HomeMy WebLinkAbout5860 OWENS AVE; ; FA010035; Permit7/24/25, 1:27 PM
Job Address:
Permit Type:
Parcel No:
Lot#:
Reference No.:
PC#:
Project Title:
Applicant:
about:blank
Fees($)
176
FA010035 Permit Data
City of Carlsbad
Fire Alarm Permit
Permit No: FA010035
5860 OWENS AV Status: ISSUED
FALARM Applied 8/21/2001
2120923300 Approved: 8/29/2001
0
Issued: 8/29/2001
Inspector:
PALOMAR HEIGHTS PLAZA BLDG. 1
Add'I Fees ($)
0
Owner:
BUIE CARLSBAD LOT 10 LL C
11260 EL CAMINO REAL #200
SAN DIEGO CA
Total($)
176
Balance($)
0
1/1
Carlsbad Fire Departmerfill[ COPY 011243
1635 Faraday Ave.
Carlsbad, CA 92008
Fire Prevention
(760) 602-4660
Plan Review Requirements Category: Alarm System Plan
Reviewed by: Date of Report: _0_81_24_;2_0_0_1 _______ _
Name: JJJ Enterprises
Address: 533 S. Vinewood
City, State: Escondido CA 92029
Plan Checker: Job #: 011243 -------
Job Name: Palomar Heights #1 Bldg#: CB011243 ----------------~~
Job Address: 5860 Owens Avenue Ste. or Bldg. No.
IZI Approved
LJ Approved
Subject to
LJ Incomplete
Review
FD Job#
The item you have submitted for review has been approved. The approval is
based on plans, information and / or specifications provided in your submittal;
therefore any changes to these items after this date, including field
modifications, must be reviewed by this office to insure continued conformance
with applicable codes and standards. Please review carefully all comments
attached as failure to comply with instructions in this report can result in
suspension of permit to construct or install improvements.
The item you have submitted for review has been approved subject to the
attached conditions. The approval is based on plans, information and/or
specifications provided in your submittal. Please review carefully all comments
attached, as failure to comply with instructions in this report can result in
suspension of permit to construct or install improvements. Please resubmit to
this office the necessary plans and / or specifications required to indicate
compliance with applicable codes and standards.
The item you have submitted for review is incomplete. At this time, this office
cannot adequately conduct a review to determine compliance with the
applicable codes and / or standards. Please review carefully all comments
attached. Please resubmit the necessary plans and / or specifications to this
office for review and approval.
1st
011243
2nd
FD File#
3rd Other Agency ID
FIRE ALARM • SECURITY • LOW VOLTAGE SYSTEMS
PALOMAR HEIGHTS PLAZA
BLDGS 1 &J:5
CARLSBAD, CA
FIRE ALARM SYSTEM
BILL OF MATERIALS
C
3 PALOMAR HEIGHTS PLAZA BLDGS 1 & /,/
CARLSBAD, CA r
FIRE ALARM SYSTEM
BILL OF MATERIALS
1 NOTIFIER AFP-200 ADDRESSABLE CONTROL PANEL
CSFM# 7165-0028:164
10 NOTIFIER FSP-751 INTELLIGENT SMOKE DETECTOR
CSFM# 7272-1209:192
W/B710LPBP BASE
CSFM# 7300-0028: 173
6 NOTIFIER FRM-1 RELAY MODUEL
CSFM# 7300-0028:202
4 NOTIFIER FST-751 INTELLIGENT HEAT DETECTOR
CSFM# 7270-0028:196
W/B710LPBP BASE
CSFM# 7300-0028: 173
C
C
C
({;})NOTIFIER®.
GENERAL
The AFP-200 is a compact, cost-effective, intelligent fire
alarm control with a capacity of 301 individually identified
and controlled points and an extensive list of powerful fea-
tures. The AFP-200 provides capabilities that exceed most
large intelligent systems, at a cost comparable to conven-
tional control panels.
FEATURES
198 intelligent device capacity (99 analog detectors and 99
monitor/control modules). Style 4, 6, or 7.
Overall 301 point capability (198 intelligent points, 4 pro-
grammable NAG circuits, 99 programmable relays).
Network ready (reference NOTI • FIRE• NET'" and NAM-
232 data sheets for more information).
Intelligent features:
v' Manual sensitivity adjustment.
v' Day/Night automatic sensitivity adjustment.
v' Drift compensation (U.S. Patent Pending) meets UL
requirements as a calibrated test instrument.
v' Auto detector test (meets NFPA 72).
v' Maintenance alert (two separate algorithms).
v Pre-alarm (AWACS™ U.S. Patent Pending).
v Activate local sounder base on pre-alarm.
v' LED blink control for sleeping areas.
v' Automatic device type check.
Releasing features:
V Four independent hazards.
v' Sophisticated cross-zone (three options)
April 5, 2001 DN-3783 • A-105
AFP-200
Analog Fire Panel
Section: Intelligent Fire Alarm Control Panels
® I California
State Fire
Marshal
7165-0028: 164
(not for releasing) LISTED CS118
S635 <8> FM U.S. Coast Guard
161.002/23/1 Approved
~
94/60004 (E1)
MEA
104-93-E Vol. VI
(not for releasing)
v' Delay timer and Discharge timers (adjustable).
v' Abort (four options).
TheAFP-200
Optional □ACT, with AC fail delay.
LCD-80 remote display/control.
ACS annunciators (EIA-485), including LDM custom.
Printer interface (BO-column and 40-column printers).
5.0 A_ usable regulated output power, plus 6.0 A expander
(maximum 8.0 A to panel circuits).
SO-character LCD display, backlit.
Real-time clock, with European format option.
History file with 650-event capacity in nonvolatile memory.
Includes non-erasable shadow history.
Waterflow or supervisory selection per point.
Alarm Verification selection per point, with tally.
Walk Test reports two devices set to same address.
Positive Alarm Sequence (PAS) Presignal per NFPA 72.
Silence inhibit and Auto Silence timer options.
March time/temporal/California code for bell circuits.
Field-programmable on panel or on PC, with user-defined
passwords, plus Autoprogram feature.
UL Listed modem interface allows remote/off-site system
integration.
FZM-1 two-wire detector interface provides compatibility
NOTl•FIRE•NET™ is a trademark of NOTIFIER, 1994.
p2.wmf
with many non-NOTI Fl ER detectors for retrofit applications
(consult factory for latest compatibility listings).
Dual-rate charger for up to 90 hours of standby power.
Two-Stage option for notification circuits (Canada).
Tornado Warning activates different notification circuit code.
Non-alarm points for lower priority functions.
Remote Silence/Reset/Evacuate via monitor modules.
Automatic time control functions, with holiday exceptions.
Rapid poll algorithm for manual stations. Responds in < 2
seconds.
Operates with untwisted, unshielded wire (up to 1,000 ft./
304.8 m) for retrofit applications (U.S. Patent 5,210,523).
UL Listed for Fire Signaling per Standard 864 & NFPA 72.
UL Listed for Burglary applications per Standard 1076.
UL Listed for Releasing Service. Complies with NFPA 12,
12A, 12B, 13, 15, 16, 2001 Standards when installed in
accordance with appropriate NFPA standard.
UL Listed for Critical Process Monitoring.
FM approved for Agent Release and Preaction/Deluge.
MEA and CSFM approved; however, not approved for
releasing by these agencies.
