HomeMy WebLinkAbout6221 METROPOLITAN ST; ; AS090027; Permit12/13/24, 4:02 PM AS090027 Permit Data
City of Carlsbad
Sprinkler Permit
Permit No: AS090027
6221
Job Address:
METROPOLITAN ST
Permit Type: SPRINK
Parcel No: 2132600100
Lot #: 0
Reference No.:
Status: ISSUED
Applied 3/27/2009
Approved: 3/27/2009
Issued: 3/27/2009
PC #: Inspector:
Project Title: GASPAR DOCTORS T.I. FIRE SPRINKLER PLAN CHECK &
INSPECTIONS
Applicant:
WEST COAST FIRE PROTECTION
271 ROYMAR RD
SUITE F
OCEANSIDE, CA
(760)754-8472
Owner:
BRESSI RANCH MEDICAL PLAZA L L C
DAVID DIRIENZO
1280 BISON AVE #139-609
NEWPORT BEACH CA
Fees ($) 1 Add'l Fees ($) Total ($) Balance ($)
130 0 130 0
about:blank 1/1
many angles, reducing
assembly effort. This sprin-
kler is available in various
temperature ratings (see
chart on page 2) and fin-
ishes to meet many design
requirements.
The recessed pendent
should be utilized with a
Model V27 recessed
escutcheon which pro-
vides up to 3/4" (19 mm) of
adjustments.
Sprinkler Operation
The operating mechanism
is a frangible glass bulb
which contains a heat
responsive liquid. During a
fire, the ambient tempera-
ture rises causing the liquid
in the bulb to expand.
When the ambient temper-
ature reaches the rated
temperature of the sprin-
kler, the bulb shatters. As a
result, the waterway is
cleared of all sealing parts
and water is discharged
towards the deflector. The
deflector is designed to dis-
tribute the water in a pat-
tern that is most effective
in controlling the fire.
Coverage
For coverage area and
sprinkler placement, refer
to NFPA 13 standards.
MATERIAL
SPECIFICATIONS
Upright Deflector:
Bronze per UNS C22000
Pendent Deflector:
Bronze per UNS C51000
Bulb: Glass with glycerin solu-
tion.
Bulb Nominal Diameter:
El Standard: 5,0 mm
Quick Response: 3,0 mm
Load Screw: Bronze per UNS
C65100
Pip Cap: Bronze per UNS
C65100
Spring: Beryllium nickel
Seal: Teflon* tape
Frame: Die cast brass 65-30
Lodgement Spring:
Stainless steel per UNS S30200
ACCESSORIES
Installation Wrench:
El Open End: V27
U Recessed: V38, V38-3
U Socket: V27
Finishes:
O Plain brass
U Chrome plated
U White painted**
U Custom painted**
U Lead**
155, 200, 286SR Only:
WaX**
U Wax over lead**
For cabinets and other accesso-
ries refer to separate sheet.
NOTE: Weather resistant recessed
escutcheons available upon request.
For K-Factor when pressure is mea-
sured in Bar, multiply S.I. units by
10.0. Teflon is a registered trademark of
Dupont Co.
UL Listed for corrosion resistance in
all configurations.
X4taulic AUTOMATICS P1NRLTERS
FIRE PROTECT ID) 'S
V27, K5.6
Models V2703, V2704, V2707 and V2708
Standard Spray
Upright, Pendent and Recessed Pendent
Standard and Quick Response
PRODUCT DESCRIPTION
These Model V27 standard
spray sprinklers are
designed to produce a
hemispherical spray pat-
tern for standard commer-
V2701 cial applications. They are
V2708 available with either stan-
Recessed dard or quick response
Pendent bulbs. The design lncorpo-
() (j) rates state-of-the-art, heat
<1Fill> responsive, frangible glass
See Victedm bulb design (standard or putrticattnn 10.01
V2707 quick response) for prompt.
V2708 precise operation.
