07-09-2014 Cogeneration Permit Permit No:CB141388
Building Inspection Request Line (760) 602-2725
Job Address:
Permit Type:
Parcel No:
Valuation
Occupancy Group:
1000 WHIMBREL CT CBAD
COGEN Sub Type: PHOTO
Lot #: 0
Constuction Type: NEW
Reference #:
2157201900
$15,200.00
Status: PENDING
Applied : 06/18/201 4
Entered By: LSM
Plan Approved:
Issued:
Inspect Area:
Plan Check #:
Project Title: MAICHEN RES-INSTALL ROOF MNT
PV SYSTEM 38 MODULES PANEL UPGRADE
Applicant:
JOHN LAVENDER
STE 218
9520 PADGETT ST
SAN DIEGO CA 92126
858-405-1514
Building Permit
Add'I Building Permit Fee
Plan Check
Add'I Plan Check Fee
Plan Check Discount
Strong Motion Fee
Green Bldg Stands (SB1473) Fee
Owner:
MAICHEN FAMILY TRUST 07-13-99
1000 WHIMBREL CT
CARLSBAD CA 92011
$185.67 PLUMBING TOTAL
$0.00 ELECTRICAL TOTAL
$129.97 MECHANICAL TOTAL
$20.03 Additional Fees
$0.00
$1.52
$1.00
TOTAL PERMIT FEES
Total Fees: $338.19 Total Payments To Date: $150.00 Balance Due:
FINAL A
Inspector: Date: -~--<----1--1--Clearance:
$0.00
$0.00
$0.00
$0.00
$338.19
$188.19
NOTICE: Please take NOTICE that approval of your project includes the "Imposition' of fees, dedications, reservations, or other exactions hereafter collectively
referred to as "fees/exactions.' You have 90 days from the date this penmit was issued to protest imposition of these fees/exactions. If you protest them, you must
follow the protest procedures set forth in Government Code Section 66020(a), and file the protest and any other required information with the City Manager for
processing in accordance with Carlsbad Municipal Code Section 3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attack,
review, set aside, void, or annul their imposition.
You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection fees and capacity
changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this project. NOR DOES IT APPLY to any
f fwhi I T h •
THE FOLLOWIN<,; APPRO\{ALS REQUIRED PRIOR TO PERMIT ISSUANCE: □PLANNING □ENGINEERING □BUILDING □FIRE □HEALTH O HAZMATIAPCD
«1 ~ C I T Y OF
CARLSBAD
Building Permit Application
1635 Faraday Ave., Carlsbad, CA 92008
Ph: 760-602-2719 Fax: 760-602-8558
email: building@carlsbadca.gov
www.carlsbadca.gov
SUITEt/SPACEt/UNIT#
-"' 'f l0/1
Plan Check No. Cfo f
Est. Value
Plan Ck. Deposit
Date &, L 1s ' SWPPP
APN
'21 ~ -7ZD -l 1
# BATHROOMS TENANT BUSINESS NAME CONSTR. TYPE
DESCRIPTION OF WORK: Include Square Feet of Affected Area(s)
1-vt!Sfe;. VlJi'11"-of c.._ '°"~ Mo~J II.~ ,!cV phe+o
w-J~ 01. ser v,'ce-tAfjr~Je-
-0 C)
CC. ROUP
EXISTING USE GARAGE (SF) AIR CONDITIONING
YES□No□
FIRE SPRINKLERS
YES0 NO□
APPLICANT NAME
Z..{ (
ZIP CITY STATE ZIP Cf t2-G
FAX
CONTRACTOR BUS. NAME
ADDRESS ADD
CITY STATE ZIP
PHONE FAX
EMAIL
STATE LIC. # CLASS Q ()
(Sec. 7031.5 Business and Professions Code: Any City or County which requires a permit to construct. alter. improve. demolish or repair anx structure, prior to Its issuance. also requires the applicant for such permit to file a signed statement that he is licensed pursuant to the provisions of the Contractor's License Law !Chapter 9. commending with Section 7000 of Division 3 of the Business and Professions Code) or Chat he Is exempt therefrom. and the basis for the alleged exemption. Any violation of Section 7031.5 by any applicant for a permit subjects the applicant to a
civil penalty of not more than five hundred dollars ($500)).
Workers' Compensation Declaration: I hereby affirm under penalty of perjury one of the following declara6ons:
0 I have and will maintain a certificate of consent to self-insure for workers' compensation as provided by Section 3700 of the Labor Code, for the performance of the work for which lhis permit is Issued.
