Loading...
HomeMy WebLinkAbout2479 OCEAN ST; ; AS000209; Permit10/29/25, 2:39 PM Job Address: Permit Type: Parcel No: Lot#: Reference No.: PC#: Project Title: Applicant: about blank Fees ($) 190 AS000209 Permit Data City of Carlsbad Sprinkler Permit Permit No: AS000209 24 79 OCEAN ST Status: ISSUED SPRINK Applied 12/15/2000 2030210400 Approved: 1/30/2001 0 Issued: 1/30/2001 Inspector: RESIDENCE 2479 OCEAN ST Owner: DAY FAMILY TRUST 05-12-87 Add'I Fees ($) 0 10429 REXFORD CT CYPRESS CA Total($) 190 Balance($) 0 1 /1 CONTRACT NO. 0& -14 7 SHEET No_L_oF __ DATE /Z.-/3-oo LOCATION _-z.,-=-_..:..;;H.D~_....,..C~A-..:.i.t"-', C,::;.· ;...' ---'--(.:.....:/ b"--"-.><.,_I /.' ..... , --=~-'-?_A-=C'""""l-'V...,,C.:;;....;;...) _______________ ~~ NOZZLE FLOW PIPE FITTING PIPE EOUIV. FRICTION 11EOUJnED HYD. TYPE !l IN SIZE a LENGTH LOSS P.S.I. REF. Pl ELEV. NOTES LOCATION G.P.M. DEVICES P.S.1./ FT 0 K'..OC 0 { ,, /XL . -, L<~ltj. i PT q, 60 -z_. ""3,;:£_ 1.x: '> FTG. !? ri "'<=: , / ~ ~, 2.K 0 )3 {PIA TOT. I~ ,0::.,iJ7 f'E ----J;,{1,;;,z7 Q LGTH. PT 'U l5' C-1/ 1C', 15" -=-rG. rr 0 ror. PE 13 a (' I 'I-t..-7 .._GTH. 16 PT~. 61 ~ -,;, t; ,__ __ {'~.,... ~ FTG. I'?.-rr , 6 7 1-,2-.k 0 13 [Pw for. ~ ~ .O'YJ7 PE_______. -;, I_'<; ~~TH. a r r , o. 2. -:-::. / q 13:. I J ' _, 0 ~TG. ~-PF I A'3 a -7,,,. c Pv~ [DT. I,.,. I !6,;:; Vi: -~ -dJ -----I II !,.{ /2.-' .._GTH. I ':'" Pr / I, 7 -~ ,... -. --~ a _.., ;.-, -:-:-,......, -'): T '7 -: TG. PF /. ,, ,:) ~ I.-°') P1 0 I 1 lPvc_ fo-T. -: Jj{ I q PE -- 0 __ G f H. PT ---::. :.? FTG, PF 0 f6T. PE (" -7o;._'/l.--z._ ,' ._,GH·L '~~,7 PT:. ~ '.J !) ,.., . _ _.,----, a -:;; ~ '-LO()f'f -.-:·,,e--',;) -10. ~~ Pr-I -JO _.., 1 0 -; f'PvC : :;.-e_~ TOT. ) : .; I crF & ri=;-- I 9 }'' 5,,._-½ _GlH. ---1-"' PT.:,, ..,1 ) c:: ,., ., ,;;-,c,~: { .-1s::,-1s 0 c.. ~ ~ ~ ,7 fTG. ~ ~ PFIU. ~ -i __ ,,.,'7 '.;, .I -I::'-. 0 -2-; ,: /Pvc c-'J<_C::.;;;c TO-T. q -I I /J,( PE -5 _J~-:, -._ a I .. Zx1.,.., /4 "::.G.l H. -:z-r f:_r I 'r, '36 ~ ?I --)y_T ..-5" FTG-'"2.._ ,! PF-:. ',J c,..C>i"..'/?z. 0 18 CP'l.l ?.,x. ~ -= -z., . lSJT-~ ... --: , oc-;;: -. PE---- 0 LGTH. Pr 0 "C :;, FlG-PF 0 T6T-PE ( ! a I" /',<L..---/1 LGTH. ts~, PT 17. 3,.'.? ,'\ SI :,:-r;:a ~ . , .~ , -. ., 3 2xr~-10 FTG: 7"} PF / _) 7 f.'50 .. f,.(JO/"'-t_' 0 _,.., TQT. PE :::; CF>-c /6 '✓ ?.-~ 7.:'-4 --.,_,, _, /. 3:7 ' . 0 }'[} , .. /Y L ;'a.- -; t.,GTH. 33 PJ -:, 1. 52. J3 ...; 1 I /y:-r FTG-I ':2 PF ~a.;; 0 ?...t CP/c.. I 'f. {?-I TCfT. 1rf.. . !/d,< r,·f ~ 0 j" '3 x,:.,,,t LGTH. 3 Pru;6o T -4 1 /'-L'_t } . .J~ ...,. F TG-10 ~F ?. ! -1 0 -? ,. !< 1SE.R. 10T. ,Jt.../q Pc --t-33 ~ I__::, -5 Pr~--z.Ao7 K 0 /" LG_TH 3-:7 fTG. P-F ,?a. ou COP TOT-7 , IS-6b Pt: ---z. {' ii:. 'r(/,.;. Z..2 LGU:i• "70 P_T "3;,.9; S-'' 0 ,., -FTG--z:z_ PF ,41 oz,: fvc fo"r. "2.. ,C/?7.../ PE-- ~4" LPJH. ~__. l'T3:C~..., ,V... ~:z 0 ---• FTG, ~v• PF f, o,? --02£ t,,ief!£ ~ PE~ 0 I,, 1~ Ii{-=-z. . ... ~ f~T"'T ,:!>"1 N FTG-2 c'_F '3i :f 1 0-z_t: UP. TQT. -z_z_.. ,JS"tb I'[ ----0 \_.GTH. PT~~.7f3 .5 '33 -f TG· P..f'-~ ;._..-..--=s-;z.¾ 0 0.f EL--90 PSI <J --Pr ·------..--....... ------.. ---. ;;:;0NTRACT NO. 00-/.17 !~AME (?,4 t Rf.5/f){;. NC£ NOZZLE FLOW PIPE FITTING PIPE EOUIV TYPE a IN SIZ[ n LENGTH LOCATION G.P.M. DEVICES '<DC a I I ( 7 ·,a,.,. ::. 4 '1 Lei ll:1 ~ JxF-~ fTG. !::,r:; tB i.,Z: k 0 Cf'./l--Z...)(J{ ::.-"'2... TOT. 9( 2. I _.. Q I I' LGTH. '"="TG- /....CtJr, Q 1.;.s c;_'('VC,. TQT. -?_ I 0 .......__ ._GTH. .:-rG. 0 TOT. -I , ~GTH. ; ' Q FTG. (_ '..-00 P, .. 0-"l,5 cPvc [OT . 17--:I r .__GTH. 0 /::,.,5 -:-rG. 0 13 c.fvc TO-T, L/4 ..-0 /'' _--C1 H. FTG, L.. COPz.-0 I -z._ c.f'vc f6T. 50 0 ..,GTl--1. ~T_G· Q fOT. ! l o '-,---,,---GlH. FTG. 'f L. Cl O r-,_} 0 6 Cf,;c, TOT. 231 0 I--, I,, ~GlH. L-FTG-- 0 19 CPve, -~T-""'ft: 0 I" LGTl-t FlG- 0 IG f..1srg TOT-' .... . ._, a I'' LGTH. FTG; Q / 15 col' TQT. s-,~ l.G_TH. 0 '2 .. FTG-18 0 f'vC. Tor. ~~ a >If LGTH. FTG-------!Y) 0 r,1O, T __o.,:f:""" 0 iY,--LGTH f'TG. 0 I ts c,,f. TOT-z.._~ 0 LGlH· FTG• 0 TC)T. 0 L~JH. r TG- 0 TQT. 0 LGTH. t:' 'J'G. 0 TQT. -0 ~GTH. -r-TG, 0 .0.·r: - --. -..... --·- . FRICTION nEOUtnEO LOSS P.S.I. P.S.1./ FT 1~.T 18_, i_ 0 Pr 4, 5"'~ i(J..560 PE I ;,C, PTZ-4, 4; PF , ,5 . o-;zq PE PT PF PE rr-z..J,4 'l PF 71 , 06'43 f'.i(-- Pr Z.5 ~.:3 PF b. z.;; ,o<=:":o fiE -l,+3_ P rz4, oo PF I. -:; c..... -'2-Zf<'., PE PT Pr Pt;: Pr-z...i . .,;:,o rFi, 7-3 .6cr;,3. PE /1 30 f:_T 2..7, Q !> Pr z,21 , tJ5to PE ---PT Z.<j_,£5" PF /, 0 '3 ,0~4? PE 4, "3 5 Pr'½:'ot: PF ~~ /',70? I' ' • .._; PE ------PJ-:S574~ rF ,z.4 .. ooz. 7 r,--E ---- f• \..,-' Pr$,~'1 PF 4,00 Pc~ P_T3'7, 6J ~F '2,,3· D 7~ 'j. Pc r_r4z..o,-s- rr- PE f'T PF PE l~T Pr re PT Pr ·-----E_L__ Pr HYO. REF. P1 0 I D C. D C A [3 A [3 i R I.A /vi SHEET N0....:Z.:..OF _ DATE IZ-l?