
(MDL).
Silence horn on horn/strobe over a single pair of wires using
a Sync•Circuit module (MDL).
•sound output varies with tone and output options selected; sound
levels based upon anechoic room measurements.
SPECIFICATIONS
Input terminals: 12 to 18 AWG (3.25 mm' to 0.51 mm').
Dimensions: see diagrams page 3.
Weight, horn only: 7.2 oz. (204 g).
Weight, strobe and horn/strobe: 8.8 oz. (250 g).
Mounting: see diagrams page 4.
Operating temperature: 32•F to 12o•F (o•c to 49•c).
Operating voltage range: .. 12 V: 10.5 -17 V. 24 V: 20 -30
V.
** These products should be operated within their rated voltage
range. UL does, however, test functional integrity to -20% and
+ 10% of manufacturer's stated ranges.
AVERAGE CURRENT (mA) ·-··· PEAK CURRENT (m~~ IN RUSH CURRENT (mA) OAHOO y11n,1,
1O.5V 12Y 17Y 20Y 24Y 30Y 10.5V 12Y 17Y 20Y 24Y 30V 10.5V 12Y 17Y 20Y 24Y ,.., Cand11l1 "''"" "' ~· "' ... "'~· "'""' "' -"' ... "' -"' ... "' -"' ... "'""' "' ... ., ... ., ... "' ... "' ... "' -15 133 1511 ,,. "' " "' 59 120 " .. .. ,, ... ... "" ... .,. ... "" 270 150 270 1-40 2!50 10 108 92 12, "" 190 170 230 220 280 '" 37 15/75 "' "' ,., "' .. ,. " ., .. " 58 132 "" ""' "" "" ... ... "' '" 170 270 "" 270 76 l<M .. 12t HIO 185 170 230 "" 270 "" 310 75 NA NA NA NA NA NA ... "' "' 159 102 "' NA NA NA NA NA NA 350 "" "" ... 330 ... NA NA NA NA NA NA 190 '"' 230 280 ,oo 110 NA NA NA NA NA NA "' "" '"' 191 115 174 NA NA NA NA NA NA ... "" "" 570 420 "" NA NA NA NA NA NA "" "" "" "" ""
Hom Only
AVERAGE CURRENT (mA)
••uu.,
Hlg""-T-1O.SV 12Y 17Y 20V 24Y 30Y TOM Yolomo .... "' ... "' ""' "' '"" "' '"" "'""' "' '"" ....... High Tom• 10 11 10 10 .. 1 19 " " ,. 29 " m"". Non 10 ,. 10 19 .. ' 17 .. 23 .. "' .,
Low Tom• NA NA NA NA NA NA 11 12 13 13 17 1 Non NA NA NA NA NA NA 12 ,. ,. " 17 ,.
3000 Hz High Tom• 11 13 11 11 ,. 1 ,. ,. " ,. ., , __ Non 11 17 11 " ,. 19 .. " " .. .. Low Tom• NA NA NA NA NA NA ,. .. 17 15 " .. Non NA NA NA NA NA NA 13 ,. ,. " " "
Hom/Strobe• 15 cd Hom/Strobe -75 cd
AYERAG! CURRENT (mA) AVERAGE CURRENT (mA)
••• u-•-High/Low Tamp 10.SV 12Y 17Y zoy 24Y 30Y Tone ---"''"" "'""' "' '"" "' '"" "' '"" "'""' ·--High To 143 170 12, ,., .. ,., 71 101 " .. 75 141 """'-Non ,., 170 , .. ,., '51 .. .. 78 100 " 130 Low To NA NA NA NA NA NA 70 .. .. .. 03 1 Non NA NA NA NA NA NA 71 .. 17 .. .. 1
3000Hz High T, 1 .. 172 1'5 1 " 1 .. 03 101 81 1n " 1 .. ,_ Non 1 .. "' 1'5 100 15 1 71 102 10 101 11 142
Low ' NA NA NA NA NA NA 73 .. 70 .. 17 ,.
Non NA NA NA N• NA NA 72 " .. .. ,.,
.. _
Tamp 10.5Y 12Y 17Y 20Y 24V 30Y TOM --mon "' ... "' ... "' ... "''"" ., ... "'-·--High Tom• NA NA NA NA NA NA 114 1•1 "' ,., 131 117 .-. Non NA NA NA NA NA NA 103 186 1-ff 108 132 1 .. Low Tom• NA NA NA NA NA NA ,,, 112 138 "' 119 1 .. Non NA NA NA NA NA NA 157 112 131 ,., 111 157 3000H, High Tomo NA "' NA NA NA 1,0 1 ,,, ,,, ,,, ,,. -Non NA NA NA NA NA NA 114 112 150 175 137 "' Low ' NA NA NA NA NA NA 151 114 1 114 1'3 100 Non NA NA NA NA NA NA 1 .. 188 139 1 .. 124 102
Hom/Strobe -15/75 cd Hom/Strobe -110 cd
AVERAGE CURRENT (mA)
,_u .... ··-·· AYER.AG! CURRENT (mA) ........ Temp 10.SV 12Y 17Y 20Y 24Y 30V Ton, --/Non "' '"" "' '"" "'""' "' '"" "' -"' -....... Hill> Tomo 171 1113 1$1 181 113 184 95 113 11 111 17 ,., ,_ Non 178 113 152 181 113 184 13 110 H 113 001 Low T NA NA NA NA NA NA 17 1CM ,. 100 ,. 1 ..
