City of Carlsbad
Hazardous Installations
Permit No: U5090120
Job Address: 5823 NEWTON DR Status: ISSUED
Permit Type: HI Applied 11/5/2009
Parcel No: 2120504300 Approved: 11/5/2009
Lot #: 0
Reference No.: Issued: 11/5/2009
PC #: Inspector:
Project Title: SKLZ HIGH PILED STORAGE PLAN CHECK & INSPECTIONS
Applicant:
CROWN LIFT
12255 KIRKHAM RD
POWAY, CA
619-696-6747
Owner:
R P H INDUSTRIAL L L C
DEPT #207
P0 BOX 4900
SCOTTSDALE AZ
Fees ($) Add'I Fees ($) Total ($) Balance ($)
L308 0 308 0
about:blank 1/1
CITY OF
CARLSBAD
U S 0 ? 0 ( :1-0
PLAN CHECK REVISION Development Services
APPLICATION
Building Department
Av 1635 Faraday nue
- B-15 760-602-2719
www.carlsbadca.gov
Plan Check Revision No. f& OS I S4 Original Plan Check No. clRoct
ProjectAddress e-o- 42 _Date-- 4 ate_ô\E O
___ ____________ Email Contact \u-ec Ph oc ___________ ___
Contact Address 'YR_(_\3OCity Cc(\5\\ck zip 4
General Scope of Work __Co RcAc.\1_n
Original plans prepared by an architect or engineer, revisions miit be signed & stamped by that person.
1 Elements revised:
tR Plans Calculations E1 Soils L1 Energy 0 Other
2
Describe revisions in detail
3
List page(s) where
each revision is
shown
4
List revised sheets
that replace
existing sheets
0'--) s 03
U
5 Does this revision, in any way, alter the exterior of the project? El Yes ER No
6 Does this revision add ANY new floor area(s)? El Yes 0 No
7 Does this revision affect any fire related issues? Yes J No
8 Is this a complete set? Yes 1 No
LI
£Signature
1635 Faraday Avenue, Carlsbad, CA 92008 Phone: 760-602-2717/ 2718/ 2719 Fax: 760-602-8558
www.carlsbadca.gov
1. Summary Table VLE COPY
1.1 High Piled Storage
TOPIC CODE SECTION CRITERIA/REQUIREMENTS
Type of Construction (Existing) VN
Approximate Square Pro-Performance Portion of the Building:
Footage Offices & Showroom: 11,917
Warehouse: 34,523
Building: 150,386
Occupancy CBC Sections 302 Mixed Use Groups B [Offices], M [Retail/Showroom] and S-i
-312 [Storage] Occupancy. No fire barrier required between B, M
and S-1 Occupancies in a sprinklered building.
Hazardous Materials NA Below exempt amounts.
High Piled Storage CFC 2302. 1, Commodity: I-IV and High Hazard [Cartoned Unexpanded
Commodity 2304.2 & 2310 Group A Plastics]
Maximum Storage Height: <26.5'
Maximum Ceiling Height: :530'
Minimum Required Aisle Width: ~:8'
High Piled Storage Area: >2,500 square feet
Storage Method: Single-Row, Double-Row, Multi-Row Racks
and Palletized Storage
Automatic Sprinkler NFPA 13 (2002 Rack Storage:
Protection Edition) Required & Existing: K-14 ESFR, 12 heads [upright or
Tables 12,3.2.3.1, pendant] calculated @75 psi
12.3.2.2.1(b) **36" clearance required between the top of the storage
Section and the sprinkler deflector for sprinkler
12.3.2.5.1.2 Hose Demand: 250gpm
Offices [Not Within the Scope]:
NFPA 13, (2007) Light Hazard Occupancy
Edition 0.1/1500
Table 14,4.1 Hose Demand: 100 gpm; Duration: 30 mm.
Smoke and Heat CFC 910.3, & Required at a minimum ratio of 1:40
Vents Table 910.3 Existing building has minimum ratios of 1:50, Therefore
CFC Table 2306.2 additional skylights will be converted to smoke and heat
vents.
Curtain Boards CFC 2306.2, Not Required by CFC Table 2306.2.
910.3.5 Not required by CBC unless >50,000 sq. ft. of undivided
area. Will be appealed.
Building Access CFC 503 & CFC Access roads within 150' all exterior walls.