-00 ELEV. NOTES 3~ =, {: 3(" --~ b SJ S-I :j~ ~x '3 s I I I I \ \ \ \ Al $ s 3 j -:fk-Ob % "fdPSI ::;;-46' --..... ~. - CENTRAL ROC 9-00 Model ROC -Residential Optin,a TM Concealed 4.2 K-Factor -Fast Response, Residential Concealed Pendent Fuslble Link Automatic Sprinkler Central Sprinkler Company 451 North Cannon Avenue, Lansdale, Pennsylvania 19446 Tel; (215) 362-0700 / Fax: (215) 362-5385 / www.centralsprinkler.com .. Product ~ Description The Central ROC -Residential Oplfma"' Concealed, 4.2 K-FactOI', Residential Pendent Sprinklers are decorative sprinklers featuring a Hat cover plate designed for use in residen- tial occupancies such as homes, apartments, dormitories. and holefs. They are to be used in wet pipe residen~al sprinkler systems for one- and two-family dwellings and mobile '1omes per NFPA 130; wel pipe residential sprinkler systems for residential occupancies up lo and including four stories in height per NFPA 13R; or wet pipe sprinkler systems for the residential portioos of any occupancy pet NFPA 13. The Cover Plate Assembly conceals the sprinkler operating components above the ceiling. The separable two-piece design of the Cover Plate and Support Cup Assemblies allows inslalfalion of the sprinklers and pressure testing of the lire protection system prior lo installation of a suspended ceiling or application of the finish coating to a fixed ceiling. They also permit removal of Sllspended ceiling panels for access to buildfng service equipment without having to first shut down the fire protection system and remove spnn- klers. Also, the separable two-piece design of the the Sprinkler provides for 1/2 inch {12.7 mm} of vertical adjust- menl, to reduce the accuracy to wh!Ch the length of fixed pipe drops to the sprinkters must be cul. The ROC Residential Pendent Sprin- klers are shipped with a Disposable Protective Caps. The Protective Cap is temporarily removed to install the ROC, and then replaced to protect the ROC whfle the ceiling is being installed and finished. The tip of the Cap can also be used to mark the center of the ceiling hole into plaster board, ceiling tiles, etc. by pushing the ceiling product aga,nst the Cap. When !he ceiling 1nst.1!1ation is complete, lhe Cap is removed and the Cover Plata Assembly Installed. Operation: When exposed to heat from a fire, the Gover Plate, wtuch is normally soldered to the Suppon Cup at three points, faNs away !o expose !he Sprinkler Assembly. Al !his point the Deflector supported by the Arms drops down lo ils operational positron. The fusible link of the Sprinkler Assembly is comprised of two Hnk halves whrch are joined together by a lhin layer of solder. When the rated temperature is reached, the solder melts and the two link hillVAS seperate, which then allows thl'! sprinkler to activate and flaw water WARNINGS Thtt ROC Rt111/dt1ntlal Pendent Sprlnklen dHcribed herein must be ln11tafled and maintained In compli• ance with this document, as well as with the appJ;cable standards of the National Fire ProttJctlon As•oclation, in addition to the atandards of any other authorities having Jurisdiction. Failure to do 110 may impair the integrity of these devices. Because of the above cited stipula- tions and the varied nature of ruid•ntial type architecture, there wlfl be some compartment designs which cannot be fully aprinklered In accordance with the recomendatlons ofNFPA 13, NFPA 13D, or NFPA 13R. In th1 event of this condition. consult the a11thorttles having Jurisdiction for gufdance and approval. The owner I• responsible for main• tafnlng their fire protection system and devices In proper operating condition. The lnstalllng contractor or sprinkler manufacturer ahould be contact•d ,efative to any questions. CENTRAL i .•• .,-,, _.·,,,-,,,,-,:,·c-; ·,:-·,.,,-;;, Residential Concealed Pendent Sprinklers No. 4-5.0 Figure 7 • Spacing for Sprinkler at the Peak of a Sloped Ceiling Arst vet1fy that lhe spriril<ler al f18 peal< is c:ons!dered k> be "Ac:oaptable" Of "Ob!llrucled" by the sloped oeiling in ao:ordance with Figu-e 12 Graph. Meas,,xe haizontaly from th& deflecfa to the sfoped celling, lhis ls equal t> 1he -o· dimension in the Figure 12 Graph. If lhe "D" dimension is "Acooptatui", flan Figure 7 applies. If ·o· is "Obstructed", !hen the protection al'M r:A the sprinkler at lhe peak wil be the horizontal distance lo the obstruct• ing ceiling. The minimum distance between sprinklers is mea· sured horizontalfy. Staggenng sp'inkleB will help maintain minimum horizontal distances in dlfflcl.At situations. Dimensions "A· and "B" are measured along !he slope. For angles g,eatel' than 60", verify with Central's Technical Services Department. C ·?