Approved for marine applications by U.S. Coast Guard and
Lloyd's Register of shipping.
This do~ument i~ not intended to be used for installation purposes. We try to keep our
pro~~ct 1nformabo~ up-to-date and accurate. We cannot cover all specific applications or
antIc1pate all requirements. All specifications are subject to change without notice
For more information, contact NOTIFIER. Phone: (203) 484-7161 FAX: (203) 484-7118 ISO 9001
CERTIFIED
@)NOTIFIER' 12 Clintonville Road, Northford, Connecticut 06472 INCINEIIINI: I MINllilfflllNI: Made in the U.S.A.
DN-3783 • 04/05/01 -Page 1 of 4
SYSTEM BLOCK DIAGRAM
NOTl•FIRE•NET'"
Optional Network Interface
via the NAM-232
FSl-751 FSP-751
Ion Photo
EIA-485
FST-751
Thermal
Fixed
SLC Intelligent Loop
DEVICES
-----------------· NBG-12LX
99 software zones
FMM-1 FCM-1
t i
IDC IAC
AFP-200
Four standard
Notification or
Releasing
circuits.
Full Alpha
keyboard for
menu-driven
programming.
5 ampere
regulated
power supply.
Voltmeter/
Ammeter
Option.
Page 2 of 4 -DN-3783 • 04/05/01
4 Notification or
Release Circuits
RS-232
PRN Series Printer
EIA-232 interface for CRT,
printer, or PC computer.
ACM-BR
Relay
Control
CRT-2
ACM/AEM-16AT
LED Annunciator
LDM-32
Custom Graphics
EIA-485 loop for
LCD or LED
annunciators.
SLC loop.
Up to 198 devices
on a single pair
of wires.
Slot for
optional
module.
3783dlag.wmf
12 AH batteries; 18 AH with BB-17.
Up to 90 hours standby power.
SO-character backlit
LCD display.
C
AWACS™ Advance Warning Addressable Combustion Sensing (U.S. Patent Pending)
SMOKE OBSCURATION
% per foot
3% ALERT ACTION ALARM
Warning at panel Shut off power Evacuate building
of possible fire to equipment monitored and call fire department
by this detector
PREALM SMOKE(PHOTOI PREALM SMOKEIPHOTOI ALARM: SMOKEIPHOTOI
FLOOR 3 EQUIP RACK 5 FLOOR 3 EQUIP RACK 5 FLOOR 3 EQUIP RACK
2% ALERT: 0.22% 1.40% ACTION: 0.51% 1.40% FIRE DEPT CALLED
11: 25 p 12/25/93 D66 11 :36 P 12125/93 066 11 :59 p 12/25/93
v v
1%
i
TIME~
ALERT and ACTION levels are completely adjustable in the field to suit the cleanliness and stability of the environment.
ALARM levels are field adjustable to one of three levels within the UL permitted range. ACTION levels latch and may be
used to perform control functions. ALERT levels self-restore and may be used to activate a local sounder base before
general ALARM evacuation.
FIELD PROGRAMMING -3WAYS
1. AUTO-PROGRAM
The AFP-200 identifies all devices that are connect-
ed, determines the type of device, and loads default
values (general alarm) into nonvolatile memory. This
is completed in less than 30 seconds.
2. ON-LINE EDIT
While still providing fire protection, the AFP-200 pro-
gram may be completely edited from the front keypad.
Menu trees ermit eas chan e of an p y g y p arameter
without referral to the programming manual. Recall,
increment and edit function speeds entry of alphanu-
meric labels. New program check routine catches
common errors.
3. OFF-LINE PC: VeriFire-200
The complete AFP-200 program may be created in
an off-line PC-compatible computer with a Windows®-
based utility, then loaded into the AFP-200 EIA-232
port. The program may also be off-loaded to a PC at
any time. High-speed data transfer completes upload
or download in less than one minute. The PC pro-
gram may also be used to access remote AFP-200
systems over dial-up phone lines, providing detail
status information and history file search/sort.
3.
AUTOPROGRAM 1.
PLEASE WAIT
O= CLR 1 = AUTO 2= POINT 2.
3= PASSWD 4= MESSAGE
5=ZONES 6 = SPL ZONES
7= SYS 8 =CHECK
DN-3783 -Page 3 of 4
AGENCY LISTINGS AND APPROVALS
See page 1 for listing agencies and file numbers. These
listings and approvals apply to the basic AFP-200 control
panel. In some cases, certain modules may not be listed by
certain approval agencies, or listing may be in process. Con-
sult factory for latest listing status.
SPECIFICATIONS
Primary input power, 120 VAC, 50/60 Hz, 3.0 Amps.
• Total Internal 24 VDC Power -5.0 A (total shared power).
ti' High-ripple regulated power: 1.5A (suitable for EIA-485
devices, except ACM-SR); 1.0 A maximum standby.
ti' Non-resettable power: 500 mA.
V Four-wire smoke detector power: 500 mA.
t/ Four built-in notification circuits:
• NAG Circuit 1: 2.25 A.
• NAG Circuits 2-4: 2.25 A (shared total).
NOTE: with optional APS-6R Power Supply NAG circuits 3
& 4 are expanded to 3.0 A (8.0 A total power).
Battery charger range: 7 AH -18 AH.
Charge high rate: 29.1 V. Float rate: 27.0 V.
• Relay contact rating: 2.0 A @ 30 VDC.
• Cabinet dimensions: 16.125" (40.9575 cm) high x 14.5"
(36.83 cm) wide x 5.5" (13.97 cm) deep.
SYSTEM CAPACITY
• Total programmable input/output points: 301
• Intelligent detectors: 99
Addressable monitor/control modules: 99
Programmable NAG circuits in panel: 4
• Programmable software zones: 99
Programmable remote relay/annunciator points: 99
• LC0-80 annunciators per system: 4
ACS annunciators per system: 10
CONTROLS AND INDICATORS
6 LED indicators: AC Power; Fire Alarm; Pre-Alarm; Super-
visory/Security; Alarm Silenced; System Trouble.
21 Membrane Switch Controls: Acknowledge/Step; Silence;
Evacuate; System Reset; 12-key Alpha pad; 4 cursor keys;
Enter.
LCD Display: 80 characters (4 x 20) with long-life LED
backlight.
COMPATIBLE INTELLIGENT DEVICES
CPX-751: Low-profile ionization detector.
SDX-751: Low-profile photoelectric detector.
SDX-551TH: Photoelectric with thermal element.
HPX-751: HARSH™ Hostile Area photoelectric detector.
FDX-551: Fixed thermal (heat) sensor.
FDX-551 R: Fixed and rate-of-rise thermal sensor.
CPX-551 DUCT: Ionization smoke detector (for duct use only).
SDX-551 DUCT: Photoelectric smoke detector (duct use only).
B710LP: Detector base, low profile.
B224RB: Intelligent relay base, low profile (low-profile only).
B224BI: Intelligent isolator base, low profile (low-profile only).
B710HD: HARSH™ detector base {HARSH™ only).
BX501: Detector base, classic (SDX-551TH, FDX-551/R only).
B501 BH: Sounder base (classic or low-profile).
BH501 BHT: Sounder base with temporal sounder (classic or
low-profile).
B524RB: Intelligent relay base (SDX-551TH, FDX-551/R only).
B524BI: Intelligent isolator base (SDX-551TH, FDX-551/R only).
