NALU: 11,375 SF TI TO EXISTING SPACE TI CONVERTING TWO SUITES (100 AND 200) (E-REVIEW)Description:
Project Title:
Applicant: DK BARNETT CONSTRUCTION INC
2420 GRAND AVE, # STE F-1
VISTA, CA 92081-7808
(760) 599-4393
Contractor: DK BARNETT CONSTRUCTION INC
2420 GRAND AVE, # STE F-1
VISTA, CA 92081-7808
(760) 599-4393
AMOUNTFEE
BUILDING PLAN CHECK $1,442.19
BUILDING PLAN REVIEW – MINOR PROJECTS (LDE)$204.00
BUILDING PLAN REVIEW – MINOR PROJECTS (PLN)$107.00
CERTIFICATE OF OCCUPANCY $21.00 COMM/IND TI – NON-STRUCTURAL $2,289.75
FIRE S Occupancies < 50,000sq. ft. TI $487.00
SB1473 – GREEN BUILDING STATE STANDARDS FEE $27.00
STRONG MOTION – COMMERCIAL (SMIP)$183.58
Total Fees:$4,761.52 Total Payments To Date:$4,761.52 Balance Due:$0.00
Please take NOTICE that approval of your project includes the "Imposition" of fees, dedications, reservations, or other exactions hereafter
collectively referred to as "fees/exaction." You have 90 days from the date this permit was issued to protest imposition of these fees/exactions. If you protest them, you must follow the protest procedures set forth in Government Code Section 66020(a), and file the
protest and any other required information with the City Manager for processing in accordance with Carlsbad Municipal Code Section
3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attack, review, set aside, void, or annul their
imposition.
You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection
fees and capacity changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this
project. NOR DOES IT APPLY to any fees/exactions of which you have previously been given a NOTICE similar to this, or as to which the statute of limitation has previously otherwise expired.
1635 Faraday Avenue, Carlsbad CA 92008-7314 ï 442-339-2719 ï 760-602-8560 f ï www.carlsbadca.gov
Building Division Page 1 of 1
David Barnett
David Barnett
Building Permit Inspection History Finaled
PERMIT INSPECTION HISTORY for (CBC2024-0215)
BLDG-Commercial 07/08/2024Application Date:Permit Type:Owner:
Tenant Improvement 10/08/2024Work Class:Issue Date:Subdivision:CARLSBAD TCT#84-09
12/08/2025Expiration Date:Status:
IVR Number: 57542
Closed - Finaled 2320 FARADAY AVE
CARLSBAD, CA 92008-7242
Address:
Scheduled
Date
Inspection Type Inspection No.Inspection
Status
Primary Inspector Reinspection InspectionActual
Start Date
11/12/2024 11/12/2024 BLDG-31
Underground/Conduit -
Wiring
267428-2024 Passed Tim Kersch Complete
COMMENTS PassedChecklist Item
BLDG-Building Deficiency Yes
NOTES Created By TEXT Created Date
Shawn Huff SUITE 201 John Folks 951-704-8166 11/08/2024
BLDG-84 Rough
Combo(14,24,34,44)
267427-2024 Passed Tim Kersch Complete
COMMENTS PassedChecklist Item
BLDG-Building Deficiency Yes
BLDG-14
Frame-Steel-Bolting-Welding
(Decks)
Yes
BLDG-24 Rough-Topout Yes
BLDG-34 Rough Electrical Yes
BLDG-44
Rough-Ducts-Dampers
Yes
11/14/2024 11/14/2024 BLDG-16 Insulation 267650-2024 Passed Tim Kersch Complete
COMMENTS PassedChecklist Item
BLDG-Building Deficiency Yes
11/18/2024 11/18/2024 BLDG-17 Interior
Lath/Drywall
268243-2024 Passed Tim Kersch Complete
COMMENTS PassedChecklist Item
BLDG-Building Deficiency Yes
06/09/2025 06/09/2025 BLDG-85 T-Bar, Ceiling
Grids, Overhead
287190-2025 Passed Tim Kersch Complete
COMMENTS PassedChecklist Item
BLDG-Building Deficiency Yes
BLDG-14
Frame-Steel-Bolting-Welding
(Decks)
Yes
BLDG-24 Rough-Topout Yes
BLDG-34 Rough Electrical Yes
BLDG-44
Rough-Ducts-Dampers
Yes
Wednesday, July 30, 2025 Page 1 of 2
PERMIT INSPECTION HISTORY for (CBC2024-0215)
BLDG-Commercial 07/08/2024Application Date:Permit Type:Owner:
Tenant Improvement 10/08/2024Work Class:Issue Date:Subdivision:CARLSBAD TCT#84-09
12/08/2025Expiration Date:Status:
IVR Number: 57542
Closed - Finaled 2320 FARADAY AVE
CARLSBAD, CA 92008-7242
Address:
Scheduled
Date
Inspection Type Inspection No.Inspection
Status
Primary Inspector Reinspection InspectionActual
Start Date
06/30/2025 06/30/2025 BLDG-Final Inspection 289094-2025 Passed Tim Kersch Complete
COMMENTS PassedChecklist Item
BLDG-Building Deficiency Yes
BLDG-Plumbing Final Yes
BLDG-Mechanical Final Yes
BLDG-Structural Final Yes
BLDG-Electrical Final Yes
Wednesday, July 30, 2025 Page 2 of 2
True North Compliance Services, Inc.