/4 k 1----e O ----€--.,< ~ ~-.\: A NFPA mtJllllum 4 ", maximum l/2 of 1he listed spacing that the spnnkler was calculated for. 8-See "E' for minimum spacing. Maximum Listed spacing Iha! the spnnkler was calculated for. c -Maximum of 3'-0" vertically from tile peak. D -Horizontal dislanoo from me deflector to the inlersectir!g sl~ceiling E -NFPA mnnnum of 8'-0" (when minimum of 8'-0" cannot be obtained due lo -o·, a baffle mus! be ins!a~ed between these sprinklers to obstruct the discharge and prevent o::ild- so!der}. See "B" for maximum. F -Acceptable for angles O· to 60". Figure 8 • Sprinkler Location on Opposing Slopes First verify that !he sprinkler nearest the peak is • Acceptable" or "Obstructed" per Figure 14. If •Acceptable", Figure 8 applies. If "Obstructed", the horizontal distance to the opposing slope is to be considered as !he protecled area. The minimum distance belween sprinklers is measured horizon• tally, shown as dimension "E". Staggering the spririkters wiU help maintain minimum horlzontal distances in diff!Cutl si luations. Dimensions ·A· and "B • are measured along the slope. For angles greater than 60°. verify with Centra!'s Technical Services Department. A --NFPA minimum of 4", maximum 1/2 of the listed spacing that lhe sprinkler was calculaled for. B -See "E" for mtnimum spacing. Maximum Listed spacing that the sprinkler was calculated for. C -MaX!mum of 3'-0" vertically from the peak. D -Minimum 4n, Also, see note above. E -NFPA minimum of 8'..Q" (when minimum of B'-0" cannot be obtained due to "B", a baffle must be Installed between these sprinklers lo obstruct the discharge and prevent cold-solder). See ·s· for maximum. F -Acceptable for angles from 0" to 60°. Figure 9 • Sprinkler location on Coffered Ceiling First verify thal •o· is "Acceptable" or "Obstructed" per Figure 13. If "Acceptable", Figure 9 applies. If "Obstructed·, additional sprinklers will be necessary to prolect the flat ceiling area. The minimum distance between sj:M'inklers is measured horizontaHy. Staggering sprinklers will help maintain minimum horizontal distances in difficult situations. Dimensions "A" and "B" are measured along the slope, For angles greater than 60°, verify With Central's Technical Services Department. A-NFPA minimum of4", maximum 1/2 of the Listed spacing that the sprinkler was calculated for. B -See •e· for minimum spacing. Maximum Listed spacing thal the sprinkler was calculated for. C -Maximum 3'-0" vertically rrom the peak. 0 -Refer lo Figure 13. _..-··---e ~-,~~~ . / ...• ·: ·/"t~---·.-../-: ;~:;:,\' };~-:~\·/•::<·/.y~~· :· C ---iL. E --NFPA minimum of 8' -0" (wtlari minimum of 8'-0" cannot be obtained due to ·s·. a baffle must be installed between these sprinklers lo obstwcl the discharge and prevent cold-solder). See ·a· for ma)(imum. F -r\cceplah!e for angles O' 10 60''. ._,.,. Table 1 • ROC Resldentlal OptlmaTIII Concealed Pendent Hydraulic Design Requfrements for NFPA 130 & NFPA 13R Occupancies Mll'llmum Deafan Flow Coverage Multlpkl Area Slngla Sprtnkler Sprlnl<lora 12' X 12' 18 GPM (18.4 P!li) 13 GPM (9.6psi) /31 r3 fm/ 611 I..,,,, (0? !HJ,I 49.1 (l)rn (D l'(i tw) 14' x 14· 18 GPM (18.4 psi) 13 GPM (9.6psi) (4.J• 4,_lr.,) tJB.1 ~n /1.Vt,arl 49.7/r,m/O&i/,at/ 16' X '6' 18 GPM (18.4 psi)1 13 GPM (9.6 psi) /4.9 • 4 9m) M.llpm/121(""1 I 4fllfr,i,•(Or;/;Mr) 18' l< 18' 24 GPM (32 7 psi) • 17 GPM {16 4 psi) (5.h5.$m) 9Mm>(:USwl 64.◄,.,.., (1. 13 /,;tr) 20' ~ 20' 24 GPM (32. 7 psi) 17GPM (16.4 psi) ~-1•6 tm/ IIO. 8 t,,n /2 35 o.,,t (U.4 lpm (I U l\;JtJ Minimum spacing between sprinklers is 8' (2.4 m). Figure 5 • Sprinkler Location for Sloped Celling Note the minimum distance be!Ween sprinklers changes by the angle of the slope. Verify the Listed flows and pressures for "maximum· and ·112 maximum· distances. Dimensions "A" and •s• are measured arong lhe slope. For angles greater than 60", verify with Cenlral's Technical Services Department. \):_, .•. :.~-----,A-_...._ i •., _!_--~-- A -NFPA minimum of 4" (verify "G" dimension minimum of 4"), maximum 112 of !he Listed spacing lhat the sprinkler was calculated for (I.e .. 