HomeMy WebLinkAbout6221 METROPOLITAN ST; ; AS090093; Permit12/13/24, 4:02 PM AS090093 Permit Data
City of Carlsbad
Sprinkler Permit
6221
Job Address:
METROPOLITAN ST
Permit Type: SPRINK
Parcel No: 2132600100
Lot #: 0
Reference No.:
Permit No: AS090093
Status: ISSUED
Applied 8/12/2009
Approved: 8/12/2009
Issued: 8/12/2009
PC #: Inspector:
Project Title: DR. GARY BRAUNSTEIN T.I. FIRE SPRINKLER PLAN CYHECK &
INSPECTION
Applicant:
WEST COAST FIRE PROTECTION
271 ROYMAR RD
SUITE F
OCEANSIDE, CA
(760)754-8472
Owner:
BRESSI RANCH MEDICAL PLAZA L L C
DAVID DIRIENZO
1280 BISON AVE #139-609
NEWPORT BEACH CA
L Fees ($) Add'I Fees ($) Total ($) Balance ($)
130 0 130 0
about:blank 1/1
tqca /Fire & Building
I Products
Technical Services: Tel: (800) 381-9312 I Fax: (800) 791-5500
Series RFII - 56 K-factor
"Royal Flush II" Pendent Concealed Sprinklers
Quick & Standard Response, Standard Coverage
General
Description
The Series RFlI Quick Response
(3 mm bulb) & Standard Response (5
mm bulb), 5.6 K-Factor, "Royal Flush
II" Concealed Pendent Sprinklers are
decorative sprinklers featuring a flat
cover plate designed to conceal the
sprinkler. It is the best choice for archi-
tecturally sensitive areas such as hotel
lobbies, office buildings, churches,
and restaurants.
Each unit includes a Cover Plate As-
sembly that conceals the sprinkler op-
erating components above the ceiling.
The separable two-piece design of the
Cover Plate and Support Cup Assem-
blies allows installation of the sprin-
klers and pressure testing of the fire
protection system prior to installation
of a suspended ceiling or application
of the finish coating to a fixed ceiling.
They also permit removal of sus-
pended ceiling panels for access to
building service equipment without
having to first shut down the fire pro-
tection system and remove sprinklers.
Also, the separable two-piece design
of the the Sprinkler provides for 1/2
inch (12,7 mm) of vertical adjustment,
to reduce the accuracy to which the
length of fixed pipe drops to the sprin-
klers must be cut.
The Series RFll Sprinklers are
shipped with a Disposable Protective
IMPORTANT
Always refer to Technical Data
Sheet TFP 700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Cap. The Protective Cap is temporarily
removed for installation, and then it
can be replaced to help protect the
sprinkler while the ceiling is being in-
stalled or finished. The tip of the Pro-
tective Cap can also be used to mark
the center of the ceiling hole into plas-
ter board, ceiling tiles, etc. by gently
pushing the ceiling product against the
Protective Cap. When the ceiling in-
stallation is complete the Protective
Cap is removed and the Cover Plate
Assembly installed.
As an option, the Series RFll Standard
Response (5 mm bulb) "Royal Flush II"
Concealed Pendent Sprinklers may be
fitted with a silicone Air and Dust Seal
(Ref. Fig. 5). The Air and Dust Seal is
intended for sensitive areas where it is
desirable to stop air and dust travel
through the cover plate from the area
above the ceiling.
WARNINGS
The Series RFII Concealed Pendent
Sprinklers described herein must be
installed and maintained in compli-
ance with this document, as well as
with the applicable standards of the
National Fire Protection Association,
in addition to the standards of any
other authorities having jurisdiction.
Failure to do so may impair the per-
formance of these devices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
Model/Sprinkler
Identification
Numbers
TY3551 (5mm bulb) & TY3531 (3 mm
bulb): maximum 175 psi (12,1 bar) by
UL, C-UL, FM, LPCB and NYC.