The die cast frame is more
streamlined and attractive
than traditional sand cast
Pendant frames. It is cast with a
V2703 hex-shaped wrench boss to
v27 allow easy tightening from
Upright
TECHNICAL SPECIFICATIONS
Models: V2703, V2704, V2707,
V2708
Style: Pendent. Upright or 9 Recessed Pendent
Nominal Orifice Size:
1/2 (13mm)
K-Factor: 5.6 Imp. (8.1 SI.1)
Nominal Thread Size:
½' NPT (15 mm)
Max. Working Pressure:
175 psi (1200 kPa)
Factory Hydrostatic Test:
100% @ 500 psi (3450 kPa)
Mm. Operating Pressure:
7 psi (48kPa) ' Temperature Rating: See
chart on page 2. Lç)
VICTAULIC® IS AN ISO 9001 CERTIFIED COMPANY
Victaulic Company of America Victaulic Company of Canada Victaulic Europe Victaulic America Latina Victaulic Asia Pacific
Phone: 1-800-PICK-VIC (1-800-742-5842) Phone: 905.884-1444 Phone: 32.9.381-1500 Phone: 610-559-3300 Phone: 65-6235-3035
Fax: 610-250.8817 Fax: 905-884.9774 Fax: 32-9-380-4438 Fax: 610-559-3608 Fax: 65-6235-0535
e-mail:pickvic@victaulic.com e-mail: viccanada@victaulic.com e-mail: viceuro@victaulic.be e-mail: vical@victaulic.com e-mail: vicap@victaxlic.com
2544 Rev.D 8103 5 Registered Trademark of Victaulic isCopynight 23 Victaulic Printed in U.S.A.
I 1
APPROVALS/LISTINGS
Nominal Approved Temperature Ratings °F/°C t
Orifice Size K-Factor
Inches Imperial Deflector
Model millimeters S.LA Response Type UL FM ULC NYC/MEAt CSFM §
V2703 1h 5.6 Standard Upright 135-360 135-360 135-360 135-360 135-360
13 8,1 57-182 57-182 57-182 57-182 57-182
V2707 ½ 5.6 Standard Pendent 135-360 135-360 135-360 135-360 135-360
13 8,1 57-182 57-182 57-182 1 57-182 57-182
½ 5.6 Recessed Pendent 135-360 135-200 135-360 135-360 135-360 V2707 13 8.1 Standard Up to 3/4 Adjustment 57-182 57-93 57-182 57-182 57-182
V2704 1h 5.6 Quick Upright 135-286 135-286 135-286 135-286 135-286
13 811 57-141 57-141 57-141 57-141 57-141
1h 5.6 135-286 135-286 135-286 135-286 135-286 V2708 13 8,1 Quick Pendent 57-141 57-141 57-141 57-141 57-141
½ 5.6 Recessed Pendent 135-200 135-200 135-200 135-200 135-200 V2708 13 8,1 Quick Up to 1h' Adjustment 57-93 57-93 57-93 57-93 57-93
V2708 ½ 5.6 Quick Recessed Pendent 135-200 No 135-200 135-200 135-200
13 8,1 UptoWAdjustment 579 5793
t Listings and approval as of printing. (3 All are approved open, except for areas designated No,
For K-Factor when pressure is measured in Bar, multiply S.I. units by 10.
t MEA#62-99-E. §CSFM#7690-0531:112
RATINGS
All glass bulbs are rated for
temperatures from -67°F
(-55°C) up to those shown
in adjacent table.
Temperature - °FPC
Nominal Maximum Sprinkler Victaulic Glass
Temperature Part Temperature Ambient Temp. Bulb
Classification Identification Rating Allowed Color
Ordinary A 135
57
100
38 Orange
Ordinary c 155 100
38 Red
Intermediate E 175
79
150
65 Yellow
Intermediate F 200
93
150
65 Green
High J 286
141
225
107 Blue
Extra High 1< 360
182
300
149 Purple
- M Open = No Bulb
Standard response only.
All arc approved open, except for areas designated No.
- 150/65 if wax coated.
L___
ORDERING INFORMATION
Please specify the following
when ordering: 0 Sprinkler Model Number U K-Factor U Sprinkler Finish
U Style U Thread Size 0 Escutcheon Finish
0 Temperature Rating U Quantity U Wrench Model Number
1WATRN iNG]
Always read and understand installation, care, and maintenance instructions, supplied with each box of sprinklers, before proceeding with installation
of any sprinklers.