Non NA NA NA NA NA NA 01 1CM 10 100 ,. 1 .. 3000 H, High To 179 111 1$1 183 11, ~ 100 111 M 118 15 1 .. --Non 17t 1111 152 113 113 1 15 114 93 111 .. 15' Low ' NA NA NA NA NA NA .., 100 03 101 ,. 1 ..
Non NA NA NA NA NA NA .. 1CM .. 107 10 1 ..
HI-Tomp 1'O.sv 12Y 17Y ,.., HY 30Y TOM Volume /Non ~ '"" ~ ... "'""' "'""' "'""' "'"'" ...... Hill> l•mn NA NA NA NA NA NA 118 2"1 ,., ... 1 .. 200 """'· Non NA NA NA NA NA NA 1 .. "' 183 211 1'5 .,,
Low Tom• NA NA NA NA NA NA 110 232 153 132 1 Non NA NA NA NA NA NA 111 232 ,, .... 132 1IO 3000H, High ' NA NA NA NA NA NA 193,.. 1 .. ,,. 1152 207 lnlam,pt. Non NA NA NA NA NA NA 1 .. ,., 117 2'7 150 ,,,
Low Tomo NA NA NA NA NA NA 103 23' 157 ... ,,, 193
Non NA NA NA NA NA NA 102 232 1 ..... 137 195
Page 2 of 6 -DN-5939
j
C
(.
ENGINEERING SPECIFICATIONS
General -SpectrAlert horns, strobes and horn/strobes
shall be capable of mounting to a standard 4" x 4" x 1-112"
(10.16 x 10.16 x 3.81 cm) backbox or a single-gang 2" x 4" x
1-112" (5.08 x 10.16 x 3.81 cm) backbox using the universal
mounting plate included with each SpectrAlerl product. Also,
SpectrAlert products, when used in conjunction with the ac-
cessory Sync•Circuit Module, shall be powered from a non-
coded power supply and shall operate on 12 or 24 volts. 12-
volt rated devices shall have an operating voltage range of
10.5 -17 volts. 24-volt rated devices shall have an operating
voltage range of 20 -30 volts. SpectrAlert products shall have
an operating temperature of 32"F to 120"F (0"C to 49"C) and
operate from a regulated DC or full-wave rectified, unfiltered
power supply.
Horn -Horn shall be a System Sensor SpectrAlert model
capable of operating at 12 and 24 volts. Horn shall
_b_e_l-is-te_d_t_o UL 464 for fire protective signaling systems. The
horn shall have two tone options, two audibility options (at 24
volts) and the option to switch between a temporal 3 pattern
and a non-temporal continuous pattern. The ham-only model
shall NOT operate on a coded power supply except those
models (model numbers contain "HC") designed to do so.
Strobe -Strobe shall be a System Sensor SpectrAlert
model ____ listed to UL 1971 and be approved for fire
protective service. The strobe shall be wired as a primary
signaling notification appliance and comply with the American~
with Disabilities Act requirements for visible signaling appli-
ances, flashing at 1 Hz over the strobe's entire operating volt-
age range. The strobe light shall consist of a xenon flash tube
and associated lens/reflector system.
DIMENSIONS
3-318"
(85.725 mm)
5-518"
(142.875 mm)
I<-2-51,S-
(58.7375 mm)
ITT
OUTER: 5-518"
(142.875 mm)
Hom/Strobe Combination -Hom/strobe shall be a
System Sensor SpectrA!ert model--~-listed to UL 1971
and UL 464 and shall be approved for fire protective service.
Horn/strobe shall be wired as a primary signaling notification
appliance and comply with the Americans with Disabilities Act
requirements for visible signaling appliances, flashing at 1 Hz
over its entire operating voltage range. The strobe light shall
consist of a xenon flash tube and associated lens/reflector
system. The horn shall have two tone options, two audibility
options (at 24 volts) and the option to switch between a tem-
poral 3 pattern and a non-temporal continuous pattern. Strobes
shall be powered independently of the sounder with the re-
moval of factory-installed jumper wires. The horn on horn/
strobe models shall operate on a coded or non-coded power
supply.