TY3504 (5 mm bulb) & TY3505 (3 mm
bulb): maximum 250 psi (17,3 bar) by
UL, C-UL, and NYC. Maximum 175
psi (12,1 bar) by FM.
Technical
Data
Approvals for Series RFll
UL and C-UL Listed. FM Approved.
NYC under MEA 353-01-E. LPCB (Ref.
No. 094a/09 for TY3551 & 094a/10 for
TY3531) Approved.
The approvals apply only to the serv-
ice conditions indicated in the Design
Criteria section and maximum pres-
sure ratings indicated in the
Model/Sprinkler Identification Num-
bers section.
Approvals for Air & Dust Seal
(Part #10908100)
UL and C-UL Listed for use with the
RFII (TY3551 & TY3504) Standard Re-
sponse Concealed Sprinkler.
Temperature Ratings
155F/68C Sprinkler - 135F/57C Plate
20017/93C Sprinkler - 165F/74C Plate
Discharge Coe9ient 11 2) = 5.6 GPM/psi (80,6 LPM/bart 2)
Adjustment
1/2 inch (12,7 mm)
Finishes
Cover Plate: Chrome Plated, Brass
Plated, or White Painted (Custom paint
matches and colors other than white
are available on request.)
Page 1 of 4 JULY, 2004 TFPI8I
Page 2 of 4 TFPI8I
1/2' NPT SEALING
ASSEMBLY
FRAME = = CAP
suppoRl.
CUP WITH - BULB
ROLL FORMED - -
THREADS
COMPRESSION
SCREW
GUIDE
PINS (2)
DEFLECTOR
(DROPPED
DEFLECTOR POSITION)
SPRINKLERISUPPORT CUP
ASSEMBLY
THREAD INTO TAINER
suoni cup THREAD 0 UNTIL MOUNTING CD MPLES
SURFACE IS
FLUSH WITH LEJECTION
CEILING RING
SOLDER 1
I L.
COVER
TABS (3) COVER PLATE/RETAINER PLATE ASSEMBLY
FIGURE 1
SERIES RFII CONCEALED SPRINKLER
ASSEMBLY
Physical Characteristics
Frame .............Bronze
Support Cup . Chrome Plated Steel
Guide Pins ......Stainless Steel
Deflector ...........Bronze
Compression Screw ......Brass
Bulb ...............Glass
Cap ........Bronze or Copper
Sealing Assembly ..........
Beryllium Nickel w/Tetlon
Cover Plate ...........Brass
Retainer ............Brass
Ejection Spring . . . . Stainless Steel
Patents
U.S.A. 4,014,388
Operation
When exposed to heat from a fire, the
Cover Plate, which is normally sol-
dered to the Retainer at three points,
falls away to expose the Sprinkler As-
sembly. At this point the Deflector sup-
ported by the Guide Pins drops down
to its operational position.
The glass Bulb contains a fluid that
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass Bulb, activating the sprinkler and
allowing water to flow.
Design
Criteria
The RFII (TY3551 & TY3504), 5 mm
Bulb Type, Concealed Pendent Sprin-
klers are UL and C-UL Listed as stand-
ard response - standard spray sprin-
klers for use in accordance with the
current NFPA standard. They are FM
Approved as standard response -
standard spray sprinklers for use in
accordance with the current FM Loss
Prevention Data Sheets.
The RFII (TY3531 & TY3505) 3 mm
Bulb Type, Concealed Pendent Sprin-
klers are UL and C-UL Listed as quick
response - standard spray sprinklers
for use in accordance with the current
NFPA standard. They are FM Ap-
proved as standard response - stand-
ard spray sprinklers for use in accord-
ance with the current FM Loss
Prevention Data Sheets.
The Series RFII Concealed Pendent
Sprinklers are only listed and ap-
proved with the Series RFII Concealed
Cover Plates having a metallic or white
painted finish.
The Series RFII must not be used in
applications where the air pressure
above the ceiling is greater than that
below. Down drafts through the Sup-
port Cup could delay sprinkler opera-
tion in a fire situation.