18' x 18' spacing is maximum of 9'-0" from a wall). B -For angles 0° lo 39" minimum B = 8'-0". For angles 40'' lo 45" minimum B = 9'-0". For angfe!i 46° lo 60' minimum B = 9'-6". Ma)(imum Listed spacing that the sprinkler was calcu- lated for. C -Maximum of 3·.tr vertically from the peak. F --Acceptable for angles 0° lo 60', G -Minimum of 4", for maximum, refer to "A" and measure along slope. figure 6 • Symmetric Sprinkler Location on Opposing Slopes• The minimum distance between sprinklers on opposing slopes is measured horizontally, some difficult conditions can be solved by staggering the sprinklers, thus fncreasing tlie horizontal distance. Remember to measure along !he slope for "A· and ·e·. For angles greater than 60", verify wilh Central's Technical Services Department. A-NFPA minimum of 4ft, maximum 1(2 of the Listed spacing thal lhe sprinkler was calculated for. B -See "E" for minimum spacing. Maximum Listed spacing that the sprinkler was calculated for. C ~ Maximum 3'-o• vertically from the peak. E -NFPA minimum of B'-0" (when minimum or 8'-0" cannot be obra,ned due to "B", a baffle must be inslallad between these sprinklers to ot>strucl lhe discharge and prevent cold-solder). See ·e· for maximum. F -Acceptable for angles 0'1 to 60". • For unequal spacing down from peak, see Figvre 8. / /~. ,/' ' .8 ,,,, / , /' ., A • /' / _ .. , .., ___ ·•·--····•F-···- Figure 2 Resfdential Optima™ Concealed Pendent (Non-Activated) I 1·· l/ 112" . (25 mn1 x 15 mm) \ 1 Reducing Coupllng I ◄ . ·-··"' ··-· -..... . •.. , ..... I 2-1/2" ±1/8" ....... ,~ .. ~---\_ I (63 5 mm ::t 3.2 mmj -, Hole Diameter 1 '1 • ,,.~11::; I I·-· .... H E j.9 1111 [~ ,· j ~ ~ ~ ! ~ N ,ti I ~ I i I, ~;\ l l j i l rrf1·l}r,rh-t,·······!I,,;· :......,.. ........ ....._......,........,.......,__. __ ,.. ~•~.,.-s.:a--:-.-.':"'1t~:."E.O:X,;,it-~7'":"X..-:"4·~-.,:,.~~,~-'..::.·y_~,.-~:7 ~f ---... ~•·······-···--· t ! 3-114" (82.6 mm) Diameter .,..1 :1116" (4 8 mm) Figure 3 Residential OptimaTM Concealed Pendent (Activated) \ \ I I I I l I / I ' L_ I I ' \ I J I ' I I I I I .J ,.__ ,__ 5/8" (15.9 mm) Miri. 1-1/8" (28.6 mm) Max. ~Technical itllData Sprinkler fdentffication Number SIN C2596 Approvals UL & C-UL Listed. MEA (7-95-E) (Refer lo the Design Criteria Section) Maximum Working Pressure 175 psi (12.1 bar) Pipe Thread Connection 112 inch NPT Discharge Coefficient K = 4.2 GPM/psi'r.1 (60.5 LPM/bar1<>) Temperature Ratings 160"F/71"C Sprinkler/135"F/57°C Plate Finishes Sprinkler: Natural Brass Cover Plate: Chrome or Brass Plated; •Fiat While, Bright White, or Custom Painted • Standard Fin;sh supplied when White is specified Physical Characteristic• The Model ROG Residential Optima"'' Concealed Pendent Sprinklers utilize a dezincificalion resislant (OZR) bronze frame and monel thermal sensitive link. The sprinkler frame orifice is sealed with a gasketed spring plate {Belleville Seal) consisting of a beryllium nickel disc spring that Is sealed on both its inside and outside edges with a Teflon1" gasket. The deflector is brass. Design Criteria The Model ROC Residential Optima"' Concealed Pendent SprinklGrs are UL, C-UL Usled and MEA. Approved for use in accordance with current NFPA. standards on we! pipe sprinkler systems. These sprinklers with a maximum ceiling to top of sprinkler deflector distance of 4 inches, have been Investigated for use under smooth flat horizontal ceilings with slopes up to 2 inches per foot using the hydraulic design requirements round in Table 1 _ When unique conditions exist such as sloping ceilings, and when acceptable to the local aulhority, guidance on the placement of residential sprinklers on sloped ceilings has been provid8d irt Figures 5 • 14. This information will provide the minimum spacing requirements necessary for preventing the wetting (i.e., cold soldering) of the heat responsive element (Hnk) of a Mn-operated Central Model ROC, which Is adjacerit to one, which has operated. In these situations the minimum required sprinkler flow rates given in Table 1 should be used. Your local authority should be consulted to determine the number of sprinklers required in lhe hydraulic design area. The Model ROC Residential Oplima111 Concealed Pendent Sprinklers are onry listed with the Series GB4/ROC Concealed Cover Plale Assembly. The minimum required flow rates for systems designed to NFPA 13D or NFPA 13R occupancies are given in Table 1 as a function of temperature rating, ceiling lo top of deflector distance, and the maximum allowable coverage arsas. The single sprinkler flow rate is the minimum required discharge from the most hydraulically demanding single sprinkler and, th@ multiple sprinkler flow rate is !he minimum required discharge from each of the total number of "design sprinklers" as specilied in NFPA 13D or NFPA 13R. TIA 99-1 (Tentative Interim Ammandment) with an effective dale of May 22, 2000 states that the minimum required discharge from each of Iha "design sprinklers" for systems designed 10 NFPA 13 mus! be calculated based on delivering a minimum design density of 0.1 gpm'sq. fl. for each of the !isled coverage areas shown in Table 1. If the