8501: Detector base, flangeless (classic or low-profile).
DHX-501: Duct housing with alarm relay.
DHX-502: Duct housing without alarm relay.
continued next column ...
Page 4 of 4 -DN-3783
MMX-1: Monitor module.
MMX-2: Two-wire detector monitor module.
MMX-101: Miniature monitor module.
CMX-2: Control module.
NBG-12LX: Advanced manual fire alarm station, addressable.
BGX-101L: Classic manual fire alarm station, addressable.
ISO-X: Isolator module.
XPS Series: Transponders (see data sheet DN-6625).
COMPATIBLE DEVICES, EIA-232 Port
(see data sheets)
PRN Serles: SO-column printer.
VS4095/S2: Printer, 40 column, 24 volts. Mounted in exter-
nal backbox (order from Keltron, Inc.).
CRT-2: Video display terminal.
NAM-232: Network Interlace Module to NOTl•FIRE•NET
wire or fiber models.
COMPATIBLE DEVICES, RS-485 Port
(see data sheets)
ACS Serles: Remote Serial Annunciator/Control systems.
LCD-80: Remote LCD display.
LDM Series: Remote custom graphic driver modules.
ACM-SR: Remote relay module. Eight Form-C relays.
NIB-96: Network Interlace Board.
RPT-485: Series Repeater, isolator and/or fiber-optic modem.
UDACT: Universal Digital Communicator.
PRODUCT LINE INFORMATION
BEAFP-200G: Basic AFP-200 equipment kit. Includes main
board with display and keypad, door, hardware and manual.
Backbox (SBB-4X or SBB-4XR) ordered separately.
BEAFP-200R: Same as BEAFP-200G, but with red door.
BEAFP-200GE: Same as BEAFP-200G but 230 VAC.
BEAFP-200RE: Same as BEAFP-200R but 230 VAC.
SBB-4X: AFP-200 backbox (no door), gray.
SBB-4XR: AFP-200 backbox (no door), red.
CAB-AM: Heavy-duty outer enclosure. Required for marine
agency approved applications.
4XTM: Plug-in Transmitter Module. Provides municipal box
and remote station connection.
RTM-8: Plug-in Relay Transmitter Module. Provides eight
Form-C relays, plus transmitter.
4XMM: AmmeterNoltmeter.
TR-4XG: Gray Trim Ring for semi-flush mounting (TR-4XR
for red).
DP-AFP200: Full-length dead-front panel (required for Cana-
dian applications).
PS-1270: Battery, 12 volt, 7.0 AH, (two required).
PS-12120: Battery, 12 volt, 12.0 AH, (two required).
PS-12180: Battery, 12 volt, 18.0 AH (two required).
APS-6R: 6.0 A expansion supply (requires 88-17).
BB-17: Battery box, required for PS-12180, or if APS-6R is
used.
411 Series: Digital Alarm Communicator/Transmitter.
VeriFire-200: Programming kit for PC. Includes diskette,
cable, and instructions.
ROM-AFP200SP: Spanish language kit. Includes software
IC, manual, and labels.
ARCHITECTURAL/
ENGINEERING SPECIFICATIONS
Specifications are available on CD-ROM with NOTIFIER's
Speci•FireTM software. Contact NOTIFIER for details.
c...\
c...
c..
LISTING No.
CATEGORY:
LISTEE:
DESIGN:
INSTALLATION:
MARKING:
APPROVAL:
NOTE:
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING -BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
7165-0028:164
Control Units (Non High-Rise)
Page 1 of 1
Notifier, A Pittway Company, One Fire-Lite Place, Northford CT 06472-1653
Contact: Larry Flood (203) 484-1200
Model AFP-200 fire alarm control unit. Local, auxiliary, remote station (PPU), proprietary
(PPU) and central station (PPU). Refer to listee's data sheet for additional detailed product
description and operational considerations. System components:
4XTM
RTM-8
DP-AFP200
TR-4XG
MMX-1, -101
ISO-X
N-ELR
CRT-2
VS4095/5
CMX-1
BB-17
AVPS-24
NAM-232
4XMM
Transmitter Module
Relay Module
Dress Panel
Trim Ring
Monitor Module
Loop Isolator Module
EOL Resistors
Terminal with Keyboard
Printer
Control Module
Battery Box
Power Supply
Network Adapter Module
Meter Module
In accordance with listee's printed installation instructions, NFPA 72, applicable codes &
ordinances and in a manner acceptable to the authority having jurisdiction.
Listee's name, model number, electrical rating and UL label.
Listed as fire alarm control unit for use with separately listed compatible initiating and
indicating devices. Suitable for central station (PPU) service when used with separately
listed compatible DACT.
This control unit can generate the distinctive three-pulse Temporal Pattern Fire Alarm
Evacuation Signal (for total evacuation) in accordance with NFPA 72, 1993 Edition. Refer
to manufacturer's Installation Manual for details.
• Also suitable for releasing service. For releasing application, Models NR-45 battery charger
and AVPS-24 power supply shall not be used. Please contact the manufacturer for action.
*Rev. 02-24-99
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test
results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or
recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation
criteria. Refer to listee's data sheet, installation instructions and/or other suitable information sources.
Date Issued:
Authorized By:
MAY 2, 2001
BEN HO, Supervising Deputy
Program Manager
Listing Expires June 30, 2002
C
C
C
~NOTIFIER~
WFIRE SYSTEMS
GENERAL
The NOTIFIER FSP-751 (photo) and FSl-751 (ion) are ana-
log, addressable, low-profile (height measures only 1.66"/
42.164 mm) smoke detectors designed for the entire line of
Intelligent systems from NOTIFIER. The FSP-751T photo
model includes a built-in thenmal (heat) detection device. If
either condition (smoke or heat) is detected, the device will
alanm.
The addressability of the FSP-751 and FSl-751 enables the
control panel to provide firefighters with a pinpoint descrip-
tion of where the fire is located. The FSP-751 and FSl-751
are also analog devices. The control panel is capable of not
only knowing the detector's location but exactly how much
smoke is in the chamber of the detector. The detector may
be set for different sensitivity settings appropriate to the en-
vironment of its location.
Analog devices continually send obscuration values to the con-
trol panel. These values may be gathered so as to allow the
control panel to detenmine if a detector has accumulated an
excessive amount of dirt or dust. A "maintenance" required
indication allows the installer to clean the smoke detector be-
fore an unwanted false alarm occurs.
The FSl-751 Intelligent Ionization Sensor incorporates a
unique single-source chamber design to respond quickly and
dependably to a broad range of fires.
The FSP-751 Intelligent Photoelectric Sensor's unique opti-
cal sensing chamber is designed with superior signal to noise
ratio. The optical chamber is engineered to sense the pres-
ence of smoke produced by a wide range of combustion
sources.
FlashScan® (patent pending) is a new communication pro-
tocol developed by NOTIFIER Engineering that greatly en-
hances the speed of communication between analog intelli--~
gent devices and certain NOTIFIER systems. Intelligent de-j
vices communicate in a grouped fashion. If one of the de-~
vices within the group has new infonmation, the panel's CPU
stops the group poll and concentrates on single points. The
net effect is response speed greater than five times that of
earlier designs.
FlashScan® is a registered trademark of NOTIFIER.
FEATURES
Sleek, low-profile design (height only 1.66"/42.164 mm).