Installation
The Series RFII must be installed in
accordance with the following instruc-
tions:
NOTES
Do not install any bulb type sprinkler if
the bulb is cracked or there is a loss of
liquid from the bulb. With the sprinkler
held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 inch
(1,6 mm) for the 155°F/68°C and 3/32
inch (2,4 mm) for the 200°F/93°C tem-
perature ratings.
A leak tight 1/2 inch NPTsprinklerjoint
should be obtained with a torque of 7
to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi-
mum of 21 ft.lbs. (28,5 Nm) of torque
is to be used to install sprinklers.
Higher levels of torque may distort the
sprinkler inlet with consequent leak-
age or impairment of the sprinkler.
Do not attempt to compensate for in-
sufficient adjustment in the Sprinkler
Assembly by under- or over-tightening
the Sprinkler/Support Cup Assembly.
Readjust the position of the sprinkler
fitting to suit.
Step 1. The sprinkler must only be
installed in the pendent position and
with the centerline of the sprinkler per-
pendicular to the mounting surface.
Step 2. Remove the Protective Cap.
Step 3. With pipe thread sealant ap-
plied to the pipe threads, hand tighten
the sprinkler into the sprinkler fitting.
Step 4. Wrench tighten the sprinkler
using only the RFII Sprinkler Wrench
(Ref. Figure 3). The RFll Sprinkler
Wrench is to be applied to the Sprin-
kler as shown in Figure 3.
Step 5. Replace the Protective Cap
(Ref. Figure 4) by pushing it upwards
until it bottoms out against the Support
Cup. The Protective Cap helps prevent
damage to the Deflector and Arms dur-
ing ceiling installation and/or during
application of the finish coating of the
ceiling. It may also be used to locate
the center of the clearance hole by
gently pushing the ceiling material up
against the center point of the Protec-
tive Cap.
NOTE
As long as the Protective Cap remains
in place, the system is considered to
be "Out of Service".
* Registered Trademark of DuPont
TFPI8I Page 3 of 4
FACE OF CLEARANCE HOLE
SPRINKLER DIAMETER
- \ FITTING DIMENSION C j
SPRINKLER
SUPPORT CUP
ASSEMBLY
(12,7 mm)
THREADED
D ADJUSTMENT
I FACE OF CEILING,
RETAINING RING
MOUNTING
SURFACE
I I
-\ T----- V
3/16"to11/16 MANUFACTURER DEFLECTOR COVER PLATE
(4,8 to 17,5 mm) PRESET GAP IN DROPPED RETAINER
REFERENCE 3/32'(2,4 mm) POSITION ASSEMBLY L COVER PLATE COVER PLATE
PROFILE DEPTH DIAMETER
DIMENSION B DIMENSION A
3-1/4 (82,6 mm) C: 2-3/8" to 2-5/8' (60,3 to 66,7 mm)
3/16(4,8 mm) D: 1-3/4' to 2-1/4" (44,5 to 57,2 mm)
FIGURE 2
SERIES RFII CONCEALED SPRINKLER
INSTALLATION DIMENSIONS
FRAME
ARM
SUPPORT
CUP
LIlI_11
SQUARE
ALIGN
ARROWS WITH
FRAME ARMS k- -ACCEPTS
FIGURE 3
RF11 SPRINKLER WRENCH
CLEARANCE
HOLE -1
FIGURE 4
DISPOSABLE PROTECTIVE CAP
Step 6. After the ceiling has been com-
pleted with the 2-1/2 inch (63,5 mm)
diameter clearance hole and in prepa-
ration for installing the Cover Plate As-
sembly, remove and discard the Pro-
tective Cap, and verify that the
Deflector moves up and down freely. If
the Sprinkler has been damaged and
the Deflector does not move up and
down freely, replace the entire Sprin-
kler assembly. Do not attempt to mod-
ify or repair a damaged sprinkler.