now rates listed 1n Tabre 1 exceed a minimum design densityof0.1 gpm/sq. ft., then the flow rates in the fable shall be used. Consult the authority having jurisdiction regarding the application of this TIA to the currently adopted NFPA 13. Model ROG Residential Pendent and Recessed Pendent Sprinklers must be installed using the obstruction criteria for axlendf!d coverage sprinklers found in the current edilion of NFPA 13. NOTES Resident/al FINI Sprinkler Systems should_ only be d11Blgned and Installed by thoN competent and completely familiar w;th automatic sprinkler system d••lgn, fnst•"•tlon procedur-es, end t.chnl(ICHIS. The •prlnkler must be secured in position by firmly fastening the sprinkler .system pipfng to ~ structure. If the sprinkler Is not pro,»rly ncured In po•ltfon, rNCtfon forces rHulting from sprinkl&r opt,ration eould alter Its orientation snd Its water distribution pattern. The sprinkler escutcheon cannot btl us«J to hold the 11prfnk~r In position. Several criteria may apply to the lnstallatlon and usage of each sprinkler. Conuq1.1t1ntly, It I• recommended that the sprinkler system designer review and devtilop a worl<fng understanding of the compt.te fist of crlterl11 prior to lnltlatlrrg the design of the sprinklH system. Questfons cone.ming sprlnk,.r Installation and usage criteria, which are not covered by the following lnstroctfons, should be submittltd to Central Sprinkler. Include sketches and technical details as appropriate. In some Instances, the requimments of this document may concern specifications which are more stringent and which take precedence over tho. sptH:m.d In NFPA 13, NFPA 130, NFPA 13R, or by the authority having Jurisdiction. Figure 1 4 ROC Sprinkler Wrench (1265) . I Figure 13 -Obstruction to Discharge by Intersecting Flat Ceiling If "O" is "Obstn.relacr per Figure 13 Graph, lhen -o· is lo be considered the area of coverage and additional sprinklers along the horizontal ceiling will be necessary, Only if "O" is "Acceptable" can "A" be considered 1/2 of Iha maicimum Listed spacing lhat Iha sprinkler was calculated for. Dimen- sion "A" IS measured along the Slope. :· ~-! ~-i ·--F i -r • --·1:· '.· --- : • ~CC:ei,,.J. i • -../-=: ~ ·- (;r:.:., ; • --1 t-11 -_-tj •• I t-: -~ • __ ·:t,:: . , I ' I -. 4 • 1·. --_, ... -----A------,. ------]--• .: . I-. ·1··-+---f--1....-+--1 ;. _ : I J • -~ ~-·J _ :_:J. L.:·:_-~--~......., r •· ,-fr •• • :NI ,.. ,111· n-•· •· ••· 4&• a· •• .,. -r· r•n11ev .... 1 A-Maicimum 1/2 of the Listed spacing lhat the sprinkler was calculated for. D -Distance to intersecting horizontal ceiling. f -Acceptable for angles O·' to 60n. Figure 1-4 • Obstruction to Discharge by an Opposing Sloped Celling Acceptable 21l'•=-+---i /I 4' 1----+---f--t-~t-Ill"• 1IL,,i!'--f If ·o· is "Obstructed" per Figum 14 Graph, then the horizontal distance to Iha opposing slope is the extent or coverage end additional sprinklers wiU be necessary to protect lhe remainder of the opposing slope. Only if ·o· is "Acoeplable" can "A" equal 112 of Iha maximum Listed spacing that the sprinkler was celwlated for. Dimension "A" "D" ----------llf l is measured along the slope. ~ Installation The Central ROC Residential Optima'" Concealed Pendent Sprinklers must be installed in accordance with lhe following instructions: NOTES Damage to the fusible Link Assembly during Installation can be avoided by handling the sprinkler by the frams anns only (i.e., do not apply pressurtJ to the fusible Link Assembly), and by using the app,op,1ate sprinkler wrench. Damaged sprinklers must be replaced. A leak tight 112 Inch NPT sprinkler joint should be obtained with a torque of 7 to 14 It.lbs. (9.5 to 19. 0 Nm}. A maKimum of 21 fl.lbs. (28.5 Nm) of torque is to be used to install sprinklers. Higher levels of torque msy distort the sprinlder inlet with consequent leskage or impaimlent of the sprinkler. (In feet) 3, t--+---:11'---t-.......,.f-;~. l ..._....,,,. ... -· I .---------1r. , . ._....___,..___,_-'-.____.__...___. 10'' H;·· 20-25·' 30·' 35° 40• 45" "F" or "G'" (whic:hever is greater) (in degrees) ~ ~{: A-NFPA minimum of 4", maximum 1/2 of Iha Usted spacing that the sprinkler was calC1Jlated for. }j D -Dislance lo opposing sloped ceiling. F & G -Acceptable for angles 0" to 60". Step 1. The sprinkler musl onty be installed in the pendent position and with ltle centerline of !he sprink18t' perpen- dicular lo the mounting surface. Step 2. Remove the Protective Cap. Step 3. With pipe ttvead sealant applied lo Iha pipe threads, and using lhe Roe Wrench shown in Figun, 1, install and lighten the Sprinkler/Support Cup Assembly into lhe filling. ROC Wrench will except a 1/2 inch ratchet drive. Step 4. Replace the Protective Cap by pushing it upwards lmfil it bottoms out against the Support CUp. The Protective Cap helps prevent damage 10 the Denector and Atm.