Common base for both photo and ion detectors.
Addressable-analog communication.
Stable communication technique with noise immunity.
Low standby current.
Rotary 01 to 159 address switches (01 to 99 on traditional
systems).
Optional remote, single-gang LED accessory (RA400Z).
Dual LED design provides 360° viewing angle.
December 15, 2000 DN-6714 • H-200
FSl-751 and FSP-751/751T
Low-Profile Intelligent Plug-in
Smoke Detectors with FlashScan®
Section: Intelligent/Addressable Devices
® (@c I ~~i!i°~~: 11 ;jj Marshal
I.:: 7272-0028:206
LISTED CS308 (FSP-751l-751T}
S1115
MARYLAND
State Fire Marshal
2020 (FSl-751)
2013 (FSP-751l-751T}
<8>
Approved -~--
7271-0028:201
(FSl-751)
MEA
277-99-E
(FSP-751I
-7517 only)
FSP-751Twith B710LP base
FSP-751 with RMK400 recessed mounting kit
Visible bicolor LEDs blink green every time the detector is
addressed, and illuminate steady red on alarm.
Walk test with address display (an address of 121 will blink
the detector LED: 12-(pause)-1) (FlashScan® systems
only).
Built-in functional test switch activated by external mag-
net.
Optional relay, isolator, or sounder bases.
Listed to UL 268.
SPECIFICATIONS
Size: 1.66" (42.16 mm) high x 4.1" (104.14 mm) diameter.
Shipping weight: 3.6 oz. (104 g).
Operating temperature: 0°C to 49°C (32°F to 120°F).
This document is not intended to be used for installation purposes. We try to keep our
product information up-to...(jate and accurate. We cannot cover all specific applications or
anticipate all requirements. All specifications are subject to change without notice.
For more information, contact NOTIFIER. Phone: (203) 484-7161 FAX: (203} 484-7118 ISO 9001
CERTIFIED (ffi} N OTI Fl ER" 12 Clintonville Road, Northford, Connecticut 06472 llllrflllNI I MMIFlnlllNI
DN-6714•12/15/00 -Page 1 of4
UL listed velocity range: ION: 0 -1500 fpm (0 -7.62 ml
sec). PHOTO: O -4000 fpm (0 -20.32 mlsec).
Relative humidity: 10% -93% noncondensing.
ELECTRICAL SPECIFICATIONS:
Voltage range: 15 -32 volts DC peak.
Standby current -ION: 200 µA@ 24 VDC (without com-
munication); 300 µA@ 24 VDC (one communication every
5 seconds with LED enabled).
Standby current -PHOTO: 250 µA @ 24 VDC (without
communication); 360 µA @ 24 VDC (one communication
every 5 seconds with LED enabled).
LED current (max.): 6.5 mA@ 24 VDC ("ON").
Air velocity ratings: FSP-751 & FSP-751T: to 4,00011./min.
(1219.2 m/min.). FSl-751: to 1,50011./min. (457.2 m/min.).
BASES AVAILABLE:
B710LP: 6.1" (154.94 mm) diameter.
B501: 4.1" (104.14 mm) diameter.
B501 BH or B501 BHT: Sounder base assembly. Includes
B501 base.
B224RB Relay Base: Screw terminals: up to 14 AWG (2.0
mm'). Relay type: Form-C. Rating: 2.0 A @ 30 VDC
resistive; 0.3 A@ 110 VDC inductive; 1.0 A@ 30 VDC in-
ductive. Dimensions: 6.2" (157.48 mm) x 1.2" (30.48 mm).
B524BI Isolator Base: Dimensions: 6.2" (157.48 mm) x
1.2" (30.48 mm). Maximum: 25 devices between isolator
bases.
Duct applications: FSP-751 and FSP-751T are Listed for
use in air ducts. See Duct Application Guide A05-1004 for
details on pendant-mount applications. NOTE: These prod-
ucts are NOT Listed for use inside a duct smoke detector
housing.
INSTALLATION
The FSP-751 and FSl-751 plug-in detectors use a separate
base to simplify installation, service, and maintenance. A
special tool allows maintenance personnel to plug in and re-
move detectors without using a ladder.
Mount base on a box which is at least 1.5" (38.1 mm) deep.
Suitable mounting base boxes include:
4" (101.6 mm) square box.
3-112" (88.9 mm) or 4" (101.6 mm) octagonal box.
Single-gang box (except relay or isolator base).
With B501BH base, use a 4" (101.6 mm) square box.
With B224RB or B224BI base, use a 3-112" (88.9 mm)
octagonal box, or a 4" (101.6 mm) octagonal or square
box.
SMOKE GUARD
Cover: 16 gauge perforated steel (3/16" [4.7625 mm] dia.
perforations on 1/4" [6.35 mm] staggered centers). 51 % open.
SDG-773 is 3" (76.2 mm) deep by 7" (177.8 mm) wide.
Frame: 3/4" x 314" (19.05 x 19.05 mm) angle, 14 gauge solid
steel.
All guards are supplied with the fol/owing:
1) Guards fasten to mounting frame with No. 10124 x 318"
(9.525 mm) long Allen-head screws (10/24 spanner-head
screws and tool option at extra cost).
PRODUCT LINE INFORMATION
Description Model
FSl-751 Low-profile intelligent ionization sensor. Must
be mounted to one of the bases listed below.
FSP-751 Low-profile intelligent photoelectronic sensor.
Must be mounted to one of the bases listed be-
low.
FSP-751T Same as FSP-751 but includes a built-in 135"F
(57"C) fixed-temperature thermal device.
BASES:
B710LPBP Standard U.S. low-profile base, pkg. of 10.
B501BP Standard European flangeless base, pkg. of 10.
B501 BH Sounder base, includes B501 base above.
B501 BHT Same as B501BH, but includes temporal sounder.
B224RB Intelligent relay base.
B224BI Intelligent isolator base. Isolates SLC from loop
shorts.
ACCESSORIES:
SDG-773 Smoke Detector Guard. This guard is mechani-
cally compatible with both FSl-751 and FSP-751
detectors. It is UL-compatibility listed with the
FSP-751 (file UL S5515). /tis NOT UL-compat-
ibility listed with the FSl-751.
F110 Retrofit replacement flange for BX-501 base.
Converts BX-501 base for use with FlashScan
detectors.
RA400Z* Remote LED annunciator. 3 -32 VDC. Fits
U.S. single-gang electrical box.
SMK400 Surface mounting kit provides for entry of sur-
face wiring conduit. For use with 8501 base
only.
RMK400 Recessed mounting kit. For use with 8501 base
only.
SMB600 Surface mounting kit for use with B710LP.
M02-04-01 Test magnet.
M02-09-00 Test magnet with telescope stick.
XR-2 Detector removal tool. Allows installation and/
or removal of FlashScan Series detector heads
from base in high ceiling installations.
XP-4 Extension pole for XR-2.
foot sections.
•supported by B710LP
and B501 bases only.
OPTIONAL
SDG-773 Smoke Guard
Comes in three five-
(1.905 cm),--------------------------------------------------------------, (1.905 cm)
~\ 7"(17.78cm) \.r;;4•
:~ tf
Celling
or Wall 2) Standard finish: "Cool Tan" baked enamel.
MOUNTING DIAGRAM ►
SDG-773 Smoke Guard
3":
(7.62 cm):
MODEL NO.