Step 7. When installing an Air and
Dust Seal, refer to Figure 5, otherwise
proceed to Step 8. To attach the Air and
Dust Seal, verify the angle of the out-
side edge of the seal is oriented ac-
cording to Figure 5. Start the edge of
the Retainer in the grooved slot of the
Air and Dust Seal and continue around
the retainer until the entire Air and
Dust Seal is engaged.
NOTE
The Air and Dust Seal is only to be
installed on the periphery of the Re-
tainer.
Step 8. Screw on the Cover Plate/Re-
tainer Assembly until the Retainer -
Figure 2 (or Air and Dust Seal - Figure
5) contacts with the ceiling. Do not
continue to screw on the Cover
Plate/Retainer Assembly such that it
lifts a ceiling panel out of its normal
position. If the Cover Plate/Retainer
Assembly cannot be engaged with the
Support Cup or the Cover Plate/Re-
tainer Assembly cannot be engaged
sufficiently to contact the ceiling, the
Sprinkler Fitting must be repositioned.
Care and
Maintenance
The Series RFll must be maintained
and serviced in accordance with the
following instructions:
NOTES
Absence of the Cover Plate Assembly
may delay sprinkler operation in a fire
situation.
Page 4 of 4 TFPI8I
SUPPORT SPRINKLER FACE OF ORIENT
CEILING SEAL
BEVEL AS
SHOWN COVER
PLATE
RETAINER
ASSEMBLY
£AINER
CLEAN
ROOM
UPOF COVER SEAL
PLATE
FIGURE 5
OPTIONAL AIR AND DUST SEAL FOR SERIES RPII (TY3551 & TY3504)
When properly installed, there is a
nominal 3/32 inch (2,4 mm) air gap
between the lip of the Cover Plate and
the ceiling, as shown in Figure 2. This
air gap is necessary for proper opera-
tion of the sprinkler. If the ceiling is to
be repainted after the installation of
The Sprinkler, care must be exercised
to ensure that the new paint does NOT
seal off any of the air gap.
Factory painted Cover Plates MUST
NOT be repainted. They should be re-
placed, if necessary, by factory
painted units.
Do not pull the Cover Plate relative to
The Enclosure. Separation may result.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, permission to shutdown the
affected fire protection system must be
obtained from the proper authorities
and all personnel who may be affected
by this action must be notified.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic sprinklers must never be
painted, plated, coated or otherwise
altered after leaving the factory. Modi-
fied sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid dam-
age to the sprinklers - before, during,
and after installation. Sprinklers dam-
aged by dropping, striking, wrench
twist/slippage, or the like, must be re-
placed. Also, replace any sprinkler that
has a cracked bulb or that has lost
liquid from its bulb. (Ref. Installation
Section).
If a sprinkler must be removed, do not
reinstall it or a replacement without
reinstalling the Cover Plate Assembly.
If a Cover Plate Assembly becomes
dislodged during service, replace it im-
mediately.
The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. The in-
stalling contractor or sprinkler manu-
facturer should be contacted relative to
any questions.
It is recommended that automatic
sprinkler systems be inspected,
tested, and maintained by a qualified
Inspection Service in accordance with
local requirements and/or national
codes.
Limited
Warranty
Products manufactured by Tyco Fire
PrOducts are warranted solely to the
original Buyer for ten (10) years
against detects in material and work-
manship when paid for and properly
installed and maintained under normal
use and service. This warranty will ex-
pire ten (10) years from date of ship-
ment by Tyco Fire Products. No war-
ranty is given for products or
components manufactured by compa-
nies not affiliated by ownership with
Tyco Fire Products or for products and
components which have been subject
to misuse, improper installation, corro-
sion, or which have not been installed,
maintained, modified or repaired in ac-
cordance with applicable Standards of
the National Fire Protection Associa-
tion, and/or the standards of any other
Authorities Having Jurisdiction. Mate-
rials found by Tyco Fire Products to be
defective shall be either repaired or
replaced, at Tyco Fire Products' sole
option. Tyco Fire Products neither as-
sumes, nor authorizes any person to
assume for it, any other obligation in
connection with the sale of products or
parts of products. Tyco Fire Products
shall not be responsible for sprinkler
system design errors or inaccurate or
incomplete information supplied by
Buyer or Buyer's representatives.