IJJ1 have and will maintain workers' c mpensatlon, as rwuired by ection 3700 of the Labor Code, for the 'rformance of the work for which this permit is issued. My workers' compensation insurance carrier and policy
number are: Insurance Co. wt r. f-'roi,cy No. 1 0 s--, 'f {. '>-Expiralion Date O r/t 3/U J 5
~ section need not be completed if the permit Is for one hundred dollars ($100) or less. LJ Certificate of Exemption: I certify that in the performance of the work for which this permit is issued, I shall not employ any person in any manner so as lo become subject to the Workers' Compensation Laws of
California. WARNING: Failure to secure worke~• compensation coverage Is unlawful, and shall subject an employer to criminal penalties and civil fines up to one hundred thousand dollars {&100,000), In
addition to the cost of compensation, damages as provided for in n 3706 ofthe L r code, Interest and attorney's fees.
RS CONTRACTOR SIGNATURE llfl(GENT I I-{
I hereby affirm that I am exempt from Contractor's Ucense Law for the /of/owing reason:
□
□
□
I, as owner of the property or my employees with wages as their sole compensation, will do the work and the structure is not Intended or offered for sale (Sec. 7044, Business and Professions Code: The Contracto(s
License Law does not apply to an owner of property who builds or improves thereon, and who does such work himself or through his own employees, provided that such improvements are nol intended or offered for
sale. If, however, the building or improvement Is sold within one year of completion, lhe owner-builder will have the burden of proving that he did not build or improve for the purpose of sale).
I, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec. 7044, Business and Professions Code: The Contracto(s License Law does not apply to an owner of
property who builds or improves thereon, and contracts for such projects with contractor(s) licensed pursuant to the Contractor's License Law).
I am exempt under Section _____ Business and Professions Code for this reason:
1. I personally plan to provide the major labor and materials for construclion of the proposed property improvement O Yes 0 No
2. I (have/ have not) signed an application for a building penmil for the proposed work.
3. I have contracted with the following person (firm) to provide the proposed construction (include name address I phone I contractors' license number):
4. I plan 10 provide portions of the work. bul I have hired the following person lo coordinate, supervise and provide the major work (include name/ address/ phone I contraclors' license number):
5. I will provide some of the work, but I have contracted (hired) the following persons to provide lhe work indicated (include name/ address I phone/ type of work):
RS PROPERTY OWNER SIGNATURE □AGENT DATE
Is the applicant or future building occupant required to submit a business plan, acutely hazardous materials registration form or risk management and prevention program under Sections 25505, 25533 or 25534 of the
Presley-Tanner Hazardous Substance Account Act? Yes No
Is the applicant or future building occupant required to obtain a permit from the air pollution control district or air Quality management district? Yes No
Is the facility to be constructed within 1,000 feet of the outer boundary of a school site? Yes No
IF ANY OF THE ANSWERS ARE YES, A FINAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUED UNLESS THE APPLICANT HAS MET OR IS MEETING THE REQUIREMENTS OF THE OFFICE OF
EMERGENCY SERVICES AND THE AIR POLLUTION CONTROL DISTRICT.
of the work this permit is issued {Sec. 3097 {i) Civil Code).
Lender's Address
I certify that I have read the application and state that the above lnfonmation Is comictand that the infonmation on the plans is accurate. I agree to comptywith all City ordinances and State la~ relating to building construction.
I hereby authorize representative of the City of Carlsbad to enter upon the above mentioned property l:>r inspection purposes. I ALSO AGREE TO SAVE, INDEMNIFY AND KEEP HARMLESS Tl-IE CllY OF CARLSBAD
AGAINST ALL LIABILITIES, JUDGMENTS, COSTS AND EXPENSES WHICH MAY IN ANY WAY ACCRUE AGAINST SAID CllY IN CONSEQUENCE OF THE GRANTING OF THIS PERMIT.
OSHA An OSHA penmrt is required for excavations over 5'0' deep and demoliton or construction of structures over 3 stories fl height.
EXPIRATION: Every pe1111it issued by the Building Official under the provisons of this Code shall expire by limitaton and become null and void ~ the building or IMlrk authorized by such penmit is not comll'enced within
180 days from the date of such penmit or if the building or IMlrk authorized b penmlt is suspended or abandoned at any till'e after the l'.Or1< is comll'enced for a period of 180days {Seeton 106.4.4 Uniform Building Code).