<1 during ceiling instanation and/or during applic.ation of lhe finish coating of the ceiling. It may also be used lo locate the (',enter of the dearance hole by gently pushing the ceiling material up against the center point of the Cap. NOTE As long Rs the Protective CRp remains in place, the system is considered to be •out of Service• Step 5. After the ceiling has been completed with the 2-1/2 inch (66. 7 mm) diameter dearance hole and in prepara- tion for installing the Cover Plate Assembly, remove and dis- card the Protective Cap, and verify that lhe Deflector moves up and down freely. If the Sprinkler has been damaged and the Deflector does not move up and down freely, replace the entire Sprinkler assembly. Do not attempt to modify or repair a damaged sprinkler. Step 6. Screw on the Gover Plate/ Retainer Assembly until its flange just comes in contact With the ceiling. Do not continue to sorew on the Covs Plate/ Retainer Assembly such that It tills a ceiling panel out of ils normal position. If the Cover Plate/Retainer Assembly cannot be engaged wilh lhe Support Cup or tt,e Cover Plate/Retainer Assembly cannot he engaged sufficienlly to contact the ceiting, the Sprinkler Fitting must be reposilioned.lhe Sprinkler Fitting must be repruutioned. cent.rel '?14 99::i l:iU4.:J Royal FlushTM J/qg --1 Concealed • Standard Response (GB4) Quick Response (GB4-FR) Automatic Sprinklers Manufaetured by: Cclltral Sprlr:kler :::ompany 461 North Cannon Avera.e, Lan$daki, Pennsylvania 19446 •Product Description The Central GB4 and O64-FR Royal Flush Adju1table Concealed Sp,v1i<•lei'S are standard spray sprinklers Iha• allow m,•r ½" (12.7 mm) of ad~ent wit'l an aesthelieally pleasing cover piste design. The GB4 ls a etandard response sip rlnkler using 8 5mm glasa bulb 8Md the QS,4..FA ls a quick re,ponae sprinkler uslhg a 3mrr. glaa1 bulb. Theso sptin!ders are per1ec1 ~°' applicatiOfls fn 1/gh~ or ordina,y hazard at standard epaclng tor projects that r9QUire UL, cUL, MEA aoo/or FM Lis•.mg and Approvals. By adding the option of the c1ea1 room seal, lhl GB4 ca,, be used In areas where dust or air 110'A cannot ts allowed betwNn the room and the area above the ceijlng, This option is used extenslvety In "clea'I room· appllcatl0M where the Integrity Of the ceiiing is crit,cef Th11 Qean Room Seal Is U.l. listed tor G84 only. H le lllQI Utbld for the GB4-fR, SH the c/Hfl room snl data sheet for details. Inherent In lhe design s !M capa~l1ty to compensate fo• oeiring heights wh!cr vary with rwspect to the s,:-r,nkler system piping. This signltlcanl feature allows the Central G84and G84-FR sprinklers :o Nat flush with ceilings t'iat can fluc!LiBto neany ½'(12.7 mm) in reigh:. The 3'•" (82 s mm) diameter cover plate pre~ents an unobstructed and aestheilc appearallOR. 11,e tliln cover plate projects a n-sr9 ¥.,' (-4.S mm) befOW the ceiling. The operating mecharniir.1 c:ons!eit .. ot a liqtild•l'illec:I 3mm o~ 5mm frangible capeule that la 011ry 20 rn:n in lengti-. OpeP'ltlon: The Centra' C84 arid G84-FR sprinklers ab$orb heat lrrough the celling cover plate Which 1$ oolde1vd 10 the adjustable retaln&r ring v.itt-a tusibie alloy. At the rated temperature, t!io alloy fu&eti, resu!ting in the plat• dropping away from the sprinkler. Atthis point. the dellector drops down below the ce!llng exposing the glasa bulb to the t!res heat The heat burst$ the bulb resulting In 8 ra;)id ex;:iulslon of tre saa11ng cap. Water can now flow in a patt•rn engineered to meo! the coverage requirements. r.iii Technical i Ii Data Model: 084 or 1384-FR Style: Concealed (adjustable) Options: •ciean Room Seal (Part #10908100) ' Clufl Room SN/ /f UL & t:UL Ll1t'1d fr;rGS4 D<lly. It ;~ not Approwd (rJ( <384-FR. ,._,. flllllt,nc~ CIHn Rool?i Seal rt111tt $11Ht for motr1 lflfotmatlo,1. Wrench: G84 (Pan #1075) or Orifice Size: ½" (12. 1 'lln) K-Factor: 5.6 (80.e metric) Thread Size: ½" (15 •nm) N.P.T. Approvals: U.L., cUl, •F.M., M.EA (64-93-E Vol. II) • F.\1 Approval ts to, s/endara r•&{)(Jflse only fQf ootn J/ghf and ordinary hazard in accotda'l..."'6 "ith FM guidelines. 7'e:11peraturo Rating: 155°F/68''C Sprlnkte1 wilh 135°F/57°C Cover Plate 200°F/93.3"C Sprinkler w1tti 165°F,74°C Cover Plate Mal(irr.um Working Pressure: 250 pal (17.3 bar}•U.L. & clJI. ot1I• 175 psi (12.1 barj·a'I other ager.c/es Factory Hydro Test 100% al 500 psi (34.5 barJ 1/2 11 (12. 