8369 Vickers Street, Suite 207, San Diego, CA 92111
T | 562.733.8030
Transmittal Letter
July 22, 2024
City of Carlsbad FIRST REVIEW
Community Development Department - Building Division City Permit No: CBC2024-0215
1635 Faraday Ave. True North No.: 24-018-601
Carlsbad, CA 92008
Plan Review: TI Nalu
Address: 2320 Faraday Ave, Carlsbad CA
Applicant Name: Barnett Construction Applicant Email: davidm@barnettconstruction.net
True North Compliance Services, Inc. has completed the review of the following documents for the project
referenced above on behalf of the City of Carlsbad. Our comments can be found on the attached list.
1. Drawings: Electronic copy dated April 15, 2024, by Barnett Construction.
Attn: Permit Technician, the scope of work on the plans has been reviewed for coordination with the scope of
work on the permit application. See below for information if the scope of work on plans differs from the permit
application:
Valuation: See Notes Below
Scope of Work: Confirmed
Floor Area: Confirmed
Notes: Valuation was not provided in the permit application.
Our comments follow on the attached list. Please call if you have any questions or if we can be of further
assistance.
Sincerely,
True North Compliance Services
Review By: Jasmine Safaqa - Plan Review Engineer
QA/QC Review By: Areli Sanchez - Plan Review Supervisor
TI Nalu City of Carlsbad– FIRST REVIEW
2320 Faraday Ave City Permit No.: CBC2024-0215
July 22, 2024 True North No.: 24-018-601
Page 2
Plan Review Comments
ELECTRONIC - RESUBMITTAL INSTRUCTIONS:
Please do not resubmit plans until all departments have completed their reviews. For status, please
contact building@carlsbadca.gov
Please make all corrections, as requested in the correction list. Corrected sets can be submitted as follows:
Email the revised plans and comment response letter(s) to building@carlsbadca.gov for continued
review.
Note: If this project requires FIRE PREVENTION review, ensure that you follow their specific
instructions for resubmittal review. The city will not route plans back to Dennis Grubb &
Associates for continued Fire Prevention review.
GENERAL INFORMATION:
A. The following comments are referred to the 2022 California Building, Mechanical, Plumbing, Electrical
Codes, California Green Building Standards Code, and Energy Code (i.e., 2021 IBC, UMC, UPC, and 2020
NEC, as amended by the State of California).
B. There may be other comments generated by the Building Division and/or other City departments that will
also require your attention and response. This attached list of comments, then, is only a portion of the plan
review. Contact the City for other items.
C. Respond in writing to each comment by marking the attached comment list or creating a response letter.
Indicate which details, specification, or calculation shows the required information. Your complete and
clear responses will expedite the re-check.
D. Where applicable, be sure to include the architect and engineer’s stamp and signature on all sheets of the
drawings and on the coversheets of specifications and calculations per CBPC 5536.1 and CBPC 6735. This
item will be verified prior to plan approval.
E. If you have any questions regarding the comments below, please contact Jasmine Saffaqa via email
jasmines@tncservices.com or telephone (562) 733-8030.
OCCUPANCY & BUILDING SUMMARY:
Occupancy Groups: B, S-1
Occupant Load: Provide this info
Type of Construction: V-B
Sprinklers: Yes
Stories: 1
Area of Work (sq. ft.): 11,375 sq. ft.
