.· CENTRAL BV4 & BV4-FR 2-01
O Model BV4 & BV4-FR
" 5.6 K-factor
0
0
Standard & Quick Response
Standard Coverage
Concealed Pendent Glass Bulb Automatic Sprinkler
Tyco Fire Products ---www.centralsprinkler.com
451 North Cannon Avenue, Lansdale, Pennsylvania 19446 ---USA
Customer Service/Sales: Tel: (215) 362-0700 / Fax: (215) 362-5385
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
General
...... Description
The Central Model BV4, 5.6 K~factor,
standard response & BV4-FR, 5.6
K-faclor, quid<. response -standard
coverage, decorative glass bulb type
spray sprinklers designed for use in light or
ordinary hazard, commercial occupancies
such as banks, hotels, shopping malls,
etc.
Each unit includes a Cover Plate Assem-
bly which conceals the sprinkler operating
components above the ceiling. The
separable two-piece design of the Cover
Plate and Support Cup Assemblies allows
installation of the sprinklers and pressure
tesllng of the fire protection system prior to
installation of a suspended ceiling or
application of the finish coating to a fixed
ceiling. They also permit removal of
suspended ,ceiling panel$ for access to
building service equipment without having
to first shut down the fire protection system
and remove sprinklers.
Also, the separable two-piece design of
the sprinkler provides for 112 inch
(12,7 mm} of vertical adjustment, to
reduce the accuracy to which the length of
fixed pipe drops to the sprinkler must be
cut.
The BV4 & BV4-FR Concealed Pendent
Sprinklers are shipped with a Disposable
Pro1ection Gap. The Protective Gap is
temporarily removed to install the BV4 &
BV4-FR, and then replaced 1D protect the
BV4 & BV4-FR while the oeiHng is being
installed and finished. The~ of the
Protection Gap can be used to mark the
center of the ceiling hole into plaster
board, ceiling tiles, etc. by pushing the
ooiling product against the Protedion Gap.
When the ceiling installation is complete,
the Protection cap Is removed and the
Cover Plate Assembly inslalled.
Opendlon: When exposed 1D heat from a
fire, the Cover Plate, which is soldered 1D
the Retainer Assembly at three points,
falls away to expose the Sprinkler
Assembly. At.1his point the Deflector
supported by 1he Arms drops down 1D its
q)8rational position.
The glass bulb contains a fluid which
expands when exposed 1D heat When the
rated temperalUre is reached, the fkJid
expands sufficiently to shatter the glass
bulb, which then allows the sprinkler to
activate & flow water.
WARNING
The Mods/ BV4 & BV4-FR ConcsaJed
Pendent Sprinklers dssctibed her8ln must
be installed & maintained in compliance
with this~ as well as with the
applicable standards of the National Are
ProtectiOn Associalim, in addition to the
standards of any other authorities having
jurisdiction. Fdn to do so may impair the
integrity of these d9tnces.
The owner is responsible tor maintaining
theirf;re proteclion S)'Ste,11 and devkm in
proper operating oondition. The inslaJling
contractor or sprinlder manufacturer
should be ccntactBd rslative to sny
questions.
~Technical
llllilData
Sprlnlder ldantlflcatlon Number
SIN C3551 -Model BV4
SIN C3531 -Model BV4-FR
Approvals
UL and C-UL Listed. NYC and
FM Approved.
(The approvals apply only to the service
concllions indicated in the Design Criteria
Seclion)
Maximum Wortclng Prauure
175 psi (12, 1 bar)
Pipe Thread Connection
1/2inchNPT
Discharge Coefficient
K "" 5.6 GPM/psi1i2 (80,6 LPMibar112)
CENTRAL
Standard Spray
Concealed
Pendent
Sprinklers
T..,..atunll Ratings
155°1=/68°C Sprinkler-135°F/57°C Plate
200°F/93°C Sprinkler -165°F/74°C Plate
Flntahaa
Sprinkler: Natural Brass
Cover Plate: Chrome or Brass Plated;
*Flat Whie, Bright While, or Custom
Painted
• Standard Flflish Sl.fpp/iBd when m1ile is
specified
Phyalcal CharllG1erlsllc
The Model BV4 & BV4-FR Concealed
Pendert Sprinklers utilize a dezincification
resistant (DZR) bronze frame and a 5 mm
(standard response) or 3 mm but> (quk:k
response). The t\\oi)ieoe button assem--
bly is brass and copper, The sprinkler
frame orifice is sealed with a gasketed
spring plate (Belleville Seal) consisting of a
beryllium nickel disc spring that Is sealed
on both 11s Inside and outside edges with a
Teflon™ gasket The anns and deflector
are bronze, and the support cup Is steel.
