HomeMy WebLinkAbout2285 RUTHERFORD RD; ; CBC2024-0334; PermitBuilding Permit Finaled
{city of
Carlsbad
Commercial Permit
Print Date: 09/30/2025
Job Address: 2285 RUTHERFORD RD, CARLSBAD, CA 92008-8815
Permit No:
Status:
CBC2024-0334
Closed -Finaled
Permit Type: BLDG-Commercial Work Class: Tenant Improvement
Parcel#:
Valuation:
Occupancy Group:
#of Dwelling Units:
Bedrooms:
Bathrooms:
Occupant Load:
Code Edition:
Sprinkled:
Project Title:
2120620800
$97,671.42
Track #:
Lot#:
Project#:
Plan#:
Construction Type:
Orig. Plan Check #:
Plan Check #:
Applied: 10/23/2024
Issued: 12/11/2024
Finaled Close Out: 09/30/2025
Final Inspection: 09/30/2025
INSPECTOR: Renfro, Chris
Description: QUIDELORTHO: (1218 SF) INTERIOR Tl// NEW WALLS, CEILINGS// PLUMBING, LIGHT FIXTURES// EQUIPMENT, FINISHES,
STRUCTURAL
Applicant: Property Owner:
MCFARLANE ARCHITECTS
SARAH MCALLISTER
ARE-SD REGION NO 71 HOLDING LLC
PO BOX 847
6256 GREENWICH DR, # STE 500
SAN DIEGO, CA 92122-5946
FEE
BUILDING PLAN CHECK
CARLSBAD, CA 92018-0847
BUILDING PLAN REVIEW -MINOR PROJECTS (LOE)
BUILDING PLAN REVIEW -MINOR PROJECTS (PLN)
CERTIFICATE OF OCCUPANCY
COMM/IND Tl -STRUCTURAL
FIRE F Occupancies Tl
SB1473 -GREEN BUILDING STATE STANDARDS FEE
STRONG MOTION -COMMERCIAL (SMIP)
Total Fees: $2,863.88 Total Payments To Date: $2,863.88
Contractor:
SKYLINE COMMERCIAL INTERIORS INC
5051 AVEN IDA ENCINAS
CARLSBAD, CA 92008-4363
(858) 720-8559
Balance Due:
AMOUNT
$663.21
$204.00
$107.00
$21.00
$1,020.32
$817.00
$4.00
$27.35
$0.00
Please take NOTICE that approval of your project includes the "Imposition" of fees, dedications, reservations, or ot her exactions hereafter
collectively referred to as "fees/exaction." You have 90 days from the date this permit was issued to protest imposition of these
fees/exactions. If you protest them, you must follow the protest procedures set forth in Government Code Section 66020(a), and file the
protest and any other required information wit h the City Manager for processing in accordance with Carlsbad M unicipal Code Section
3.32.030. Fai lure to timely follow that procedure will bar any subsequent legal action to attack, review, set aside, void, or annul their
imposition.
You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection
fees and capacity changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this
project. NOR DOES IT APPLY to any fees/exactions of which you have previously been given a NOTICE similar to this, or as to which t he
statute of limitation has previously otherwise expired.
Building Division Page 1 of 1
1635 Faraday Avenue, Carlsbad CA 92008-7314 I 442-339-2719 I 760-602-8560 f I www.carlsbadca.gov
( City of
Carlsbad
COMMERCIAL
BUILDING PERMIT
APPLICATION
B-2
Plan Check
Est. Value
PC Deposit
Date
(!Bl 1/f)l, ~ -D13'-I
i~&3 -2-l
Job Address 2285 RUTHERFORD ROAD Suite: APN: 212-062-08-00 -----
Tenant Name #: QUIDELORTHO Lot#: Year Built: 1982 ,_________________ --------------
Year Built: 1982 Occupancy: B, s1 Construction Type: Ill-A Fire sprinklers0'ESQNO A/C:Q YESQNO
BRIEF DESCRIPTION OF WORK: INTERIOR Tl, INCLUDING MODIFICATIONS EXISTING PRE-FABRICATED DRY ROOM PANELS, NEW
.WALLS, CEILINGS, LIGHT FIXTURES, PLUMBING FIXTURES, FINISHES, TENANT EQUIPMENT, MEP & STRUCTURAL AS REQUIRED.
D Addition/New: ____________ New SF and Use, __________ New SF and Use
_______ SF Deck, _______ SF Pat io Cover, ________ SF Other (Specify) ___ _
LAB LAB, MECHANICAL
0Tenant Improvement: _1_,2_18 ___ SF, Existing Use: _______ Proposed Use: ______ _
_____ SF, Existing Use: Proposed Use: ______ _
D Pool/Spa:. _____ SF Additional Gas or Electrical Features? ____________ _
D Solar: ___ KW,, ___ Modules, Mounted: ORoof C G round
D Re roof: _____________________________________ _
0 Plumbing/Mechanical/Electrical PLUMBING FIXTURES, ASSOCIATED MECHANICAL, ELECTRICAL, PLUMBING
0 Other: STRUCTURAL FOR TENANT EQUIPMENT
APPLICANT (PRIMARY CONTACT) PROPERTY OWNER
Name: SARAH MCALLISTER / MCFARLANE ARCHITECTS Name: AREA-SD REGION NO. 71, LLC, A DELAWARE LIMITED LIABILITY COMPANY
Address· 6256 GREENWICH DRIVE, STE 500 Address: 10996 TORREYANA ROAD, SUITE 250
City· SAN DIEGO State: CA Zip:_9_21_2_2 --City: SAN DIEGO State: CA Zip:._9_2_12_1 __ _
Phone· 858-453-1150 Phone: 858-638-2800
Email · sam@mcfarlaneachitects.com Email: ____________________ _
DESIGN PROFESSIONAL
Name: NEAL MCFARLANE / MCFARLANE ARCHITECTS
Address: 6256 GREENWICH DRIVE, STE 500
CONTRACTOR OF RECORD
Business Name: PREVOST CONSTRUCTION
Address: 5051 AVENIDA ENCINAS
City: SAN DIEGO State:_c_A __ Zip: 92122 City: CARLSBAD State:_C_A __ Zip: 92008
Phone: 858-453-1150 Phone: 858-720-8559 / 858-967-7927
Email: nkm@mcfarlanearchitects.com Email: msoth@prevostconstruction.com
Architect State License: _c_-2_3_69_1_________ CSLB License #: 727637 Class:_B ______ _
Carlsbad Business License# (Required}: BLoso12253-08-2022
APPLICANT CERT/FICA TION: I certify that I have read the application and state that the above information is correct and that the
information on the plans is accurate. I agree to comply with all City ordinances and State laws relating to building
construction. SARAH MCALLISTER / MCFARLANE
NAME (PRINT): _A_R_C_H_IT_EC_T_S ______ _ SIGN:'""=~~--Q-c:o:::,--~~,..JJ_c::::::IC=-r-:::-== DATE: 1 o-18-2024
1635 Faraday Ave Carlsbad, CA 92008 Ph: 442-339-2719 Fax: 760-602-8558 Email: Building@carlsbadca.gov
REV. 07/21
THIS PAGE REQUIRED AT PERMIT ISSUANCE PLAN CHECK NUMBER: ______ _
A BUILDING PERMIT CAN BE ISSUED TO EITHER A STATE LICENSED CONTRACTOR OR A PROPERTY OWNER. IF THE PERSON
SIGNING THIS FORM IS AN AGENT FOR EITHER ENTITY AN AUTHORIZATION FORM OR LETTER IS REQUIRED PRIOR TO
PERMIT ISSUANCE.
(OPTION A): LICENSED CONTRACTOR DECLARATION:
I herebyaffirmunder penalty of perjury that I am licensed under provisions of Chapter9 ( commencing with Section 7000)of Division3
of the Business and Professions Code, and my license is in full force and effect. I also affirm under penalty of perjury one of the
following declarations {CHOOSE ONE):
D1 have and will maintain a certificate of consent to self-Insure for workers' compensation provided by Section 3700 of the Labor Code, for the performance of the
work which this permit Is Issued. PollcyNo .. ______________________________________ _
-OR-
Q1 have and wlll maintain worker's compensation, as required by Section 3700 of the Labor Code, fnr th .. !"'rfnrm:anr,. nf th .. wnrl( for which this permit Is Issued.
My workers' icnm!"'n<,.tinn insurance carrier and policy number are: lnsuranceCompany Name: old Republic Insurance co
Polley No .. MWcJ1211s24 Expiration Date:_ 21112s
-OR-
Ocertlflcate of Exemption: I certify that In the performance of the work for which this permit Is Issued, I shall not employ any person In any manner so as to become
subject to the workers' compensation Laws of californla. WARNING: FaHure to secure workers compensation coverage Is unlawful and shall subfect an employer to
criminal penalties and clvll fines up to $100,000.00, In addition the to the cost of compensation, damages as provided for In Section 3706 of the Labor Code,
Interest and attorney's fees.
CONSTRUCTION LENDING AGENCY, IF ANY:
I hereby affirm that there is a construction lending agency for the performance of the work this permit Is Issued (Sec. 3097 (i) Ovil Code).
Lender's Name:. ____________________ Lender'sAddress: ___________________ _
CONTRACTOR CERTIFICATION: I certify that I have read the application and state that the above information is correct and that
the information on the plans is accurate. I agree to comply with all City ordinances and State laws relating to building
COnstrUCtfon. DIOltally signed by
Mi<;~ael Soth
Daft: 2024.10.19 NAME (PRINT): -M-ic_h•_e_i _50_th _______ SIGNATURE: ______ 10_,ss_:_ss_.o_roo_· __ DATE:. _______ _
Note: If the person signing above Is an authorized 11ent for the contractor provide a letter of authorization on contractor letterhead.
-OR·
(OPTION B): OWNER-BUILDER DECLARATION:
I hereby affirm that I am exempt from Contractor's License Law for the following reason: n I, as owner of the property or my employees with wages as their sole compensation, will do the work and the structure Is not Intended or offered for sale (Sec. '-,d«, Business and Professions Code: The Contractor's license Law does not apply to an owner of property who builds or Improves thereon, and who does such
work himself or through his own employees, provided that such Improvements are not intended or offered for sale. If, however, the building or improvement Is sold
within one year of completion, the owner-builder will have the burden of proving that he did not build or improve for the purpose of sale).
-OR-D 1. as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec. 7044, Business and Professions Code: The
Contractor's license Law does not apply to an owner of property who builds or improves thereon, and contracts for such projects with contractor(s) licensed
pursuant to the Contractor's License Law).
-OR-□, am exempt under Business and Professions Code Division 3, Chapter 9, Article 3 for this reason:
AND, D FORM 8-61 "Owner Builder Acknowledgement and Verlfkatlon Form" Is required for any permit issued to a property owner.
By my signature below I acknowledge that, except for my personal residence in which I must have resided for at least one year prior to completion of the
Improvements covered by this permit, I cannot legally sell a structure that I have built as an owner-builder if It has not been constructed in its entirety by licensed
contractors./ understand that ocowof theoppllcoble low, Section 7044of the Business and Professions Code, Is ovo/lobleupon request when this application Is
submitted or at the following Web site: http:l lwww.leginfo.ca.gov/calaw.html.
OWNER CERTIFICATION: I certify that I have read the application and state that the above information is correct and that the
information on the plans ts accurate. I agree to comply with all City ordinances and State laws relating to building
construction.
NAME (PRINT): _________ _ SIGN: __________ DATE: ______ _
Note: If the person slgnln1 above Is an authorized a1ent for the property owner Include form B-62 slsned by property owner.
1635 Faraday Ave Carlsbad, CA 92008 Ph: 442-339-2719 Fax: 760-602-8558 Email: Bulldlng@carlsbadca.gov
2 REV. 07/21
PERMIT INSPECTION HISTORY for (CBC2024-0334)
Permit Type: BLDG-Commercial
Work Class: Tenant Improvement
Application Date: 10/23/2024 Owner: ARE-SD REGION NO 71 HOLDING LLC
Issue Date: 12/1 1/2024 Subdivision: CARLSBAD TCT#81-10 UNIT#01
Status:
Scheduled
Date
08/05/2025
08/19/2025
09/30/2025
Closed -Finaled Expiration Date: 02/02/2026
IVR Number: 59711
Address: 2285 RUTHERFORD RD
CARLSBAD, CA 92008-8815
Actual Inspection Type
Start Date
08/05/2025 BLDG-14
Frame/Steel/Bolting/We
lding (Decks)
Checklist Item
Inspection No. Inspection Primary Inspector
Status
292153-2025 Partial Pass Chris Renfro
COMMENTS
BLDG-Building Deficiency Partial pass framing at New doorway. OK
to close up. Call for final inspection when
complete.
08/19/2025 BLDG-Final Inspection
Checklist Item
293469-2025
COMMENTS
Partial Pass Chris Renfro
BLDG-Building Deficiency Partial pass final inspection, pending 859
form and construction waste receipts.
BLDG-Plumbing Final
BLDG-Mechanical Final
BLDG-Structural Final
BLDG-Electrical Final
09/30/2025 BLDG-Final Inspection
Checklist Item
296949-2025
COMMENTS
Passed Chris Renfro
BLDG-Building Deficiency Partial pass final inspection, pending 859
form and construction waste receipts.
BLDG-Plumbing Final
BLDG-Mechanical Final
BLDG-Structural Final
BLDG-Electrical Final
Reinspection Inspection
Reinspection Incomplete
Passed
Yes
Reinspection Incomplete
Passed
No
Yes
Yes
Yes
Yes
Complete
Passed
No
Yes
Yes
Yes
Yes
Tuesday, September 30, 2025 Page 2 of 2
Building Permit Inspection History Finaled
{city of
Carlsbad
Permit Type:
Work Class:
Status:
Scheduled
Date
01/14/2025
01/23/2025
02/11/2025
02/19/2025
05/29/2025
PERMIT INSPECTION HISTORY for (CBC2024-0334)
BLDG-Commercial Application Date: 10/23/2024 Owner: ARE-SD REGION NO 71 HOLDING LLC
Tenant Improvement Issue Date: 12/11/2024 Subdivision: CARLSBAD TCT#81-10 UNIT#01
Closed -Finaled Expiration Date: 02/02/2026 Address: 2285 RUTHERFORD RD
IVR Number: 59711 CARLSBAD, CA 92008-8815
Actual Inspection Type
Start Date
Inspection No. Inspection Primary Inspector Reinspection Inspection
Status
01/14/2025 BLDG-21 273222-2025 Passed Chris Renfro
Underground/Underflo
or Plumbing
Checklist Item
BLDG-Building Deficiency
COMMENTS
01/23/2025 BLDG-11 274203-2025 Partial Pass Chris Renfro
Foundation/Ftg/Piers
(Rebar)
Checklist Item
BLDG-Building Deficiency
COMMENTS
Patch back slab work for underground
trenching. OK to pour.
02/11/2025 BLDG-84 Rough
Combo(14,24,34,44)
275838-2025 Partial Pass Chris Renfro
Checklist Item
BLDG-Building Deficiency
BLDG-14
Frame-Steel-Bolting-Welding
(Decks)
BLDG-24 Rough-Topout
BLDG-34 Rough Electrical
BLDG-44
Rough-Ducts-Dampers
COMMENTS
Partial pass rooftop, air handlers, exhaust
and return. Curb framing.
02/19/2025 BLDG-17 Interior
Lath/Drywall
276382-2025 Partial Pass Chris Renfro
Checklist Item
BLDG-Building Deficiency
COMMENTS
Partial pass, rough framing in mechanical
room
05/29/2025 BLDG-84 Rough
Combo(14,24,34,44)
286209-2025 Partial Pass Chris Renfro
Checklist Item
BLDG-Building Deficiency
BLDG-14
Frame-Steel-Bolting-Welding
(Decks)
BLDG-24 Rough-Topout
BLDG-34 Rough Electrical
BLDG-44
Rough-Ducts-Dampers
COMMENTS
Partial pass rough combo ceiling area in
equipment room.
Complete
Passed
Yes
Reinspection Incomplete
Passed
Yes
Re inspection Incomplete
Passed
No
Yes
Yes
Yes
Yes
Reinspection Incomplete
Passed
Yes
Reinspection Incomplete
Passed
No
Yes
Yes
Yes
Yes
Tuesday, September 30, 2025 Page 1 of 2
,a~ ,■i
NOVA Services
NOVA Services, Inc.• San Diego
4373 Viewridge Avenue, Suite B
San Diego, CA 92123
Phone:858-292-7575
Date: 08/06/2025
Daily Field Report
Client:
Quidel Corporation
6675 Summer Ridge Rd
San Diego, CA 92121
Project:
1025008
Quidel lyo T.I.
2285 Rutherford Road
Carlsbad, CA 92008
Subcontractor: Skyline
TimeArrived: 10:00
General Contractor: Skyline
Time Departed: 12:00 Hours: 2.00 Lunch Period (minutes): 0
Permit#: CBC2024-0334 Jurisdiction: Carlsbad
lnapectorlTechnician: Lamb, Morgan Certification#: San Diego #1471 , ICC #9984114, ACI #02142219
Reference Documents: Approved project documents.
Type of Inspection: Post Installed Anchors / Torque Testing
Work Inspected:
Post Installed Anchors
Arrived onsite as Nova representative to provide special inspection for the installation of mechanical unit anchors to the existing slab
per detail 5/S800.
Holes were drilled prior to my arrival. Verification of holes depths, diameters and cleanliness was performed. Approximately (14) 1/2"x4
1 /2" Hilti KB-TZ2 were installed with a minimum effective depth of 2 1/2". Anchors were then torqued to 50ft-lbs. using a current
calibrated torque wrench. Anchors were torqued with zero reported failures, effective embedment was reverified.
Anchor installation was performed in accordance with the approved plans and ESR-4266. No problems noted.
Tests Performed on Site: Torque Testing 50ft.lbs.
The work WAS inspected in accordance with the requirements of the approved documents.
The work inspected MET the requirements of the approved documents.
Material Sampling: N/A
"9e1otl
J&\ , ..
NOVA SC'rvice~
NOVA Services, Inc.• San Diego
4373 Viewridge Avenue, Suite B
San Diego, CA 92123
Phone: 858-292-7575
Daily Field Report
Client:
Quidel Corporation
6675 Summer Ridge Rd
San Diego, CA 92121
Project:
1025008
Quidel Lyo T.I.
2285 Rutherford Road
Car1sbad, CA 92008
Page 2 of 3
,a\ ••~ NOVA
Services
NOVA Services, Inc.• San Diego
4373 Viewridge Avenue, Suite 8
San Diego, CA 92123
Phone: 858-292-7575
Daily Field Report
Client:
Quidel Corporation
6675 Summer Ridge Rd
San Diego, CA 92121
Project:
1025008
Quidel Lyo T.I.
2285 Rutherford Road
Carlsbad, CA 92008
Page 3 of 3
True North
COMPLIANCE SERVICES
December 3, 2024
City of Carlsbad
Community Development Department -Building Division
1635 Faraday Ave.
City of Carlsbad -FINAL REVIEW
City Penn it No: CBC2024-0334
True North No.: 24-018-959
Carlsbad, CA 92008
Plan Review: TI Quidelortho
Address: 2285 Rutherford Rd
Applicant Name: Sarah McAllister
Applicant Email: Sam@mcfarlanearchitects.com
OCCUPANCY AND BUILDING SUMMARY:
Occupancy Groups: ~-1, B
Occupant Load: 1,006 (Tota~ Building)
Type of Construction: III-B
Sprinklers: Yes
Stori es: I
Area of Work (sq. ft.): 1,218 sq. ft.
The plans have been reviewed for coordination with the permit application.