Module -Module shall be a System Sensor Sync•Circuit
model ____ listed to UL 464 and shall be approved for
fire protective service. The module shall synchronize
SpectrAlert strobes at 1 Hz and horns at temporal 3. Also, the
module shall silence the horns on horn/strobe models, while
operating the strobes, over a single pair of wires. The module
shall be capable of mounting to a 4-11/16" (119.0625 mm)
square x 2-118" (53.975 mm) deep backbox and shall control
two Style Y (class B) or one Style Z (class A) circuit. Module
shall be capable of multiple zone synchronization by daisy-
chaining multiple modules together and resynchronizing each
other along the chain. The Module shall NOT operate on a
coded power supply.
I<-2-15116" ~ I (74.6125 mm) I 15116"--...,_
(23.8125 mm)
T
5-5116"
(134.9375 mm)
1
1-5116" /
(33.3375 mm)
UPPER LEFT: Hom/Strobe with Small Footprint Mounting
Plate (same dimensions for strobe only).
LOWER LEFT: Hom/Strobe with Universal Mounting Plate
(same dimensions for strobe only).
UPPER RIGHT: Hom only (may be mounted with ellher Small
Footprint or Universal Mounting Plate).
LOWER RIGHT: Sync•Circuit Module (MDL). r--5-114" (133.35 mm) --+J
T 0
0 0
E (I) L--
0 0
J
DN-5939 -Page 3 of 6
MOUNTING DIAGRAMS
2• x 4" x 1-7/8" backbox
0
Hom
Direct
Mount ...
...
Hom with Universal Mounting Plate
(included with each product)
4" X 4" X 1-1/2"
backbox
0
0
0
I 4" x 4" 1-1/2" backbox
-=
....
4-11/16" X 4-11/16" X 2-1/8"
(119.0625 x 119.0625 x 53.975 mm)
backbox
\~'r"-rlr--..-~::cc--i --...
--
T
....
....
0
0
0
Strobe or Horn/Strobe with
Universal Mounting Plate
(included with each product)
4" x 4" x 1-1/2" backbox
I.,,,,,.
0
0
0
Hom Surface Mount
with accessory
Backbox Skirt
....
....
2" x 4" x 1-7/8" backbox
/ S-MP
m_/'?~:7\,,,
...
...
Strobe or Horn/Strobe
with accessory
Small Footprint
Mounting Plate
Sync•Clrcuit Module Direct Mount Strobe or Hom/Strobe Surface Mount
with accessory Backbox Skirt
SOUND OUTPUT GUIDE (dBA)
UL Reverberant Room dBA @ Volts DC Anechoic Room Peak dBA @ 10 ft.NOC
10.5 12 17 20 24 30 10.5 12 17 20 24 30
LOW Electromechanical NA NA NA 75 75 79 NA NA NA 94 96 98
TONE 3000 Hz lntenupted NA NA NA 75 79 79 NA NA NA 94 96 98 Temporal Electromechanical 75 75 79 82 82 82 94 95 98 100 101 102 HIGH TONE 3000 Hz lntenupted 75 75 79 82 85 85 94 95 98 100 101 102
LOW Electromechanical NA NA NA 79 82 85 NA NA NA 94 96 98
TONE 3000 Hz lntenupted NA NA NA 82 82 85 NA NA NA 94 96-98
~on-Electromechanical 79 79 85 98 100 101 102 emporal HIGH 85 88 88 94 95
TONE 3000 Hz lntenupled 79 82 85 88 88 90 93 95 98 100 101 102
Page 4 of 6 -DN-5939
(_
(_
WIRING DIAGRAMS
NOTE: Do NOT loop wires under terminal screws.
(-)
1-)
Tandem Operation
HORN/STROBE COMBO
FACTORY
INSTALLED
JUMPERS 1-)
}
EB!JMFACP, (-I.IODULEOR
~---'• ';tJ'((;~us
HORN/STROBE STROBE ONLY
,~----,(+)
Two-wire system, any mix of models,
wired for TANDEM OPERATION.
• 0 L
T Horns silenced over two-wire circuit.
• Any mix of horn/strobes or strobe-only devices is
acceptable.
Horn control connects to interruptible power
source.
FACP ti
(•J, ---,c---+-H-<: NAC,
(-l•--1-->-t-<e
FACP 1112
MODULE 1
IIODULE2
M } NAC' -++++++-o~I :--1 H
DIAGRAM NOTES:
TO NEXT
Spect,Alttt DEVICE OOEO<.
>
AN SpectrAJert
horns, horn/strobes.
and strobes wfll
operate In sync.
1) Any mix of SpectrAlert horn/strobe. strobe-only. or horn-
only devices is allowable for Zone 1.