2306.6 Access doors required in each 100' section along all
exterior walls of the building which face a fire department
vehicular access road,
Access roads are existing and were approved as part of the
original building plans.
Access doors are provided within the high piled storage
area along the exterior walls that face a required access
road [i.e. three sides].
Rev 1.0 Klausbruckner & Associates
4.3 Building Access/Doors
Where access is required in CFC Section 503, fire apparatus access roads shall be provided
within 150 feet of all portions of the exterior walls of the first story of the building or
facility as measured by an approved route.
Fire apparatus access roads shall have an unobstructed width of not less than 20 feet,
except for approved security gates in accordance with Section 503.6, and an unobstructed
vertical clearance of not less than 13 feet 6 inches. The fire code official shall have the
authority to require an increase in the minimum access widths where they are inadequate
for fire or rescue operations. Fire apparatus access roads shall be designed and maintained
to support the imposed loads of fire apparatus and shall be surfaced so as to provide all-
weather driving capabilities. The required turning radius of a fire apparatus access road
shall be determined by the fire code official. Dead-end fire apparatus access roads in
excess of 150 feet in length shall be provided with an approved area for turning around fire
apparatus. The grade of the fire apparatus access road shall be within the limits established
by the fire code official based on the fire department's apparatus. Fire department
vehicular access exists on all four sides of the building.
CFC Section 2306.6.1 also states that a minimum of one access door shall be provided in
each 100 lineal feet, or fraction thereof, of the exterior walls which face required fire
apparatus access roads. Emergency vehicle access roads and doors exist on the east of the
building. Access doors are provided in each 100 lineal foot section of exterior wall facing
the required high-piled storage roadway. (Attachment #9)
Access doors have been provided along the exterior wall for the three sides of the
warehouse that face a required access road.
4.4 Smoke and Heat Vents
Per CFC Table 2306.2 and Table 910.3 [as amended by Carlsbad Fire Department], smoke
and heat vents are required at a ratio of 1:40 [one square foot of vent per 40 square feet of
floor area] (Attachment #10).
Per CFC 910.3, where installed in buildings equipped with an approved automatic sprinkler
system, smoke and heat vents shall be designed to operate automatically. The effective
venting area shall not be less than 16 square feet with no dimension less than 4 feet,
excluding ribs or gutters having a total width not exceeding 6 inches. Smoke and heat vents
shall be located 20 feet or more from adjacent lot lines and fire walls and 10 feet or more
from fire barrier walls. Vents shall be uniformly located within the roof area above high-
piled storage areas, with consideration given to roof pitch, draft curtain location, sprinkler
location and structural members.
Smoke and heat vents are existing at a ratio of 1:50. Therefore additional skylights will be
converted to smoke and heat vents.
Rev 1.0 Klaus bruckner & Associates Page 8
0
•
-
JSG R PXE
ALUMINUM SMOKE HATCH SKYLIGHTS - CURB MOUNT AND SELF FLASHING'' . . P?
Smokehatch skylights shall be Skyview) acrylic dome skylight model# 5'1 J as manufactured by Solar Industries, Inc., Tucson, Arizona. They
shall be factory-assembled units each consisting of a high impact acrylic single or double dome, thermo formed from Solar Industries acrylic material. The
dome assembly shall be attached to the frame by a hinge bracketThe dome assembly shall be compressed loaded by torsion springs and secured on the
opposite side by UL listed and FM approved fusible link Skylight frame shall be mill finish or bronze painted 6060-T5 extruded aluminum with a minimum .
wall thickness of 070 The retainer cap shall be mill finish or bronze painted 6063 T5 extruded aluminum with a wall thickness if 060 Skyvie S'lights
have mitered and :heliarc welded watertight corners, with an integral condensation and weepage gutter. High impact acrylic dome shall be t .
clear, bronze, or white. All units are, guaranteed against defective materials and workship.. . . .
C
Outer Acrylic
Double dome glazing Dome 187 thick
(4'x 8 Units)
6063-T5 .060 extruded
. Single dome glazing
aluminum retaining cap
retaining screws *
Weep holes at corner /
Hinge bracket
_
6063-T5.060 extruded I . . . . . . . .. .. .. . .. . aluminum smokehatch
base frame
2x wood curb & flashing
02003 Solar Industries Inc,
.
-All Rigtts Reserved
...