IN NO EVENT SHALL TYCO FIRE
PRODUCTS BE LIABLE, IN CON-
TRACT, TORT, STRICT LIABILITY OR
UNDER ANY OTHER LEGAL THE-
ORY, FOR INCIDENTAL, INDIRECT,
SPECIAL OR CONSEQUENTIAL
DAMAGES, INCLUDING BUT NOT
LIMITED TO LABOR CHARGES, RE-
GARDLESS OF WHETHER TYCO
FIRE PRODUCTS WAS INFORMED
ABOUT THE POSSIBILITY OF SUCH
DAMAGES, AND IN NO EVENT
SHALL TYCO FIRE PRODUCTS' LI-
ABILITY EXCEED AN AMOUNT
EQUAL TO THE SALES PRICE.
r.ii;r1l-f'i
YfJ;l;TJhIl*
Ordering
Procedure
When placing an order, indicate the full
product name. Contact your local dis-
tributor for availability.
Sprinkler Assembly:
Specify: (SIN), (specify temperature
rating) Series RFII Concealed Pen-
dent Sprinkler, P/N (specify).
155F/68C 200F/93C
TY3551 51-790-1-155 51-790-1-200
TY3504 51-796-1-155 51-796-1-200
TY3531 51-792-1-155 51-792-1-200
1Y3505 51-797-1-155 51-797-1-200
Separately Ordered Cover Plate:
Specify: (specify temperature rating)
Series RFII Concealed Cover Plate
with (specify finish), P/N (specify).
I35Fj57c(a) 165F!74C(b)
Brass 56-792-1-135 56-792-1-165
Bright Brass 56-792-2-135 56-792-2-165
Chrome 56-792-9-135 56-792-9-165
Brushed Chrome 56-792-8-135 56-792-8-165
White 56-792-0-135 56-792-0-165
White (RAL9010)* 56-792-3-135 56-792-3-165
Bright White 56-792-4-135 56-792-4-165
Off White 56-792-5-135 56-792-5-165
Black 56-792-6-135 56-792-6-165
Custom 56-792-x-135 56-792-x-165
For use with 155F168C sprinklers.
For use with 200F/93C sprinklers.
* Eastern Hemisphere sales only.
Sprinkler Wrench:
Specify: RFII Sprinkler Wrench,
P/N 56-000-1-075.
Air and Dust Seal:
Specify: Air and Dust Seal,
P/N 56-908-1-001.
TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446
4 tiuiic
AUTOMATIC SPRI1!EFS V
FIRE PROTECTION TQ
V27, K5.6
Models V2703, V2704, V2707 and V2708
Standard Spray
Upright, Pendent and Recessed Pendent
Standard and Quick Response
PRODUCT DESCRIPTION
These Model V27 standard
spray sprinklers are
designed to produce a
hemispherical spray pat-
tern for standard commer-
cial applications. They are
2707
V2708 available with either stan-
Recessed dard or quick response
Pendent bulbs. The design incorpo-
() (j)
<>
rates state-of-the-art, heat
responsive, frangible glass
See Victaulic
1001 publication
bulb design (standard or
for details. quic k response) for prompt, V2707
V2708 _ precise operation. w 1
Pendent 1
V2703 L,
V2704
O
OJT
Upright
The die cast frame is more
streamlined and attractive
than traditional sand cast
frames. It is cast with a
hex-shaped wrench boss to
allow easy tightening from
many angles, reducing
assembly effort. This sprin-
kler is available in various
temperature ratings (see
chart on page 2) and fin-
ishes to meet many design
requirements.
The recessed pendent
should be utilized with a
Model V27 recessed
escutcheon which pro-
vides up to 3/4 (l9 min) of
adjustments.
Sprinkler Operation
The operating mechanism
is a frangible glass bulb
which contains a heat
responsive liquid. During a
fire, the ambient tempera-
ture rises causing the liquid
in the bulb to expand.