2) No devices or horn-only are allowed on Zone 2. If no de-
vices are installed on Zone 2, terminate EOL resistor at
horn control terminal.
Independent Operation
HORN AND STROBE FACTORY
INSTALLED
JUMPER WIRES
REMOVED
HORNS
H
(+)
(-)
(+)
(-)
H
0 R
N
ic ,o
;M
•B
:o
s
T
R
0
B E
H
0
R
N
s
T
R 0
B E
(•)
Four-wire system, combo models,
wired for INDEPENDENT OPERATION.
(Hom can be turned off at the panel
whl/e strobes continue to operate.)
Temp 3 coding of Multi-Alert
and PA400 sounders.
NOTE: Strobes must be powered from non-coded
supply.
IIODULE1
o},... >
0-f"ACP TO NEXT
DEVICE
~}:.""" °""°'-NAC1
>
~Jru ,_,{e > NACZ
TO NEXT
DEVICE U:--.... .:{e OREOl
> □ Hom& will be
TEMP. JUMPER ON temporal-codfld
and In sync.
DN•5939 -Page 5 of 6
z
0
I
0 ... z -Ill z -.. ... u ::,
1:1
2 a.
Horn/Strobes
Canadian Models,
Horn/Strobes
Spanish Labeling, HIS
Strobes
Canadian Models,
Strobes
Spanish Labeling, Strobes
Horns
Accessories .....
Sync•Clrcult Module
Small Footprint Mountln!p
Plate for Single-Gang ON. Y
Surface-Mount Backbox Skirt
Universal Mounting Plata
(replacement)
Weatherproof Backbox
RED
P1215
P121575
P2415
P241575
P2475
P24110
P241575K (wealherprooQ
P2475K (wealherprooQ
P24110K (wealherprooQ
P2415A
P241575A
P2475A
P24110A
P241575KA (wealherprooQ
P2475KA (wealherprooQ
P24110KA (wealherprooQ
P241575F (FUEGO)
$1215
S121575
S2415
S241575
S2475
S24110
S241575K (wealherprooQ
S2475K (wealherprooQ
S24110K (wealherprooQ
S2415A
S241575A
S2475A
S24110A
S241575KA (wealherprooQ
S2475KA (wealherprooQ
S24110KA (wealherprooQ
S241575F (FUEGO)
H12/24
H12/24K (wealherprooQ
HC12/24 (coded powe~
HC12/24K (wealherprool br coded power)
H12/24A
H12/24KA (wealherprooQ
HC12/24A (coded power)
Mill
MOLA
S-MP
BBS
D-MP
WBB
l'\lilTE
P1215W
P121575W
P2415W
P241575W
P2475W
P24110W
-
-
-
P2415WA
P241575WA
P2475WA
P24110WA
-
-
-
S1215W
S121575W
S2415W
S241575W
S2475W
S24110W
-
-
-
S2415WA
S241575WA
S2475WA
S24110WA
--
-
H12/24W
-
HC12/24W (coded powe~
-
H12/24WA
-
HC12/24WA (coded power)
Mlll.W
MDI.WA
S-MPW
BBSW
D-MPW
-
voltage candala l'lg. mA'@ l'lg. mA'@
nom. voe nom.FM
12 15 124 167
12 15175 152 181
24 15 78 98
24 15175 91 111
24 75 148 167
24 110 165 209
24 1!il75 91 111
24 75 148 167
24 110 165 209
24 15 78 98
24 1!il75 91 111
24 75 148 167
24 110 165 207
24 1!il75 91 111
24 75 148 167
24 110 165 209
24 15175 91 111
12 15 114 157
12 1!il75 142 171
24 15 53 80
24 1!il75 66 93
24 75 123 149
24 110 140 191
24 15175 66 93
24 75 123 159
24 110 140 191
24 15 53 80
24 15175 66 93
24 75 123 149
24 110 140 191
24 1!il75 66 93
24 75 123 149
24 110 140 191
24 1!il75 66 93
12/24 NA 12/23-12 / 21
12/24 NA 12 / 23 12 I 21
12/24 NA 12 / 23 12 / 21
12/24 NA 12 / 23 12 / 21
12/24 NA 12 / 23 12 / 21
12/24 NA 12 / 23 12 I 21
12/24 NA 12 / 23 12 / 21
12/24 NA 16 24
12/24 NA 16 24
NA NA NA NA
NA NA NA NA
NA NA NA NA
NA NA NA NA
NOTES: 1) Canadian model numbers end in ·A·. 2) Lalin Amencan model numbers end In "F". 3) All weatherproof models must
use weatherproof backbox model WBB. 4) All SpectrAlert products are designed for wall•mount only. 5) Installation of less than 75 ....._.,
candela strobes may be permissible under the equivalent facilitation clause of the ADAAG (Sec. 2.2). However, It Is the responsibility .,.J
of the person or entity designing the fire alarm system to determine the acceptability of less than 75 candela strobes. 6) All 15ll5
candela strobes or horn/strobes are recommended for 20' x 20' rooms or less. *For a complete listing of SpectrAlert current require-
ments, please refer to the Current Draw tables on page 2 of this document, or the Instruction Manual. Hom and horn/strobe current
draws assume the ham Is set at Temp 3, electromechanical tone, and high audibility.