The cover plate and relainer assembly are
brass.
No. 1-8.0
0
0
Figure 3 • Cross section Model BV4 & BV4-FR,
Concealed Pendent Sprinkler
GLASS BULB
OPERATING
ELEMENT
GASKETED
SPRING PLATE
(BELLEVILLE SEAL)
.-----+------. DEFLECTOR ~~~::;l ® l ~ J~
COVER PLATE COVER PLATE -ASSEMBLY
installation and.for during application of the finish coating of the
ceiling. It may also be used to locate the center of the
clearance holes by gently pushing the ceiling material up
against the center point of the Protective Cap.
NOTE
As Long as the Protective Cap remains in place, the system is
considered to be ·0ut of Service·
Step 6. After the ceiling has been completed with the 2-1 /2
inch (66,7 mm) diameter clearance hole and in preparation for
installing the Cover Assembly, remove and discard the
Protective Cap, and verify that the Deflector moves up and
down freely. If the Sprinkler has been damaged and the
Deflector does not move up and down freely, replace the
entire Sprinkler Assembly. Do not attempt to modify or repair
a damaged sprinkler.
Step 7. Screw on the Cover Plate/Retainer Assembly until its
flange just comes in contact with the ceiling. Do not continue
to screw on the Cover Plate/Retainer Assembly such that it
lifts a ceiling panel out of its normal position. If the Cover
Plate/Retainer Assembly cannot be engaged sufficiently to
contact the ceiling, the sprinkler fitting must be repositioned.
Figure 4 -BV4 Sprinkler WIW1Ch
(Part #1075)
lffllcare & LJ1 Maintenanm
The Model BV4 & BV4-FR Concealed Pendent Sprinklers
must be maintained and serviced in accordance with the
following instructions.
NOTES
Absence of the Cover Plates which is used to cover a
clearance hole, may delay the lime to operation in a fire
situation.
When properly installed, there Is a nominal 3132 inch (2,4
mm) air gap between the lip of the Cover Plate and the
ceiling. This air gap is necessary tot proper operation of the
sprinkler. If the ceiling is to be repainted atter the installa-
tion of the sprinkler, care must be exercised to ensure that
the new paint does NOT seal off any of the sir gap.
Factory painted Cow,r Plates MUST NOT be repainted.
They should be replaced, if necessary, by factory painted
units.
Do not pull the Cover Plates relatiw, to the Retainer
Assembly. Separation may result.
Before closing a fire protection system main control valve
for maintenance work on the fire protection system it
controls, permission to shut down the affected fire protec•
tion systems must be obtained from the proper authorities.
All personnel who may be affected by this action must be
notified.
Sprinklers which are found to be leaking or exibiting visible
signs of corrosion must be replaced.
Automatic sprinklers must never be shipped or stored
where their temperatures will exceed 100°F/38°C and they
must never be painted, plated, coated or otherwise altered
after leaving the factory. Modified sprinklers must be
replaced. Sprinklers that have been exposed to corrosive
products of combustion, but have not operated, should be
replaced if they cannot be completely cleaned by wiping the
sprinkler with a cloth or by brushing it with a soft bristle
brush.
Care must be exercised to avoid damage • before, during,
and after installation. Sprinklers damaged by dropping,
striking, wrench twist/slippage, or the like, must be re-
placed. Also, replace any sprinkler that has a cracked bulb
or that has lost liquid from its bulb {Ref. Installation Sec-
tion).