ARCHITECTURAL COMMENTS:
A1. Roof mounted equipment must be screened and roof penetration should be minimized. City Policy 80-6
A2. Per city policy, specify the roofing material to have a Class A fire classification.
TI Nalu City of Carlsbad– FIRST REVIEW
2320 Faraday Ave City Permit No.: CBC2024-0215
July 22, 2024 True North No.: 24-018-601
Page 3
A3. Sheet A1.2:
a) Please provide occupant load calculation breakdown for the area of work, not only the new rooms.
Additional comments may be generated.
b) Please revise the occupant load factor of the Break Room and the Bristo area to be 15 instead of 50
per CBC Table 1004.5.
c) Wherever the maximum occupant load exceeds 50 occupants please provide a sign that is posted
with the occupant load of the room/space at conspicuous place, near the main exit or exit access
doorway from the room/space per CBC 1004.9.
d) Regarding the means of egress system for this project, provide a Code Analysis on the plans
which includes the following information:
i) Where a room, area, or building requires two exits per CBC 1006, Please revise the
training room show the distance between the exits and the overall diagonal distance of the
room, area, or building to ensure that the two exits are separated by more than one-third
the diagonal CBC 1007.1.1.
ii) Identify the Common Path of Egress Travel (CPET) at the “worst case scenario”. Show
the paths graphically and label each with the associated length/distance of the CPET.
Paths must begin from the most remote point within the story, and end where two
separate and distinct paths to two exits are available. Ensure that no CPET exceeds the
limits set forth in CBC 1006.2.1.
iii) Identify the Exit Access Travel Distance at each story at the “worst case scenario” per
CBC 1017.3 Paths must begin from the most remote point within the story, and end at the
exit (exit door, exit stair, exit passageway, etc.). Ensure that no Exit Access Travel
Distance exceeds the limits set forth in CBC Table 1017.2.
iv) Identify all exits on the plans, including exit doors and exit access doors, and show the
number of occupants using each exit door.
A4. Provide information for the floor finishes.
a) Specify floor finishes for walking surfaces to be stable, firm, slip-resistant surface and be securely
attached per CBC 1003.4 and 11B-302.1.
b) Specify transitions between various floor finishes that results in elevation change shall comply with
CBC 11B-303. Details showing the change in level should be included in the plan. See CBC Figure
11B-303.2 and 11B-303.3.
TI Nalu City of Carlsbad– FIRST REVIEW
2320 Faraday Ave City Permit No.: CBC2024-0215
July 22, 2024 True North No.: 24-018-601
Page 4
ACCESSIBILITY COMMENTS:
D1. CBC 11B-202.3 requires that accessibility be provided to the altered spaces. This accessibility shall
include the requirements of CBC 11B-202.4, which entails: a primary entrance, a primary path of travel,
sanitary facilities serving the area, a drinking fountain, and signs. Please address the following:
a) Sheet C1.0:
i) Please address the following regarding the accessible path of travel:
(1) specify the accessible route to be 5% maximum running slope with 2% maximum
cross slope per CBC 11B-402.2.
(2) Specify the accessible route to be at least 48” in width. CBC 11B-403.5.1
ii) Revise the cross-referenced detail at the parking stall to reference Detail 7 in Sheet AD-
2.0 instead of SD-2.0.
b) Regarding the proposed restrooms, please address the following:
i) Please cross reference the restroom details provided in Sheet AD1.0 on Sheet A1.1.
ii) For the proposed urinal, please provide the following information per CBC 11B-605:
(1) Urinals shall be the stall-type or wall-hung type with the rim at 17 inches maximum
above the finish floor or ground. CBC 11B-605.2
(2) Urinal shall be 13.5-inches deep minimum, measured from the outer face of the
urinal rim to the back of the fixture. CBC 11B-605.2
(3) The door encroaches the clear floor space in front of the urinal. A clear space of
30 inches wide and 48 inches depth shall be provided for forward approach. CBC
11B-605.3 and -305. Please revise.
(4) Accessible urinal within an alcove that is more than 24 inches deep shall be
provided with a clear width of 36 inches minimum per CBC 11B-605.3 and 11B-
305.7.1. Revise to show compliance.
(5) Specify hand operated or automatic flush controls for urinals per CBC 11B-604.6.