Always wear safety glasses and foot protection.
Depressurize and drain the piping system before attempting to install, remove, or adjust any Victaulic piping products. . 0 • installation rules, especially those governing obstruction, must be strictly followed.
Painting, plating, or any re-coating of sprinklers (other than that supplied by Victaulic) is not allowed.
Failure to follow these instructions could result in serious personal injury and/or property damage.
The owner is responsible for maintaining the fire protection system and devices in proper operating condition. For minimum maintenance and inspection requirements, refer to the
current National Fire Protection Association pamphlet that describes care and maintenance of sprinkler systems. in addition, the authority having jurisdiction may have additional
maintenance, testing, and inspection requirements that must be followed.
If you need additional copies of this publication, or if you have any questions about the safe installation of this product, contact Victaulic World Headquarters, P.O. Box 31, Easton,
Pennsylvania 18044-0031, 610-559-3300.
40.10-2
DIMENSIONS
1 M
(37 mm)
2W
(60 mm) 159
(41 mm)
f r-
(25 mm)
Standard Pendant- V2707, V2708
1W
(41 mm) 2W
(60 mm) I
Standard Upright - V2703, V2704
L_211b" (60 mm) Max Hole
2(51 mm)
Mm. Hole
' ±Finished Surface (30 mm)
Typical Ceiling T49 (27 mm)
MAXIMUM RECESS
-
(75 mm)
MAXIMUM EXTENSION
½" Adjustment
Recessed V2707, V2708
(Drawing not to scale)
2W'(60 mm) Max. Hole
2(51 mm)
Mix. Hole
Typical Ceiling Tile
(33 mm)
Finished Surface (24 mm)___
MAXIMUM RECESS
(75 mm)
MAXIMUM EXTENSION
:Y4" Adjustment
Recessed - V2707, V2708
(Drawing not to scale)
AVAILABLE WRENCHES
V27
Socket
V38 or V38-3
Recessed
V27
Open End
V2107, V2108 Pendent / / /
V2707, V2708 Recessed Pendent V / -
V2703, V2704 Upright - / /
40.10-3
(24 mm)
1vo-
(43 mm)
DISTRIBUTION PATTERNS
MODELS V2707, V2108
K5.6 STANDARD PENDENT AND RECESSED PENDENT
DISTRIBUTION PATTERNS - TRAJECTORY
10' I I I I I I I I 3,0 m
8'
2,4 rn
7 psi
48 kPa
6-
1,8 m
15 psi
103 kPa
4'
1,2 m
30 psi ------
207 kPa
2'
0,6 m
0
0,6rn 1,2m 1.8m 2,4ni 3,0m 3,7m 4.3m
MODELS V2703, V2704
K5.6 STANDARD UPRIGHT DISTRIBUTION PATTERNS - TRAJECTORY
-- -
m
---'c;—
'
-
m
-
_\—
m S\ \
-
2' 4' 6. 8' 10' 12' 14' 16'
0,6m 1,2m 1,8m 2,4m 3.0 nn 3,7m 4,3m 4,9m
NOTES:
Data shown is approximate and can vary due to differences in installation
These graphs illustrate approximate trajectories, floor-wetting, and wall-wetting patterns for these specific Victaulic FireLock Automatic Sprinklers. They are
provided as information for guidance in avoiding obstructions to sprinklers and should not be used as minimum sprinkler spacing rules for installation. Refer to
the appropriate NFPA National Fire Code and the authority having jurisdiction for specific information regarding obstructions, spacing limitations and area of
coverage requirements. Failure to follow these guidelines could adversely affect the performance of the sprinkler and will void all Listings, Approvals and War-
ranties.
All patterns are symmetrical to the centerline of the waterway.
WARRANTY Refer to the Warranty section
of the current Price List or
contact Victaulic for details.
This product shall be manufactured by Victaulic Company. All products to be installed in accordance with current Victaulic installahon/assembly instructions.
Victaulic reserves the right to change product specifications, designs and standard equipment without notice and without incurring obligations,
40.10-4
10'
3,0 m
a
2,4
6
1,8
4
1,2
2
0,6
0
7psi
48 kPa
15 psi
103 kPa
30 psi
207 kPa