Valuation: See Notes Below
Scope of Work: See Notes Below
Floor Area: Confirmed
Notes: Valuation: Information was not provided on the permit application form. Scope of Work: Please refer to
architectural comment A I, a) requesting for scope of work to be revised to include construction of a 1,000 + sf.
mechanical room within the Tl floor area.
Attn: Building & Safety Department,
True North Compliance Services, Inc. has completed the final review of the following documents for the project
referenced above on behalf of the City of Carlsbad:
I.
2.
3.
Drawings: One (I) copy dated November 19, 2024, by Mcfarlane Architects.
Structural Calculations: One (I) copy dated October 18, 2024, by KPFF Consulting Engineers.
Other Documents: One (I) copy dated November I 0, 2024.
The 2022 Californ ia Building, Mechanical, Plumbing, and Electrical Codes (i.e., 202 1 IBC, UMC, UPC, and 2020
NEC, as amended by the State of California), 2022 California Green Building Standards Code, 2022 California
Existing Building Code, and 2022 California Energy Code, as applicable, were used as the basis of our review.
Please note that our review has been completed and we have no further comments.
We have enclosed the above noted documents bearing our review stamps for your use. Please call if you have any
questions or ifwe can be of further assistance.
True North Compliance Services, Inc.
8369 Vickers Street, Suite 207, San Diego, CA 92111
T / 562.733.8030
Sincerely,
True North Compliance Services
Review By: Mulham Hweidi -Plan Review Engineer
QA/QC Review By: Alaa Atassi Plan Review Engineer
Transmittal Letter
October 31, 2024
City of Carlsbad
Community Development Department -Building Division
1635 Faraday Ave.
Carlsbad, CA 92008
Pl an Review: Tenant Improvement to lab areas and mezzanine.
Address: 2285 Rutherford Rd., Carlsbad CA
True North
C OM PLI ANC E SERVI CES
FIRST REVIEW
City Permit No: CBC2024-0334
True North No.: 24-01 8-959
Applicant ame: Sarah McAllister Applicant Email: sam@mcfarlanearchitects.com
True North Compliance Services, Inc. has completed the review of the following documents for the project
referenced above on behalf of the City of Carlsbad. Our comments can be found on the attached list.
I.
2.
Drawings: Electronic copy dated October 21, 2024, by McFarl ane Architects.
Structural Calculations: Electronic copy dated October 18, 2024, by KPFF Consul ting Engi neers.
Attn: Permit Technician, the scope of work on the plans has been reviewed for coordination with the scope of
work on the permit application. See below for information if the scope of work on plans differs from the permit
application:
Valuation:
Scope of Work:
Floor Area:
See Notes Below
Confirmed
Confirmed
Notes: Valuation not found on application form.
Our comments follow on the attached list. Please call if you have any questions or if we can be of further
assistance.
Sincerely,
True orth Compliance Services
Review By: Jesse Sanchez -Plans Examiner
Quality Review By: Alaa Atassi -Senior Plan Review Engineer
True North Compliance Services, Inc.
8369 Vickers Street, Suite 207, San Diego, CA 92111
T / 562.733.8030
Tenant Improvement to lab areas and mezzanin e.
2285 Rutherford Rd.
City of Carlsbad-FIRST REVIEW
City Permit No.: CBC2024-0334
True North No.: 24-018-959
Page2
October 31, 2024
Plan Review Comments
ELECTRONIC -RESUBMITT AL INSTRUCTIONS:
Please do not resubmit plans until all departments have completed their reviews. For status, please
contact building@carlsbadca.gov
Please make all corrections, as requested in the correction list. Corrected sets can be submitted as follows:
Email the revised plans and comment response letter(s) to building@carlsbadca.gov for continued
review.
Note: Tf this project requires FIRE PREVENTION review, ensure that you follow their specific
instructions for resubmittal review. The city will not route plans back to Dennis Grubb &
Associates for continued Fire Prevention review.
GENERAL INFORMATION:
A.
B.
C.
D.
E.
The following comments are referred to the 2022 California Building, Mechanical, Plumbing, Electrical
Codes, California Green Bui lding Standards Code, and Energy Code (i.e., 2021 IBC, UMC, UPC, and 2020
NEC, as amended by the State of California).
There may be other comments generated by the Building Division and/or other City departments that will
also require your attention and response. This attached list of comments, then, is only a portion of the plan
review. Contact the City for other items.
Respond in writing to each comment by marking the attached comment list or creating a response letter.
Indicate which details, specification, or calculation shows the required information. Your complete and
clear responses will expedite the re-check.
Where applicable, be sure to include the architect and engineer's stamp and signature on all sheets of the
drawings and on the coversheets of specifications and calculations per CBPC 5536.l and CBPC 6735. This
item will be verified prior to plan approval.
lfyou have any questions regarding the comments below, please contact Jesse Sanchez via email
jesses@tncservices.com or telephone (562) 733-8030.
OCCUPANCY & BUILDING SUMMARY:
Occupancy Groups:
Occupant Load:
Type of Construction:
Sprinklers:
Stories:
Area of Work (sq. ft.):
S-1, B
1,006 (total)
III-B
Yes
2
1,218 sq. ft.
ARCIIlTECTURAL COMMENTS:
General:
Al. For sheet CS 100 please address the fo llowing comments:
Tenant Improvement to lab areas and mezzanine.
2285 Ru therfo rd Rd.
City of Carlsbad-FIRST REVIEW
City Permit No.: CBC2024-0334
True North No.: 24-018-959
Page3
October 31, 2024
a) Under scope of work, please specify TI work includes construction of a 1,000 +SF. mechanical
room and related equipment. Also, since no work is shown in the mezzanine area, please remove it
from scope.
CONSTRUCTION SCOPE OF WORK INCLUDES:
1. DEMOLITION AS REQUIRED FOR NEW WORK.
2. INTERIOR WORK TO INCLUDE MODIFICATIONS TO THE LAB AREAS
ON THE FIRST LEVEL AND 1vtEZlAt◄lt◄E OF At◄ EXISflt◄6 BUILDlr◄6.
TENANT EQUIPMENT, LIGHT FIXTURES, FINISHES, WALLS, DOORS.
PLUMBING FIXTURES ETC.
3. STRUCTURAL REINFORCEMENT OF CONCRETE SLAB FOR TENANT
EQUIPMENT.
4. ASSOCIATED IMPROVEMENTS AND MODIFICATIONS TO
STRUCTURAL. MECHANICAL. PLUMBING AND ELECTRICAL AS
REQUIRED FOR NEW WORK.
5. ROOF TOP MECHANICAL EQUIPMENT
6. NO FLOOR AREA IS BEING ADDED UNDER THIS PROJECfS SCOPE
OF WORK.
b) Provide the following note: Site and restrooms are fully accessible under permit number CBC2021-
0l 11
A2. For sheet A2 l 3, the enlarged fl oor plan calls out eight (8) separate pieces of equipment in the new
mechanical room. Please provide the equipment schedule as referenced on the symbol legend for all
equipment.
,
' ' ' ' i------t--t~
..... ', ···~j·.1. ...... ,.,,.-r·, ,;
',,,, i (---~~ C----~---rr !
l I r---------1
r: ~---l~ l_____ 1
! ,E
I
M0Vt0
>, c~o AS 1tf'OUleO.
SYMBOL LEGEND
D (XafN:)f:\OObNOAt&AMOIASETOHRt).l()Y(Of()t Mtw~ COffflAC101f0Cl.CA.."iSUffAC(.PA1'04AN01P'AaAttr'LA.IGfi
Ct'IOIS I" nar,,,c SlJJ AK:> Plt0Yl)l A SMOOfH NC> ltve. WlfAGf. to. NSlAUAIION 0, NEW fNSHG Jl"EJt P'\AI<.
CMOl!ADO: COf,RA,CtOI: 10 P'll0Va a«i 1, ffl:NG NfO Al'C"ION g ll())lfOlrmorva:,....-..am~"80HTSOICXU.
@$~~--~-
A3. Sheet A00 lidentifies the proposed mechanical room as "SDGE Electrical". Please clarify.
Tenant Improvement to lab areas and mezzanine.
2285 Rutherford Rd.
October 31, 2024
' ' .,., ,,_
~ ~ £XIT 1.7
IOCE
El!CTit!CN
l.17U r
I/JOO .
City of Carlsbad-FIRST REVIEW
City Permit No.: CBC2024-0334
True North No.: 24-018-959
Page 4
A4. Mechanical plans show work on the first and second floor along the westerl y areas of gridli nes H and T.
Provide architectural floor plans as needed to identify the proposed work within these areas.
A5. Electrical sheet E212 shows what appears to be re located equipment on the first floor along the westerly
areas of gridlines H, I and J. Provide architectural floor plans as needed to identify the proposed work within
these areas.
A6. For sheet A2 I 3, provide a note to indicate the card reader is only for access control and wi ll not restrict
egress door operation at any time.
a)
ACCESSIBILITY COMMENTS:
General:
Dl. For sink shown on sheet A213, provide the following information per CBC l lB-606:
a) Provide clear floor space in accordance with CBC l lB-305 for a forward approach. CBC l lB-
606.2.
b) Provide knee and toe clearance in accordance with CBC l lB-306. CBC l lB-606.3.
c) Specify height of lavatory to be 34 inches maximum, measured from higher of the rim or counter
surface. CBC l lB-606.3.
d) For faucet controls, the following comments apply per CBC l lB-606.4:
i) Specify the h~ight of the operable parts to be 44 inches maximum per CBC l lB-308.2.2.
Tenant Improvement to lab areas and mezzanin e.
2285 Rutherford Rd.
October 31, 2024
City of Carlsbad-FIRST REVIEW
City Permit No.: CBC2024-0334
True North No.: 24-018-959
Page5
ii) Specify the control to be operable with one hand and shall not require tight grasping,
pinching, or twisting of the hand. CBC 11 B-309.4.
iii) Specify activation of the control to require a maximum force of 5 pounds. CBC 11 B-309.4.
iv) Hand-operated metering faucets shall remain open for 10 seconds minimum.
e) Specify exposed piping underneath the lavatory to be insulated. CBC 11 B-606.5.
D2. For sheet A2 I 3, provide dimensions between the equipment and other elements. An aisle width of the
following is required:
a)
b)
44" where aisle serves elements on both sides.
36" where aisle serves only one side.
·--, l I j. ,---, µ r--------::i, 7-, ? I U f
I~] i i i
[J!:i L-------1 1~ : ;J ___ ,!,I ·181 . -r .... "' '":' ,, -.. .. I f -----,
j ... ~
DE]
I
1:
I
:-181
I
...
r -----,
I I
c) L-~--+~J
I
I I I I I
L-----
HAZARDOUS MATERIAL COMMENTS:
CBC l lB-403.5.1. Exception 4
Hl. Provide a completed Hazardous Materials Questionnaire form HMBP Questionnaire
Tenant Improvement to lab areas and mezzanine.
2285 Rutherford Rd.
City of Carlsbad-FIRST REVIEW
City Permit No.: CBC2024-0334
True North No.: 24-018-959
Page 6
October 31, 2024
H2. If applicable, identify the types of hazardous materi als stored, or in open or closed systems for the new
mechanical room and related equipment. Provide a hazardous materials list and provide a comparison with
the maximum allowable quantities per CBC Table 414.2.5(] ). Show comp! iance with CBC Table 414.2.2.
ELECTRICAL COMMENTS:
E I . For the new mechanical room:
a) Show location of installed emergency egress lighting equipped with battery backup in case of
primary power loss. CBC I 008.3
b) Provide exit signs installed at the required exit and exit access doorways of the building in
accordance with CBC 41 I . 7 and 1013.
GREE BUILDING COMME TS:
G I. Climate Action Plan requirements apply to all new structures, residential additions/remodels equal to or
exceeding $60,000 in valuation, and commercial City of Carlsbad requires that all projects that qualify for
CAP compliance wi ll require a completed Cli mate Action Plan (CAP) Consistency Checklists (city forms
B-50) to be completed by the APPLICANT.
https://www.carlsbadca.gov/home/showpublisheddocument/6878/638225157825900000
a) For plans submitted to the City the following Climate Action Plan requirements apply, per Carlsbad
ordinance:
b) The applicant is to fill out the B-50 CAP Consistency Checklist. The scope of work and project
valuation will determine which sections of the CAP are required.
c) Plan examiners review the B-50 CAP Consistency Checklist for completion. For example: If new
residential construction is the scope of work, CAP sections 2A, 3A, and 4A are required to be filled
on the B-50 checklist.
STRUCTURAL COMMENTS:
Plans:
S 1. For sheet S2 l l, provide structural details for all equipment installation call outs shown.
Structural Calculations:
S2. In addition to the refrigeration and vacuwn skid, provide calculations for all other remaining equipment
and components shown on sheet S21 l per ASCE 7-16 Section 13.
If you have any questions regarding the above comments, please contact Jesse Sanchez email
jesses@tncservices.com or telephone (562) 733-8030.
[END]
~
Mc FARLA NE ARCHITECTS PLA\ Clll~CK Hl~SPO\SES
Project Nome: Project Nome Dote: l l /20/2024
City Project No: CBC2024-0334
MA Project No: 24-108-35
Cycle No:
DESIGN CHANGES (NOT AS A RESULT OF CITY COMMENTS)
Chanae # Description of Chanae
l Proposed scullery sink along Gridline 2 wos removed from the scope of work. See sheet A213. All affected
sheets hove been updated.
2 Utilities for future tenon! equipment in the wet room 117 hos been removed. Affected sheets hove been
updated.
3 Per conditional fire approval, we hove updated the egress count .. the square footage we were previously
showing wos incorrect .. see snipil below for corrected sf ond occupant count.
-
D
~ u.a· NON-~ ~~L A
l/100
I .,
TRUE NORTH REVIEW: Jesse Sanchez ·esses@tncservices.com 562-733-8030
Issue#
Al
Written Res onse
See sheet CS l 00 where the scope of work wos updated:
• Included verbiage about the 'Mechanical' room.
• Removed the reference of the Mezzonine.
• Added requested note obout the site ond restrooms being occessible.
The square footoge information wos not included in the scope of work however, os this is already noted
on the CS l00 sheet under 'Area of Improvements'. It would be redundant to include the some
information under the scope of work os it is olreody been mode clear who! the square footage of the
oreo of work is. For easy reference, o snipit from the CS l 00 sheet hos been provided below showing
the revised 'scope of work' verbioge olong with the 'Area of Improvements' previously included.
I. ~_...,...;,;;;..;.;;.;;a;;o,;;;,:;;~~:;..,;,.;;:.:;;,..__,._.,._,,_,....,.,
2. MOOIFICATIONS 10 THE I.AB AREAS
EXISTING 8UllOING FOR PROPOSED A
EQUIPMENT. UGHT FIXTURES.
4. ASSOCIATED IMPROVEMENTS AND MOOIACATIONS 10
STRUCTURAL MECHANICAL PI.UM81NG AND ElEClRICAL AS
REQUIRED FOR NEW WORK.
5. ROOF TOP MECHANICAL EQUIPMENT
6. NO FLOOR AREA IS 8BNG ADDEO UNOER THIS PROJECTS SCOPE
OfW RK
L TI O RLS DI AC 0 . • O.UNII . I. ECIIYO
CARLSBAD. COUNT Of SAN DIEGO. STATE Of CALIFORNIA.
ACCORDING TO MAY THEREOF NO. 10330. ALEO IN THE OFFICE Of
COUNTY RECORDfR Of SAN DIEGO COUNTY, FfBRUARY 1982
Architecture • Planning • Interiors 6256 Greenw,ch Drive, Su,te 510, San Diego, Cahforn,a, 92122 • P: 858.453.1150
Project Nome:
City Project No:
MA Project No:
Dote:
Poge:
A2
A3
A4
A5
A6
Project Nome
C8C2024-0334
24-108-35
11/20/2024
2 of 4
AREA OF PROPOSED IMPROVEMENTS: 1m~~L
1.218 SF
PL\\ C l I ECK B ESPO\SES
21::!ClL~tL IQI6L
OSF 1.218SF
The equipment schedule wos previously included on sheet A950 'Schedule -Door, Finish, Mounting Height
& Equipment'. A Snipit of the equipment schedule that wos included on thot sheet hos been provided below
for eosv reference.
I!!-
llll'"fUUM.,\a;.,,._.. Laboratory Equipment list ----· 1£ i ! I ! I d1 I s I 11
11
I I I I I I I I II Ii JI I l I 1 f ,I • t i ---I I I I I I ,-,-----a.-........
' _, ..,,,, , . ............ -~ .. • .,. , .... . . ........,._.,._ .. -. ,..,_
, __ , .. .. • ,, .. " ---' ,_ -,-,_,_ .. . . . . --_ ... t -.,_ --... ... ... . . . . --' -·--·-1n -. ' .. --t ---,-,-" . . . --·~ . ' ' --. ·~ ' . --t --" ...... .. t . H
l..,1'.ti ..... 14 ,__ . --.. -1• ... • . ~-t ·--,·-,-,-" .
This wos o typo ond hos been corrected. See sheet A00l where we hove changed the nome lo 'Mechonicol'
on the ec:iress pion.
The mechonicol plans where showing mechonicol work os required to provide utilities to possible future
tenant equipment but were not shown on the Architectural os it wos 'Mechonicol' work .. That said, per above
'Design Changes', the tenant hos decided to remove this scope of work from this project ond affected sheets
hove been updated.
Electrical sheet E212 wos showing the relocation of utilities for possible future tenant equipment. There is
nothing being relocated ond oll 'equipment' shown wos just speculative in nature. That soid, per above
'Design Changes', the tenant hos decided to remove this scope of work from this project ond affected sheets
hove been uodoted.
Doors 120A ond 1208 ore not 'egress doors'. If you look ot the egress pion on sheet A00l (snipit provided
below for easy reference), you will see that the path of travel to the exit is through the lob (green space) ond
not through the mechonicol space. Cord readers ore allowed on doors tho! ore not in the poth of travel,
which these ore not.
Architecture • Planning • Interiors 6256 Greenwich Drive, Suite 500, San Diego, Cahforn1a, 92122 • P: 858453.1150
Project Nome:
City Project No:
MA Project No:
Dote:
Page:
D1
D2
Hl
H2
Project Nome
CBC2024-0334
24-108-35
11/20/2024
3 of 4
I ElCIT
I OISCHl\l!GE i EXIT 1.7
I
•
I
I
PL \, CI IEC "-H ES PO, SES
•
S0G(
llfC1IIICAt I 176 Sf
11300 •
The proposed scullery sink hos been removed from the scope of work on this project, and os such, this
comment no Ion er o lies.
Per 118-203.5 (Machinery Spaces):
Spaces frequented only by service personnel for maintenance, repair or occasional monitoring of equipment
shall not be required to comply with these requirements or to be on on accessible route.
Per the above code section, os the proposed oreo in question is o Mechanical room, it is not required to
com I with the cha ter 11 8 or be on on accessible route.
The Hazardous Materials Questionnaire was already reviewed, approved and hod been included in our
submittal to the Ci of Carlsbad. We hove attached another co to our o licont res onse.
The only new 'hazardous materials' include refrigerant for the proposed Lyophilizer's located in the
mechanical room. Thee ui men! in uestion ore 18, 28 and 38 os shown on the floor Ion, sheet A213.
• Lyo2 (18)
o R-22 30Ibs
o R-5088 50 lbs
o Silicone oil 45 gallons
• Stokes 220 (28)
o 3 refrigeration circuits.
o Each circuit will have between 45-65 lbs of R507 refrigerant.
o T otol refrigerant 135-195 lbs
• Hull 140(38)
o 2 refrigeration circuits.
o Each circuit will hove between 45-50 lbs of R507 refrigerant.
o Total refri eront 135-150 lbs.