For hand operated flush controls, the following comments apply:
TI Nalu City of Carlsbad– FIRST REVIEW
2320 Faraday Ave City Permit No.: CBC2024-0215
July 22, 2024 True North No.: 24-018-601
Page 5
(a) Specify the control to be located a maximum of 44 inches above the floor.
CBC 11B-604.6.
(b) Specify the control to be operable with one hand and shall not require tight
grasping, pinching, or twisting of the hand. CBC 11B-309.4.
(c) Specify the control to be mounted on the wide side of the water closet area.
CBC 11B-604.6.
(d) Specify activation of the control to require a maximum force of 5 pounds.
CBC 11B-309.4.
iii) Sheet AD1.0: Revise the grab bar dimension to be to the top of the gripping bar instead of
the center line. CBC 11B-609.4.
iv) Address the following comments for the shower compartments:
(1) Dimension clear floor space in front of the shower.
(2) Specify doors and panels of shower and bathtub enclosures shall be fully tempered,
laminated safety glass, or approved plastic. CBC 2406.8.
(3) Specify shower enclosures to be such that it shall not obstruct controls, faucets,
and shower spray units or obstruct the transfer from wheelchairs onto the shower
seats per CBC 11B-608.8.
(4) Specify the threshold of the roll-in type shower to be ½ inch maximum per CBC
11B-608.7.
(5) Specify the shower has a seat mounted and located per one of section in CBC
11B-610.3.
(6) Specify the floor or ground surface of the showers to comply with the following
per CBC 11B-608.9:
(a) Floor and ground surface shall be stable, firm, and slip resistant per CBC
11B-302.1
(b) Floor and ground surface shall be sloped 1:48 maximum in any direction.
(c) Where the drains are provided, the grate openings shall be 1/4" maximum
and flush with the floor surface.
D2. Sheet A1.1:
a) Please specify a strike width of 18” minimum for the pull side of the door at each of the following
locations per CBC 11B-404.2.4.1.
i) For the door of the (LAB 2) room.
TI Nalu City of Carlsbad– FIRST REVIEW
2320 Faraday Ave City Permit No.: CBC2024-0215
July 22, 2024 True North No.: 24-018-601
Page 6
ii) For the door between the break area and the restrooms.
b) For all dining tables, please provide a tabulation of each type of dining surface. 5% of seats of the
seating and standing spaces at the dining surfaces shall comply with CBC 11B-902. CBC 11B-
226.1.
i) Accessible dining surfaces shall be dispersed throughout the dining area. CBC 11B-226.2
ii) Provide clear floor space of 30” by 48” minimum positioned for forward approach in
accordance with CBC 11B-305. See CBC Figure 11B-305.3 for illustration.
iii) Specify tops of the dining surfaces to be 28” to 34” above the finish floor or ground. CBC
11B-902.3.
iv) Provide toe and knee clearance under the accessible dining surface in accordance with CBC
11B-306 and 11B-902.4.1. See CBC Figure 11B-306.3 for illustration.
D3. Provide information for the existing and proposed doors that are within the area of work.
a) Door hardware is operable with one hand and do not require tight grasping, pinching, or twisting
of the hand. CBC 11B-404.2.7 and 11B-309.4.
b) Specify door thresholds, if provided at doorways, to be ½ inch high maximum. Raised thresholds
and changes in level at doorways shall comply with CBC Section 11B-302 and 11B-303. CBC
11B-404.2.5.
c) Door opening force is 5-pounds maximum for interior and exterior doors per CBC 11B-404.2.9.
d) Door opening hardware is mounted 34” to 44” above the finish floor per CBC 11B-404.2.7.
e) The lower 10 inch of the door surface is provided with a smooth surface for the full width of the
door, at the push side of the door per CBC 11B-404.2.10.
D4. Multiple sinks are provided in the proposed area. at least 5 percent, but no fewer than one, of each type
provided in each accessible room or space shall be in compliance with CBC 11B-606 per CBC 11B-
212.3. Ensure to include the following and revise details 3 and 7/Sheet Q9.1 accordingly.
a) Provide clear floor space for the provided sink per CBC 11B-606.2. Ensure to provide knee and toe
clearances in compliance with 11B-306.
b) Specify the height of the sink to be 34” maximum above finish floor per CBC 11B-606.3.
MECHANICAL COMMENTS:
No comments.
TI Nalu City of Carlsbad– FIRST REVIEW
2320 Faraday Ave City Permit No.: CBC2024-0215
July 22, 2024 True North No.: 24-018-601
Page 7
ELECTRICAL COMMENTS:
No comments.
PLUMBING COMMENTS:
P1. Provide the following note for the use of recycled water for irrigation: The City of Carlsbad requires the
installation of a “bypass tee and associated ball valves” be installed above grade on the main water supply
line before it enters the building. Please include the location and specifications for this fitting on the
plumbing plans. (The City Engineer has a detail available, Standard drawing W35).
P2. Revise plans to show all sinks and floor drains in the kitchen (Break and Dining rooms) to drain the grease
interceptor.
P3. Ice machines, iceboxes, drink dispensers, coffee machines, freezers, refrigeration coils, and similar
equipment, if any, shall be indirectly connected to the drainage system. CPC Sec. 801.3.
P4. Food waste disposal unit or dishwasher shall not be connected to or discharge into any grease
interceptor. Commercial food waste disposers shall be permitted to discharge directly into the building’s
drainage system. (CPC Sec. 1014.1.3)
GREEN BUILDING COMMENTS:
G1. Climate Action Plan requirements apply to all new structures, residential additions/remodels equal to or
exceeding $60,000 in valuation, and commercial City of Carlsbad requires that all projects that qualify for
CAP compliance will require a completed Climate Action Plan (CAP) Consistency Checklists (city forms
B-50) to be completed by the APPLICANT.
https://www.carlsbadca.gov/home/showpublisheddocument/6878/638225157825900000
a) For plans submitted to the City the following Climate Action Plan requirements apply, per Carlsbad
ordinance:
b) The applicant is to fill out the B-50 CAP Consistency Checklist. The scope of work and project
valuation will determine which sections of the CAP are required.
c) Plan examiners review the B-50 CAP Consistency Checklist for completion. For example: If new
residential construction is the scope of work, CAP sections 2A, 3A, and 4A are required to be filled
on the B-50 checklist.
ENERGY COMPLIANCE COMMENTS:
No comments.
STRUCTURAL COMMENTS:
No comments.
If you have any questions regarding the above comments, please contact Jasmine Saffaqa via email
jasmines@tncservices.com or telephone (562) 733-8030.
[END]
True North Compliance Services, Inc.
8369 Vickers Street, Suite 207, San Diego, CA 92111
T | 562.733.8030
Transmittal Letter
August 18, 2024
City of Carlsbad SECOND REVIEW
Community Development Department - Building Division City Permit No: CBC2024-0215
1635 Faraday Ave. True North No.: 24-018-601
Carlsbad, CA 92008
Plan Review: TI Nalu
Address: 2320 Faraday Ave, Carlsbad CA
Applicant Name: Barnett Construction Applicant Email: davidm@barnettconstruction.net
True North Compliance Services, Inc. has completed the review of the following documents for the project
referenced above on behalf of the City of Carlsbad. Our comments can be found on the attached list.
1. Drawings: Electronic copy dated April 15, 2024, by Barnett Construction.
Attn: Permit Technician, the scope of work on the plans has been reviewed for coordination with the scope of
work on the permit application. See below for information if the scope of work on plans differs from the permit
application:
Valuation: See Notes Below
Scope of Work: Confirmed
Floor Area: Confirmed
Notes: Valuation was not provided in the permit application.
Our comments follow on the attached list. Please call if you have any questions or if we can be of further
assistance.
Sincerely,
True North Compliance Services
Review By: Jasmine Safaqa - Plan Review Engineer
QA/QC Review By: Areli Sanchez - Plan Review Supervisor
TI Nalu City of Carlsbad– SECOND REVIEW
2320 Faraday Ave City Permit No.: CBC2024-0215
August 18, 2024 True North No.: 24-018-601
Page 2
Plan Review Comments
ELECTRONIC - RESUBMITTAL INSTRUCTIONS:
Please do not resubmit plans until all departments have completed their reviews. For status, please
contact building@carlsbadca.gov
Please make all corrections, as requested in the correction list. Corrected sets can be submitted as follows:
Email the revised plans and comment response letter(s) to building@carlsbadca.gov for continued
review.