If a sprinkler must be removed for some reason, do not
reinstall it or a replacement without reinstalling the Cover
Plate Assembly. If a Cover Plate Assembly becomes
dislodged during service, replace it immediatly.
The owner is responsible for the inspection, testing, and
maintenance of their fire protection system and devices in
compliance with this document, as well as with the appli-
cable standards of the National Fire Protection Association
(e.g., NFPA 25), in addition to the standards of any other
authorities having jurisdiction. The installing contractor or
sprinkler manufacturer should be contacted relative to any
questions.
It is recommended that automatic sprinkler systems be
inspected, tested, and maintained by a qualified Inspection
Service.
0
CENTRAL BV-QR & BVLO-QR 2-01
M .... ~ BY-QR & B -----R
4.2, 5.6 & 8.0 K-factor
Quick Response
Standard Coverage
Upright, Pendent & Rec. Pendent Glass Bulb Automatic Sprinkler
Tyco Fire Products ---www.centralsprinkler.com
451 North Cannon Avenue, Lansdale, Pennsylvania 19446 ---USA
Customer Service/Sales: Tel: (215) 362-0700 / Fax: (215) 362-5385
Technical Services: Tel: (800) 381-9312/ Fax: (800) 791-5500
1J11 General ~ Description
lhe Central Model BV-OR, 4.2 & 5.6
K-factor (7/16" & 1/2" orifice) & Model
BVLO-OR, 8.0 K-factor (17/32" orifice),
Upright, Pendent, and Rec. Pendent
Sprinklers are quick response -s1andard
coverage, decorative glass but, type
spray sprinklers designed for use in light &
ordinary hazrud, commeroial occupancies
such as banks, hotels, shopping malls etc.
The recessed vetSion of the Central Model
BV-OR, intended for use in areas with a
finished ceiling, uses a tNo-f)iece Model
BV Res/QR Recessed Escutcheon
(Vented m Unvented). The Model BV
Res/QR Recessed Escutcheon provides
up to 318 inch (9,5 mm) of total adjustment
from 'the flush pendent position. The
recessed version of the Central Model
BVLO-QR, also intended for use in areas
with a finished ceiling, uses a two-piece
Model ELO Recessed Esc:utcheon. The
Model ELO Recessed Esrutchaon
provides up to 3/4 inch (19, 1 mm) of total
adjustment from the flush pendent
positioo. lhe adjustment provided by
these Recessed Escutcheons redJces the
accuracy to which the fixed pipe drops to
the sprinklers must be cut.
These sprinklers are available with a
polyester coating that may be utilized to
extend 1he life of copper alloy sprinklers
beyond that which would otherwise be
oblained when exposed to corrosive
atmospheres.
Although polyester coated sprinklers have
passed 11e standard corrosion tesls of the
applicable approval agencies, the testing
is not representative of all possible
corrosive atmospheres. Consequently, it is
recommended that 1he end user be
consulted with respect to the suitability of
this corrosion resistant coating for any
given corrosive environment The effeds
of ambient temperature, concentralion of
chemicals, and gas/chemical velocity,
should be considered, as a minimum,
along with the corrosive nature of the
chemical to which the sprinklers will· be
exposed.
Operation: The glass bulb contains a fluid
which expands when exposed to heat.
When the rated temperature is reached,
the fluid expands sufficiently to shatter the
glass bulb, which then allows the sprinkler
to activate & flow water.
WARNING
The Model BV-QR & BVLO-QR Upright,
Pendent & Rec. Pendent Sprinklers
d8scribed herein must be installed and
maintained in compliance with this
document, as well as with the applicable
standards of the National Fire Protedion
Association, in a.ddiJion to the standaJr:Js of
any other authorities having jurisdiction.
FaHum to do so may impair the integrity of
these devices.
The owner is responsib/6 for maintaining
their firs prol8clion system and devic8s in
proper operating condtion. The inslBJling
contractor or sprinkler manufacturer
should be contacted relative to any
queslions.
Figure 1 -Cross Section
Model BVLO-QR,
Upright Sprinkler
BUTTON GASKETED SPRING
ASSEMBLY PLATE
(BELLEVILLE
SEAL)
~
CEI\ITRAL
Standard Spray
Upright, Pendent
& Rec. Pendent
Sprinldms
No.1-7.0
0
0
0
Design
__ criteria
The Model BV-OR & BVLO-QR Upright,
Pendent & Rec. Pendent Sprinklers are
Standard Response, Standan:t Coverage,
Spray Sprinklers Intended for fire
protection systems designed in
aocoRiance with the standard installation
rules recognized by the applicable listing
or Approval agency.
The 42 K-Factor, Model BV-OR
Sprinklers (Ref. Table 1) are UL & ULC
listed and NYC Approved for use in
accordance with CUIT8l1t NFPA standards.
The 5.8 K-Faclor, Model BV-OR
Sprinklers (Ref. Table 1) are UL & ULC
listed and NYC Approved for use in
acoordance with a.irrent NFPA standards,
and FM Approved for use in accordanoe
with the FM Loss Prevention Data Sheets.
The 8.0 K-Factcr, Model BVLO-QR
Sprinklers (Ref. Table 2) are UL & C-UL
listed for use in accordance with rurrent
NFPA standards, and FM ApprOll9d for
use in aoc:ordance with the FM Loss
Prevention Data Sheets.
The Model BV-OR & BVLO-OR
Sprinklers can be used with any metalic
flush or extended esa.dcheon, provided
the maximum ceiling to top of sprinkler
deflectordmension specified in NFPA 13
is maintained. For recessed 3PJ)llcations,
only the Model BV Re&'QR Vented or
Unvented, (for 42 & 5.6 K-factor
sprinkers) and ELO (for 8.0 K-factor
sprinklers) Recessed Escutcheon
Assemblies may be used.
NOTE
lnquiriss conceming the appmprla1Bness
of polyesl.sr costsd sptfnkJers for a given
CXJl70Sllle environmBnt should be
submitfsd to the da'llion of the Technical
Services Department. Polyester coated
splinkJsls ate not suilabl8 for use in opsn
sprfnkJer applicalions.
~ Installation
The Model BV-OR & BVLO-OR Sprinklers
must be Installed in acoordance with the
following insll'uctions:
NOTES
Do not instaN any bub t)Pe sprinldsr if the
bulb is aacksd or there is a Joss of liquid
from the bub. Wllh lhs sprinkJsr held
horizontally, a small air lxbble should be
present The diameter of lhs air blAJbls is
app,mdmatsiy 1116 inch (1,6 mm) for the
135°F/57"C to 3'32 Inch {2,4 mm) for the
250"F/121°C rating.
A leak tig11 1/2 inch NPT sprinkler joint
should be obtained with a to,qlJe of 7 to 14
ftlbs. (9,5 to 19,0 Nm). A mmdmum of
(Continu8d on Page 4)
Figure 3 ~ Model BVLO-QR, Upright, Pendent &
Rec. Pendent Sprinkler
llEVATION VIIIW \ ' I / '
I ,
\
I
2·11'8"
~-,
318" (9,5 mm)
Min.
1-118" C28.6 mm)
2·1/4" (57,2 mm) Min. _j
2-3/4" (89,9 mm} Max.
i--~-3-1/4" (82,6 mmi---.....
\ Max.
FINISHED
CEILING LINE
Table 2 -Laboratory Listings and Approvals, Model BVLO-QR
SPRINKLER FINISH & STYLE
Tem~rature Bulb Natural Chrome Polyester Recessed
Ratlna Color Code Brass Plated Coated
135°F/57"C Orange 1,2,3 1,2,3 1,2,3 1,2,3
155°F/68"C Red 1,2,3 1,2,3 1,2,3 1,2,3
175°F/79°C Vallow 1,2,3 1,2,3 1,2,3 1,2,3
200"F/93"C Green 1,2,3 1,2,3 1,2,3 1,2,3
250°F/121 °C Blue 1,2,3 1,2,3 1,2,3 ·---
1. Listed by Underwriters Laboratories, Inc.
2. Listed by Underwriters Laboratories for use in Canada (C-UL).
3. Approved by Factory Mutual Research Corporation.