SDG-773
4762sdgm.wmf , ___ L_ ___________ ____,
Page2of4-DN-6714•12/15/00
C
C
C
DETECTORS, EXPLODED VIEW
SENSOR
COVER
~ {) -COVER lQ.l
REMOVAL TABS
--
SENSOR
__ SCREEN ~===~µ===~
ilJ □
6714exp1,wrnl
.... FSP-751 and FSP-751T Photo
TEST MAGNET POSITIONING
PAINTED
SURFACE
□
MAGNET TEST
MARKER
D []J
TEST MAGNET
6714mag1.wmf
.... FSP-751 and FSP-751T Photo
~:::::::::::::::::::::::::::::::::~~:::::::::::::::::::::::::::::::~SENSOR
,,Lz=°~===°::=l~~====='a'S::COVER
@ {) -COVER {)
REMOVAL TABS
~ SENSOR
~SCREEN
! SENSOR CONTACTS SENSING
CHAMBER _.--SENSING
CHAMBER
ilJ □
6714a~p2.wml
.... FSl-751 Ion
PAINTED
SURFACE
D []J
TS
6714mag3.tif
.... FSl-751 Ion
DN-6714 • 12/15/00 -Page 3 of 4
WIRING DIAGRAMS
Listed
Compatible
CONTROL
PANEL
+
REMOTE ANNUNCIATOR
+
-------------------------------------------~ OPTIONAL RETURN LOOP -------------------------------------------------------+
REMOTE ANNUNCIATOR
+
A FSP-751 and FSP-751T Photo
/£..CAUTION/ T
DO NOT LOOP wire under terminals 1 or 2.
Break wire run to provide supervision of connections.
+~~---,-----/---------
1
Control
Panel
+
I
~-----'~---------''----/-----'I
______ STYLE6llOPT/ONALWIRING ----~-----~ ____ _
A FSl-751 Ion
Page 4 of 4 -DN-6714 • 12/15/00
L
LISTING No.
CATEGORY:
LISTEE:
DESIGN:
RATING:
INSTALLATION:
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE ARE MARSHAL
ARE ENGINEERING -BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
7272-1209:192
Photoelectric Smoke Detector
System Sensor, 3825 Ohio Avenue, St. Charles, IL 60174
Contact: Andrej Nikolic (630) 377-6674
Page 1 of 1
Models FSP-751 and FSP-751T photoelectric type smoke detectors. Each unit consists
of resistors, capacitors, diodes, transistors, microprocessor, LED, photoelectric chamber,
mounted on a printed wiring board inside an enclosure which has an opening to the
outside air. Model FSP-751 T employs an integral heat sensor. This sensor is intended for
use only as a supplemental to the smoke detector. Refer to listee's data sheet for
additional detailed product description and operational considerations.
24VDC
In accordance with listee's printed installation instructions, applicable codes & ordinances
and in manner acceptable to the authority having jurisdiction.
L !ARKING: listee's name, product number, electrical rating and UL label.
L
APPROVAL: listed as smoke detectors for use with Notifier's separately listed compatible bases and
fire alarm control units. Suitable for open areas with air velocities between 0-4000 fpm.
08-30-99
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test
results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or
recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation
criteria. Refer to iistee's data sheet, installation instructions and/or other suitable information sources.
Date Issued:
Authorized By:
JUNE 7, 2001
BEN HO, Supervising Deputy
Program Manager
Listing Expires June 30, 2002
C'
c...
LISTING No.
CATEGORY:
LISTEE:
DESIGN:
INSTALLATION:
MARKING:
APPROVAL:
XLF:
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING· BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
7300-0028:173
Misc. Devices/Control Unit Accessories
Page 1 of 1
Notifier. A Pittway Company. One Fire-Lite Place, Northford CT 06472-1653 Contact:
Lawrence Flood (203) 484-1200
Models BX501, B610LP, B612LP. B614LP. B616LP and B710LP detector bases. Refer to
listee's data sheet for additional detailed product description and operational considerations.
In accordance with listee's printed installation instructions, applicable codes and
ordinances and in a manner acceptable to the authority having jurisdiction.
Listee's name, product designation, electrical rating and UL label.
Listed as detector bases for use with separately listed compatible detectors.
7300-1209:128
07-29-94
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test
results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or
recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation
criteria. Refer to listee's data sheet, installation instructions and/or other suitable information sources.
Date Issued:
Authorized By:
MAY 4, 2001
BEN HO, Supervising Deputy
Program Manager
Usting Expires June 30, 2002
C
C
C
~NOTIFIER®
WFIRE SYSTEMS
GENERAL
The FST-751 Serles intelligent thermal detector is used
with the intelligent NOTIFIER Fire Alarm Systems to mea-
sure thermal levels caused by a fire and report the analog
level of the thermal measurement to the control panel.
The use of analog information provides significant ben-
efits to the end user, installer, and service personnel in
ways which are not possible with a conventional type sys-
tem. Since this detector is addressable, it helps firefighters
to more quickly locate a fire in its early stages.
FlashScan (patent pending) is a new communication pro•
tocol developed by NOTIFIER Engineering that greatly en-
hances the speed of communication between analog intelli-
gent devices. Intelligent devices communicate in a grouped
fashion. If one of the devices within the group has new infor-
mation, the panel's CPU stops the group poll and concen-
trates on single points. The net effect is response speed
greater than five times that of earlier designs.
FEATURES
Sleek, low-profile, stylish design.
State-of-the-art thermistor technology for fast response.
Rate-of-rise model (FST-751R), 15°F (8.3°C) per minute.
Factory preset at 135°F (58°C).
Addressable by device.
Direct 01 -159 entry of address (01 -99 on traditional
systems).
Two-wire loop connection.
Visible LEDs "blink" every time the unit is addressed.
360°-field viewing angle of the visual alarm indicators (Two
bicolor LEDs). LEDs blink green in Normal condition and
tum on steady red in Alarm.
Integral communications and built-in device-type iden-
tification.
Remote test feature from the panel.
Built-in functional test switch activated by external mag-
net.
Walk test with address display (an address of 121 will blink
the detector LED 12-(pause)-1).
Low standby current.
Listed to UL 521.
Built-in tamper-resistant feature.
Designed for direct-surface or electrical-box mounting.
Sealed against back pressure.
Plugs into separate base for ease of installation and main-
tenance.
Separate base allows interchange of photoelectric, ioniza-
tion and thermal sensors.
SEMS screws for wiring of the separate base.
94-5V plastic flammability rating.
September 15, 2000 DN-6716 • H-210
FST-751 Series
Intelligent Thermal (Heat) Detectors
with FlashScan ™
Section: lntelligenUAddressable Devices
® I California <8> State Fire Marshal
7270-0028:196
LISTED Approved
MARYLAND (AFC-600)
S747 State Fire Marshal
Permit 2011 MEA
278-99-E
Remote LED output connection to optional RA400Z remote
LED annunciator.
Optional sounder, relay, and isolator bases.
Optional recessed (RMK400) or surface (SMK400) base
mounting kits.
APPLICATIONS
Use thermal detectors for protection of property.
For further information call NOTIFIER for manual 156-407-
00, Applications Manual for System Smoke Detectors, which
provides detailed information on detector spacing, placement,
zoning, wiring, and special applications.
CONSTRUCTION
These detectors are constructed of Bayblend® in an off-white
color.