When the ambient temper-
ature reaches the rated
temperature of the sprin-
kler, the bulb shatters. As a
result, the waterway is
cleared of all sealing parts
and water is discharged
towards the deflector. The
deflector is designed to dis-
tribute the water in a pat-
tern that is most effective
in controlling the fire.
Coverage
For coverage area and
sprinkler placement, refer
to NFPA 13 standards.
TECHNICAL SPECIFICATIONS
Models: V2703. V2704, V2707
V2708
Style: Pendent, Upright or
Recessed Pendent
Nominal Orifice Size:
½' (13 mm)
K-Factor: 5.6 Imp. (8.1 S. 1.
Nominal Thread Size:
½' NFl (15 mm)
Max. Working Pressure:
175 psi (1200 kPa)
Factory Hydrostatic Test:
100% @ 500 psi (34 50 kP
Mm. Operating Pressure:
7ps1 (48kPa)
Temperature Rating: See
chart on page 2.
MATERIAL
SPECIFICATIONS
Upright Deflector-
Bronze per UNS C22000
Pendent Deflector:
Bronze per UNS C51000
Bulb: Glass with glycerin solu-
tion.
Bulb Nominal Diameter:
U Standard: 5,0 mm
U Quick Response: 3,0 mm
Load Screw: Bronze per UNS
C65100
Pip Cap: Bronze per UNS
C65 100
Spring: Beryllium nickel
Seal: Teflon* tape
Frame: Die cast brass 65-30
Lodgement Spring:
Stainless steel per UNS S30200
ACCESSORIES
Installation Wrench:
U Open End: V27
U Recessed: V38, V38-3
U Socket: V27
Finishes:
U Plain brass
U Chrome plated
U White painted**
U Custom painted**
U Lead**
155, 200, 2865R Only:
U Wax**
U Wax over lead**
For cabinets and other accesso-
ries refer to separate sheet.
NOTE: Weather resistant recessed
escutcheons available upon request.
For K-Factor when pressure is mea-
sured in Bar, multiply S.I. units by
10.0.
Teflon is a registered trademark of
Dupont Co,
UL Listed for corrosion resistance in
all configurations.
VICTAULIC® IS AN ISO 9001 CERTIFIED COMPANY
Victaulic Company of America Victaulic Company of Canada Victaulic Europe Victaulic America Latina Victaulic Asia Pacific
Phone: 1-800-PICK-VIC (1-800-742-5842) Phone: 905-884-7444 Phone: 32.9.381-1500 Phone: 610-559-3300 Phone: 65-6235-3035
Fax: 610-250-8817 Fax: 905-884-9774 Fax: 32-9-380-4438 Fax: 610-559-3608 Fax: 65-6235-0535
e-mail:pickvic@victaulic.conl e-mail: viccanada@victaulic.com e-mail: viceuro@viclaulic.be e-mail: vical@victaulic.com e-mail: vicap@victaulic.com
2544 Rev.D 8103 a Registered Trademark of Victaulic 0 CopyrIght 2003 Victaulic -Tirrtea in
APPROVALSILISTINGS
Nominal Approved Temperature Ratings °FI°C
Orifice Size K-Factor
Inches Imperial Deflector
Model millimeters at Response Type UL FM ULC NYC/MEAt CSFM §
1h 5.6 135-360 135-360 135-360 135-360 135-360
V2703 13 8,1 Standard Upright 57-182 57-182 57-182 57-182 57-182
1h 5.6 135-360 135-360 135-360 135-360 135-360
V2707 13 8,1 Standard Pendent 57-182 57-182 57-182 57-182 57-182
½ 5.6 Recessed Pendent 135-360 135-200 135-360 135-360 135-360
V2707 13 8,1 Standard Upto 14 Adjustment 57-182 57-93 1 57-182 57-182 57-182
½ 5.6 135-286 135-286 135-286 135-286 135-286
V2704 13 8,1 Quick Upright 57-141 57-141 57-141 57 -141 57 -141
½ 5.6 135-286 135-286 135-286 135-286 135-286
V2708 13 8,1 Quick Pendent 57-141 57-141 57-141 57-141 57-141
½ 5.6 Recessed Pendent 135-200 135-200 135- 200 135-200 135 -200
V2708 13 8,1 Quick Up to W Adjustmcnt 57-93 57-93 57-93 57-93 57-93
½ 5.6 Recessed Pendent 135-200 No 135-200 135-200 135-200
V2708 13 8.1 Quick Up to ~ Adjustment 57-93 5793 57-93
t Listings and approval as of printing. Cl All are approved open, except for areas designated No.