~ APPLICANT'S SIGNATURE
STOP: THIS SECTION NOT REQUIRED FOR BUILDING PERMIT ISSUANCE.
Complete the following ONLY if a Certificate of Occupancy will be requested at final inspection.
CERTIFICATE OF OCCUPANCY fCommcrcial Projects On I y I
Fax (760) 602-8560, Email building@carlsbadca.gov or Mail the completed form to City of Carlsbad, Building Division 1635 Faraday Avenue, Carlsbad, California 92008.
I CO#: (Office Use Only)
CONTACT NAME OCCUPANT NAME
ADDRESS BUILDING ADDRESS
CITY STATE ZIP CITY STATE ZIP
Carlsbad CA
PHONE I FAX
EMAIL OCCUPANT'S BUS. LIC. No.
DELIVERY OPTIONS
PICK UP: CONTACT (Listed above) OCCUPANT (Listed above)
CONTRACTOR (On Pg. 1)
ASSOCIATED CB#
MAIL TO: CONTACT (Listed above) OCCUPANT (Listed above)
CONTRACTOR (On Pg. 1) NO CHANGE IN USE/ NO CONSTRUCTION
MAIL/ FAX TO OTHER: CHANGE OF USE / NO CONSTRUCTION
~ APPLICANT'S SIGNATURE DATE
EsGil Corporation
In <Partners nip witfi (Jovernment for CBui{aing Safety
DATE: 07/07/2014
JURISDICTION: Carlsbad
PLAN CHECK NO.: Cb14-1388
PROJECT ADDRESS: 1000 Whimbrel Ct.
SET: II
□ APPLICANT
□ JURIS.
□ PLAN REVIEWER
□ FILE
PROJECT NAME: Maicher 3 8@240 Watt micro inverter Solar Photovoltaic System
D The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's codes.
~ The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
D The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
D The applicant's copy of the check list has been sent to:
D Esgil Corporation staff did not advise the applicant that the plan check has been completed.
D Esgil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Telephone#:
Date contacted: (by: Fax#:
Mail Telephone Fax In Person E-mail:
~REMARKS: Applicant to make changes, see sheet 4 clouded area, applicant to make \.o/ changes to all city sets prior to issuing the permit, set 2 is identical to set I.
By: John Le Vey
EsGil Corporation
0 GA O EJ O PC
Enclosures:
07/07/2014
9320 Chesapeake Drive, Suite 208 ♦ San Diego, California 92123 ♦ (858) 560-1468 ♦ Fax (858) 560-1 576
EsGil Corporation
In <Partnersfiip witfi (]overnment for (]JuiUing Safety
DATE: 06/30/2014
JURISDICTION : Carlsbad
PLAN CHECK NO .: Cb14-1388
PROJECT ADDRESS: 1000 Whimbrel Ct.
SET: I
□_..,.APPLICANT
..,..ei JURIS.
0 PLAN REVIEWER
0 FILE
PROJECT NAME: Maicher 38@240 Watt micro inverter Solar Photovoltaic System
D The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's
codes when minor deficiencies identified below are resolved and checked by building
department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
~ The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
D The applicant's copy of the check list has been sent to:
D Esgil Corporation staff did not advise the applicant that the plan check has been completed.
~ Esgil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted : John Lavender Telephone#: 858-405-1514
Date contacted: l1?, I ?l> (b~
~Mail / Telephone Fax In Person
0 REMARKS:
By: John Le Vey
EsGil Corporation
□ GA □ EJ □ PC
Fax #:
E-mail: john@inallproducts.com
Enclosures:
06/23/2014
9320 Chesapeake Drive, Suite 208 ♦ San Diego, California 92123 ♦ (858) 560-1 468 ♦ Fax (858) 560-1 576
Carlsbad Cb14-1388
06/30/2014
GENERAL PLAN CORRECTION LIST
JURISDICTION: Carlsbad
PROJECT ADDRESS: 1000 Whimbrel Ct.
DATE PLAN RECEIVED BY
ESGIL CORPORATION: 06/23/2014
REVIEWED BY: John Le Vey
FOREWORD (PLEASE READ):
PLAN CHECK NO.: Cbl4-1388
DATE REVIEW COMPLETED:
06/30/2014
This plan review is limited to the technical requirements contained in the International Building
Code, Uniform Plumbing Code, Uniform Mechanical Code, National Electrical Code and state
laws regulating energy conservation, noise attenuation and disabled access. This plan review
is based on regulations enforced by the Building Department. You may have other corrections
based on laws and ordinances enforced by the Planning Department, Engineering Department
or other departments.