Architecture • Planning • Interiors 6256 Greenwich Drive. Suite SOD, San o,ego, California. 92122 • P: 858.453 1150
Project Nome:
City Project No:
MA Project No:
Dote:
Page:
El
Gl
Sl
S2
Project Nome
CBC2024-0334
24-l 08-35
l l /20/2024
4 of 4
I --+-~-~ ~ I I
I I ~ I I • I I I I
t -1111 • 1r
T------
: ------t --1QJ:
----, ,.. r--""'I ' I I \ \ ' \,,
r-
'
I r--------~ I Hj-µ] I I I
• ·~: L---------r: l n~ ___ !Jlj •lil T ..,
• 4
I f -i
I I I I I I
~[¥) T ~~ : ____ l ~ I I I I L-----
' I _,.' . ' I
See electrical res onse.
PL \, CI I EC I\. B ES PO\ SES
Per the City of Carlsbad's Tenant Improvements B-6 form, a 'Completed B-50 Climate Action Pion' is only
required for 'Tl's over 200k valuation. The valuation for the proposed work per the ICC Building Valuation
Dato is $99,742.02. As this falls below the 200,000, o Com leted B-50 Climate Action Pion is not re uired.
See structural res onse.
Architecture • Planning • Interiors 6256 Greenwich D11ve, Suite 500, San Diego, Cahforn,a, 92122 • P: 858.453.1150
lqili
Comment # Response
Quidel Rutherfurd L YO
Response to Plan Check Comments
KPFF Project# 2400108
Prepared by KPFF
11/13/2024
(619) 521-8500
#S1 All structural details have been provided for equipment installation call outs shown on
plan. Fan coils are anchored per 15/S800, and exhaust fan is anchored per 10/S800. All (8)
pieces of equipment referenced on S211 are anchored to existing slab per 5/S800. All
references are included on S211 and details are provided on S800.
#S2 Existing slab is checked for the refrigeration skid and vacuum skid, as well as the heaviest
piece of equipment in the room {Hull 140). These calculations are found on pages Al-A3 of
the calculation package. All (8) pieces of equipment referenced on S211 are anchored to
existing slab per 5/S800. Calculations can be found on pages 81-813 of the calculation
package. Anchorage for these pieces of equipment is provided per requirements of ASCE
7-16 Chapter 13. Fan coil equipment anchorage calculations can be found on pages 814-
817 of the calculation package. Exhaust fan weighs less than 400#, and additional
calculations are not required for this equipment per ASCE7-16 Chapter 13.
Quidel Rutherford LYO
Plan Check Responses
11/13/2024 Page 1 of 1
vnceot ~lectrical §vlutitJn§~ Inc.
November 20, 2024
City of Carlsbad
Community Development Department -Building Division
Attention: Plans Examiner
Subject:
Dear examiner,
Tenant Improvement to lab areas and mezzanine
2285 Rutherford Rd., Carlsbad CA
PCIS #CBC2024-0334 / 24-018-959
CES Project Number: 189-010
Thank you for taking the time to review our plan submittal regarding the subject project
indicated above. Below are my responses to your comments:
ISSUE E1 RESPONSE
a) See Sheet E210 -All lighting in this facility is on an emergency back up generator.
b) See Sheet E210 -Exit sign added at door leading to corridor.
If you have any questions, please do not hesitate to call and discuss.
Sincerely, ,4
Robert Aarsleff
Principal
Concept Electrical Solutions, Inc.
phone: 858.449.5732 I fax: 858.679.0611 I 14427 Elmport Lane, Poway, CA 92064
Robert.aarsleff@conceptelectricalsolutions.com website: conceptelectricalsoiutions.com
3131 Camino Del Rio North, Suite 1080 San Diego, CA 92108 619.521.8500 kpff.com
Quidel Rutherford L YO
Structural Calculations
Plan Check Resubmittal
KPFF Project #2400108
CITY
Calculation Index
Job: Quidel Rutherford L YO KPFFJob No 2400108
Address: 2285 Rutherford Road, Carlsbad, CA 92008
(These calculations apply to the job at this address only)
Revision No. 1
Item: Sheet: REVO REV 1
Existing Slab Evaluation Al-A3 Al -A3
Equipment Anchorage Design Bl -B17 Bl -B17
Index page 1 of 1
3131 Camino Del Rio North. Suite 1080 San Diego, CA 92108 619.521.8500 kpff.com
Quidel Rutherford L YO
Existing Slab Evaluation
3131 Camino Del Rio N
Suite 1080
oroiect Quidel Rutherford LYO
E~g,neers
San Diego, CA 92108
p (619) 521-8500
f (619) 521-8591
www.kpff.com
Existing Slab Evaluation
location
client
Existing drawings general notes:
6 SOIL DESIGN PRESSURE : 2500 F.~.F,
by TB
date 10/18/24
job no. 2400108
7 foR CHARACTER OF SO IL SEE REPORT BY: GEO&OIL"::», INC ,
~e-poFi,T N° W.O. -=,~c, -&P, DATED MAFZ, 14, IC:,8°1,
11 CONCRETE SHALL HAVE A MINIMUM TWENTY-El6HT DAY COMPRES-
SIVE STRENGTH, F'C, AS FOLLOVS MITH A MINIMUM QF 517
LBS OF CEMENT PER CUBIC YARD:
PAD FOOTINGS
CONT• FOOTINGS
6RADE BEAMS
SLAB ON GRADE
COLUMNS
WALLS
8,
Existing slab checked for several worst case equipment types.
Refrigeration skid:
103.4" L x 56.4" W
PLF = 9000#/2 sklds/103.4" = 523plf
523 PLF 523 PLF 523PLF'18" BAR SPACING= 785#
2.o::::o PSI•
2.oOQ PS I•
SOOQ PSI• -:;;zcx::,o PSI•
3000 PSI•
==-oc,o PSI•
t t
,rf-56.4" -+· of
PhiVs = 0.6'60ksi'0.2inA2 = 7.2k capacity at each bar. Rebar ok
for this skid loading for shear check
1·-0·
Vacuum skid:
(2) 33.9" L X 25.4" W
PLF = [1000#/ (25.4")]/2 skids • 237plf
237 PLF 237 PLF 237PLF'18" BAR SPACING = 360#
-··
t t
,rf-33.9· -+·-of
PhiVs • 0.6'60ksi'0.2inA2 = 7.2k capacity at each bar. Rebar ok for this skid loading for shear check
1·-0·
EXISTING SLAB IS #4@18" OC -->As= 0.13inA2/ft
sheet no.
A2
3131 Camino Del Rio N
Suite 1080
San Diego, CA 92108
p (619) 521-8500
f (619) 521-8591
www.kpff.com
Existing Slab Evaluation
Hull140
Check bearing pressure:
92_1" L x 67.7" W x 62" H
oroiect Ou idel Rutherford L YO
location
client
PSF = 20000#/ (92.1 "*67.7") = 462 psf < BEARING PRESSURE, OK
Check existing slab:
1.4DL
1.4*20,000#/2 skids/67_7in = 2482plf/2 either side of skid= 1200plf
Assuming unreinforced 12" width of slab
PhiVc = 0.75*sqrt(f'c)bd = 0.75*sqrt(2000psi)*12"*5" = 2012#
OCR = 1200plf*1 ft /2012# = 0.6 < 1.0
Existing slab ok
bv TB sheet no.
A3
date 10/18/24
job no. 2400108
B1
3131 Camino Del Rio North, Suite 1080 San Diego, CA 92108 619.521.8500 kpff.com
Quidel Rutherford L YO
Equipment Anchorage
3131 Camino Del Rio N
Suite 1080
San Diego, CA 92108
p (619) 521-8500
I (619) 521-8591
www.kpll.com
Equipment Anchorage (5/S800)
ro·ect
location
client
( 4) MIN ½" DIAM HILTI KB-TZ2
CS x 4½" (hef = 2½ ") (ESR
4266). MIN (2) AT EA SIDE OF
EQUIPMENT, ( 4) TOTAL.
uidel Rutherford LYO b TB
date 10 18 24
job no. 2400108
,----------7
I 'V MECH UNIT PER 1 MECH DWG
I
I
I
I
I
I
I
I
I
I
I
EXISTING 5" SLAB
ON GRADE
sheet no.
82
MECHANICAL UNIT ANCHORAGE TO EXISTING SLAB ON GRADE
SCALE: 1 "=1 '-0"
ASCE 7-16
83
Lhe stair shall be designed wiLh !lo corresponding Lo Lhe seismic
force-resisting system but not less Lhan 2 -I /2.
13.6 MECHANICAL AND ELECTRICAL
EXCEPTION: LighL fixLures, lighLed signs, and ceiling fans
not connected to ducts or piping, which are supported by chains
or otherwise suspended from the structure, are not required to
satisfy the seismic force and relative displacement requirements
provided Lhat they meet all of the following criteria:
COMPONENTS
13.6.1 General. Mechanical and electrical components and
Lheir supports shall satisfy Lhe requirements of this section.
The aLLachment of mechanical and electrical components and
Lheir supports Lo Lhe structure shall meet Lhe requirements of
Section 13.4. Appropriate coefficients shall be selected from
Table 13.6-1.
I. The design load for such items shall be equal to 1.4 times
the operating weight acting down with a simultaneous
horizontal load equal to 1.4 times the operating weight.
The horizontal load shall be applied in Lhe direction that
results in the most critical loading for the design.
2. Seismic interaction effects shall be considered in accor-
dance with Section 13.2.3.
Table 13.6-1 Seismic Coefficients for Mechanical and Electrical Components
Component•
MECHANICAL AND ELECTRICAL COMPONENTS
Air-side HV ACR, fans, air handlers, air conditioning units, cabinel heaters, air distribution boxes, and other mechanical components 2½
constructed of sheel metal framing
Wet-side HVACR, boilers, furnaces, atmospheric tanks and bins, chillers, waler heaters, heat exchangers, evaporators, air
separators, manufacturing or process equipment, and other mechanical components constructed of high-defonnability materials
Air coolers (fin fans), air-cooled heal exchangers, condensing units, dry coolers, remote radiators and other mechanical 2½
components elevated on integral structural steel or sheet metal supports
Engines, turbines, pumps, compressors, and pressure vessels not supported on skirts and not within the scope of Chapter 15
Skirt-supported pressure vessels not within the scope of Chapler 15 2½
Elevator and escalator components I
Generators, batteries, inverters, motors, transformer.., and other electrical components constructed of high-deformability materials I
Motor control centers, panel boards, switch gear, instrumentation cabinets, and other components constructed of sheet metal framing 2½
Communication equipment, computers, instrumen1a1ion, and controls
Roof-mounted stacks, cooling and electrical towers laterally braced below their center of mass 2½
Roof-mounted stacks, cooling and electrical towers laterally braced above their center of mass I
Lighting fixtures
Other mechanical or electrical com onents
VIBRA Tl ON-ISOLA TED COMPONENTS AND SYSTEMS
Components and systems isolated using neoprene elements and neoprene isolated floors with built-in or separate elastomeric snubbing 2½
devices or resilienl perimeter stops
Spring-isolated components and systems and vibration-isolated floors closely restrained using built-in or separate elastomcric 2V2
snubbing devices or resilient perimeter stops
Internally isolated components and systems 2½
Suspended vibration-isolated equipment including in-line duel devices and suspended internally isolated components 2½
DISTRIBUTION SYSTEMS
Piping in accordance with ASME 831 (200 I, 2002, 2008, and 20 I 0), including in-line components with joints made by welding or 2½
brazing
Piping in accordance with ASME 831, including in-line components, constructed of high-or limited-defonnability materials, with 2½
joinls made by threading, bonding, compression couplings, or grooved couplings
Piping and tubing not in accordance with ASME 831, including in-line components, constructed of high-deforrnability materials, 2V2
with joints made by welding or brazing
Piping and lubing nol in accordance with ASME 8 31, including in-line components, constructed of high-or limited-deformability 2½
materials, with joints made by threading, bonding, compression couplings, or grooved couplings
Piping and tubing constructed of Jow-defom1ability materials, such as cast iron, glass, and nonductilc plaslics 2½
Ductwork, including in-line components, constructed of high-deformabili1y materials, with joints made by welding or brazing 2½
Ductwork, including in-line components, constructed of high-or limited-deforrnability materials with joints made by means other 2½
than welding or brazing
Ductwork, including in-line componen1s, constructed of low-deformability materials, such as cast iron, glass, and nonduc1ile 2½
plastics
Electrical conduit and cable trays 2½
Bus ducts
Plumbing I
Pneumatic tube transport systems 2½
R• , o,•
6 2
2½ 2
3 IV2
2½ 2
2V2 2
2½ 2
2½ 2
6 2
2½ 2
3 2
2½ 2
I½ 2
I½ 2
2½ 2
2 2
2 2
2½ 2
12 2
6 2
9 2
4½ 2
3 2
9 2
6 2
3 2
6 2
2½ 2
2V2 2
6 2
• A lower value for ap is permitted where justified by detailed dynamic analyses. The value for aP shall not be less than I. The value of aP equal to I is for rigid
components and rigidly attached components. The value of aP equal to 2½ is for flexible components and flexibly attached components.
bComponents mounted on vibration isola1ors shall have a bumper restrain! or snubber in each horizon1al direction. The design force shall be taken as 2FP if the
nominal clearance (air gap) between the equipment support frame and restraint is greater than 0.25 in. (6 mm). If the nominal clearance specified on the
construction documents is not greater than 0.25 in. (6 mm), the design force is pennitted to be taken as FP"
<overstrength as required for anchorage to concrete and masonry. See Sec1ion 12.4.3 for seismic load effects including overstrength.
Minimum Design Loads and Associated Criteria for Buildings and Other Structures 129
l (111111 (111111 3131 Camino Del Rio N
Suite 1080
oroiect Ouidel Rutherford LYO by
~ U ■■I I
■ 1 Consulting
Engu1eers
San Diego, CA 92108
p (619) 521·8500
f (619) 521·8591
www.kpff.com
Equipment Anchorage
13.3.1 Seismic Design Force
location
client
13.3.1.1 Horizontal Force. The horizontal seismic design force
(Fp) shall be applied at the component's center of gravity and
distributed relative to the component's mass distribution and
shall be determined in accordance with Eq. (13.3-1):
0.4apSosWp ( z)
Fp = G:) I + 2,; (13.3-1)
F P is not required to be taken as greater than
F P = l.6S0sl P W P (13.3-2)
date
job no.
0.4*1 .0*0.932Wp (1 + 2*0)/(1.5/1.0) =
0.249Wp
1.6*0.932*1.0Wp = 1.49Wp
sheet no.
B4
and F P shall not be taken as less than
F P =0.3S0sl pWp (13.3-3) 0.3*0.932*1.0Wp = 0.28Wp <--GOVERNS
ap = 1.0
Rp = 1.5
Omega= 2.0
Sds = 0.932g
Ip = 1.0
Ev = 0.2Sds*Wp = 0.2*0.932Wp = 0.19Wp
7. 0.9D-Ev +Eh
For STOKES 220 (20k equipment):
Overturning = 0.28*20,000*73" high/64" spacing between anchors/2 anchors = 3189#
0.9D = 0.9*20,000#/4 anchors = 4500#
Ev = 0.19*20,000#/4 anchors = 932#
4500# -3189# -932# = 378# compression --> in Hilti no tension is applied
Sh ear = 2.0*0.28*20,000#/4 anchors = 2800# (includes omega)
Equipment Anchorage --.... ..-HaxwtlcM-(1) Hinwew,t(f) l lftlth (In) Wldtll (In) HeW11 (in) IOI anchon Olert~ 0.90
St0ktt220Hain~ 20000 15000 .. .. 1 .. • 3119 ....
Stotes 220 Condenslnc Charntlef 10000 .... 104 80 .. • 1111 22>0
St0kts220Rdf_,,c,ontk,d l ,000 10000 120 71 110 . 15Sf 337S
LY02 7500 7500 132 .. .., . 784 1681
HUil 1'0 Ftetlt 0rytt' ¥tSSel 20000 20000 105 73 12 . 1250 ....
HUil 140 RdrtCetltion Mid ........ 111 .. 100 • 1210 20:ZS
Hull 140YKUUmtkid 2200 2200 73 34 100 . 513 ....
$totes 220 YKIA.Wn ltid 2200 ---2200 _ 111 76 100 • 214 ....
"'
• 11 CompJH'60n, • rll tensk>ft
lnduoeomeplfvatuelSnea
o.90-et-En Tention tot ancnor
932 379 ... ...
350
932 ...
103
103
...
1117 ....
2312
396
·120
179
• ts comprusk)n, • b tension --~ omeaa Ir nut is nti
°"""""" 0.90 "' 0.-TtntiOnfOt~
379 2392 337S ... ... ... 719 1350 210 351
1117 um 22>0 ... 745 .... ,... 1681 350 ....
2312 1250 .... 932 2312
396 1210 202S ... 311
-735 513 .... 103 ·120
179 214 ... 103 179
HIL Tl IS CHECKED FOR
WORST CASE COMBINATION
OF TENSION AND SHEAR
TwtMOatotMChcw{mu) ...
85
,,,..,,1nc10fMJ,I)
C12Bl
1· = f f 5 • • ----------------------Hilti PROFIS Engineering 3.1.4
www.hilti.com
Company:
Address:
Phone I Fax:
Design:
Fastening point:
Specifier•s comments:
1 Input data
Anchor type and diameter:
Item number:
Specification text:
Effective embedment depth:
Material:
Evaluation Service Report:
Page:
Specifier:
I
Concrete -Oct 9, 2024
Kwik Bolt TZ2 -CS 1/2 (2 1/2) hnom3
2210255 KB-TZ2 1/2x4 1/2
Hilti KB-TZ2 stud anchor with 3 in embedment,
1/2 (2 1/2) hnom3, Carbon steel, installation
per ESR-4266
h01,ac1 = 2.500 in., hnom = 3.000 in.
Carbon Steel
ESR-4266
E-Mail:
Date:
86
10/17/2024
Issued I Valid:
Proof:
12/1/2023 112/1/2025
Design Method ACI 318-19 / Mech
2,500psi CONCRETE STRENGTH IS REASONABLE
EXPECTED STRENGTH FOR THIS SLAB USING
ENGINEERING JUDGMENT Stand-off installation:
Anchor plateR:
Profile:
Base material:
Installation:
Reinforcement:
Seismic loads (cat. C, D, E, or F}
0.500 in.; (Recommended plate thickness: not calculated}
no profile
cracked concrete, 2500, fc' = 2,500 psi; h = 5.000 in.
Hammer drilled hole, Installation condition: Dry
tension: not present, shear: not present; no supplemental splitting reinforcement present
edge reinforcement: none or < No. 4 bar
Tension load: yes (17.10.5.3 (d})
Shear load: yes (17.10.6.3 (c))
R -The anchor calculation is based on a rigid anchor plate assumption.
Geometry [in.] & Loading [lb, in.lb]
X
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademarl< or Hilti AG, Schaan
1·:115.-1
Hilti PROFIS Engineering 3.1.4
www.hilti.com
Company:
Address:
Phone I Fax:
Design:
Fastening point:
1.1 Design results
Case
I
Concrete -Oct 9, 2024
Description
Combination 1
2 Load case/Resulting anchor forces
Anchor reactions [lb]
Tension force:(+ Tension, -Compression)
Anchor Tension force Shear force
735 2,796
Max. concrete compressive strain: -[%o)
Max. concrete compressive stress: -[psi)
Resulting tension force in (x/y)=(0.000/0.000): 735 [lb)
Resulting compression force in (x/y}=(-/-}: 0 [lb)
Shear force x
2,796
Page:
Specifier:
E-Mail:
Date:
Forces [lb)/ Moments [in.lb)
N = 735; V, = 2,796; Vy= 0;
M, = 0; My = 0; M, = 0;
Shear force y
0
Anchor forces are calculated based on the assumption of a rigid anchor plate.