Page 6 of 6 -DN-5939
(_
C
c..
06-01-99 11:43:21
LISTING tlo.
CATEGORY:
LISTEE:
DESIGN:
RATING:
INSTALLATION:
MARKING:
APPROVAL:
NOTE:
FROM: SYSTEM SENSOR FAX TO: 777
CALIFORNIA DEPARTMENT OF FORESTRY• FIRE l'ROTEC'nON
OFFICE: OF THE STATE FIRE NARSNAL
FIRE: E:NGINEE:RING DIVISION
LISTING SERVICE
7136-1209:173
Audible Devices
System Sensor, 3826 Ohio Ave, St Charles IL 60174
Contact: Adam Kozlowski (8301 377-6580
PAGE
USTING EXPIRES
JUNE 30, 1999
Page 1 of 1
Modelo P1215, P121576, P2416, P241576, P241575F, P241676EV,
P2430, P2460, P2476, P2496 and P24110 horn/strobes with or without
suffix -W (white color). Suffix F is for fuego design and suffix EV indicating
the Ions hes the word •EVAC" on It. Refer to Dstee'a data sheet for
additional detaUed product description and operational considerations.
Electrical: -12, 10.s -11 voe
-24: 20 -ao voe
Candela: -15: 16cd
-1575: 15cd, 76cd on axis
-30: 30cd•
-60: 60cd•
-95: 95cd•
-76: 76cd
-110: 110cd
In accordance with llstee'a printed Installation Instructions, applicable codes.&
ordinances and in a manner acceptable to the authority having jurisdiction.
These sounder/strobe combination units are not intended for field assembly.
Llstee's name. moder number. rating and UL label.
Listed as horn strobes for use with separately ftsted compatible fiAI alarm control
units. Suitable for the hearing Impaired application. For wall mount and Indoor
use only.
Units can generate the distinctive three-pulse Temporal Pattem Fire Alarm
Evacuation Signal !for total evacuation) In accordance with NFPA 72, 1993
Edition. Refer to manufecturer'e Installation Manual for details.
Models P1216 and P121575 BAI .llll2I Intended for Public Mode Fire Alarm
Service when used on 1 2 V cont,vl panel at low volume.
T'Hlsl.lS1'DIG•IMSEDUPON'1"£ICHNICALDATASUltMlTTED8YntEAPPUCANT. CSFMF'UmENGU EENWGffAFf'KASREYIIEWED
1HE1al'RESUl.!n AND/OR O'l'HIDI DATA_,.. DOIES NOT NAU AH UIDIIPDIDl:N'l'VDlll'ICA'rlON OI' ANTD.AIMS. Tlm l.-nND m NOT
ANDIDCMIDIDft'ClllllbOOMMDID4TIONOP,,_mrM USTm. nllSLBTWa8H0111.Dtar•U1mTOVBIIPYCOIIBCl'C>l"DATIONAL ~ OR INSTAUA110N CRIT1EIIIA. Rau TO usnra DATA 9HEEI'. INSTALLATION INSl1IUC110N9 AND/OR ontD
sun'Aa.KINPOMIA.1IONSOURCD.
DATE lssUED: JULY 21, 1998 APPROVED Br.
EFFEc:TlvE ISSUE DATE TO EXPIRATION DATE
.Jl.N-01-1999 10:15 SYSTEM~ FAX P.05
s
(_
(._
(_
06-01-99 11:43:21
USTINQNo.
CATEGORY:
USTEE:
DESIGN:
RATING:
INSTALLA TlON:
MARKING:
APPROVAL:
FROM: SYSTEM SENSOR FAX TO: 777
CALIFORNIA DEPAMTMENTOF Jl'ORDTRV a FIRE f"ROI EChON
OFF1CEOF1ltl! STATI! l'IRE MARIIHAL
FIRE ENGINEERING DIVISION
LISTING SERVICE
7125-1209: 174
Fire Alann Oevices far Hearing Impaired
System Sensor, 3825 Ohio Avenue, St. Charles IL 60174
Contact: Adam Kozlowski 16301 377-8580
PAGE
I l.JSnNG ExPIREs JUNa30,1"9
Page 1 of 1
Models 51215, 52415, 52476, 524110, 5121575 and S241575 strobe fiohta.
Model number may be followed by suffix -W indicating color wtite. Refer to
list••• data net for detaled product deactiption and operational considerations.
Electrical: -12: 10.5-17VDC
-24: 20 -30 voe
Candela: -15: 15cd
-1575: 15cd, 75cd on a><is
-75: 75cd
-110: 110cd
In accordance with listee's printed installation instructions, applicable codes &
otdinances and in a manner acceptable to the authority having jurisdiction.
Listee' s name, model number, electrical and candela rating and UL label.
listed as hearing i~aired strobe lights for use with separately listed compatible
fire alarm control unit. For wall mount and Indoor use only.
02-03-97
THlaLISnNCl•MS&DUPONTKCHNICALDATA&JIIMiii&WaYTlfBAPPLICANT, CSFMF1uENGINDNNGsrMFHASIIIIE\'IEw.D
THl:l'WSTRUUL'QANDl"'OllunaRDATAa&n'DO.-NOTNAKEANIHDD'CNDDITVElllrlCATIONCWANTCI.AIMa. 'Tlll8...,...■NOT
AN 1bC ~l..aP'TOII RDXIMlllmimA.110NOftTHEll'DI US1'1ED. l)tll l.8l"Ntcl 8HOULD f«Jl" •USIEDTOVIERIP'(CQ JZCI OPIDIATIONAL
JUQUIRDQN1'9 OIi u.rAU.ATION Cltrr'EIIIA. RsPIDt TO USl'D"B DATA SHEET', IN8TAU.ATION RISl'RUC'l'ICII Nf/0/0ff OTHat
SUff'AIILIE INPOMIATION 90URCa::L
DATI;; ISSUED: MAY 15, 1998 APPROVED Br.
EFFECTIVE ISGIJE DATE TO EXPIRATION DATE
6
I
JU,/-01-1999 10:15 SYSTEM 5ENSCR FAX P.06
(_
LISTING No.
CATEGORY:
LISTEE:
DESIGN:
RATING:
INSTALLATION:
CALIFORNIA DEPARTMENT Of FORESTRY & FIRE PROTECTION
OFFICE OF THE ST ATE FIRE MARSHAL
FIRE ENGINEERING -BUILDING MATERIALS LISTING PROGRAM ...
LISTING SERVICE
7125-1209:182
Fire Alarm Devices for the Hearing Impaired
System Sensor, 3825 Ohio Avenue, St. Charles IL 60174
Contact: Adam Kozlowski (630) 377-6580
,,
Listing Expires
June 30, 2000
Page 1 of 1
Models P2475K, P241575K and P24110K horn/strobes. Suffix "K" indicating
extended indoor operating temperature range of 32° F to 150° F and a NEMA
3R enclosure rating. Refer to listee's data sheet for additional detailed product
description and operational considerations. •
20 -30 voe
In accordance with listee's printed installation instructions, NFPA 72, applicable
codes & ordinances and in a manner acceptable to the authority having
jurisdiction.
L MARKING: listee's name, model number, electrical rating and UL label.
APPROVAL: Listed as horn strobes suitable for the hearing impaired application when used
with separately listed compatible fire alarm control units. For indoor use and
wall mount only.
If these units are required to produce a distinctive three-pulse Temporal
Pattern Fire Alarm Evacuation Signal (for total evacuation) in accordance with
NFPA 72, 1993 Edition, they must be used with a fire alarm control unit that
can generate the temporal pattern signal. Refer to manufacturer's Installation
Manual for details.
07-14-98
This listing is based upon technical data submitted by the applicant CSFM fire Engineering staff has reviewed the test results and/or
other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the
item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet,
installation instructions and/or other suitable information sources.
Date Issued: JULY 1, 1999
Effective issue date to expiration date
Authorized By: ~ ~ Deputy State Fire Marshal Ill
l.
l.
(_
GENERAL
The System Sensor DH400ACDC samples air currents
passing through a duct. It gives dependable performance
for management of fans, blowers and air conditioning sys-
tems, preventing the spread of toxic smoke and fire gases
through the protected area.
System Sensor's DH400ACDC 4-wire duct detector hous-
ing will accommodate either the 1451 DH ionization sensor
or the 2451 photoelectric sensor. The twist-in, twist-out
detector heads allow easy removal for quick cleaning and
maintenance, or a change in application without removing
the duct housing.
NOTE: The System Sensor DH400ACDC Duct Detector
Housing is supplied with either the 1451DH Sensor (order
DH400ACDCI) or the 2451 Photoelectric Sensor (order
DH400ACDCP).
FEATURES
24 voe operation.
Accommodates ionization or photoelectric heads.
Simple change-out of detector heads: twist in, twist out.
Easy to maintain.
Powered outputs for remote LED and Sounder/Strobe.
Air velocity rating from 500 to 4,000 feet per minute (3.175
to 25.4 m./sec.).
UL 268A listed.
Reset time: 0.3 seconds (maximum).
Clear polycarbonate cover for convenient visual inspec-
tion of sampling tube filters.
Rugged plastic housing (mounting portion).
Remote test station option.
Easy and quick mounting to round or rectangular ducts
from 1' to 12' (0.305 to 3.66 m) wide.
Three-year limited warranty.
APPLICATIONS
DH400ACDC detectors are designed to operate on 24 VDC,
24 VAC, 120 VAC, or 240 VAC. Alarm and supervisory
relay contacts are available for control panel interface
(alarm initiation), HVAC control, and other auxiliary func-
tions. These detectors are NOT designed for 2-wire appli-
cations.
Duct detectors are:
NOT a substitute for open area smoke detectors.
NOT a substitute for early warning detection.
NOT a replacement for a building's regular fire detection
system.
Refer to NFPA 90A for additional duct detector application
information.
June 18, 1998 1-352
DH400ACDC Series
4-Wire Duct Detector Housings for
Ionization and Photoelectric Sensors
Section: Conventional Initiating Devices
I California State Fire Marshal
3240-1209:155
S911 CS308
MEA
427-91-E <8>
OV3AO.AY
DH400ACDCP Duct Detector Housing
with 2451 Photoelectric Sensor
CONSTRUCTION AND INSTALLATION
The twist-in, twist-out detector and base allow the removal
of detectors easily and quickly for cleaning and mainte-
nance. In addition, detector heads can be changed to fit
the application without removing the duct housing. The
DH400ACDC comes with built-in exhaust tube. Sampling
tubes are available to fit ducts from 1 to 12 feet (0.305 to
3.66 meters) wide.
ENVIRONMENTAL LIMITS
Temperature: 32°F to 120"F (0°C to 49°C).
DO NOT INSTALL where normal ambient temperatures
exceed 120"F (50"C).
Relative humidity: 10% to 93%.
Air velocity: 500 to 4,000 ft./min. (3.175 to 25.4 m./sec.).
MECHANICAL SPECIFICATIONS
Width: 14.5 inches (36.83 cm).
Height: 5 inches (12.70 cm).
Depth (installed): 4 inches (10.16 cm).
Weight: 4.5 pounds (2.041 kg).
This document is not intended to be used for installation purposes. We by to keep our
product information up-to-date and accurate. We cannot cover all specific applications or
anticipate all requirements. All specifications are subject to change without notice. For
more information, contact NOTIFIER. Phone: (203) 484-7161 FAX; (203) 484-7118
1S0-9001
Engineering and Manufacturing
Qualily Syslem Certified lo
lnlemational Standard 150-9001 @) N OTI Fl En· 12 Clintonville Road, Northford, Connecticut 06472 Made In the U.S.A.
DN-3251 -Page 1 of2
ELECTRICAL CHARACTERISTICS
Power supply voltage: 20-29 voe 24 VAC, 50-00 Hz 120 VAC, 50-00 Hz 220/240 VAC,
50-00 Hz
Ripple voltage: 4 Vpp NIA NIA NIA
Input capacitance: 270 µF max. 270 µF max. NIA NIA
Reset voltage: 3 voe min. 2 VAC min. 10VAC min. 20VAC min.
Reset time wHh RTS451 ): 0.03 kl 0.30 sec. 0.03 kl 0.30 sec. 0.03 kl 0.30 sec. 0.03 kl 0.30 sec.
Reset time (by power down): 0.6 sec. max. 0.6 sec. max. 0.6 sec. max. 0.6 sec. max.
Power up time: 34 sec. max. 34 sec. max. 34 sec. max. 34 sec. max.
Alarm response time: 2 kl 17 sec. 2 kl 17 sec. 2 kl 17 sec. 2 kl 17 sec.
CURRENT & POWER REQUIREMENTS (using no accessories)
Maximum standby current: 25mA 35 mARMS 20 mARMS 20 mARMS
Maximum standby power: 1 Watt 1 Watt avg. 3 Watts avg. 3 Watts avg.
Maximum alarm current: 95mA 55 mA RMS 55 mARMS 30 mARMS
Maximum alarm power: 4 Watts 4 Watts avg. 4 Watts avg. 4 Watts avg.
CONTACT RATINGS
Alarm Initiation contacts (SPST): 2.0 A@ 30 VAC/DC (0.6 power factor).
Alarm auxiliary contacts (DPDT): 10 A@30 voe.
10 A @ 277 VAC (0.75 power factor).
240 VA@ 240 VAC (0.4 power factor).
1/8 HP@ 120 VAC.
1/4 HP @ 240 VAC.
Trouble contacts (SPST): 0.3 A @ 32 voe (resistive).