Note: If this project requires FIRE PREVENTION review, ensure that you follow their specific
instructions for resubmittal review. The city will not route plans back to Dennis Grubb &
Associates for continued Fire Prevention review.
GENERAL INFORMATION:
A. The following comments are referred to the 2022 California Building, Mechanical, Plumbing, Electrical
Codes, California Green Building Standards Code, and Energy Code (i.e., 2021 IBC, UMC, UPC, and 2020
NEC, as amended by the State of California).
B. There may be other comments generated by the Building Division and/or other City departments that will
also require your attention and response. This attached list of comments, then, is only a portion of the plan
review. Contact the City for other items.
C. Respond in writing to each comment by marking the attached comment list or creating a response letter.
Indicate which details, specification, or calculation shows the required information. Your complete and
clear responses will expedite the re-check.
D. Where applicable, be sure to include the architect and engineer’s stamp and signature on all sheets of the
drawings and on the coversheets of specifications and calculations per CBPC 5536.1 and CBPC 6735. This
item will be verified prior to plan approval.
E. If you have any questions regarding the comments below, please contact Jasmine Saffaqa via email
jasmines@tncservices.com or telephone (562) 733-8030.
OCCUPANCY & BUILDING SUMMARY:
Occupancy Groups: B, S-1
Occupant Load: Provide this info
Type of Construction: V-B
Sprinklers: Yes
Stories: 1
Area of Work (sq. ft.): 11,375 sq. ft.
ARCHITECTURAL COMMENTS:
A3. Sheet A1.2:
d) Regarding the means of egress system for this project, provide a Code Analysis on the plans
which includes the following information:
TI Nalu City of Carlsbad– SECOND REVIEW
2320 Faraday Ave City Permit No.: CBC2024-0215
August 18, 2024 True North No.: 24-018-601
Page 3
ii) Identify the Common Path of Egress Travel (CPET) at the “worst case scenario”. Show
the paths graphically and label each with the associated length/distance of the CPET.
Paths must begin from the most remote point within the story, and end where two
separate and distinct paths to two exits are available. Ensure that no CPET exceeds the
limits set forth in CBC 1006.2.1.
PC2: Please show each CPET from the Most Remote Point each area or space. Plans
appear to only show the distances traveled after reaching the CPET (therefore
capturing the exit access travel distance only).
ACCESSIBILITY COMMENTS:
No comments.
MEP COMMENTS:
No comments.
GREEN BUILDING COMMENTS:
G1. Climate Action Plan requirements apply to all new structures, residential additions/remodels equal to or
exceeding $60,000 in valuation, and commercial City of Carlsbad requires that all projects that qualify for
CAP compliance will require a completed Climate Action Plan (CAP) Consistency Checklists (city forms
B-50) to be completed by the APPLICANT.
https://www.carlsbadca.gov/home/showpublisheddocument/6878/638225157825900000
a) For plans submitted to the City the following Climate Action Plan requirements apply, per Carlsbad
ordinance:
b) The applicant is to fill out the B-50 CAP Consistency Checklist. The scope of work and project
valuation will determine which sections of the CAP are required.
c) Plan examiners review the B-50 CAP Consistency Checklist for completion. For example: If new
residential construction is the scope of work, CAP sections 2A, 3A, and 4A are required to be filled
on the B-50 checklist.
PC2: This comment will remain outstanding until the required form is provided.
ENERGY COMPLIANCE COMMENTS:
No comments.
STRUCTURAL COMMENTS:
No comments.
If you have any questions regarding the above comments, please contact Jasmine Saffaqa via email
jasmines@tncservices.com or telephone (562) 733-8030.
[END]
Hazardous Materials Questionnaire
County of San Diego, Department of Environmental Health and Quality
PO Box 129261, San Diego, CA 92112-9261
(858) 505-6700 (800) 253-9933 www.sdcdehq.org
Record ID #: Not in System
Plan Check #: DEH2024-HHMBP-014730
Business Name Business Contact Telephone #Plan File #
Nalu Medical Chelsea Gutierrez (714) 401-0608
Project Address City State Zip Code APN #
2320 Faraday AVE 100 Carlsbad CA 92008 -
Applicant Applicant E-Mail Applicant Telephone #
Chelsea Gutierrez chelsea@nalumed.com (714) 401-0608
The following questions represent the facility's activities, NOT the specific project description.