The FST Series plug-in intelligent thermal detector is de-
signed to commercial standards and offers an attractive ap-
pearance.
INSTALLATION
The FST Series plug-in intelligent thermal detector uses a
separate base to simplify installation, service, and mainte-
nance.
Installation instructions are shipped with each detector.
Mount base (all base types) on box which is at least 1.5"
(38.1 mm) deep. Suitable boxes include:
• 4" (101.6 mm) square box.
FlashScan™ is a trademark of NOTIFIER. Bayblend® is a registered trademark of Bayer Corporation.
This document is not intended to be used for installation purposes. We try to keep our
product information up-lo-date and accurate. We cannot cover all specific applications or
anticipate all requirements. All specifications are subject to change without notice. For
more information, contact NOTIFIER. Phone: (203) 484-7161 FAX: (203) 484-7118
@) N OTI Fl ER" 12 Clintonville Road, Northford, Connecticut 06472
ISO 9001
CERTIFIED
INIINl!IINC l MMIIAfflUNC
ON-6716 • 09/15/00 -Page 1 of 2
3-1/2" (88.9 mm) or 4" (101.6 mm) octagonal box.
Single-gang box (except relay or isolator base).
With 85018H or B501BHT base, use a 4" (101.6 mm)
square box.
With B224RB or 822481 base, use a 3-1/2" (88.9 mm) or
4" (101.6 mm) octagonal box, or a 4" (101.6 mm) square
box.
NOTES: 1) Because of the inherent supervision provided by the
SLC loop, end-of-line resistors are not required. Wiring "T-taps"
or branches are permitted for Style 4 (Class "B'? wiring. 2) When
using relay or sounder bases, consult data sheet DN-2243
(ISO-X) for device limitations between isolator modules and iso-
lator bases.
OPERATION
Each FST Series uses one of 159 possible addresses
(99 on traditional systems) on a control panel SLC loop. It
responds to regular polls from the control panel and it
reports its type and status, including the analog level of its
heat-sensing elements. If it receives a test command
from the panel (or a local magnet test), it stimulates its
electronics and reports an alarm analog level. It blinks its
LEDs when polled and turns the LEDs on when com-
manded by the panel (detector blink is optional). The FST
Series offers features and performance that represent the
latest in thermal detector technology.
SPECIFICATIONS
Size: Diameter installed in 8710LP: 6.1" (154.94 mm);
Diameterinstalledin8501: 4.1"(104.14mm). Height: 1.66"
(42.16 mm). Weight: 5 oz. (150 gm).
Operating temperature: -4"F to 100'F (-20'C to 38'C).
Operating humidity range: 10% to 93% relative humidity,
noncondensing.
Operating voltage/current range: 15 -28 V (Peak DC), 5
mA current for visible LEDs latched on.
Detector standby current: 300 µA @ 24 VDC (one com-
munication every 5 seconds with LED blink enabled). For
bases 8224RB or 822481: < 700 µA @ 24 VDC (includes
detector).
Sensor: electronic, dual thermistors.
Fixed temperature setpoint: 135'F (57'C).
WIRING DIAGRAM
REMOTE ANNUNCIATOR
+
+f-f---~
Control
Panel
Rate-of-rise option: 1 S'F (8.3'C) per minute.
B224RB relay base: Screw terminals: up to 14 AWG (2.00
mm'). Relay type: Form-C. Ratings: 2 A @ 30 VDC resis-
tive; 0.3 A@ 110 VDC inductive; 1.0 A@ 30 VDC inductive.
Dimensions: 6.2" (157.48 mm) diameter x 1.2" (30.48
mm) high. See Note 2 (left column).
B224BI isolator base: Dimensions: 6.2" (157.48 mm)
diameter x 1.2" (30.48 mm) high. Maximum: 25 devices
between isolator bases. See Note 2 (left column).
PRODUCT LINE INFORMATION
Model Description
FST-751 Intelligent thermal sensor.
FST-751R Intelligent thermal sensor with rate-of-rise fea-
ture.
BASES:
B710LPBP Standard U.S. style low-profile base, package
often (10).
B501BP Standard European flangeless base, pack-
age of ten (10).
B501BH Sounder base, includes B501 base above.
24 VDC, 85 dBA internal horn.
B501 BHT Same as B501 BH but with temporal pattern
sounder.
B224RB Intelligent relay base.
B224BI Intelligent isolator base. Isolates SLC from loop
shorts.
ACCESSORIES:
RA400Z' Remote LED annunciator. 3 -32 VDC. Fits
U.S. single-gang electrical box.
SMK400 Surface mounting kit provides for entry of sur-
face wiring conduit. For use with B501 base
only.
RMK400 Recessed mounting kit. For use with 8501
base only.
M02-04-00 Test magnet.
•supported by 8501 and B710LP base only.
ARCHITECTS' & ENGINEERS'
SPECIFICATIONS
Specifications are available on these and all NOTIFIER prod-
ucts. Please contact NOTIFIER.
------1 I ~----/----
I I
---t-ir--... I
I
I
I
I
I
I
I
I
I
I ~-------~ ~---/---~ I I -------------------------/-----~ + ______ STY)...E6/7OPTIONALWIR/NG ____ 1 ___________ I
6714wlr2.lif
Page 2 of 2 -DN-6716 • 09/15/00
C
LISTING No.
CATEGORY:
LISTEE:
DESIGN:
RATING:
INSTALLATION:
MARKING:
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING -BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
7270-0028:196
Heat Detector
Page 1 of 1
Notifier, A Pittway Company, One Fire-Lite Place, Northford CT 06472-1653
Contact: Lawrence Flood (203) 484-1200
Models FST-7 51 (fixed temperature) and FST-7 51 R (fixed temperature with Rate-of-Rise)
electronic heat detectors. Refer to listee's data sheet for additional detailed product
description and operational considerations.
135° F fixed temperature
In accordance with listee's printed installation instructions, applicable codes & ordinances
and in a manner acceptable to the authority having jurisdiction.
Listee's name, model number, electrical ratings, and UL Inc. Label
c... APPROVAL: Listed as heat detectors for use with Model B501 or B71 OLP base (CSFM Listing No.
7300-0028:173) and listee's separately listed compatible fire alarm control units.
(_
08-06-99
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test
results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or
recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation
criteria. Refer to listee's data sheet, installation instructions and/or other suitable information sources.
Date Issued:
Authorized By:
MAY 4, 2001
BEN HO, Supervising Deputy
Program Manager
Listing Expires June 30, 2002
C.
(_
(..
LISTING No.
CATEGORY:
USTEE:
DESIGN:
INSTALLATION:
MARKING:
APPROVAL:
XLF:
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING -BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
7300-0028:173
Misc. Devices/Control Unit Accessories
Page 1 of 1
Notifier, A Pittway Company, One Fire-Lite Place, Northford CT 06472-1653 Contact:
Lawrence Flood (203) 484-1200
Models BX501, B61 OLP, B612LP, B614LP, B616LP and B71 OLP detector bases. Refer to
listee's data sheet for additional detailed product description and operational considerations.
In accordance with listee's printed installation instructions, applicable codes and
ordinances and in a manner acceptable to the authority having jurisdiction.
Listee's name, product designation, electrical rating and UL label.
Listed as detector bases for use with separately listed compatible detectors.
7300-1209:128
07-29-94
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test
results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or
recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation
criteria. Refer to listee's data sheet, installation instructions and/or other suitable information sources.