PRODUCT LINE INFORMATION
Model No. Description
DH400ACDCI DH400ACDC duct detector housing with ST-10
1451 DH ionization sensor.
Metal sampling tube, duct widths 8' (1.2192
m) to 12' to (3.6576 m).
DH400ACDCP DH400ACDC duct detector housing with APA451
2451 photoelectric sensor.
1451OH Replacement ionization smoke detector RA400Z
head. PA400
2451 Replacement photoelectric smoke detector
head. M02-04-00
ST-1.5 Metal sampling tube, duct widths 1' (0.3048 RTS451 m) to 2' (0.6096 m). M0D400R
ST-3 Metal sampling tube, duct widths 2' (0.6096 CRT-400 m) to 4 (1.2192 m).
ST-5 Metal sampling tube, duct widths 4' (1.2192
m) to 8' (2.4384 m).
Annunciator with piezo, alarm, and power
LEDs.
Remote annunciator alarm LED.
Piezo alert sounder (offered in red [RJ, white
[WJ, or beige [BJ).
Test magnet.
Remote test station.
Sensitivity test kit.
Ionization cover removal tool.
ACCESSORY CURRENT LOADS AT 24 VDC
Any combination of accessories may be used such that
the given current loads total:
• 100 mA or less in the Standby state.
• 15 mA or less in the Alarm state.
*Note: When initiating an alarm using the test magnet. The
RTS451 requires 71 mA maximum in pre-alarm and 78 mA in alarm.
Normal standby current is O mA. The alarm current drops to 7 mA
when the test magnet is removed from the RTS451.
Page 2 of 2 -DN-3251
DEVICE
APA451
PA400
RA400Z
RTS451
STANDBY ALARM
12 mA max. 30 mAmax.
OmA 15 mA max.
OmA 7mAmax.
OmA* 7 mA max.*
c..
L
LISTING No.
CATEGORY:
LISTEE:
DESIGN:
INSTALLATION:
MARKING:
APPROVAL:
NOTE:
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING DMSION
LISTING SERVICE
3240-1209: 155
Duct Detector Housing/Base
System Sensor, 3825 Ohio Avenue, St. Charles, IL 60174
Contact: Adam Kozlowksi (630) 377-6580
LfsnNG ExPIRES
JUNE 30, 1999
Page 1 of 1
Duct smoke detector units, Models DH400, DH400ACDC, DH400ACDCIR,
DH400ACDCP5V, DH400ACDCl5V, DH400ACDCIHT•, OH400REL, DH500,
DH500ACDC, P270-10001 and P270-1000P. Unit consists of a housing, relay,
electrical components, sampling and exhaust tubes and a listed detector head.
Series DH400 and P270 are intended for use with Models 1451 DH (CSFM Listing
No. 7271-1209: 126) and 2451 (CSFM Listing No. 7272-1209: 131 I detector heads
for open area protection which have been tested for duct applications. •Model
DH400ACDCIHT is intended for use with Model 1451DHHT smoke detector
(CSFM listing No. 7271-1209: 126)
Series DH500 are intended for use with Models 1551 (CSFM Listing No. 7271-
1209:106) and 2551 (CSFM listing No. 7272-1209:107) detector heads for open
area which have been tested for duct applications.
Refer to listee·s data sheet for additional detailed product description and
operational considerations.
In accordance with listee's printed installation instruction, applicable codes and
ordinances and in a manner acceptable to the authority having jurisdiction.
Listee's name, model designation. air velocity rating and UL label.
Listed as duct detector units when used with listee's separately listed compatible
control units. Intended for use in HVAC systems having air velocities between
300 to 4000 ft/min.
Formerly 3240-1 209: 137 & 139
"Rev. 12-10-97
THIS LISTING IS BASED UPON TECHNICAL DATA SUBMmEo BY THE APPLICANT. CSFM FIRE ENGINEERING STAFF HAS REVIEWED
THE TEST RESUL'rS AND/ OR OTHER DATA BllT DOES NOT MAKE Ali INDEPENDENT VERJFlCA TION OF ANY Cl.AIMS. THIS LISTING IS NOT
AN ENDORSEMENT OR RECOMMENDATION OF THE ITEM lJST'ED, THIS LISTING SHOULD NOT BE USED TO VERIFY CORREcr OPERATIONAL
"EQUIREMENTS OR INSTAL.l.ATION CRITERIA. REFER TO US'TEE'S DATA SHEET, INSTAL.1.ATION INSTRUCTIONS AND/OR OTHER C !fTASLE INFORMATION SOURCES.
DATE lssuEo: MAY 15, 1998 APPROVED Bv:
EFFECTIVE ISSUE DATE TO EXPIRATION DATE
PROGRAM COORDINATOR