7 mm) Orifice Adjustable Concealed Ceiling Sprinkler Standard Finishes: Sprinkler: brass Cover Plate; brass, chrome plated, white painted, or custom painted Length: 2½" to 3" (63 s mm to 76.2 mm) Cover Plate: 3¼" diameter (82.5mm} CeMing Opening: 2½" ±¼' diameter (~S mm± 3.2 mm) Adjustability: Y~" r12 . .,, mm) Weight 6.6 oz. r,s, g,am.) with celling plate assembly Patents: Patent #4,014,388 other patents are pending. N•, 1-a.o Old Cat. No. 3,,10,1 ,.. .... Dec 13 00 09illa Central Figure 1 GBUR (shown.I Royal Flush AdJuetable Concealed Pendent (Non-Activated) ' ms· (I I l,n-,,, .-,er.; ' l I I I I I I I If i]~ t,I'" ~, '" ::: ., ,,lj ·1~ l i l I I_ w ' -.---~' I I C&Jlng L,ne Figure 2 0 G84 or GB4-FR Royal Flush Adjustable Concealed Pendent (Activated) 1 1/Z"(l~m) NI-'- . , / \_2 11~• J.1/8"itil Smm .t.~.2,,,m)_J___,,.-: ___ _ H<llt Oiamcittlf , / , x---1 ~- ~--J:l/4" ·i!O &mrt1 ::r. IS.4rnrr,} I I I i I '· -· ♦ i Cedr.g L;ne 0 . 2 Dec 13 00 09:t2a lffll Cara & ~ Maintenance Sprinklers must be handled carefully. They mtJSt not be transported or stored where ambient temperature may exceed 100"F/38"'C. For best results, store them in a dry. cool location In the original shipping package. 0o not install sprinklers that have been dropped or visrbly damaged. Sprinklers must never be painted, coated, plated or altered in any other way from manufactured condition or they may not function property. Any sprinklers altered in such manner muat be replaced. The owner Is responsible for the proper operating condition of all fire protection devk:es and acce~ories. The NFPA standard 25 enlitied, wlnspec'tlon Testing and Main/Mance of Water-Based F;,. Protection Systems"contaJns !J.Jidelines and minimum maintenance requirements. Furthermore, the local Autnorfty Having Jurlsdlclfon may have addi- tional regulations and requirements for ma/ntena:ice, testing. and Inspec- tion that must be obeyed. It is advisable to have sprinkler systems inspected regularly t-y a qualffled inspection service. Length of time between such Inspections can vary due to acclSllblllty, ambient atmoaphere, water supply, and site activity. Do not attempt to reassemble 0t otherwise reuse a sprinkler tnat ttas operated. Replace any sprinkler exhibiting corrosion or damage; always use new sprink.lers of the same orifice, style, and temperatur& rating as replacements. Because the discharge pattern is critical to protection of life and property, nothing Sl'lould be hung or ~1998 Cen1ral Sprinkler Company Fr1nted In U.S.A. attached to the sprinkler. Such obstructions must be removed. In the e,·ent that construction has altered the original configuration, aclditlom11 sprinklers should be installed to maintain the protection level. Do not attempt to replace sprinklers without first removing the fn protec- tion system from service. Be certain 10 secure permission from all authori- ties having jurisdiction, and notlly all personnel who may be affected duril'\g system shutdown. A fire watch during maintenance periods is a recommended precaullon. To ~emove the system from service node, first refer to the system operating guide and valve Instruction, Drain water and reNeve pressure in the pipes. Remove the e>dsting unit and install the replacement, using only the recommended sprinkler wrench. Be certain to match model, style. orifice, and temperature ratlrig. A fire protection aystem that hae been shut off after an actlvatJon should be repaired ancl returned to service imrr.e<ffately. Inspect Ile entire system for damage and replace or •epa1r as necessary. Sprlnklers that did nor opera1e but were subjected to corrosive elements of combustion or excessive temperatures should be inspected, and repla08d it need ba. The Authority Having Jutlsdlction will detail minimum replacement require- ments and regulatlons. leak stopping products, such as water glass, must NEYIB be Intro- duced Ir-to a sprinkler system. CENTRAL Central Sprfnlcler Company 451 Nortll C111non Avenue,lallldate, PA f9446 PHONE (215} 302-0700 en (2fS; 3132·5315 GtlarantN: Central Sprinkler Company will repair and/or rwplaoe any products found to be defective In material or workmanship within a period of one year from the date of shipment Please refer to the current Price Lisi for further detaRs of Iha warranty. .. Ordering 1±:1 Information Ordering lntormatfan: When placing an ord•~. lridicate the f\jl product name. Please specify the quantity, modal, style, orifice me, temperature rating, sprinkler finish, cover plate finish, and sprinkler wrench. For speolal painted cover plate finishes, the customer must supply a quick-drying paint, preferably In a 1aoquer-base finish to Insure proper color duplication. Without such a guide, Central Sprinkler Company cannot be responsible for acceptable COior rnatchfng. All custom palr1lng of the cover plate must be completed at the factory. .AvallablHty and Service: Central sprinklers, valves, accessories and other producta are available through• out the U.S. and Canada, and intemaflonally, through a network of Central Sprinkler distribution centers. You may write directly to Central Sprtnkler Company, or call 215-362- 0700 for the distributor nearest Y0&I. Plt9nbl: Patent #4,014,388 other patents are pending. Conversion Table: 1 Inch = 25.400 mm 1 foot = 0.3048 m l !)OlMld == 0.4S36 kg 1 foot pound= 1.36 Nm 1 psi• 6,895 kpa c0.06B9bar = 0,0703 kg/~ 1 U.S. gallon =-3.785 ~ = 3. 