Date Issued:
Authorized By:
MAY 4, 2001
BEN HO, Supervising Deputy
Program Manager
Usting Expires June 30, 2002
C
C
~NOTI Fl ER@
WFIRE SYSTEMS
GENERAL
FCM-1 Control Module -The FCM-1 Addressable
Control Module provides NOTIFIER intelligent control pan-
els a circuit for Notification Appliances (horns, strobes, speak-
ers, etc.) or to monitor a telephone circuit. Addressability
allows the FCM to be activated, either manually or through
panel programming, on a select (zone or area of coverage)
basis.
FRM-1 Relay Module -The FRM-1 Addressable Re-
lay Module provides the system with a dry-contact output for
activating a variety of auxiliary devices, such as fans, damp-
ers, control equipment, etc. Addressability allows the dry
contact to be activated, either manually or through panel
programming, on a select basis.
FlashScan (patent pending) is a new communication pro-
tocol developed by NOTIFIER Engineering that greatly en-
hances the speed of communication between analog intelli-
gent devices. Intelligent devices communicate in a grouped
fashion. lf one of the devices within the group has new infor-
mation, the panel CPU stops the group poll and concentrates
on single points. The net effect is response speed greater
than five times that of other designs.
FEATURES
Built-in type identification automatically identifies these
devices to the control panel.
Internal circuitry and relay powered directly by two-wire SLC
loop. The FCM module requires power (for horns, strobes,
etc.), audio (for speakers), or a telephone riser (for hand-
sets). Internal relay feature available on FlashScan sys-
tems only.
Integral LED "blinks" green each time a communication
is received from the control panel and turns on in steady
red when activated.
LED blink may be deselected globally (affects all de-
vices).
High noise immunity (EMF/RFI).
The FCM may be used to switch 24-volt NAC power, au-
dio (up to 70.7 VRMS) or telephone.
Wide viewing angle of LED.
SEMS screws with clamping plates for wiring ease.
Direct-dial entry of address 01-159 for FlashScan, 01 -
99 on traditional systems.
Speaker, audible/visual, and telephone applications may
be wired for Class B or A (Style Y or Z).
APPLICATIONS
The FCM is used to switch 24 VDC audible/visual power,
high-level audio (speakers), or control telephone devices,
The FRM may be programmed to operate dry contacts for
door holders, Air Handling Unit shutdown, etc., and to re-
set four-wire smoke detector power.
August 9, 2000 DN-6724 • H-230
FCM and FRM Series
Control and Relay Modules
with FlashScan '"
Section: Intelligent/Addressable Devices
® @b9 I California
State Fire
Marshal ""' 7300-0028:202
LISTED CS669 <8> S3705 MARYLAND
MEA State Fire Marshal
Permit #2020 Approved
457-99-E
(} 0 ~ ~ 0
0 9 0
~
578910
8 4 11 1 3 12
2 13 7 101514 2
TEN~\789 3 6 4
3 5 2 4
ONE~ O
LOOP ADDRESS
~ 0 0 ~ 0
FCM-1 Module
(See wiring diagram Fig. 5 for FRM-1)
CONSTRUCTION
The face plate is made of off-white Noryl®.
Controls include two rotary switches for direct-dial entry
of address (01-159).
The FCM is configured for a single Class B (Style Y) or
Class A (Style Z) Notification Appliance Circuit.
The FRM provides two Form-C dry contacts that switch
together,
OPERATION
Each FCM or FRM uses one of 159 possible module ad-
dresses on a SLC loop. II responds to regular polls from
the control panel and reports its type and status, including
the open/normal/short status of its Notification Appliance
Circuit (NAC). The LED blinks with each poll received. On
Flash Scan™ is a trademark of NOTIFIER.
Noryl® is a registered trademark of GE Plastics, a subsidiary of
General Electric Company.
This document is not intended to be used for installation purposes. We try to keep our
product information up-to-date and accurate. We cannot cover all specific applications or
anticipate all requirements. All specifications are subject to change without notice. For
more information, contact NOTIFIER. Phone: (203) 484-7161 FAX: (203) 484-7118 ISO 9001
CERTIFIED @) N OTI Fl ER• One Fire-Lite Place, Northford, Connecticut 06472 INIIM'IIINC I MANDFAmllNI
DN-6724 • 08/09/00 -Page 1 of 4
command, it activates its internal relay. The FCM super-
vises Class B (Style Y) or Class A (Style Z) notification or
control circuits.
Upon code command from the panel, the FCM will discon-
nect the supervision and connect the external power supply
in the proper polarity across the load device. The discon-
nection of the supervision provides a positive indication to
the panel that the control relay actually turned ON. The ex-
ternal power supply is always relay isolated from the com-
munication loop so that a trouble condition on the external
power supply will never interfere with the rest of the system.
Rotary switches set a unique address for each module. The
address may be set before or after mounting. The built-in
TYPE CODE (not settable) will identify the module to the
control panel, so as to differentiate between a module and a
sensor address.
A built-in magnetic test switch is provided to simulate a short
circuit on the NAG to test the FCM-1.
SPECIFICATIONS lor FCM
Normal operating voltage: 15 to 32 VDC.
Maximum current draw: 5.1 mA (LED on).
Average operating current: 390 µA (LED flashing).
External supply voltage {between Terminals T3 and T4):
maximum 80 volts (RMS or DC).
Drain on external supply: 2 mA maximum (using internal
EOL relay).
EOL resistance: 47K ohms.
Temperature range: 32"F to 120"F (0"C to 49"C).
Humidity range: 10% to 93% non-condensing.
Dimensions: 4.5" (114.3 mm) high x 4" (101.6 mm) wide x
1.25" (31.75 mm) deep. Mounts to a 4" (101.6 mm) square
x 2.125" (53.975 mm) deep box.
SPECIFICATIONS lor FRM
Normal operating voltage: 15 to 32 VDC.
Maximum current draw: 5.1 mA (LED on).
Average operating current: 270 µA (LED flashing).
EOL resistance: not used.
Temperature range: 32"F to 120"F (0"C to 49"C).
Humidity range: 10% to 93% non-condensing.
Dimensions: 4.5" (114.3 mm) high x 4" (101.6 mm) wide
x 1.25" (31.75 mm) deep. Mounts to a 4" (101.6 mm) square
x 2.125" (53.975 mm) deep box.
RELAY CONTACT RATINGS
lor both FCM and FRM models
Load Description Application Maximum Current Voltage Rating
Resistive Non-Coded 30VDC 3.0A
Resistive Coded 30VDC 2.0A
Resistive Non-Coded 110 VDC 0.9A
Resistive Non-Coded 125 VAC 0.9A
Inductive (UR= 5 ms) Coded 30VDC 0.5A
Inductive (UR= 2 ms) Coded 30VDC 1.0A
Inductive (PF = 0.35) Non-Coded 125 VAC 0.5A
PRODUCT LINE INFORMATION 6724rate.lbl
FCM-1
FRM-1
Intelligent Addressable Control Module.
Intelligent Addressable Relay Module.
A2143-20 Capacitor, required for Class A (Style Z) op-
eration of speakers.
SMB500 Optional Surface-Mount Backbox.
CB500 Control Module Barrier -required by UL for
separating power-limited and non-power limited
wiring in the same junction box as FCM-1.