3 Tension load
Load Nu• [lb] Capacity ♦ N0 [lb]
Steel Strength• 735 8,433
Pullout Strength* N/A N/A
Concrete Breakout Failure•• 735 2,023
• highest loaded anchor ••anchor group (anchors in tension}
lnpot data end results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademar1< of Hilti AG, Schaan
87
2
10/17/2024
Seismic Max. Util. Anchor [%)
yes 65
V
Tension
Utilization PN = Nu.I♦ N" Status
9 OK
N/A N/A
37 OK
2
•· = i i S ~ • ----------------------Hilti PROFIS Engineering 3.1 .4
www.hilti.com
Company:
Address:
Phone I Fax: I
Design: Concrete• Oct 9, 2024
Fastening point:
3.1 Steel Strength
N.. = ESR value
♦ N .. ~ Nua
refer to ICC-ES ESR-4266
ACI 318-19 Table 17.5.2
Variables
A..N [in.1
0.10
Calculations
N .. [lb)
11,244
Results
N .. [lb)
11,244
futa [psi]
114,004
+ steel
0.750
3.2 Concrete Breakout Failure
-(ANc) Neb -ANGO lj/ ed.N lj/ c,N lj/ cp,N Nb
♦ Neb~ Nu•
♦ nonductile
1.000
~ see ACI 318-19, Section 17.6.2.1, Fig. R 17.6.2.1(b)
~ = 9 h!,
lj/ ed,N = 0. 7 + 0.3 ( ~.•Sh:J !5: 1.0
lj/ = MAX(ca,min 1.5h•') 1.0
cp,N Cac , Cac ~
. /7 1.5 Nb = kc ).. 8 "lfc h01
Variables
h81 [in.] c, min [in.] lj/ c,N
2.500 .. 1.000
Calculations
~c[in.2) ~[in.2] lj/ ed,N
56.25 56.25 1.000
Results
Neb [lb) + c:oncrele 4tae11m~
4,150 0.650 0.750
Page:
Specifier:
E-Mail:
Date:
♦ N18 [lb) Nua [lb)
8,433 735
ACI 318-19 Eq. (17.6.2.1a)
ACI 318-19 Table 17.5.2
ACI 318-19 Eq. (17.6.2.1.4)
ACI 318-19 Eq. (17.6.2.4.1b)
ACI 318-19 Eq. (17.6.2.6.1b)
ACI 318-19 Eq. (17.6.2.2.1)
cac [in.] kc
6.750 21
lj/ cp,N Nb [lb]
1.000 4,150
♦ noodudlle ♦ Neb [lb)
1.000 2,023
Input data and results must be checked tor conformity with the existing conditions and for plausibiityl
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademarl< or Hilti AG, Schaan
1.000
735
B8
3
10/17/2024
( [psi]
2,500
3
•·=ii S -i Hiltl PROFIS Engineering 3.1.4
www.hllti.com
Company:
Address:
Phone I Fax: I
Design: Concrete -Oct 9, 2024
Fastening point:
4 Shear load
Load Vu• [lb]
Steel Strength• 2,796
Steel failure (with lever arm)' N/A
Pryout Strength .. 2,796
Concrete edge failure in direction •• N/A
• highest loaded anchor .. anchor group (relevant anchors)
4.1 Steel Strength
V u .eq = ESR value
4' v ,1ee1 ~ v u.
Variables
A..v [in .1
0.10
Calculations
V11,09 (lb)
6,878
Results
v .. ,09 (lb)
6,878
refer to ICC-ES ESR-4266
ACI 318-19 Table 17.5.2
fu1e [psi]
114,004 1.000
4' nondudile
0.650 1.000
4, V11_09 (lb)
4,471
Input data and results must be checked for conformity with the existing conditions and for plausibility!
Page:
Specifier:
E-Mail:
Date:
Capacity ♦ V" [lb]
4,471
N/A
5,811
N/A
2,796
PROFIS Engineering ( c) 2003-2024 Hiltl AG, FL-9494 Schaan Hilti is a registered Trademar1< of Hilti AG, Schaan
89
4
10/17/2024
Utilization Pv = V uat+ V n Status
63 OK
N/A N/A
49 OK
N/A N/A
4
1· = i i 5 • • ----------------------Hilti PROFIS Engineering 3.1.4
www.hilti.com
Company:
Address:
Phone I Fax: I
Design: Concrete -Oct 9, 2024
Fastening point:
4.2 Pryout Strength
V cp = kcp [ (.:;:) lj/ ed,N lj/ c,N lj/ cp,N Nb ]
cp vcp ~ v..,.
~ see ACI 318-19, Section 17.6.2.1, Fig. R 17.6.2.1(b)
~ = 9 h!,
lj/ ed,N = 0.7 + 0.3 ( ~.•s~:,) $ 1.0
'V = MAX(c• min 1.5h•') 1.0 cp,N Cac • Cac S
. I' 1.5 Nb = kc A • -•,lfc h01
Variables
kcp h., [in.] C8 min [in.]
2 2.500 ..
cac [in.] kc "-•
6.750 21 1.000
Calculations
~c [in.2] ~[in.2] lj/ ed,N
56.25 56.25 1.000
Results
cp ooncr•t• cp seosmlc
8,301 0.700 1.000
Page:
Specifier:
E-Mail:
Date:
ACI 318-19 Eq. (17.7.3.1a)
ACI 318-19 Table 17.5.2
ACI 318-19 Eq. (17.6.2.1.4)
ACI 318-19 Eq. (17.6.2.4.1b)
ACI 318-19 Eq. (17.6.2.6.1b)
ACI 318-19 Eq. (17.6.2.2.1)
lj/ c,N
1.000
fc [psi]
2,500
lj/ cp,N Nb [lb)
1.000 4,1 50
cp nonductlle cp Vw [lb)
1.000 5,811
5 Combined tension and shear loads, per ACI 318-19 section 17.8
Utilization ~N v [%) Status
0.363 0.625 5/3 65 OK
Input data and results must be checked kx conformily with the existing conditions and for plausibililyl
PROFIS Engineering ( c) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademarl< of Hilti AG. Schaan
Vua [lb]
2,796
810
5
10/17/2024
5
•·=iiS~• 811
Hilti PROFIS Engineering 3.1.4
www.hilti.com
Company: Page: 6
Address: Specifier:
Phone I Fax: I E-Mail:
Design: Concrete -Oct 9, 2024 Date: 10/17/2024
Fastening point:
6 Warnings
The anchor design methods in PROFIS Engineering require rigid anchor plates per current regulations (AS 5216:2021 , ETAG 001/Annex C,
EOTA TR029 etc.). This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered -the
anchor plate is assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Engineering calculates
the minimum required anchor plate thickness with CBFEM to limit the stress of the anchor plate based on the assumptions explained above. The
proof if the rigid anchor plate assumption is valid is not carried out by PROFIS Engineering. Input data and results must be checked for
agreement with the existing conditions and for plausibility!
Condition A applies where the potential concrete failure surfaces are crossed by supplementary reinforcement proportioned to tie the potential
concrete failure prism into the structural member. Condition B applies where such supplementary reinforcement is not provided, or where pullout
or pryout strength governs.
Refer to the manufacturer's product literature for cleaning and installation instructions.
For additional information about ACI 318 strength design provisions, please go to https://submittals.us.hilti.com/PROFISAnchorDesignGuide/
"An anchor design approach for structures assigned to Seismic Design Category C, D, E or Fis given in ACI 318-19, Chapter 17, Section
17.10.5.3 (a) that requires the governing design strength of an anchor or group of anchors be limited by ductile steel failure. If this is NOT the
case, the connection design (tension) shall satisfy the provisions of Section 17.10.5.3 (b), Section 17.10.5.3 (c), or Section 17.10.5.3 (d). The
connection design (shear) shall satisfy the provisions of Section 17.10.6.3 (a), Section 17.10.6.3 (b}, or Section 17.10.6.3 (c)."
Section 17.10.5.3 (b) / Section 17.10.6.3 (a) require the attachment the anchors are connecting to the structure be designed to undergo ductile
yielding at a load level corresponding to anchor forces no greater than the controlling design strength. Section 17.10.5.3 (c) / Section 17.10.6.3
(b) waive the ductility requirements and require the anchors to be designed for the maximum tension / shear that can be transmitted to the
anchors by a non-yielding attachment. Section 17.10.5.3 (d) / Section 17.10.6.3 (c) waive the ductility requirements and require the design
strength of the anchors to equal or exceed the maximum tension I shear obtained from design load combinations that include E, with E increased
by co0.
Hilti post-installed anchors shall be installed in accordance with the Hilti Manufacturer's Printed Installation Instructions (MPII}. Reference ACI
318-19, Section 26.7.
Fastening meets the design criteria!
Input data and results must be checked for confom,ity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilli AG, FL-9494 Schaan Hilti is a registered Trademark of HilU AG, Schaan
6
,-:,,s., 812
Hilti PROFIS Engineering 3.1.4
www.hilti.com
Company: Page: 7
Address: Specifier:
Phone I Fax: I E-Mail:
Design: Concrete -Oct 9, 2024 Date: 10/17/2024
Fastening point:
7 Installation data
Profile: no profile
Hole diameter in the fixture: df = 0.562 in.
Plate thickness (input): 0.500 in.
Recommended plate thickness: not calculated
Drilling method: Hammer drilled
Cleaning: Manual cleaning of the drilled hole according to instructions for use is
required.
Anchor type and diameter: Kwik Bolt TZ2 -CS 1/2 (2 1/2)
hnom3
Item number: 2210255 KB-TZ2 1/2x4 1/2
Maximum installation torque: 602 in.lb
Hole diameter in the base material: 0.500 in.
Hole depth in the base material: 3.250 in.
Minimum thickness of the base material: 5.000 in.
Hilti KB-TZ2 stud anchor with 3 in embedment, 1/2 (2 1/2) hnom3, Carbon steel, installation per ESR-4266
7.1 Recommended accessories
Drilling
Suitable Rotary Hammer
• Properly sized drill bit
Coordinates Anchor [in.]
Anchor X y
0.000 0.000
Cleaning
• Manual blow-out pump
h y
6.000
e 1
6.000
Input data and results must be checked for conformity with the existing conditions and for plausibility!
6.000
6.000
PROFIS Engineering ( c) 2003-2024 Hilli AG, FL-9494 Schaan Hilti is a regislered Trademarl< of Hilti AG, Schaan
0 0 0 r.o
0 0 0 r.o
Setting
Torque controlled cordless impact tool
• Torque wrench
Hammer
0 0 0 r.o
~ ...
X
0 0 0 r.o
7
1·:115;.1 813
Hllti PROFIS Engineering 3.1.4
www.hilti.com
Company: Page: 8
Address: Specifier:
Phone I Fax: I E-Mail:
Design: Concrete -Oct 9, 2024 Date: 10/17/2024
Fastening point:
8 Remarks; Your Cooperation Duties
Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles. formulas and
security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be strictly
complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted prior to using
the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the data you put in.
Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be put in by you.
Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly with regard to
compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an aid to interpret norms
and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or suitability for a specific
application.
You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for the
regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do not use
the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software in each
case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or damaged data
or programs, arising from a culpable breach of duty by you.
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c) 2003-2024 Hilti AG, FL-9494 Schaan Hilti Is a registered Trademarl< of Hilti AG, Schaan
8
Engineers
3131 Camino Del Rio N
Suite 1080
San Diego, CA 92108
p (619) S21-8S00
f (619) 521-8591
www.kpff.com
uidel Rutherford LYO
location
client
Fan Coil Equipment Anchorage (15/S800)
P1000 UNISTRUT
CROSS BRACE
EA. SIDE TYP
" HILTI KH-EZ
w/ 2" EFF.
EMBED (ESR-3027)
MAX 600#
b TB
date 10 18 24
job no. 2400108
P1000 UNISTRUT
TYP. AS SHOWN
~
1. 4 BRACES TOTAL (2 IN EACH ORTHOGONAL DIRECTION).
2. BRACES MAY BE ROTATED 1 ao·
3. WHERE CONCRETE WALL INTERFERES WITH BRACE, CONNECT TO
WALL OR EXTEND BOTTOM UNISTRUT TO WALL AND BOLT WITH
¾" EXPANSION ANCHOR.
sheet no.
814
sheet no.
3131 Camino Del Rio N
Suite 1080
proiect Quidel Rutherford LYO bv TB t--J--'-------'-'=~~~.C...----------'-=-------t815
E ~111eers
San Diego, CA 92108
p (619) 521-8500
f (619) 521-8591
www.kplf.com
location
client
Mech units anchorage design: (per ASCE 7-16, chapter 13.3)
CEILING MOUNTED UNITS (MAXIMUM WEIGHT :600 LBS)
SEISMIC FORCE: (per ASCE 7-16, chapter 13.3)
W=600 lbs
z/h=1
ap=2.5 ,Rp=6.0, Ip= ,Op=2, Sds=0.932
Fp=0.4*2.5*0.932*Wp/(6/1 )*(1 +2*1 )=0.466Wp=0.466*600=280 lbs, LRFD
Fpmin=0.3*0.932*1 *Wp=0.29Wp < Fp, OK
Fpmax=1 .6*0.932*1 *Wp=1.52Wp > Fp, OK
Ev = 0.2SDSWp = 0.2*0.932*600# = 111 #
USE 12GA HANGER WIRE, OK IN TENSION
CHECK ELEMENTS FOR LC=(1 +0.2*0.7*Sds)D+0.7E=1.13D+0.7E
CHECK P1000 CAPACITY FOR UNIFORM LOAD
date 10/18/24
job no. 2400108
MAXIMUM ALLOWABLE UNIFORM LOAD=680*0.66*1 =449 LBS> (1 .13*600/2+0.7*111#/2) =377
LBS, OK
THREADED ROD CAPACITY: (PER AISC, CHAPTER J, eq. J3-1)
3/8"<P THREADED ROD CAPACITY=Fn.An/O=(0.75*58)*0.11 /2=2.4 k > (1.13*600/2+0.7*111#/2)
=377 LBS, OK R., = F,,Ab
IP= 0.75 (LRFD) n = 2.00 (ASD)
THREADED ROD PULL OUT ALLOWABLE CAPACITY=1000 LBS> 377 LBS, OK
sheet no.
f I I • l<Rff 3131 Camino Del Rio N oroiect by 816 Suite 1080
San Diego, CA 92108 location date
p (619) 521-8500
f (619) 521-8591 client job no.
Erglneers www.kpff.com
Mech units anchorage design: (CONT.)
Load and Support Load Deflection
Condition Factor Factor
1. Simple Beam, f :zzzz~~;.~zzzzz:I 1.00 1.00 Uniform Load
2. Simple Beam, I .50 .80 Concentrated Load at Center I t
LATERAL BRACING LOAD REDUCTION CHARTS
Span Single Channel Double Channel
Ft. (m) In. (cm) P1000 P1100 P2000 PJOOO P3300 P4000 P4100 P4400 P4520 P5000 P5500 P1001 P1101 P2001 P3001 P3301 P4001 P4101 P4401 P4521 P5001 P5501
2 (0.61} 24 (61) 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0.98 0.99 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
3 (0.91) 36 (91) 0.94 0.89 0.88 0.96 1.00 0.94 0.98 1.00 1.00 0.85 0.89 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
4 (1 22) 48 (122) 0.88 0.78 0.75 0.91 1.00 0.88 0.94 0.98 1.00 0.70 0.77 1.00 0.98 0.98 1.00 1.00 0.98 1.00 1.00 1.00 0.97 0.98
5 (1.52) 60 (152) 0.82 0.68 0.61 0.88 0.98 0.83 0.91 0.96 1.00 0.55 0.67 0.97 0.93 0.92 0.98 1.00 0.93 0.96 1.00 1.00 0.90 0.93
6 (1.83) 72 (183) 0.78 0.59 0.48 0.84 0.97 0.79 0.89 0.94 0.98 0.44 0.58 0.93 0.87 0.85 0.95 0.97 0.88 0.92 0.97 0.97 0.83 0.87
7 (2.13) 84 (213) 0.75 0.52 0.41 0.82 0.96 0.75 0.86 0.92 0.97 0.38 0.51 0.89 0.82 0.78 0.92 0.95 0.83 0.89 0.95 0.95 0.76 0.81 --
6 (2.44) 96 (244) 0.71 0.47 0.35 0.79 0.94 0.72 0.84 0.91 0.96 0.33 0.46 0.85 0.76 0.71 0.88 0.92 0.79 0.85 0.92 0.92 0.68 0.76
9 (2 74) 108 (274) 0.69 0.43 0.32 0.77 0.93 0.69 0.82 0.89 0.95 0.30 0.42 0.81 0.70 0.64 0.85 0.90 0.74 0.81 0.90 0.90 0.61 0.70
10 (3.05) 120 (305) 0.66 0.40 0.29 0.75 0.92 0.66 0.80 0.87 0.94 0.28 0.40 0.78 0.65 0.57 0.82 0.87 0.69 0.78 0.87 0.87 0.54 0.64
12 (3 66) 144 (366) 0.61 0.36 0.25 0.70 0.89 0.60 0.76 0.84 0.91 0.24 0.36 0.70 0.54 0.45 0.76 0.82 0.60 0.71 0.82 0.83 0.43 0.53 --
P1000 -IIEM LGAllM
Chonnel Allowoolo
Nut Pu--1.,.. Doi.• Slzt. s .. ngtt, ..... FM.N
_....,. __
Channtl Ttv...i G,ugt LI>• ti,.;n Ll>I ""' PNI ---2,500 1,700 '125 ..... -Laod I.Old ....,, . ..,_.. .....
1~•.9 12 lo Ll>I lo Ll>I Ll>I Ll>I 11 12 7/iil 170 24 1,690 0.06 1,690 1,690 1,690
11"·10 12 2.500 1,700 •125 36 1,130 013 1,130 1,130 900
1112 7/iil 170 ~ &50 022 &50 760 500
¾"-11 12 2,500 1,500 '100 1111 680 OJ5 650 ~ l20 11.12 667 135 P1000 2.000 1,500 50 n 560 050 450 340 220
P3000 W-13 12 P4400 IIIO 467 70 14 ~ 0.61 330 250 11111
P4S:K 1,400 1.000 35 96 420 089 250 190 130
PSOOO ~--,. 12 623 445 50 1118 3llO 114 200 150 100 P5500 1.000 800 19 120 340 140 11111 120 10 ¾0 -16 12 445 3/iil 25 144 2.i 2.00 110 10 1111
!lo"· 18 12 800 500 11 161 240 2.n 10 eo 40
3/iil 2 22 15 192 210 3.56 EO 50 NR
600 300 6 ---V.--20 12 216 190 '58 50 40 NR
267 133 8 240 170 562 40 Nfl NR 1,500 1,500 50
oroiect Ouidel Rutherford LYO sheet no.
l<pff 3131 Camino Del Rio N bv TB 817 Suite 1080
date 10/18/24 San Diego, CA 92108 location
p (619) 521-8500
f (619) 521-8591 client job no. 2400108
~ g neers www.kpff.com
Screw Anchor to underside of composite deck (ESR-3027)
TABLE a-HIL Tl KH-EZ I AND KH-EZ E TENSION AND SHEAR DESIGN DATA FOR INSTALLATION IN THE UNDERSIDE OF
CONCRETE-Fl.LED PROFILE STEEL DECK ASSEMBLIES'.0.7
L_,._ I --~ .,_ -NoonlnalAnc:Mr~ .,. .,. ,,. .,.
Head Style -lntomaly (I) Threadod and lnlemaly lnlemelly (I) -and lnlomally
Exlomaly (E) Ttvaaded Ttvoaded Extemaly CE• Ttveaded Ttveaded
Embedment ,,_ in. 11,, 2•1, 1'1, 211, 21,, 1'1, 21/2 1'1, 2½ 211,
(mm) (41) (64) (41) (64) (54) (41) (64) (41) (64) (54)
Minimum Hole Depll, h. In, 2 2'1o 2 211, 23/, 2 21,, 2 211, 2'1,
(mm) (51) 173) (51) 173) 160) 151) 173) 151) 173) 160)
Internal Thread In, . ,. ,, . ,,, .,. .,. ,,,
Dlameler (mm) (8.4) (G.5) (12.7) (8.4) (9,5) (12.7)
Effoctive Embedment in. 1.18 1.92 1.18 1,92 1.54 1.18 1.92 1.18 1.92 1.54
Depth h« (mm) (30) (49) (30) (49) (39) (30) (49) (30) (49) (39)
Pullout R&1istanco. lbl. 1,210 1,875 1,210 1,875 1,720 1,490 1,960 1,490 1,960 2,660
(uncrad<ed
a,nc,eta)'
N,,-,unc," (kN) (5,4) (8 3) (5.4) (8.3) (7.7) (6.6) (8.7) (6.6) (8.7) (11.6)
Pullout Retistanca !bl. 620 830 620 830 I 1.220l 730 975 730 975 1.885
(~ad conctele N,.._., (kN) (2.8) (4.1) (2,8) (4.1) (5.4) (3.2) (◄.3) (3.2) (4.3) (8.4) and selstric loads)'
Sleet Streng1h In v .... lbl 860 1,025 2,380 1,015 1.525 3.650
Shear lkNl (38) 14 6) 110.6) 14.5) (6.11) (16.21
Stool Strength In v .. _,. lbl. 385 875 2.380 \ 445 1.295 3,650
Sheat.Selsmic lkNl 11.7) (3_g) (10.6) (2.0) (5,8) (16.2)
Fo, SI: 1 Inch• 25.4 mm. 1 ft..ft>I • 1.356 N-m. 1 pol• 6.89 kPa, 1 in2 • 645 mm2, 1 lb/In• 0.175 m.
'lna-tlon must c:omplywith Sections 4.1.10 ond 4.3 and£111m..lla, 1112, and .12 ol lh,t r9t)Ofl
'Tha-liltedmustbeUMdlnllCCOtdance\MthSectJon4.1.4ollhisr9t)Ofl 'The vlluN lilled muct be UMd In ICCOfdonce wilh 5aa,on 4.1.A and 4.1 8.2 of this r9t)Ofl
'The vol-Isled must be used lnllCCOtdancewilh Secllon4.1.5 and4.1.8.3ollhil rOj)Ofl.
'The v-lo< #, In laNllon and Iha vaJ-IO<#,, In .._ eon be found In lllal ol lhlo report.
'For the 11.--lnch-diameter (KH-EZ I) al 2•1/ainch nomioat embedment the chatK1er1stJc pullout resiltance for ete eompresstve atrenglhl great• than 3.000
pol may be Increased by mulllplylng Iha value In the too. by (f,13,000/"IO< pol a, (f.12(1.7/"for MPa. 7For Iha 'l,-lncn-dlamelor onc:llOB (KH-EZ I ond KH-EZ E) 111'/a-lnc:h nominal ambedment chlrldonotlc pt.itoot r for conctele CXlfflP(llltvl llrenglhl
greate< lhon 3,000 pol mey be lncrHsed by mlAtlplytng Iha Yolua ~ Iha talJla by (f ,13,000!" for 1)110< (f .no. 7f-' rc, Pa
l
1,000# capacity of rod--> DCR = 1000/1220# = 0.81 < 1.0 OK
ACTUAL MAX POINT LOAD= 1.13*600#/2 RODS+ 0.7*111#/2
RODS*OMEGA = 416# < 1000#
ANCHORAGE IS OK
3131 Camino Del Rio North, Suite 1080 San Diego, CA 92108 619.521.8500 kpff.com
CITY
Quidel Rutherford L YO
Structural Calculations
KPFF Project #2400108
These structural calculations have been prepared by me or under my direction and are
intended to be submitted for plan review. Final calculations will be stamped and signed
by me in accordance with the requirements of the Business and Professional Code of the
state of California pr" r to the issuan o th onstruction permit for this project.
Date 10/18/24 -------
CBC2024-0334
2285 RUTHERFORD RD
Tenant Improvement: QUIDELORTHO: (1218 SF) INTERIOR Tl // NEW
WALLS, CEILINGS // PLUMBING, LIGHT FIXTURES// EQUIPMENT,
FINISHES, STRUCTURAL
2120620800
10/23/2024
CBC2024-0334
Calculation Index
Job: Quidel Rutherford L YO KPFFJob No 2400108
Address: 2285 Rutherford Road, Carlsbad, CA 92008
(These calculations apply to the job at this address only)
Revision No. 0
Item: Sheet:
Existing Slab Evaluation Al -A3
Equipment Anchorage Design Bl -817
Index page 1 of 1
A1
3131 Camino Del Rio North, Suite 1080 San Diego. CA 92108 619.521.8500 kpff.com
Quidel Rutherford L YO
Existing Slab Evaluation
3131 Camino Del Rio N
Suite 1080
proiect Quidel Rutherford LYO by TB
San Diego, CA 92108
p (619) 521-8500
location date 10/18/24
f (619) 521-8591 client job no. 2400108
Eng r www.kpff.com
Existing Slab Evaluation
Existing drawings general notes:
6 SOIL DESIGN PRESSURE: 2&00 F,5,F,
7 foR CHARACTER OF SOIL SEE REPORT BY: GEo&OIL"=>, INC,
~E:flQFZT N° w.o, 4€:>9 -&P, DATED MAFl, 1-4) 198°1,
11 CONCRETE SHALL HAVE A "INl"U" TWENTY-EIGHT DAY CO"PRES-
SIVE STRENGTH1 F1 C1 AS FOLLOWS WITH A "INIMUM OF 517
LBS OF CEMENT PER CUBIC YARD:
PAD FOOTINGS 2COO PSI•
CONT• FOOTINGS 2.ooQ PS I•
GRADE BEA"S '3000 PS I•
SLAB ON GRADE ~ PS I•
COLUMNS 3000 PS I•
WALLS ~o PSI•
-a . ~LAS oN 1,G~APE &tiALL es S'' TH 1e,.;::;. ~/ ♦~ c-> 1e, 0, C, E~. WAY 0\/Efiii=, 2.11 ~D
OYet-z:. ~ M IL, l'--10l&TW~e e,+bp.Ftlf=Fi..,
6A&e &I IALL ee 2..'' ~NO FOFZ A TOTAL
OF~" OF ~ANO BE-LOW "5LA..B.
Existing slab checked for several worst case equipment types.
Refrigeration skid:
103.4" L x 56.4" W
PLF = 9000#/2 skids/103.4" = 523pll
523 PLF 523 PLF
1·-0·
Vacuum skid:
(2) 33.9" L X 25.4" W
523PLF'18" BAR SPACING = 785#
PhiVs = 0.6'60ksi'0.2inA2 = 7.2k capacity at each bar. Rebar ok
for this skid loading for shear check
PLF = [1000#/ (25.4 "))/2 skids -237plf
237 PLF 237 PLF 237PLF'18" BAR SPACING= 360#
PhiVs = 0.6'60ksi'0.2inA2 = 7.2k capacity at each bar. Rebar ok for this skid loading for shear check
1·-0·
EXISTING SLAB IS #4@18" OC -->As= 0.13in"2/ft
sheet no.
A2
3131 Camino Del Rio N
Suite 1080
San Diego, CA 92108
p (619) 521-8500
f (619) 521-8591
E , r www.kpff.com
Existing Slab Evaluation
Hull140
Check bearing pressure:
92.1" L x 67.7" W x 62" H
project Quidel Ruth erford LYO
location
client
PSF = 20000#/ (92.1 "*67.7") = 462 psf < BEARING PRESSURE, OK
Check existing slab:
1.4DL
1.4*20,000#/2 skids/67.7in = 2482plf/2 either side of skid= 1200plf
Assuming unreinforced 12" width of slab
PhiVc = o_75*sqrt(f'c)bd = 0.75*sqrt(2000psi)*12"*5" = 2012#
OCR= 1200plf*1ft/2012# = 0.6 < 1.0
Existing slab ok
by TB
date 10/18/24
sheet no.
A3
job no. 2400108
81
3131 Camino Del Rio North, Suite 1080 San Diego, CA 92108 619.521.8500 kpff.com
Quidel Rutherford l YO
Equipment Anchorage
3131 Camino Del Rio N
Suite 1080
San Diego, CA 92108
p (619) 521-8500
f (619) 521-8591
www.kpff.com
Equipment Anchorage (5/S800)
project Qu idel Rutherford LYO
location
client
,----------7
I I
bv TB
date 10/18/24
job no. 2400108
I Iv MECH UNIT PER
I I MECH DWG I
(4) MIN ½" DIAM HILTI KB-TZ2
CS x 4½" (hef = 2½ ") (ESR
4266). MIN (2) AT EA SIDE OF
EQUIPMENT, (4) TOTAL.
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
1-I J~ r-.. #:--c, .... -:·. : ~
"'jjl I lffiTTTI 11 · I ~i 1 _ .... c...,L
/
EXISTING 5" SLAB
ON GRADE
.. -.1· . .
.:...:..__'
sheet no.
82
:s)~~f~-~,~~~AL UN IT ANCHORAGE TO EXISTING SLAB ON GRADE
ASCE 7-16
B3
the stair shall be designed with no corresponding to the seismic
force-resisting system but not less than 2 -I /2.
13.6 MECHANICAL AND ELECTRICAL
EXCEPTION: Light fixtures, lighted signs, and ceiling fans
not connected to ducts or piping, which are supported by chains
or otherwise suspended from the structure, are not required to
satisfy the seismic force and relative displacement requirements
provided that they meet all of the following criteria:
COMPONENTS
13.6.1 General. Mechanical and electrical components and
their supports shall satisfy the requirements of this section.
The auachment of mechanical and electrical components and
their supports to the structure shall meet the requirements of
Section 13.4. Appropriate coefficients shall be selected from
Table 13.6-1.
I. The design load for such items shall be equal to 1.4 times
the operating weight acting down with a simultaneous
horizontal load equal to l.4 times the operating weight.
The horizontal load shall be applied in the direction that
results in the most critical loading for the design.
2. Seismic interaction effects shall be considered in accor-
dance with Section 13.2.3.
Table 13.6-1 Seismic Coefficients for Mechanical and Electrical Components
Components
MECHANICAL AND ELECTRICAL COMPONENTS
.. ,
Air-side HVACR, fans, air handlers, air conditioning units, cabinet heaters, air distribution boxes, and other mechanical components 2½
constructed of sheet metal framing
Wet-side HVACR, boilers, furnaces, atmospheric tanks and bins, chillers, water heaters. heat exchangers, evaporators, air
separators, manufacturing or process equipment, and other mechanical components constructed of high-defonnability materials
Air coolers (fin fans), air-cooled heat exchangers, condensing units, dry coolers, remote radiators and other mechanical 2½
components elevated on integral structural steel or sheet metal supports
Engines, turbines, pumps, compressors, and pressure vessels not supported on skirts and not within the scope of Chapter 15
Skirt-supported pressure vessels not within the scope of Chapter 15 2½
Elevator and escalator components I
Generators, batteries, inverters, motors, transformers, and other electrical components constructed of high-deformability materials
Motor control centers, panel boards, switch gear, instrumentation cabinets, and other components constructed of sheet metal framing 2½
Communication equipment, computers, instrumentation, and controls I
Roof-mounted stacks, cooling and electrical towers laterally braced below their center of mass 2½
Roof-mounted stacks, cooling and electrical towers laterally braced above their center of mass
Lighting fixtures
Other mechanical or electrical com onents
VTB RA TI ON-ISOLA TED COMPONENTS AND SYSTEMS
Components and systems isolated using neoprene elements and neoprene isolated floors with built-in or separate elastomeric snubbing 2½
devices or resilient perimeter stops
Spring-isolated components and systems and vibration-isolated floors closely restrained using built-in or separate elastomeric 2½
snubbing devices or resilient perimeter stops
Internally isolated components and systems 2½
Suspended vibration-isolated equipment including in-line duct devices and suspended internally isolated components 2½
DISTRIBUTION SYSTEMS
Piping in accordance with ASME 8 31 (200 I, 2002, 2008, and 20 I 0), including in-line components with joints made by welding or 2½
brazing
Piping in accordance with ASME 8 31, including in-line components, constructed of high-or limited-deformability materials, with 2½
joints made by threading, bonding, compression couplings, or grooved couplings
Piping and tubing not in accordance with ASME 831, including in-line components, constrnctecl of high-cleforrnability materials, 2½
with joints made by welding or brazing
Piping and tubing not in accordance with ASME 8 31, including in-line components, constructed of high- or limited-deformability 2½
materials, with joints made by threading, bonding, compression couplings, or grooved couplings
Piping and tubing constructed of low-deformability materials, such as cast iron, glass, and nonductile plastics 2½
Ductwork, including in-line components, constructed of high-deformabiliry materials, with joints made by welding or brazing 2½
Ductwork, including in-line components, constructed of high-or limited-deformability materials with joints made by means other 2½
than welding or brazing
Ductwork. including in-line components, constructed of low-deformability materials, such as cast iron, glass, and nonductile 2V2
plastics
Electrical conduit and cable trays 2V2
Bus ducts I
Plumbing I
Pneumatic tube transport systems 2V2
R• , n• '
6 2
2V2 2
3 I½
2V2 2
2½ 2
2V2 2
21/2 2
6 2
2V2 2
3 2
2V2 2
IV2 2
IV2 2
2½ 2
2 2
2 2
2V2 2
12 2
6 2
9 2
4V2 2
3 2
9 2
6 2
3 2
6 2
2V2 2
2½ 2
6 2
"A lower value for al' is pern1itted where justified by detailed dynamic analyses. The value for aP shall not be less than I. The value of aP equal to I is for rigid
components and rigidly attached components. The value of aP equal to 2V2 is for flexible components and flexibly attached components.
bComponents mounted on vibration isolators shall have a bumper restraint or snubber in each horizontal direction. The design force shall be taken as 2FP if the
nominal clearance (air gap) between the equipment support frame and restraint is greater than 0.25 in. (6 mm). If the nominal clearance specified on the
constrnction documents is not greater than 0.25 in. (6 nun), the design force is permitted 10 be taken as FP.
coverstrength as required for anchorage to concrete and masonry. See Section 12.4.3 for seismic load effects including oversrrength.
Minimum Design Loads and Associated Criteria for Buildings and Other Structures 129
3131 Camino Del Rio N
Suite 1080
project Quidel Rutherford L YO by
Engml'er
San Diego, CA 92108
p (619) 521-8500
f (619) 521·8591
www.kpff.com
Equipment Anchorage
13.3.1 Seismic Design Force
location
client
13.3.l .l Horizontal Force. The horizontal seismic design force
(F1,) shall be applied at the component's center of gravity and
distributed relative to the component's mass distribution and
shall be determined in accordance with Eq. (13.3-1):
_ 0.4aPS0 5W,, ( z)
Fp -G;) I + 2h (13.3-1)
F,, is not required to be taken as greater than
FP=l.6S05/PWP
and F,, shall not be taken as less than
(1 3.3-2)
date
job no.
0.4*1.0*0.932Wp (1 + 2*0)/(1.5/1.0) =
0.249Wp
1.6*0.932*1.0Wp = 1.49Wp
sheet no.
84
F,, = 0.3S05/P w,, (1 3.3-3) 0.3*0.932*1.0Wp = 0.28Wp <--GOVERNS
ap = 1.0
Rp = 1.5
Omega= 2.0
Sds = 0.932g
Ip= 1.0
Ev = 0.2Sds*Wp = 0.2*0.932Wp = 0.19Wp
7. 0.9D-Ev +Eh
For STOKES 220 (20k equipment):
Overturning= 0.28*20,000*73" high/64" spacing between anchors/2 anchors= 3189#
0.90 = 0.9*20,000#/4 anchors = 4500#
Ev = 0.19*20,000#/4 anchors = 932#
4500# -3189# -932# = 378# compression --> in Hilti no tension is applied
Shear = 2.0*0.28*20,000#/4 anchors = 2800# (includes omega)
Equipment Anchorage
.... _. ,.._ H.Mwewitlt) HinMW!t{f) Ltft(th(SII Wknh(in) HeW'lt(ltll tOfanchOrs OwertlMninC 0.tO
5'ote1220HM!Ch¥nbef 20000 15000 .. .. 1 .. • .... ....
StOUI 220 CondtnSlnf c:hambef 10000 .... 104 .. .. • 1111 2250
Stoke$220~irltfaoonskld 15000 10000 120 71 110 • 1.55-9 3375
L't'O2 7SOO 7SOO 132 .. 02 • , .. 1 ...
Hutt 140 F1uze Dryer 'iHsel L 20000 20000 1 .. 73 .. . 1251 ....
Hull 140Rd1padon skid 9000 .... 118 .. 100 . 12.10 202,
Htat 140VxwmMid 2200 2200 73 .. 100 . '13 -Stotes220VKWTisldd 2200 -2200 118 _?6 __ 100 -. ,,. -
"'
• ti COffllN't:Sslon. • Is tension
klcludeOfl\ttllf'lllueisnte
0.90-&-Eh Tentt0ntoranch0f 932 .,. ... ... ... 1117
3'0 ... .,, 2312 ... ...
103 ·120
103 179
• Is COfnpfeSJIOn. • Is 1MSion
minwei&f'lt lndude onva, ii value 19 nee -.._ 0.90 "' 0 90-Ev-Eh T enlicn for anchOf
379 ,,., 33,S ... , .. ... 719 13'0 ,.. 351
1117 1039 2250 ... , .. ... 714 1 ... ... . ..
2312 12'e .... 932 2312
396 1210 202> ,nt ...
.735 "' ... 103 ·120
179 ,,. -103 ,,.
HIL Tl IS CHECKED FOR
WORST CASE COMBINATION
OF TENSION AND SHEAR
TenNOn '°' MCIIOf (mu.) ,..
85
SMM(inctomettl
CZ!Bl
1:115,.1
Hilti PROFIS Engineering 3.1.4
www.hilti.com
Company: Page:
Address: Specifier:
Phone I Fax: E-Mail:
Design: Concrete• Oct 9, 2024 Date:
Fastening point:
Specifier's comments:
1 Input data
Anchor type and diameter:
Item number:
Specification text:
Effective embedment depth:
Material:
Evaluation Service Report:
Kwik Bolt TZ2 • CS 1/2 (2 1/2) hnom3
2210255 KB-TZ2 1/2x4 1/2
Hilti KB-TZ2 stud anchor with 3 in embedment,
1/2 (2 1/2) hnom3, Carbon steel, installation
per ESR-4266
h01.ect = 2.500 in., hnom = 3.000 in.
Carbon Steel
ESR-4266
86
10/17/2024
Issued I Valid:
Proof:
12/1/202311211/2025
Design Method ACI 318-19 / Mech
2,500psi CONCRETE STRENGTH IS REASONABLE
EXPECTED STRENGTH FOR THIS SLAB USING
ENGINEERING JUDGMENT Stand-off installation:
Anchor plateR:
Profile:
Base material:
Installation:
Reinforcement:
Seismic loads (cat. C, D, E, or F)
0.500 in.: (Recommended plate thickness: not calculated)
no profile
cracked concrete, 2500, fc' = 2,500 psi; h = 5.000 in.
Hammer drilled hole, Installation condition: Dry
tension: not present, shear: not present; no supplemental splitting reinforcement present
edge reinforcement: none or < No. 4 bar
Tension load: yes (17.10.5.3 (d))
Shear load: yes (17.10.6.3 (c))
R -The anchor calculation is based on a rigid anchor plate assumption.
Geometry [in.) & Loading [lb, in.lb)
Input data and resuhs must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademar1< of Hiltl AG, Schaan
•=iiS~• Hilti PROFIS Engineering 3.1.4
www.hiltl.com
Company:
Address:
Phone I Fax: I Design: Concrete -Oct 9, 2024
Fastening point:
1.1 Design results
Case Description
Combination 1
2 Load case/Resulting anchor forces
Anchor reactions [lb]
Tension force: (+Tension, -Compression)
Anchor Tension force Shear force
735 2,796
Max. concrete compressive strain: -(%o]
Max. concrete compressive stress: -[psi]
Resulting tension force in (x/y)=(0.000/0.000): 735 [lb)
Resulting compression force in (x/y)=(-/-): O [lb]
Shear force x
2.796
Page:
Specifier:
E-Mail:
Date:
Forces [lb]/ Moments [in.lb]
N = 735; Vx = 2,796; Vy= 0;
MX = 0; My = 0; M, = 0;
Shear force y
0
Anchor forces are calculated based on the assumption of a rigid anchor plate.
3 Tension load
Load Nu• [lb) Capacity ♦ N0 [lb)
Steel Strength• 735 8,433
Pullout Strength• N/A N/A
Concrete Breakout Failure .. 735 2,023
• highest loaded anchor .. anchor group (anchors in tension)
Input data and resuhs must be checked fo, confo,mity with the existing conditions and for plausibility!
PROFIS Engineering ( c) 2003-2024 Hilti AG, FL-9494 Schaan Hihi Is a registered Trademarl< of HilU AG. Schaan
Seismic
yes
Tension
Utilization 13N = Nua/♦ N.
9
N/A
37
B7
2
10/17/2024
Max. Util. Anchor[%]
65
• y ..
Status
OK
N/A
OK
2
r: i i S ~ • ----------------------Hilti PROFIS Engineering 3.1.4
www.hilti.com
Company:
Address:
Phone I Fax: I
Design: Concrete -Oct 9, 2024
Fastening point:
3.1 Steel Strength
N.. = ESR value
q> N .. ~ Nua
refer to ICC-ES ESR-4266
ACI 318-19 Table 17.5.2
Variables
A_.N ~n.1
0.10
Calculations
N .. [lb]
11,244
Results
N18 [lb)
11,244
futa [psi]
114,004
4> steel
0.750
3.2 Concrete Breakout Failure
Neb = (t ) IV od,N IV c,N IV cp,N Nb
4> Neb~ Nu•
4> nonductile
1.000
~c see ACI 318-19, Section 17.6.2.1, Fig. R 17.6.2.1(b)
~c0 = 9 h!,
IV ed,N = 0.7 + 0.3 c c.•s~:J S 1.0
= MAX(c•min 1.5h•') 1.0 IV cp,N cac ' cae :5
. /7 1.5 Nb = kc A • Vfc h01
Variables
h8,[in.] c. m1n [in.) IV c.N
2.500 00 1.000
Calculations
ANc [in.2] ANGO [in.2) IV ed,N
56.25 56.25 1.000
Results
Neb [lb] 4> conc,oto 4>solsmlc
4,150 0.650 0.750
Page:
Specifier:
E-Mail:
Date:
4> N .. [lb] Nua [lb]
8,433 735
ACI 318-19 Eq. (17.6.2.1a)
ACI 318-19 Table 17.5.2
ACI 318-19 Eq. (17.6.2.1.4)
ACI 318-19 Eq. (17.6.2.4.1b)
ACI 318-19 Eq. (17.6.2.6.1b)
ACI 318-19 Eq. (17.6.2.2.1)
cac [in.] kc
6.750 21
IV cp,N Nb [lb]
1.000 4,150
4> nonductilo 4> Neb [lb]
1.000 2,023
Input data and results must be checked fo, confo,mity with the existing conditions and for plausibility!
PROFIS Engineering ( c) 2003-2024 Hilti AG, FL-9494 Schaan Hiltl Is a registered Trademark or Hiltl AG, Schaan
1.000
735
88
3
10/17/2024
( [psi]
2,500
3
C: i i S • • ----------------------Hilti PROFIS Engineering 3.1.4
www.hllti.com
Company:
Address:
Phone I Fax: I
Design: Concrete -Oct 9, 2024
Fastening point:
4 Shear load
Load Vu• [lb]
Steel Strength• 2,796
Steel failure (with lever arm)* NIA
Pryout Strength** 2,796
Concrete edge failure in direction .. NIA
• highest loaded anchor ••anchor group (relevant anchors)
4.1 Steel Strength
V oa.eq = ESR value
$ v.tee1 ~ v u.
Variables
A.,v [in.2]
0.10
Calculations
v .... [lb]
6,878
Results
v .. ,eg (lb)
6,878
refer to ICC-ES ESR-4266
ACI 318-19 Table 17.5.2
futa [psi]
114,004 1.000
$ steel $nonductile
0.650 1.000
$ V,a,eq (lb]
4,471
Input data and results must be checked for confom,ity with the existing conditions and for plausibility!
Page:
Specifier:
E-Mail:
Date:
Capacity ♦ V0 [lb]
4,471
NIA
5,811
NIA
2,796
PROFIS Engineering ( c) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademar1< of Hilti AG, Schaan
Utilization 13v = V u.l♦ v.
63
NIA
49
NIA
B9
4
1011712024
Status
OK
NIA
OK
NIA
4
,:,,s.,
Hilti PROFIS Engineering 3.1 .4
www.hilti.com
Company:
Address:
Phone I Fax: I
Design: Concrete -Oct 9, 2024
Fastening point:
4.2 Pryout Strength
V cp = kcp [ (:;:) 'I' td,N 'I' c,N 'I' cp,N Nb ]
<I> v cp ~ v u.
~c see ACI 318-19, Section 17.6.2.1, Fig. R 17.6.2.1(b)
~co = 9 h!,
lj/ ed,N = 0.7 + 0.3 ( ~-•5~:,) S 1.0
= MAX(c•.min, 1.5h•') ,, 1.0 lj/ cp,N Cac Cac .:,
JI 1.s Nb = kc A 8 "4fc h81
Variables
kcp
2
c.c [in.)
6.750
Calculations
ANc [in.2]
56.25
Results
8,301
h0, [in.)
2.500
kc
21
ANco [in.1
56.25
<I> concrete
0.700
Ca min [in.]
00
"-a
1.000
lj/ td,N
1.000
<l>selsmlc
1.000
Page:
Specifier:
E-Mail:
Date:
ACI 318-19 Eq. (17.7.3.1a)
ACI 318-19 Table 17.5.2
ACI 318-19 Eq. (17.6.2.1.4)
ACI 31 8-19 Eq. (17.6.2.4.1b)
ACI 318-19 Eq. (17.6.2.6.1b)
ACI 318-19 Eq. (17.6.2.2.1)
lj/ c,N
1,000
fc [psi]
2,500
lj/ cp,N Nb [lb)
1.000 4,150
4>nonductile <I> Vcp [lb)
1.000 5,811
5 Combined tension and shear loads, per ACI 318-19 section 17.8
Utilization f:lN v [%) Status
0.363 0.625 5/3 65 OK
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
810
5
10/17/2024
Vu• [lb)
2,796
5
r: ii S • i 811
Hilti PROFIS Engineering 3.1.4
www.hilti.com
Company: Page: 6
Address: Specifier:
Phone I Fax: I E-Mail:
Design: Concrete -Oct 9, 2024 Date: 10/17/2024
Fastening point:
6 Warnings
The anchor design methods in PROFIS Engineering require rigid anchor plates per current regulations (AS 5216:2021, ETAG 001/Annex C,
EOTA TR029 etc.). This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered -the
anchor plate is assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Engineering calculates
the minimum required anchor plate thickness with CBFEM to limit the stress of the anchor plate based on the assumptions explained above. The
proof if the rigid anchor plate assumption is valid is not carried out by PROFIS Engineering. Input data and results must be checked for
agreement with the existing conditions and for plausibility!
Condition A applies where the potential concrete failure surfaces are crossed by supplementary reinforcement proportioned to tie the potential
concrete failure prism into the structural member. Condition B applies where such supplementary reinforcement is not provided, or where pullout
or pryout strength governs.
Refer to the manufacturer's product literature for cleaning and installation instructions.
For additional information about ACI 318 strength design provisions, please go to https://submittals.us.hilti.com/PROFISAnchorDesignGuide/
"An anchor design approach for structures assigned to Seismic Design Category C, D, E or F is given in ACI 318-19, Chapter 17, Section
17.10.5.3 (a) that requires the governing design strength of an anchor or group of anchors be limited by ductile steel failure. If this is NOT the
case, the connection design (tension) shall satisfy the provisions of Section 17.10.5.3 (b), Section 17.10.5.3 (c), or Section 17.10.5.3 (d). The
connection design (shear) shall satisfy the provisions of Section 17.10.6.3 (a), Section 17.10.6.3 (b), or Section 17.10.6.3 (c)."
Section 17 .10.5.3 (b) / Section 17 .10.6.3 (a) require the attachment the anchors are connecting to the structure be designed to undergo ductile
yielding at a load level corresponding to anchor forces no greater than the controlling design strength. Section 17.10.5.3 (c) / Section 17.10.6.3
(b) waive the ductility requirements and require the anchors to be designed for the maximum tension I shear that can be transmitted to the
anchors by a non-yielding attachment. Section 17.10.5.3 (d) / Section 17.10.6.3 (c) waive the ductility requirements and require the design
strength of the anchors to equal or exceed the maximum tension I shear obtained from design load combinations that include E, with E increased
by roo·
Hilti post-installed anchors shall be installed in accordance with the Hilti Manufacturer's Printed Installation Instructions (MPII). Reference ACI
318-19, Section 26.7.
Fastening meets the design criteria!
Input data and results must be checked for conformity with the existing conditions and fo, plausibilityl
PROFIS Engineering ( c) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
6
,:,,s.,
Hilti PROFIS Engineering 3.1 .4
www.hilti.com
Company:
Address:
Phone I Fax: I Design: Concrete -Oct 9, 2024
Fastening point:
7 Installation data
Profile: no profile
Hole diameter in the fixture: d1 = 0.562 in.
Plate thickness (input): 0.500 in.
Recommended plate thickness: not calculated
Drilling method: Hammer drilled
Cleaning: Manual cleaning of the drilled hole according to instructions for use is
required.
812
Page: 7
Specifier:
E-Mail:
Date: 10/17/2024
Anchor type and diameter: Kwik Bolt TZ2 -CS 1/2 (2 1/2)
hnom3
Item number: 2210255 KB-TZ2 1/2x4 1/2
Maximum installation torque: 602 in.lb
Hole diameter in the base material: 0.500 in.
Hole depth in the base material: 3.250 in.
Minimum thickness of the base material: 5.000 in.
Hilti KB-TZ2 stud anchor with 3 in embedment, 1/2 (2 1/2) hnom3, Carbon steel, installation per ESR-4266
7.1 Recommended accessories
Drilling
Suitable Rotary Hammer
• Properly sized drill bit
Coordinates Anchor [in.]
Anchor X y
0.000 0.000
Cleaning
• Manual blow-out pump
... y
I 6.000
( 1
6.000
Input data and results must be checked for conformity wtth the existing conditions and for plausibility!
6.000
6.000
PROFIS Engineering ( c) 2003-2024 Hilti AG, FL-9494 Schaan Hilli is a registered Trademar1< of Hilti AG, Schaan
Setting
• Torque controlled cordless impact tool
• Torque wrench
• Hammer
0 0 0
0 0 0 <O <O
~ ...
X
0 0 0 0 0 0 <D <O
-
7
l = i i 5 • • ----------------------813
Hilti PROFIS Engineering 3.1 .4
www.hilti.com
Company: Page: 8
Address: Specifier:
Phone I Fax: I E-Mail:
Design: Concrete -Oct 9, 2024 Date: 10/17/2024
Fastening point:
8 Remarks; Your Cooperation Duties
Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas and
security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be strictly
complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted prior to using
the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the data you put in.
Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be put in by you.
Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly with regard to
compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an aid to interpret norms
and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or suitability for a specific
application.
You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for the
regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do not use
the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software in each
case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or damaged data
or programs, arising from a culpable breach of duty by you.
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
8
F g
3131 Camino Del Rio N
Suite 1080
San Diego, CA 92108
p (619) 521-8500
I (619) 521-8591
www.kpll.com
location
client
uidel Rutherford LYO b TB
date 10 18 24
job no. 2400108
Fan Coil Equipment Anchorage (15/S800)
P1000 UNISTRUT
CROSS BRACE
EA. SIDE TYP
.t:!Q]Th
...
" HILTI KH-EZ w/ 2" EFF.
EMBED (ESR-3027)
MAX 600#
1. 4 BRACES TOTAL (2 IN EACH ORTHOGONAL DIRECTION).
2. BRACES MAY BE ROTATED 180"
P1 000 UNISTRUT
TYP. AS SHOWN
3. WHERE CONCRETE WALL INTERFERES WITH BRACE, CONNECT TO
WALL OR EXTEND BOTTOM UNISTRUT TO WALL AND BOLT WITH
¾" EXPANSION ANCHOR.
sheet no.
814
sheet no.
3131 Camino Del Rio N l-'-pr~oj_,ect_~Qui_d_el_R_u_th_e_rf_o_rd_L_YO ______ b~1v_T~B------1 B15
Suite 1080
San Diego, CA 92108 location date 10/18/24
p (619) 521-8500
f (619) 521-8591 client job no. 2400108
E 1 , www.kpff.com
Mech units anchorage design: (per ASCE 7-16, chapter 13.3)
CEILING MOUNTED UNITS (MAXIMUM WEIGHT :600 LBS)
SEISMIC FORCE: (per ASCE 7-16, chapter 13.3)
W=600 lbs
z/h=1
ap=2.5 ,Rp=6.0, Ip= ,Op=2, Sds=0.932
Fp=0.4*2.5*0.932*Wp/(6/1 )*(1 +2*1 )=0.466Wp=0.466*600=280 lbs, LRFD
Fpmin=0.3*0.932*1 *Wp=0.29Wp < Fp, OK
Fpmax=1.6*0.932*1 *Wp=1.52Wp > Fp, OK
Ev = 0.2SDSWp = 0.2*0.932*600# = 111 #
USE 12GA HANGER WIRE, OK IN TENSION
CHECK ELEMENTS FOR LC=(1 +0.2*0.7*Sds)D+0.7E=1 .13D+0.7E
CHECK P1000 CAPACITY FOR UNIFORM LOAD
MAXIMUM ALLOWABLE UNIFORM LOAD=680*0.66*1=449 LBS > (1.13*600/2+0.7*111#/2) =377
LBS, OK
THREADED ROD CAPACITY: (PER AISC, CHAPTER J, eq. J3-1)
3/8"<1> THREADED ROD CAPACITY=Fn_An/O=(0.75*58)*0.11 /2=2.4 k > (1 .13*600/2+0.7*111#/2)
=377 LBS, OK R,, = FnAb
<I>= 0.75 (LRFD) Q = 2.00 (ASD)
THREADED ROD PULL OUT ALLOWABLE CAPACITY=1000 LBS > 377 LBS, OK
sheet no.
l{P,ff 3131 Camino Del Rio N project bv B16 Suite 1080
San Diego, CA 92108 location date
p (619) 521-8500
f (619) 521-8591 client job no.
E 1gmeer www.kpff.com
Mech units anchorage design: (CONT.)
Load and Support Load Deflection
Condition Factor Factor
1. Simple Beam, ~:zzzz~~;.~zzzzz:I 1.00 1.00 Uniform Load
2. Simple Beam, I .50 .80 Concentrated Load at Center I I
-------- -LATERAL BRACING LOAD REDUCTION CHARTS
Span Single Channel Double Channel
Ft. (m) In. (cm) P1000 P1100 P2000 P3000 P3300 P4000 P4100 P4400 P4520 P5000 P5500 P1001 P1101 P2001 P3001 P3301 P4001 P4101 P4401 P4521 P5001 P5501
2 (0.61) 24 (61) 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0.98 0.99 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
3 (0.91) 36 (91) 0.94 0.89 0.88 0.96 1.00 0.94 0.98 1.00 1.00 0.85 0.89 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
4 (1.22) 48 (122) 0.88 0.78 0.75 0.91 1.00 0.88 0.94 0.98 1.00 0.70 0.77 1.00 0.98 0.98 1.00 1.00 0.98 1.00 1.00 1.00 0.97 0.98
5 (1.52) 60 (152) 0.82 0.68 0.61 0.88 0.98 0.83 0.91 0.96 1.00 0.55 0.67 0.97 0.93 0.92 0.98 1.00 0.93 0.96 1.00 1.00 0.90 0.93
6 (1.83) 72 (183) 0.78 0.59 0.48 0.84 0.97 0.79 0.89 0.94 0.98 0.44 0.58 0.93 0.87 0.85 0.95 0.97 0.88 0.92 0.97 0.97 0.83 0.87
7 (2.13) 84 (213) 0.75 0.52 0.41 0.82 0.96 0.75 0.86 0.92 0.97 0.38 0.51 0.89 0.82 0.78 0.92 0.95 0.83 0.89 0.95 0.95 0.76 0.81 ----
8 (2.44) 96 (244) 0.71 0.47 0.35 0.79 0.94 0.72 0.84 0.91 0.96 0.33 0.46 0.85 0.76 0.71 0.88 0.92 0.79 0.85 0.92 0.92 0.68 0.76
9 (2.74) 108 (274) 0.69 0.43 0.32 0.77 0.93 0.69 0.82 0.89 0.95 0.30 0.42 0.81 0.70 0.64 0.85 0.90 0.74 0.81 0.90 0.90 0.61 0.70 ------
10 (3.05) 120 (305) 0.66 0.40 0.29 0.75 0.92 0.66 0.80 0.87 0.94 0.28 0.40 0.78 0.65 0.57 0.82 0.87 0.69 0.78 0.87 0.87 0.54 0.64
12 (3 66) 144 (366) 0.61 0.36 0.25 0.70 0.89 0.60 0.76 0.84 0.91 0.24 0.36 0.70 0.54 0.45 0.76 0.82 0.60 0.71 0.82 0.83 0.43 0.53 ---
P1000 • BEAM I.OADINO
Channtl AUowab~
N"1 Pu!~ Anlltanca r....,. Deft." s~ .. Strength IOSlip fl-lbs UniformloadingllDlfll<tion Chann1I Th<tod 011191 u,, (JIN) Lbs (kN) (Nomi ..... -UnifOffll
2.500 1,700 '125 Span Unfformlold Lold Spon/1IO $pll\'2◄0 lpon/3'0
¾"-9 12 In u,, In u,, u,, u,,
11.12 7 56 170 2◄ 1,690 0.06 1,690 1,690 1,690
W-10 12 2.500 1.700 "125 J6 1.130 013 1130 1.130 900 11.12 7.56 170 '8 850 022 850 760 500
11· • 11 2.500 1.500 ·100 60 680 035 850 ◄ao 320 12 11 12 667 135 n 560 0.50 450 340 220 PIOOO
P3000 ½"-13 12 2.000 1.500 50 8◄ '80 063 n, 250 160 P'400 890 6.67 70
P,526 1,◄00 1.000 35 !16 ◄20 089 250 1110 130
PSOOO ¼"-14 12 623 HS 50 106 360 11◄ 200 150 100 P5SOO
1,000 BOO 19 120 340 1 ◄O 160 120 80 ¾"-16 12 HS 356 25 144 280 200 110 IO fJO
BOO 500 11 163 240 2n IO 60 ◄O ,,. •. 18 12 356 2 22 15 192 210 355 60 50 NR
Y.--20 12 600 300 6 216 1110 ◄58 50 '° NR 267 133 8 2◄0 170 5.62 '° NR NR
1.500 1.500 50
oroiect Quidel Rutherford LYO sheet no.
l<Hff 3131 Camino Del Rio N by TB B17 Suite 1080
San Diego, CA 92108 location date 10/18/24
p (619) 521-8500
I (619) 521-8591 client job no. 2400108
E g,ne r www.kpll.com
Screw Anchor to underside of composite deck (ESR-3027)
TABLE 8-HILTI KH-EZ I AND KH-EZ E TENSION AND SHEAR DESIGN DATA FOR INSTALLATION IN THE UNDERSIDE OF
CONCRETE-FILLED PROFILE STEEL DECK ASSEMBLIES'-'-'
L_,Flulit I u-Flute
Chwac:teriatlc S,ml>ol Untt• Nomlnal Anchor 01-ter . ,. .,. . , . ., .
Head Style lntomally (I) Throadod and Internally lnlernally (I) Threaded and lnlornally
ExternaNy (E) Th<eaded Threaded Exlemelly (E) Threaded Threaded
Embedment h-in. ,,,, 211, 1&1, 21/1 21,, 1s1, 2½ 1'1, 211-1 21/1
(mm) (41) (64) (41) (64) (5'1) (41) (64) (41) (64) (54)
Minimum Hate Depth ho In. 2 211, 2 2'1, 2'3/, 2 211, 2 211, 23/1
(mm) (51) (73) (51) (73) (60) (51) (73) (51) (73) (60)
Internal Thread in. .,. .,. .,, ¼ .,. .,,
Diameter (mm) (6.4) (9.5) (t2.7) (6.4) (9.5) (12.7)
EffoctJve Embcdroont h« in. t.18 1.92 1.t8 1.92 1.5'1 1.18 1.92 1.18 1.92 1.54
Depth (mm) (30) (49) (30) (49) (39) (30) (49) (30) (49) (39)
Pullout Reslotance, lbl. 1,210 1.875 1.210 1,875 1,720 1,490 1,960 1,490 1,960 2,660 (uncrad<ad Np1'K'-.,. (kN) (5.4) (8.3) (5.4) (8.3) (7.7) (6.6) (8.7) (6.6) (8.7) (1 1.8) concreto)'
Pullout Resistance lbl. 620 930 620 930 I 1.220i 730 975 730 975 1,885 (cmckod concrete Np,-...,, (kN) (2.8) (4.1) (2.8) (4.1) (5.4) (3.2) (4.3) (3.2) (4.3) (8.4) end seismic lottdsf
Steel Strength In Vu-lbl 860 1.025 2.380 1.015 1,525 3,650
Shear' (kN) (3.8) (4.6) (10.6) (4.5) (6.8) (16.2)
Sleet Slrength In v ....... lb/. 385 875 2.380 I\ 445 1,295 3.650
Shear. seismic (kN) (1.7) (3.9) (10.6) (2.0) (5.8) (162)
FO< S1: 1 Inch• 25.4 mm, 1 ft~bf • 1.356 N-m. 1 psi • 6.89 kPa, 1 tn2 • 645 mm2, 1 lbfm • 0.175 NI m.
'lnstaNalion muot comply with Seotions 4.1.10 and 4.3 and f.illal.lla, 1lJ2, and .IZ ol th11 repon.
trhe YakJel lilted must be used in accordance With SectlOO 4.1.4 of this ,-port.
'The values lilted must be used in accordance with Section 4.1,4 and 4 1 8.2 of thfs repott --rhe values li,tod must be used In &CCOrdanoe With Sectloo 4. 1.5 and • 1 8.3 of this report
-rhe values for ;. In lension and the vatuee for I,. In shear can be found in llt!!l.2 of this report.
"For Che 11 .. -lnch-dlameter (KH-EZ I) at 2-½ inch nominal embedment the charac:tef1stic pullout resistance for ete oomPNtsslve strengths greater than 3,000
pol mey be Increased by multiplying tho valuo In tho l8blo by tr,f.1,000/~for polo, (r,/20,7)" lo, MPa.
1For the ¼-ww:n-<:llameter ancnors (KH-EZ I and KH-EZ E) •t 111,-lnch nomtnal embedment charaawlstlc pullout r lstanoe fof concrele compresWe strengths
greate< than 3,000 pol may be lneo-easod by mul!lplylng the value In the table by (r ,f.1,000)"' for psi o, (r ,/20 r)"• lor Pa
1,000# capacity of rod --> OCR = 1000/1220# = 0.81 < 1.0 OK
ACTUAL MAX POINT LOAD= 1.13*600#/2 RODS+ 0.7*111#/2
RODS*OMEGA = 416# < 1000#
ANCHORAGE IS OK
□ □ □
□ □ □ □
□ □ □
Date: 12-10-2024
ENCINA WASTEWATER AUTHORITY
IN DUSTRIAL WASTEWATER DISCHARGE PERMIT
SCREENING SURVEY
6200 Avenida Encinas, Carlsbad, CA 9201 1
Phone: 760-438-3941 Fax: 760-476-9852
SourceControl@encinajpa.com
Business Name: QuidelOrtho ---------------------
Street Address: 2285 Rutherford Road, Carlsbad, CA. 92009
Email Address: sam@mcfarlanearchitects.com
PLEASE CHECK HERE IF YOUR BUSINESS IS EXEMPT • (ON REVERSE SIDE CHECK TYPE OF BUSINESS) □
Check all below that are present at your facility:
Acid Cleaning D Food Processing D Metal Powders Forming
Assembly D Glass Manufacturing 0 Nutritional SupplemenWitamin
Automotive Repair 0 Industrial Laundry 0 Manufacturing
Battery Manufacturing O Ink Manufacturing D Painting/Finishing
Biofuel Manufacturing O Laboratory O Paint Manufacturing
Biotech Laboratory 0 Machining/Milling 0 Personal Care Products
Bulk Chemical Storage 0 Membrane manufacturing 0 Manufacturing
Car Wash O (i.e. waterfilter membranes) O Pesticide Manufacturing/ Packaging
Chemical Manufacturing O Metal Casting/Forming O Pharmaceutical Manufacturing
Chemical Purification 0 Metal Fabrication 0 (including precursors)
D Dental Offices D Metal Finishing 0 Porcelain Enameling D Dental Schools 0 Electroplating 0 Power Generation D Dental Clinics 0 Electroless Plating 0 Print Shop D Dry Cleaning D Anodizing ~ Research and Development
□ Electrical Component D Coating (i.e. phosphating) 0 Rubber Manufacturing
□ Manufacturing D Chemical Etching/Milling D Semiconductor Manufacturing
□ Fertilizer Manufacturing D Printed Circuit Board D Soap/Detergent Manufacturing
□ Film/ X-ra y Processing D Manufacturing D Waste Treatment/Storage
New Business? YesO NoE) SIC Code(s) if known: Date operation began/will begin: 05•02•2025
Tenant Improvement? Yes E]NoO If yes, briefly describe improvement: Interior Tl to add mechanical room for tenant
equipment.
. . There are no plumbing fixtures Description of operations generating wastewater (discharged to sewer, hauled or evaporated): __________ _
or wastewater in this project.
. . . b d' h d ( I/ d ) See above response. Estimated volume of industrial wastewater to e Isc arge ga ay : _____________________ _
List hazardous wastes generated (type/volume ):_NI_A_._N_o_h_az_a_r_d_ou_s_w_a_s_te_. ____________________ _
Have you applied for a Wastewater Discharge Permit from the Encina Wastewater Authority? YesO Date: _____ NoD
Page 1 of 2
Hazardous Materials Questionnaire
County of San Diego, Department of Environmental Health and Quality
PO Box 129261, San Diego, CA 92112-9261
(858) 505-6700 (800) 253-9933 www.sdcdehq.org
Business Name
QUIDELORTHO
Project Address
2285 RUTHERFORD RD
Applicant
Sarah A McAllister
Business Contact
KEN DRYDEN
City
CARLSBAD
State
CA
Applicant E-Mail
sam@mcfarlanearchitects.com
Record ID#: DEH2002-HUPFP-132942
Plan Check#: DEH2024-HHMBP-014769
Telephone# Plan File#
(858) 552-7925
Zip Code
92008-8815
Applicant Telephone#
(858) 552-7925
APN#
212-062-08-00
The following questions represent the facility's activities, NOT the speclllc project descrlpllon.
PART 1· EIRE DEPARTMENT· HAZARDOUS METERIALS PIYISION· OCCUPANCY CLASSIFICATION· (Not required for projects within the City of San Diego.)
Indicate by selecting the item, whether your business will use, process, or store any of the following hazardous materials. If any of the items are selected, Applicant must
contact the Fire Protection Agency with jurisdiction prior to plan submittal.
Occupancy Rating: B Facility's Square Footage (including proposed project): 199687
0 Explosive or Blasting Agents 0 Organic Peroxides 0 Water Reactives O Corrosives
li!I Compressed Gases 0
0
Oxidizers O Cryogenics O Other Health Hazards
0 Flammable/Combustible Liquids Pyrophorics 0 Highly Toxic or Toxic Materials 0 None of These
0 Flammable Solids 0 Unstable Reactives O Radioactives
PART n· SAN DIEGO COUNTY DEPARTMENT OF ENVIRONMENTAL HEALTH· HAZARDOUS MATERIALS DIVISION IHMP)· If the answer to any of the questions is
yes, applicant must contact the County of San Diego Hazardous Materials Division, in person at 5500 Overland Ave., Suite 110, San Diego, CA 92123, or by phone at (858)
505-6700 prior to Issuance of a building permit. FEES ARE REQUIRED.
Project Completion Date: 5/1/2025
YES NO
1. 00 0
2. 0 1iil
3. 00 0
4. 0 D
5. 0 1i!l
6. D 1iil
7. D 1i!l
8. D 1B)
Is your business listed on the reverse side of this form? (check all that apply).
Will your business dispose of Hazardous Substances or Medical Waste in any amount?
Will your business store or handle Hazardous Substances in quantities equal to or greater than
55 gallons, 500 pounds, or 200 cubic feet?
Will your business handle carcinogens or reproductive toxins In any quantity?
Will your business use an existing, or install an underground storage tank?
Will your business store or handle Regulated Substances (CalARP)?
Will your business use or install a Hazardous Waste Tank System (Title 22, Article 1 O)?
Will your business store petroleum in tanks or containers at your facility with a total storage capacity
equal to or greater than 1,320 gallons? (California's Aboveground Petroleum Storage Act).
0
D
D
CalARP Exempt
CalARP Required
CalARP Complete
Review Date:
PART m· SAN DIEGO COUNTY AIR POLLUTION CONTROL DISTRICT {APCP): If the answer to Question #1 is 'Yes' and the answer to Question #2 is 'No', the applicant
must contact the APCD prior to the issuance of a building or demolition permit. If any answer to Questions #3, #4, or #5 is 'Yes', the applicant must contact the APCD prior to
the issuance of a building or demolition permit. If the answer to Question #3 or #4 is 'Yes·, the applicant may need to submit an asbestos notification form to the APCD at
least 10 working days prior to commencing demolition or renovation (some residential projects may be exempt from the notification requirements). Contact the APCD at
10124 Old Grove Road, San Diego, CA 92131 or telephone (858) 586-2600 for more information.
YES NO
1. 0 @
2. 0 D
3. 0 0
4. 0 li!I
Will any existing building materials be disturbed as part of this project? (If the answer is 'Yes', an asbestos survey may be required.)
Has a survey been performed to determine the presence of asbestos containing materials?
Will the project involve handling or disturbance of any asbestos containing materials?
Will the project involve the removal of any load supporting structural member?
5. 0 0 Will the subject facility or construction activities include operations or equipment that emit or are capable of emitting an air contaminant? (See the APCD
factsheet at http://Www.sdapcd.org/info/facts/perrnits.pdf
6. 0 0 (ANSWER ONLY IF QUESTION 5 IS 'YES') Will the subject facility be located within 1,000 feet of the outer boundary of a school (K through 12)? Search
the California School Directory at http://Www.cde.ca.gov/re/sd/ for public and private schools or contact the appropriate school district.
Briefly describe business activities: Briefly describe proposed project:
tNVITRO DIAGNOSTICS COMPANY SPECIALIZING IN RESPIRATORY HEALTH INTERIOR TENANT IMPROVEMENT INCLUDING MINOR DEMOLITION, NEW
DIAGNOSTICS, TRANSFUSION MEDICINE, IMMUNOASSAY & MOLECUAR WALLS, PREFAB CLEAN ROOM PANELS, D()ORS, FINISHES, PLUMBING
I declare under penalty of perjury that to the best of my knowledge and belief, the responses made herein are true and correct. O; Fees Acknowledged: 1i!l
SARAH MCALLISTER / MCFARLANE ARCHITECTS 10n/2024
Name of Owner or Authorized Agent Date
FOR OFFICIAL USE ONLY
FIRE DEPARTMENT OCCUPANCY CLASSIFICATION:
BY: DATE: __________ _
EXEMPT OR NO FURTHER INFORMATION RELEASED FOR BUILDING PERMIT BUT NOT FOR RELEASED FOR OCCUPANCY
REQUIRED OCCUPANCY
COUNTY-HMO" APCD COUNTY-HMO APCD COUNTY-HMO APCD
~ -(Of ~a ~
AEVIEWE.O
T . Yousif
8IOHATutl£
10/10/2024
DA
.... An
• A stamp in this box only exempts businesses from completing or updating a Hazardous Materials Business Plan. Other permitting requirements may still apply.
DEHQ_HMD_HMBP _Questionnaire v 2.0 (8/2021)
Printed on: 10/10/2024@ 11:30 PM
Building Permit Finaled
Revision Permit
Print Date: 09/30/2025
Job Address: 2285 RUTHERFORD RD, CARLSBAD, CA 92008-8815
Permit No:
Status:
(city of
Carlsbad
PREV2024-0245
Closed -Finaled
Permit Type: BLDG-Permit Revision Work Class: Commercial Permit Revision
Parcel#:
Valuation:
Occupancy Group:
#of Dwelling Units:
Bedrooms:
Bathrooms:
Occupant Load:
Code Edition:
Sprinkled:
Project Title:
2120620800 Track #:
$0.00 Lot#:
Project#:
Plan#:
Construction Type:
Orig. Plan Check#: CBC2024-0334
Plan Check#:
Applied: 12/26/2024
Issued:
Finaled Close Out: 09/30/2025
Final Inspection:
INSPECTOR:
Description: QUIDELORTHO: DEFERRED SUBMITTAL FOR DRY ROOM INSULATED METAL PANELS
FEE
THIRD PARTY REVIEW -Consultant Cost (BLDG)
Property Owner:
ARE-SD REGION NO 71 HOLDING LLC
PO BOX 847
CARLSBAD, CA 92018-0847
Total Fees: $900.00 Total Payments To Date: $900.00
Building Division
Contractor:
SKYLINE COMMERCIAL INTERIORS INC
5051 AVENIOA ENCINAS
CARLSBAD, CA 92008-4363
(858) 720-8559
Balance Due:
AMOUNT
$900.00
$0.00
Page 1 of 1
1635 Faraday Avenue, Carlsbad CA 92008-7314 I 442-339-2719 I 760-602-8560 f I www.carlsbadca.gov
(City of
Carlsbad
Document Missing
From File
Permit Number PREV2024-0245
APN 2120620800
Address 2285 RUTHERFORD RD
City/State/Zip CARLSBAD, CA 92008
The following document is missing from this file:
□ B-1
Development Services
Building Division
1635 Faraday Ave
www .carlsbadca.gov
-----------------------
□ B-10
[Z] B-15 -----------------------□
□
This file was printed on: 9/30/25
1
Transmittal Letter
January 29, 2025
City of Carlsbad
Community Development Department -Building Division
1635 Faraday Ave.
Carlsbad, CA 92008
Plan Review: Deferred-TI Quidelortho
Address: 2285 Rutherford Rd, Carlsbad CA
True North
'/_ COMPLIA NCE SERVICES
SECOND REVIEW
City Permit No: PREV2024-0245
True North No.: 24-018-11 76
Applicant Name: Willian Reyes Applicant Email: william@prevostconstruction.com
True North Compliance Services, Inc. has completed the review of the following documents for the project
referenced above on behalf of the City of Carlsbad. Our comments can be found on the attached list.
1. Drawings: Electronic copy ''Not dated", by Clarion Construction, INC.
Attn: Permit Technician, the scope of work on the plans has been reviewed for coordination with the scope of
wo rk on the permit application. See below for information if the scope of work on plans differs from the permit
application:
Valuation:
Scope of Work:
Floor Area:
Notes: NIA
Confirmed
Confirmed
Confirmed
This project is hourly. Please charge the applicant the following hours of plan review.
Review # Hours Rate Total
1st Review 4 $120.00 $480
2nd Review 2 $120 $240
Our comments follow on the attached list. Please call if you have any questions or if we can be of further
assistance.
Sincerely,
True North Compliance Services
Review By: Mulham Hweidi -Plan Review Engineer
Quality Review By: Alaa Atassi -Plan Review Supervisor
True North Compliance Services, Inc.
8369 Vickers Street, Suite 207, San Diego, CA 92111
T / 562. 733.8030
Deferred-TI Quidelortho
2285 Rutherford Rd
January 29, 2025
City of Carlsbad-SECOND REVIEW
City Permit No.: PREV2024-0245
True North No.: 24-018-1176
Pagel
Plan Review Comments
HARD COPY -RESUBMITT AL INSTRUCTIONS:
Please do not resubmit plans until all departments have completed their reviews. For status, please
contact building@carlsbadca.gov
Please make all corrections, as requested in the correction list. Submit FOUR new complete sets of plans
for commercial/industrial projects (THREE sets of plans for residential projects). Corrected sets can be
submitted as follows:
Deliver THREE corrected sets of plans and TWO corrected calculations/reports directly to the City
of Carlsbad Building Division, 1635 Faraday Ave., Carlsbad, CA 92008, (442) 339-2719. The city
will route the plans to True North, Planning and Land Development Engineering Departments (if
applicable) for continued review.
Note: If this proj ect requires FIRE PREVENTION review, ensure that you follow their specific
instructions for resubmittal review. The city will not route plans back to Dennis Grubb &
Associates for continued Fire Prevention review.
GENERAL INFORMATION:
A. The following comments are referred to the 2022 California Building, Mechanical, Plumbing, Electrical
Codes, California Green Building Standards Code, and Energy Code (i.e., 2021 IBC, UMC, UPC, and 2020
NEC, as amended by the State of California).
B. There may be other comments generated by the Building Division and/or other City departments that will
also require your attention and response. This attached list of comments, then, is only a portion of the plan
review. Contact the City for other items.
C. Respond in writing to each comment by marking the attached comment list or creating a response letter.
Indicate which details, specification, or calculation shows the required information. Your complete and
clear responses will expedite the re-check.
D. Where applicable, be sure to include the architect and engineer's stamp and signature on all sheets of the
drawings and on the coversheets of specifications and calculations per CBPC 5536.1 and CBPC 6735. This
item will be verified prior to plan approval.
E. If you have any questions regarding the below comments, please contact Mulham Hweidi via email
mulhamh@tncservices.com or telephone (562) 733-8030.
OCCUPANCY & BUILDING SUMMARY:
Occupancy Groups:
Occupant Load:
Type of Construction:
Sprinklers:
Stories:
Area of Work (sq. ft.):
S-1, B
(See comments below)
III-B
Yes
2
(See comments below) sq. ft.
Deferred-TI Quidelortho
2285 Rutherford Rd
January 29, 2025
ARCIDTECTURAL COMMENTS:
Al. Designate the exact area of work in this deferred submittal.
PC2: No response provided. Comment remains outstanding.
City of Carlsbad-SECOND REVIEW
City Permit No.: PREV2024-0245
True North No.: 24-018-11 76
Page3
A2. Proposed changes require update on the egress plan and the occupant load, address the following comments:
a) Two dry rooms has been separated, show the egress/exit path for each part of the floor plan to the
outside of the building to meet the following:
i) Show the exit access travel distance to the exit discharge
ii) No egress plan provided. Please revise the floor plan to identify the Common Path of
Egress Travel (CPET). Paths must begin from the most remote point within the story, and
end where two separate and distinct paths to two exits are available. Ensure that no CPET
exceeds the limits set forth in CBC 1006.2.1.
iii) Revise plans to show location of installed exit signs conforming to the CBC 1013. Exit
signs shall be readily visible from any direction of approach and shall be located as
necessary to clearly indicate the direction of egress travel.
iv) Specify tactile egress signage to be installed on the wall adjacent to the latch side of the
exit doors mounted 60 inches above the finish floor to the centerline of the sign complying
with CBC llB-703.1, llB-703.2, llB-703.3 and llB-703.5, per CBC 1013.4. Show
location and details on plans.
b) No occupant load calculation provided. On the floor plans, identify the floor area of each room,
the occupant load factor of each room, the number of occupants in each room and the total
number of occupants. CBC Table 1004.5.
PC2: No response provided and plans not updated to address comments above. Comments remain
outstanding.
A3. Load bearing elements and the primary structure frame for the building have been altered, and as per CBC
Table 601, as this building has a type III-A construction, all loadbearing walls and primary frame of the
structure shall be I-Hour fire rated. Please revise plans and show
PC2: No response provided and plans not updated to address comment above. Comment remains
outstanding.
A4. On sheet A-2. lA,
b) Clarify if there are any proposed changes in the mechanical room from the original permit.
PC2: No response provided. Comment remains outstanding.
c) Clarify what is the use of this newly enclosed room, further occupancy and egress comments may
be generated.
PC2: No response provided. Comment remains outstanding.
pgy gOOM " I I c.
t__..
t" -· I
Deferred-TI Quidelortho
2285 Rutherford Rd
January 29, 2025
City of Carlsbad-SECOND REVIEW
City Permit No.: PREV2024-0245
True North No.: 24-018-1176
Page 4
d) Clarify if the vestibules are new or not, as the wall legend indicates that the enclosed meatal
sheathing is new. If new, provide information on the proposed doors.
i) If new, revise the plan to show a clearance of 48" plus the width of door as required per
CBC l lB-404.2.6.
PC2: No respo11se provided. Comme11t remains outsta11ding.
_New.----
walls/doors?
e) Clarify if in any proposed enclosed rooms or enclosed areas have resulted in an occupancy change.
i) If so, provide an allowable area analysis CBC Table 506.2.
PC2: No respo11se provided. Comme11t remains outsta11di11g.
A5. Provide a site plan showing,
b) Parking facilities.
c) Clarify exterior alterations if proposed.
d) Show the exit path from the inside of the building (and scope of work area) to the public way.
PC2: No respo11se provided a11d pla11s 11ot updated to address comme11ts above. Comme11ts remain
outsta11ding.
ACCESSIBILITY COMMENTS:
D 1. Please note that accessibility upgrades are required in this permit due to the fact that the original permit was
a mechanical units upgrade only permit, and as the designer presented CBC 11 B-203 .5 section that exempts
mecharucal rooms from accessibility upgrades, and the changes proposed in the current deferred submittal
triggers accessibility upgrades as per CBC l lB-202.3. This accessibility shall include the requirements of
CBC l lB-202.4, which entails: a primary entrance, a primary path of travel, sanitary facilities serving the
area, a drinking fountain, and signs. Please address the following:
a) Upon providing a site plan:
i) Show the accessible path of travel from the accessible parking and public way to the area
of alteration.
( 1) Accessible parking shall be located at shortest route to the entrance of the building.
Deferred-TI Quidelortho
2285 Rutherford Rd
January 29, 2025
City of Carlsbad-SECOND REVIEW
City Permit No.: PREV2024-0245
True North No.: 24-018-1176
Page5
ii) Specify the accessible route to be 5% maximum running slope with 2% maximum cross
slope per CBC l lB-403.3.
iii) Specify the accessible route to be at least 48" in width. CBC l lB-403.5.1
iv) Provide detectable warning where the accessible route crosses or adjoins the vehicular path
of travel per CBC l lB-247.1.2.5. Provide detectable warning details in accordance with
CBC llB-705.1.
v) Show location and provide details for curb ramps in accordance with CBC l lB-406.
vi) Clarify if a ramp is provided at the exterior of the building. Provide details and
dimensions for the ramp to show compliance with CBC l lB-405. Include information on
ramp slope, handrails, handrail extensions, and landings.
vii) Provide details and dimensions of accessible parking, accessible aisles, markings,
signage, etc., to verify it meets the requirements of CBC l lB Division 5.
b) Provide plans and detai ls for the restrooms serving the area to verify that it meets the requirements
of CBC l lB Division 6.
c) Show the location and provide details for the drinking fountain serving this area to verify that it
meets the requirements of CBC l lB-21 1.1 and CBC l lB-602.
PC2: No response provided and plans not updated to address comments above. Comments remain
outstanding.
D2. Provide information for the existing and proposed doors that are within the area of work.
a) Confirm the clear width of the doorways are 32" minimum per CBC l lB-404.2.3. A 3 ft wide door
provides 32" clear width.
PC2: Doors tags are provided for just some doors. Please provide door information on all doors
within th e area of work.
D3. Dimension 18" strike clearance and 60" maneuvering clearance at the pull side of all doors per CBC l lB-
404.2.4.1.
PC2: Dimensions not provided for all doors. Please provide doors tag for ALL doors within the area of
work, and provide all required clearances.
D4. Dimension 12" strike clearance and 48" maneuvering clearance at the push side of all doors per CBC l lB-
404.2.4.1.
PC2: Dimensions not provided for all doors. Please provide doors tag for ALL doors within the area of
work, and provide all required clearances.
DS. Some doors are doors in series. Revise the plan to show a clearance of 48" plus the width of door as required
per CBC l lB-404.2.6.
PC2: Comment above not addressed and remains outstanding.
MEP COMMENTS:
M l. Clarify if this deferred permit proposes any MEP work. Further comments may apply.
PC2: No response provided. Comment remains.
Deferred-TI Quidelortho
2285 Rutherford Rd
January 29, 2025
GREEN BUILDING COMMENTS:
No Comments.
ENERGY COMPLIANCE COMMENTS:
No comments.
STRUCTURAL COMMENTS:
City of Carlsbad-SECOND REVIEW
City Permit No.: PREV2024-0245
True North No.: 24-018-1176
Page6
SL New structural work is proposed, yet no structural calculations were provided with the first submittal.
a) Provide calculations for the lateral system as they propose an update on the metal wall panels.
b) Justify the maximum height specified in the metal schedule.
c) Engineer of record to stamp and sign all structural plan sheets and calculation package.
d) Provide metal framing details for the proposed panels.
e) Provide general and material information for the proposed elements.
PC2: The provided structural sheet only shows calculations for gravity members. In addition, the
calculations show the panels as failing. Lateral resisting elements design not provided. Please revise as
the structural is incomplete, does not address the above comments, and
BENDING LOADS
Span or Support
Support Moment
No. EL (R) lb.NR
2 1 IS.00 0.0
I 100.00 0.0
Design Max
SJ>"n Shear
Moment (LeR)
lb.NR lb/R
632.8 168.8
Safety OK
Criteria Stress (psi) Faccor
Faci.t 9313 1.45 ' Liner 8961 3.34 ,,
Core Shear 3.601 4.58 ,,
Note:
Shear
(Right)
lb/R
-168.8
Panel will fail. Deflection does not meet L/240
OK
MidsJ>"n Deflection Support
Deflection Limit Reoetior
in lb/R
168.8
1.027 11175 X 168.8
Positiv<
If you have any questions regarding the above comments, please contact Mulbam Hweidi via email
mulhamh@tncservices.com or telephone (562) 733-8030.
[END]
Transmittal Letter
January 6, 2025
City of Carlsbad
Community Development Department -Building Division
1635 Faraday Ave.
Carlsbad, CA 92008
Plan Review: Deferred-Tl Quidelortho
Address: 2285 Rutherford Rd, Carlsbad CA
True North
COMPLIANCE SERVICES
FIRST REVIEW
City Permit No: PREV2024-0245
True North No.: 24-018-1176
Applicant Name: Willian Reyes Applicant Email: william@prevostconstruction.com
True North Compliance Services, Inc. has compl eted the review of the following documents for the project
referenced above on behalf of the City of Carlsbad. Our comments can be found on the attached list.
1. Drawings: Electronic copy "Not dated", by Clarion Construction, INC.
Attn: Permit Technician, the scope of work on the plans has been reviewed for coordination with the scope of
work on the permit application. See below for information if the scope of work on plans differs from the permit
application:
Valuation:
Scope of Work:
Floor Area:
Notes: NIA
Confirmed
Confirmed
Confirmed
This project is hourly. Please charge the applicant the following hours of plan review.
Review # Hours Rate Total
pt 4 $120.00 $480
Our comments follow on the attached list. Please call if you have any questions or if we can be of further
assistance.
Sincerely,
True North Compliance Services
Review By: Mulham Hweidi -Plan Review Engineer
Quality Review By: Alaa Atassi -Plan Review Supervisor
True North Compliance Services, Inc.
8369 Vickers Street, Suite 207, San Diego, CA 92111
T / 562. 733.8030
Deferred-TI Quidelortho
2285 Rutherford Rd
January 1, 2025
Plan Review Comments
HARD COPY -RESUBMITTAL INSTRUCTIONS:
City of Carlsbad-FIRST REVIEW
City Permit No.: PREV2024-0245
True North No.: 24-018-1 176
Page2
Please do not resubmit plans until all departments have completed their reviews. For status, please
contact buildin2@carlsbadca.gov
Please make all corrections, as requested in the correction list. Submit FOUR new complete sets of plans
for commercial/industrial projects (THREE sets of plans for residential projects). Corrected sets can be
submitted as follows:
Deliver THREE corrected sets of plans and TWO corrected calculations/reports directly to the City
of Carlsbad Building Division, 1635 Faraday Ave., Carlsbad, CA 92008, (442) 339-2719. The city
will route the plans to Trne North, Planning and Land Development Engineering Departments (if
applicable) for continued review.
Note: If this project requires FIRE PREVENTION review, ensure that you fo llow their specific
instructions for resubrnittal review. The city will not route plans back to Dennis Grubb &
Associates for continued Fire Prevention review.
GENERAL INFORMATION:
A. The following comments are referred to the 2022 California Building, Mechanical, Plumbing, Electrical
Codes, California Green Building Standards Code, and Energy Code (i.e., 2021 IBC, UMC, UPC, and 2020
NEC, as amended by the State of California).
B. There may be other comments generated by the Building Division and/or other City departments that will
also require your attention and response. This attached list of comments, then, is only a portion of the plan
review. Contact the City for other items.
C. Respond in writing to each comment by marking the attached comment list or creating a response letter.
Indicate which details, specification, or calculation shows the required information. Your complete and
clear responses will expedite the re-check.
D. Where applicable, be sure to include the architect and engineer's stamp and signature on all sheets of the
drawings and on the coversbeets of specifications and calculations per CBPC 5536.1 and CBPC 6735. This
item will be veri fied prior to plan approval.
E. If you have any questions regarding the below comments, please contact Mulham Hweidi via email
mulharnh@tncservices.com or telephone (562) 733-8030.
OCCUPANCY & BUILDING SUMMARY:
Occupancy Groups:
Occupant Load:
Type of Construction:
Sprinklers:
Stories:
Area of Work (sq. ft.):
S-1, B
(See comments below)
III-B
Yes
2
(See comments below) sq. ft.
Deferred-TI Quidelortho
2285 Rutherford Rd
January 1, 2025
City of Carlsbad-FIRST REVIEW
City Permit No.: PREV2024-0245
True North No.: 24-0 18-1 176
Page3
ARCIDTECTURAL COMMENTS:
Al. Designate the exact area of work in this deferred submittal.
A2. Proposed changes require update on the egress plan and the occupant load, address the following comments:
a) Two dry rooms has been separated, show the egress/exit path for each part of the floor plan to the
outside of the building to meet the following:
i) Show the exit access travel distance to the exit discharge
ii) No egress plan provided. Please revise the floor plan to identify the Common Path of
Egress Travel (CPET). Paths must begin from the most remote point within the story, and
end where two separate and distinct paths to two exits are available. Ensure that no CPET
exceeds the limits set forth in CBC 1006.2.1.
iii) Revise plans to show location of installed exit signs conforming to the CBC 1013. Exit
signs shall be readily visible from any direction of approach and shall be located as
necessary to clearly indicate the direction of egress travel.
iv) Specify tactile egress signage to be installed on the wall adjacent to the latch side of the
exit doors mounted 60 inches above the finish floor to the centerline of the sign complying
with CBC llB-703.1, llB-703.2, llB-703.3 and l lB-703.5, per CBC 1013.4. Show
location and details on plans.
b) No occupant load calculation provided. On the floor plans, identify the floor area of each room,
the occupant load factor of each room, the number of occupants in each room and the total
number ofoccupants. CBC Table 1004.5.
A3. Load bearing elements and the primary structure frame for the building have been altered, and as per CBC
Table 601, as this building has a type III-A construction, all loadbearing walls and primary frame of the
structure shall be 1-Hour fue rated. Please revise plans and show
A4. On sheet A-2.lA,
a) From the original permit, changes have been proposed for the below highlighted wall, the original
(Approved) plan set show three doors in the area below, please revise.
" .,.
l2fai
~
I
I
l
I -,
b) Clarify if there are any proposed changes in the mechanical room from the original permit.
c) Clarify what is the use of this newly enclosed room, further occupancy and egress comments may
be generated.
Deferred-TI Quidelortho
2285 Rutherford Rd
January 1, 2025
DRY ROOM A ...,._._...I c.
City of Carlsbad-FIRST REVIEW
City Permit No.: PREV2024-0245
True North No.: 24-018-1 176
Page 4
d) Clarify if the vestibules are new or not, as the wall legend indicates that the enclosed meatal
sheathing is new. If new, provide information on the proposed doors.
i) If new, revise the plan to show a clearance of 48" plus the width of door as required per
CBC l lB-404.2.6.
I
J
-N8-W ----
walls/doors?
e) Clarify if in any proposed enclosed rooms or enclosed areas have resulted in an occupancy change.
i) If so, provide an allowable area analysis CBC Table 506.2.
A5. Provide a site plan showing,
a) Parking facilities.
b) Clarify exterior alterations if proposed.
c) Show the exit path from the inside of the building (and scope of work area) to the public way.
ACCESSIBILITY COMMENTS:
D 1. Please note that accessibility upgrades are required in this permit due to the fact that the original permit was
a mechanical units upgrade only permit, and as the designer presented CBC l lB-203.5 section that exempts
mechanical rooms from accessibility upgrades, and the changes proposed in the current deferred submittal
triggers accessibility upgrades as per CBC l lB-202.3. This accessibility shall include the requirements of
CBC 1 lB-202.4, which entails: a primary entrance, a primary path of travel, sanitary facilities serving the
area, a drinking fountain, and signs. Please address the following:
a) Upon providing a site plan:
i) Show the accessible path of travel from the accessible parking and public way to the area
of alteration.
Deferred-TI Quidelortho
2285 Rutherford Rd
January 1, 2025
City of Carlsbad-FIRST REVIEW
City Permit No.: PREV2024-0245
True North No.: 24-018-1176
Page 5
(1) Accessible parking shall be located at shortest route to the entrance of the building.
ii) Specify the accessible route to be 5% maximum running slope with 2% maximum cross
slope per CBC l lB-403.3.
iii) Specify the accessible route to be at least 48" in width. CBC l lB-403 .5 .1
iv) Provide detectable warning where the accessible route crosses or adjoins the vehicular path
of travel per CBC l lB-24 7.1.2.5. Provide detectable warning details in accordance with
CBC l lB-705.1.
v) Show location and provide details for curb ramps in accordance with CBC l lB-406.
vi) Clarify if a ramp is provided at the exterior of the building. Provide details and
dimensions for the ramp to show compliance with CBC l lB-405. Include information on
ramp slope, handrails, handrail extensions, and landings.
vii) Provide details and dimensions of accessible parking, accessible aisles, markings,
signage, etc., to verify it meets the requirements of CBC l lB Division 5.
b) Provide plans and details for the restrooms serving the area to verify that it meets the requirements
of CBC l lB Division 6.
c) Show the location and provide details for the drinking fountain serving this area to verify that it
meets the requirements of CBC 11 B-211.1 and CBC 11 B-602.
D2. Provide information for the existing and proposed doors that are within the area of work.
a) Confirm the clear width of the doorways are 32" minimum per CBC 1 lB-404.2.3. A 3 ft wide door
provides 32" clear width.
b) Door hardware are operable with one hand and do not require tight grasping, pinching, or twisting
of the hand. CBC llB-404.2.7 and llB-309.4.
c) Specify door thresholds, if provided at doorways, to be ½ inch high maximum. Raised thresholds
and changes in level at doorways shall comply with CBC Section l lB-302 and l lB-303. CBC
l lB-404.2.5.
d) Door opening force is 5-pounds maximum for interior and exterior doors per CBC l lB-404.2.9.
e) Door opening hardware is mounted 34" to 44" above the finish floor per CBC llB-404.2.7.
f) Lower 10 inch of the door surface is provided with a smooth surface for the full width of the door,
at the push side of the door per CBC l 1B-404.2.10.
D3. Dimension 18" strike clearance and 60" maneuvering clearance at the pull side of all doors per CBC l lB-
404.2.4.1.
D4. Dimension 12" strike clearance and 48" maneuvering clearance at the push side of all doors per CBC l lB-
404.2.4.1.
D5. Some doors are doors in series. Revise the plan to show a clearance of 48" plus the width of door as required
per CBC llB-404.2.6.
MEP COMMENTS:
Ml. Clarify if this deferred permit proposes any MEP work. Further comments may apply.
Deferred-TI Quidelortho
2285 Rutherford Rd
January 1, 2025
GREEN BUILDING COMMENTS:
No Comments.
ENERGY COMPLIANCE COMMENTS:
No comments.
STRUCTURAL COMMENTS:
City of Carlsbad-FIRST REVIEW
City Permit No.: PREV2024-0245
True North No.: 24-018-1176
Page 6
S 1. New structural work is proposed, yet no structural calculations were provided with the first submittal.
a) Provide calculations for the lateral system as they propose an update on the metal wall panels.
b) Justify the maximum height specified in the metal schedule.
c) Engineer of record to stamp and sign all structural plan sheets and calculation package.
d) Provide metal framing details for the proposed panels.
e) Provide general and material information for the proposed elements.
If you have any questions regarding the above comments, please contact Mulham Hweidi via email
mulhamh@tncservices.com or telephone (562) 733-8030.
[END]