PART I; FIRE DEPARTMENT - HAZARDOUS METERIALS DIVISION: OCCUPANCY CLASSIFICATION: (Not required for projects within the City of San Diego.)
Indicate by selecting the item, whether your business will use, process, or store any of the following hazardous materials. If any of the items are selected, Applicant must
contact the Fire Protection Agency with jurisdiction prior to plan submittal.
Occupancy Rating: Facility's Square Footage (including proposed project): 13000
o Explosive or Blasting Agents o Organic Peroxides o Water Reactives o Corrosives
o Compressed Gases o Oxidizers o Cryogenics o Other Health Hazards
o Flammable/Combustible Liquids o Pyrophorics o Highly Toxic or Toxic Materials o None of These
o Flammable Solids o Unstable Reactives o Radioactives
PART II; SAN DIEGO COUNTY DEPARTMENT OF ENVIRONMENTAL HEALTH - HAZARDOUS MATERIALS DIVISION (HMD): If the answer to any of the questions is
yes, applicant must contact the County of San Diego Hazardous Materials Division, in person at 5500 Overland Ave., Suite 110, San Diego, CA 92123, or by phone at (858)
505-6700 prior to issuance of a building permit. FEES ARE REQUIRED.
Project Completion Date: 11/1/2024
YES NO
1.o ý Is your business listed on the reverse side of this form? (check all that apply).o CalARP Exempt
2.ý o Will your business dispose of Hazardous Substances or Medical Waste in any amount?o CalARP Required
3.o ý Will your business store or handle Hazardous Substances in quantities equal to or greater than
55 gallons, 500 pounds, or 200 cubic feet?
o CalARP Complete
4.o o Will your business handle carcinogens or reproductive toxins in any quantity?Review Date:
5.o ý Will your business use an existing, or install an underground storage tank?
6.o ý Will your business store or handle Regulated Substances (CalARP)?
7.o ý Will your business use or install a Hazardous Waste Tank System (Title 22, Article 10)?
8.o ý Will your business store petroleum in tanks or containers at your facility with a total storage capacity
equal to or greater than 1,320 gallons? (California's Aboveground Petroleum Storage Act).
PART III; SAN DIEGO COUNTY AIR POLLUTION CONTROL DISTRICT (APCD): If the answer to Question #1 is 'Yes' and the answer to Question #2 is 'No', the applicant
must contact the APCD prior to the issuance of a building or demolition permit. If any answer to Questions #3, #4, or #5 is 'Yes', the applicant must contact the APCD prior to
the issuance of a building or demolition permit. If the answer to Question #3 or #4 is 'Yes', the applicant may need to submit an asbestos notification form to the APCD at
least 10 working days prior to commencing demolition or renovation (some residential projects may be exempt from the notification requirements). Contact the APCD at
10124 Old Grove Road, San Diego, CA 92131 or telephone (858) 586-2600 for more information.
YES NO
1.ý o Will any existing building materials be disturbed as part of this project? (If the answer is 'Yes', an asbestos survey may be required.)
2.ý o Has a survey been performed to determine the presence of asbestos containing materials?
3.o ý Will the project involve handling or disturbance of any asbestos containing materials?
4.o ý Will the project involve the removal of any load supporting structural member?
5.o ý Will the subject facility or construction activities include operations or equipment that emit or are capable of emitting an air contaminant? (See the APCD
factsheet at http://www.sdapcd.org/info/facts/permits.pdf
6.o o (ANSWER ONLY IF QUESTION 5 IS 'YES') Will the subject facility be located within 1,000 feet of the outer boundary of a school (K through 12)? Search
the California School Directory at http://www.cde.ca.gov/re/sd/ for public and private schools or contact the appropriate school district.
Briefly describe business activities:Briefly describe proposed project:
Medical Device Operations Additional Office Space and Training Facilities
I declare under penalty of perjury that to the best of my knowledge and belief, the responses made herein are true and correct. ý; Fees Acknowledged: ý
Chelsea Gutierrez 9/24/2024
Name of Owner or Authorized Agent Date
FOR OFFICIAL USE ONLY
FIRE DEPARTMENT OCCUPANCY CLASSIFICATION:
BY:DATE:
EXEMPT OR NO FURTHER INFORMATION
REQUIRED
RELEASED FOR BUILDING PERMIT BUT NOT FOR
OCCUPANCY
RELEASED FOR OCCUPANCY