1
MOUNTING
DIAGRAMS
Page 2 of 4 -DN-6724 • 08/09/00
Note CB500 Module Barrier,
which creates isolated quadrant.
ISOLATED
QUADRANT
C
C
C
[j;JJ
CAUTION
◄ The Face Plate
.... WIRING DIAGRAMS
"T The following wiring diagrams are provided:
1) FCM-1: Typical notification appliance circuit configuration,
NFPA Style Y.
2) FCM-1: Typical fault-tolerant notification appliance circuit con-
figuration, NFPA Style Z.
3) FCM-1: Typical wiring for speaker supervision and switching,
NFPA Style Y.
4) FCM-1: Typical fault-tolerant wiring for speaker supervision
and switching, NFPA Style Z.
5) FRM-1: Relay module wiring diagram.
OE-ENERGIZE UNIT PRIOR TO SERVICING
T Fig. 1 FCM-1: Typical notification appliance circuit configuration, NFPA Style Y.
Connect modules to listed compatible NOTIFIER control panels only.
All wiring shown is supervised and power limited.
Module polarities are shown in alarm.
47K EOL
Resistor
ELR-47K \ ~-~
---UL listed
EOL Relay
shown
energized
24 VDC coil
A77-716B
TO NEXT control module or EOL Relay.
ONE RELAY REQUIRED for each circuit.
Some control panels have the RELAY BUil T IN
and do not require external wiring.
Refer to the NOTIFIER manual.
24VDC
POWER
SUPPLY
Power Supply:
Isolated, regulated,
power-limited
per NFPA 70.
Listed for fire protection
with battery backup.
T Fig. 2 FCM-1: Typical fault-tolerant notification appliance circuit configuration, NFPA Style Z.
Connect modules to listed compatible NOTIFIER control panels only.
All wiring shown is supeivised and power limited.
Module polarities are shown in alarm.
---UL listed
EOL Relay
shown
energized
24 VDC coil
A77-716B
TO Next
Device
• TO NEXT control module or EOL Relay.
• ONE RELAY REQUIRED for each circuit.
• Some control panels have the RELAY BUILT IN
and do not require external wiring.
Refer to the NOTIFIER manual.
Communication Line 32 VDC max.
T • t d-pair is recommended.
(-) FROM Panel
,f.:X:X:::,(_ ( +) or Previous
Device
24 voe Circuit
I DONOTLOOPwire
on terminals 3 & 4.
Break wire to provide
supervision of connections. (-)
(+) 24VDC
POWER
SUPPLY
Power Supply:
Isolated, regulated,
power-limited
perNFPA 70.
Listed for fire protection
with battery backup.
DN-6724 • 08/09/00 -Page 3 of 4
T Fig. 3 FCM-1: Typical wiring for speaker supervision and switching, NFPA Style Y.
Connect modules to listed compatible
NOTIFIER control panels only.
All wiring shown is supervised.
Wires must be supervised per NFPA.
Module polarities are shown in alarm.
47K EOL
Resistor
ELR-47K
'-,._
TO Next
Device
Speaker Switching Circuit: NFPA STYLE W
Speakers must be listed for fire protection.
Communication Line
TO Next
32 VDC max. Twisted-pair recommended.
( -FROM Panel
n:::><:::><::::::< ( +) or Previous Device
Audio Circuit
I DONOTLOOPwlre
on temiinals 3 & 4.
Break wire to ensure
supetvision of connections.
H AUDIO AMPLIFIER
70.7 VRMS max.
Use only models AA-30,
AA-100, or AA-120.
Amplifier must provide
wiring supervision per NFPA.
SUPERVISION
Refer to the Relay Contact Rating table for maximum load.
Control Module
Last module must return
wires for supervision. 6724wlr3.wmf
T Fig. 4 FCM-1: Typical fault-tolerant wiring for speaker supervision and switching, NFPA Style Z.
Connect modules to listed compatible NOTIFIER control panels only.
All wiring shown is supervised.
Wires must be supervised per NFPA.
Module polarities are shown in alarm.
EOL Resistor is internal at terminals 8 & 9.
Bypass Capacitors: A2143-20, 100 µf,
16 V, non-polarized,< 10 µA leakage.
Speaker Switching Circuit: NFPA STYLE X
Speakers must be listed for fire protection.
Communication Line
TO Next
32 VDC max. Twisted-pair recommended.
(-) FROMPanel
f-::X::X::::,(J([:i+J)_: or Previous r Device
Audio Circuit
I DONOTLOOPwire
on terminals 3 & 4.
Break wire to ensure
supervision of connections.
H
+ AUDIO AMPLIFIER
70.7 VRMS max.
Use only models AA-30,
AA-100, or AA-120.
Amplifier must provide
wiring supervision per NFPA. ~ SUPERVISION
Refer to the Relay Contact Rating table for maximum load.
Control Module
Last module must return
wires for supervision. 6724wlr4.wmf
NOTES regarding AUDIO AMPLIFIER in Figures 3 & 4 above.
1) Audio circuit wiring must be twisted-pair as a minimum. See NOTIFIER installation manual for detailed information.
2) When a 70.7 V audio amplifier is used, terminals 1 and 2 are power-limited, while terminals 3 through 9 are non-power-limited. In this case,
the CBSOO barrier is required. Otherwise, all terminal wiring is power-limited. The CBSOO includes a label indicating which terminals are non-
power-limited. This label MUST BE PLACED adjacent to the nameplate label, which is on the module housing.
~ ~ ~ ' \ ' \ ' \ , ..... TO Next I l l l l l (+) I Device \ I \ ' \ I I ♦------V _____ l,,..I " ,_ ,
RELAY
cJ MODULE <:o --,
'
0 oO
6724wlr5.wmf
Page 4 of 4 -DN-6724 • 08/09/00
~ ~ ~ r, I \ I \ I \
\ I I I I (+)
(-) FROM Panel
or Previous
Device \ \ I \ I \ I
, r-V---~.l.-----V------◄
f--Communication Line I
(" ---) ---32 VDC maximum.
Shielded twisted-pair
is recommended.
◄ Fig. 5
FRM-1: Relay module
wiring diagram.
Connect modules to listed
compatible control panels only.
Module does NOT supervise
controlled circuits.
C.
<...
(_
LISTING No.
CATEGORY:
LISTEE:
DESIGN:
INSTALLATION:
MARKING:
APPROVAL:
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING -BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
7300-0028:202
Misc. Devices/Control Unit Accessories
Page 1 of 1
Notifier, A Pittway Company, One Fire-Lite Place, Northford CT 06472-1653
Contact: Larry Flood (203) 484-1200 Fax (203) 484-7309
Models FMM-1, FMM-101 . FZM-1, FSM-101, FDM-1 * monitor modules and Models
FCM-1, FRM-1 control modules. Refer to listee's data sheet for additional detailed
product description and operational considerations.
In accordance with listee's printed installation instructions, applicable codes & ordinances
and in manner acceptable to the authority having jurisdiction.
Listee's name. product number and UL label.
Listed as control unit accessories for use with listee's separately listed compatible fire alarm
control units.
•Rev. 05-02-01
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test
results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement
or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation
criteria. Refer to listee's data sheet, installation instructions and/or other suitable information sources.
Date Issued:
Authorized By:
JUNE 18, 2001
BEN HO, Supervising Deputy
Program Manager
Listing Expires June 30, 2002