785 liters Conversions are approximate. 084.2 ~ '-' •-... IF I ■ ,.,,.,_ T .. -•••••·.-·•• ... .., -•• ,,...,..,, ~..,.,...,.,.. .. ~·. I •• . "· • Dec 13 00 09: 14a ) ,.,"\ J ' . '.,~. ' GB4 Wrench Part 11075) DNlgn Requirements• Standard AppllcatJons 15S"FlfrC and 20fYF/93"C Listing/Approval i Sprinkler Designation !: Bulb Type ' ---------··--·---··1·-·-Ul, cUL, FM, MEA j G84 5mm UL. cUL, FM, MEA I Q84-FR ! 3mm The GB4 Royal Flush Adjustable Concealed Pendent Sprinkler is UL, cUL and MEA Approved tor standard area coverages and standard flow a"ld pressure requirements as specified in current NFPA 13 Standards for llght and ordinary hazard occupancies t1rld FM Approved for light and ordinary hazard In accordance with the F.M. guidelines. The (i84.FR is UL, cUL and MEA Approved for Quick Response Appllcatlons for standard area ooverages and standard flow and pressure requrements as specified In current NFPA 13 Standards In both ordinary and Ugnt hazard. The GB4•FR i8 FM Aporoved (but not as quick response) for light and ordinary haZard in accordance with the F.M. Guidelines. Ceiling cover ptates a~e available in a variety of motaUic or painted finishes. For custom painted finishes, the customer must fumlsh a quick-dryir,g paint. preferably lacquer~based, to ensure propar co!Or duplication. One quart of paint 18 required for each 200 plates. '] Installation of a thread leak, remove the unit, inside the threaded support cup. A apply new pipe ;otnt compound or leak light Joint requm a only 1 to 14 :ape, and relnstan. ft. lbs. (li.5. fl).ONm) of torque. Torque levels greater than 21 ft. lbs. (28.8 Nmt rnsta1ta11on 5equence may diSIOrt the orifice aeal, reeultlng The Central GB4 and G84-FA must in leakage be instafled in conformance with Step 1. The unit must be installed in current NFPA 13 Standards. Oevia• the pendent position. Step 5. To install the celll09 cover tlons from these requirements and plate, manually thread the cover standards, or any a1teraticn to the Step 2. The face of lhe sprinkler relalner Into the support cup. Con- sprinkler assembly itself will void any Mting should be Installed a nominal 2• tinue threading until the cover warranty made by Central Sprinkler ±¼" :so.e mm :te.4mm) behind the retainer's flange rests against the Company. In addition, installation finiShed ceiling line. Adjustments, to surface of the ce!Ung. musl 1110 meet local goveMrrient compensate for variations In fitting provisions, codes and standards, as 'ace to ceiling height. may be made Caution: Special care must be taken applicable. by thteading the cover plate re!alner wnen installing with a CPVC system. in or out of the support cup. Sprinldars must be Installed after the The system plplng must ce p·operty Step 3. Use only a non-hardening manufacturer's recommendect settl ng sized to ensure the minimum re• time for the solvent cement system to quired flow rate at the sprin.-;ler. pipe joint compound. or Teflon• tape. ensure that neither accumulate wilhln Check for the proper model. style. Apply only to the male threads. the sprinkler. orifice size and' temperature rar,,g "Trion 1 .. 4 l1ad•-rl< QI .. OuPo . ..: Corp. Special care must be taken when prior to Jnstaltation. Install sprinklers Step 4. Hand tighten the sprlnkier installing wltn a copper system. attar 1he peping is in p:ace to avoid Sprinklers must be installed only after mechanical damage: replace any into the fitting. Al/Old making contact tne Inside of the sprinkler drop and damaged units. Wet pipe systems with the deflector when using the associaled f~ings have been wire must be protected from freez-jn;. Central Sprir:kte, GB4 Wrench to brushed to remove any flux. ~e- lighten the unit into the fitting. "ihe sidua: flux can cause corrosion and in Upon completion ot the installation, GB4 wrench is designed to mate extreme cases can Impair proper the system must be tested por with tho frame's wrench bosses, sprinkler operation. recognized standa•ds. In the event 3 • ;··--·· ........ ::.?•·::::;·:-;:· }~' . •.:;•