The following items listed need clarification, modification or change. All items must be satisfied
before the plans will be in conformance with the cited codes and regulations. The approval of
the plans does not permit the violation of any state, county or city law.
• Please make all corrections and submit two new complete sets of prints to:
ESGIL CORPORATION.
• To facilitate rechecking, please identify, next to each item, the sheet of the plans upon
which each correction on this sheet has been made and return this sheet with the
revised plans.
• Please indicate here if any changes have been made to the plans that are not a result of
corrections from this list. If there are other changes, please briefly describe them and where
they are located on the plans. Have changes been made not resulting from this list?
□ Yes □ No
Carlsbad Cb14-1388
06/30/2014
{DO NOT PAY -THIS IS NOT AN INVOICE]
VALUATION AND PLAN CHECK FEE
JURISDICTION: Carlsbad
PREPARED BY: John Le Vey
PLAN CHECK NO.: Cbl4-1388
DATE: 06/30/2014
BUILDING ADDRESS: 1000 Whimbrel Ct.
BUILDING OCCUPANCY:
BUILDING AREA Valuation
PORTION ( Sq. Ft.) Multiplier
PV system
Air Conditioning
Fire Sprinklers
TOTAL VALUE
Jurisdiction Code cb By Ordinance
Bldg. Permit Fee by Ordinance ~
Plan Check Fee by Ordinance
Type of Review: □ Complete Review
D Repetitive Fee
~ Repeats
• Based on hourly rate
Comments: 1.5 hour plan review.
D Other
G] Hourly
EsGil Fee
TYPE OF CONSTRUCTION:
Reg. VALUE
Mod .
D Structural Only
~---1-.5---11 Hrs. @ •
$86.00_
($)
$161 .251
$129.001
Sheet 1 of 1
macvalue.doc +
Carlsba·d Cb14-1388
06/30/2014
ELECTRICAL and ENERGY COMMENTS
PLAN REVIEWER: John Le Vey
ELECTRICAL (2013 CALIFORNIA ELECTRICAL CODE)
1. Please show the over current breakers for the Array's in the main electrical panel which
breaker will be connected to which array.
2. Please provide an A/C disconnect on the roof within site of the farthest inverter per CEC
section 690 .14( d)(2).
Note: If you have any questions regarding this Electrical and Energy plan review list please
contact John Le Vey at (858) 560-1468. To speed the review process, note on this list (o r a
copy) where the corrected items have been addressed on the plans.
<<1 ~ CITY OF
CARLSBAD
PLANNING DIVISION
BUILDING PLAN CHECK
APPROVAL
P-29
DATE: 6-19-14 PROJECT NAME: PROJECT ID:
Development Services
Planning Division
1635 Faraday Avenue
(760) 602-4610
www.carlsbadca.1wv
PLAN CHECK NO: CB 14-1388 SET#: 1 ADDRESS: 1000 Whimbrel APN:
[ZI This plan check review is complete and has been APPROVED by the
Division.
By: Chris Sexton
A Final Inspection by the Planning Division is required □ Yes [8J No
You may a/so have corrections from one or more of the divisions listed below. Approval
from these divisions may be required prior to the issuance of a building permit.
Resubmitted plans should include corrections from all divisions.
D This plan check review is NOT COMPLETE. Items missing or incorrect are listed on
the attached checklist. Please resubmit amended plans as required.
Plan Check APPROVAL has been sent to:
For questions or clarifications.on the attached checklist please contact the following reviewer as marked:
PLANNING ENGINEERING FIRE PREVENTION
760-602-4610 760-602-2750 760-602-4665
~ Chris Sexton □ Kathleen Lawrence □ Greg Ryan
760-602-4624 760-602-27 41 760-602-4663
Chris,SextQn~i;2rlsb2Q!;g.gQv K2thleen.Lawreni;e~i;2rlsb2Q!;g.gQv GregQr:y.Ry2n~i;2rlsb2dQ2.gQv
□ Gina Ruiz □ Linda Ontiveros □ Cindy Wong
760-602-46 7 5 760-602-2773 760-602-4662
Gina.Ruiz~!;;arls!2adca.gov Linda.OntiverQ~~c9rl~b9dca.gov Cyn!hi9.WQng~Q9rl~!;!9QQ9.gQv
□ □ □ Dominic Fieri
760-602-4664
DominiQ.Fieri~c9rls!29d!;;9.gQv
Remarks: