AS 120132 Permit Data
City of Carlsbad
Sprinkler Permit
Permit No: AS120132
5545 FERMI CT Status: APPROVED
SPRINK Applied 10/9/2012
2121303700 Approved: 10/22/2012
0
Issued: 10/22/2012
Inspector:
TAYLOR MADE CANOPY ADDITION CANOPY
Owner:
EPIC FIRE PROTECTION, INC.
765 TURTLE POINT WY
T M G PROPERTY
SAN MARCOS, CA
760-310-6122
about:blank
Fees($)
268
Add'I Fees ($)
0
1000 PIONEER WAY
EL CAJON CA
Total($)
268
Balance($)
0
1 /1
EPIC FIRE PROTECTION, INC:
765 TURTLE POINT WAY
SAN MARCOS, CA 92069
(760) 310-6122 FAX (760) 798-0556
Hydraulic Design Information Sheet
Name: TAYLOR MADE CANOPY ADDITION
Location: 5545 FERMI CT. CARLSBAD
Date: 10-3-12
Building: --'E=XI=S~T ___________________ System No. -=2....:O:.::F....:2:.._ ___ _
Contractor: EPIC FIRE PROTECTION, INC. Contract No.
Calculated By: RAB Drawing No. I OF 1
Construction: 0 Combustible /gj Non-Combustible Ceiling Height -"-.-=.::.-'--'----F-t-.
SYSTEM DESIGN
~ NFPA 13: D Light Hazard Ordinary Hazard Group t8:\ 1 LJ 2 LJ 3 D Extra Hazard
0 NFPA231 0 NFPA 231C: Figure: Curve:
D Other (Specify)
D Specific Ruling Made By Date
Area of Sprinkler Operation lSOOSQ FT (. /
SvruimTwe
Density .15 ~Wet 0 Dry D Deluge D Pre-Action
Area Per Sprinkler 20X20MAX S11rinkler or Nozzle
Hose Allowance GPM: Inside 0 Make VIKING Model EC UPRIGHT
Hose Allowance GPM: Outside 250 Size .64" K-factor: 11.2
Rack Sorinkler Allowance NA Temnerature Ratin~ 200DEG.
CALCULATION SUMMARY
GPM Required --'3:..:9:...:7.:.:.2::.:7 ______ PSI Required -'-80"".'"'39 ______ At Base of Riser
"C" Factor Used: Overhead 120 Under round 150
WATER SUPPLY
Water Flow Test Pump Data Tank or Reservoir
Date& Time BASE OF RISER Rated Capacity Capacity
Static PSI CALC At PSI Elevation
Residual PSI Elevation
GPMFlowing Well
Elevation 0 Proof Flow GPM
Location EXISTING BASE OF RISER DEMAND IS 1412.4 GPM AT 86.8 PSI
Source of Information
COMMODITY STORAGE
Commodity OUTSIDE CANOPY Class Location
Storage Height Area Aisle Width
Storage Method: Solid Piled % Palletized %Rack
Rack D SingleRow D Conventional Pallet D Automatic Storage D Encapsulated
D DoubleRow D Slave Pallet 0 Solid Shelving D Non-Encapsulated
D Multiple Row D Open
Flue S11acing In Inches Clearance From TQI! of Storage to Ceiling -
Longitudinal Transverse Ft. In.
Horizontal Barriers Provided
SUBMITTAL SERIAL N0:2932HY7
TAYLOR MADE CANOPY ADDITION .15/1500
SUMMARY OF SPRINKLER OUTFLOWS
ACTUAL MINIMUM
SPR FLOW FLOW K-FACTOR --------
10 74.45 60.00 11.20
11 73.78 60.00 11.20
12 66.37 60.00 11.20
13 62.28 60.00 11.20
14 60.39 60.00 11.20
15 60.00 60.00 11.20
TOTAL WATER REQUIRED FOR SYSTEM
OUTSIDE HOSE STREAMS AT 0
TOTAL WATER REQUIREMENT
PRESSURE REQUIRED AT 0
MAXIMUM PRESSURE UNBALANCE IN LOOPS
MAXIMUM VELOCITY FROM 5 TO 6
PRESSURE --------
44.18
43.40
35.12
30.92
29.07
28.70
397.27 GPM
250.00 GPM
647 .27 GPM
80:39 PSI
0.00 PSI
22.21 FPS
10-03-2012 PAGE 1
SUBMITTAL SERIAL NO:2932HY7
TAYLOR MADE CANOPY ADDITI9N .15/1500
' ---Location
From To
Flow
in
GPM
Pipe'·
Size
IN
Fittings
&
Devices
Equiv
Length
Ft
14
13
12
6
10
6
5
4
2
1
0
15
Q
14DQ
Q
13DQ
Q
60.00
60.39
120.39
62.28
182.67
12DQ 66.37
Q 249.04
11
Q
l0DQ
Q
6DQ
Q
5
Q
4
73.78
74.45
148.23
249.04
397.27
397.27
Q 397.27
2
Q 397.27
2.203
BN
2.203
BN
2.203
BN
2.203
BN
2.203
BN
2.203
BN
2.703
BN
3.314
BNl
6.357
FM
8.249
FM
L 14.00
F 0.00
T /14.00
L 19.00
F j O .00 T . 19. 00
L 20.00
F 0.00
T J 20.00
L, 34.00
F 4.80
T/38.80
L
F
T
L
20.00
0.00
20.00
33.00
F=E F 4.80
37.80 T
@; 22.00
29.90
51.90
F=2T
F=2E
L
F
T
9.00
37.80
46. 8.0
L, 150.00
F _ ~LOO
T 150.00
L 118.00
F 42.28
T 160.28
1
/I'/
I ._ 8.249 L 31.00
QI 397 .27 1 F=GV,CV,E, F 25.84
.\ ; FR is• T 56. 84
V,iCTAULIC SERIES 717 -FIRELOCK
10-03-2012 PAGE 2
Friction
Loss
PSI/Ft
Pressure
Summary
PSI
C=120 PT
PE
0.0268 PF
28.70 ( 15)
0.00
0.38
C=120 PT
PE
0.0971 PF
29.08 ( 14)
0.00
1.84
C=120 PT
PE
30.92 ( 13)
0.00
0.2100 PF 4.20
C=120 PT 35.12
PE 0.00
0.3726 PF 14.46
PT 49.58
C=120 PT
PE
0.0393 PF
43.40
0.00
0.79
12)
6)
11)
C=120
0.1427
C=120
0.3265
PT 44.19 ( 10) -
PE 0 • 0 0 ill •" ..AA PF 5 .39 ,.2_5 ll"--"'-·.
PT~49.~-8 6)
p ~: 9
PF .95
C=120 PT
PE
0.1210 PF
C=120 PT
PE
0.0051 PF
C=120 PT
PE
0.0014 PF
C=120 PT
PE
0.0014 PF
CHECK VALVE
59.60
0.43
5.66
65.69
0.00
0.77
66.46
0.00
0.22
66.68
13.43
0.08
0.20
5)
4)
2)
1)
PT 80.39 0)