" For K-Factor when pressure is measured in Bar, multiply S.I. units by 10.
t MEA#62-99-E. §CSFM#7690-0531:112
RATINGS
All glass bulbs are rated for
temperatures from -67°F
(-55°C) up to those shown
in adjacent table.
Temperature - °FI°C
Sprinkler Victaulic Nominal Maximum Glass
Temperature Pad Temperature Ambient Temp. Bulb
Classification Identification Rating Allowed Color
Ordinary A 135
57
100
38 Orange
Ordinary C 155
68
100
38 Red
Intermediate E 175 150
65 Yellow
Intermediate F 200
93
150
65 Green
High -
286
141
225 -
107 Blue
Extra High t K 360
182
300
149 Purple
- M Open : No Bulb
Standard response only.
All arc approved open, except for areas designated No".
-150/65 if wax coated,
ORDERING INFORMATION
Please specify the following
when ordering: U Sprinkler Model Number U K-Factor U Sprinkler Finish
U Style U Thread Size U Escutcheon Finish
U Temperature Rating 0 Quantity U Wrench Model Number
!1\WATRN Ii
. Always read and understand installation, care, and maintenance instructions, supplied with each box of sprinklers, before proceeding with installation
of any sprinklers.
Always wear safety glasses and foot protection.
Depressurize and drain the piping system before attempting to install, remove, or adjust any Victaulic piping products. . 0 Installation rules, especially those governing obstruction, must be strictly followed.
Painting, plating, or any re-coating of sprinklers (other than that supplied by Victaulic) is not allowed.
Failure to follow these instructions could result in serious personal injury and/or property damage.
The owner is responsible for maintaining the fire protection system and devices in proper operating condition. For minimum maintenance and inspection requirements, refer to the
current National Fire Protection Association pamphlet that describes care and maintenance of sprinkler systems. In addition, the authority havingjurisdiction may have additional
maintenance, testing, and inspection requirements that must be followed.
If you need additional copies of this publication, or if you have any questions about the sale installation of this product, contact Victaulic World Headquarters, P.O. Box 31, Easton,
Pennsylvania 18044-0031. 610-559-3300.
-
40.10-2
DIMENSIONS
2W
(60 mm) 159
(41 mm)
(25 mm)
Standard Pendent - V2707, V2708
(60
Standard Upnght V2703, V2704
(60 mm)
Max. Hole
2"(51 mm)
Mm. He r 1¼o"
(17 mm) (14 mm) ;s
T— I
__________________
_______
,,cwtmm) Typical Ceding Tile
t We
11 /*" Finished Surface (30 torn)
(43 mm)
-
____
MAXIMUM RECESS
(75 mm) -
MAXIMUM EXTENSION
½ Adjustment
Recessed - V2707, V2708
(Drawing not to scale)
2W'(60 mm)
Max. I-lola
aim
Me Typical Ceding Tile (2m)
(43
(14 mm) -A
11y'd, \—Finished Surface
I MAXIMUM RECESS
(75 mm)
MAXIMUM EXTENSION
zK" Adjustment
Recessed - V2707, V2708
(Drawing not to scale)
1 1
AVAILABLE WRENCHES
V27
Socket
V38 or V38-3
Recessed
V27
Open End
V2707 V2708 Pendent
V2707, V2708 Recessed Pendent
V2703V2704Upr)ght
40.10-3
---.
M
---r:—
-
_
-- --
' N-- -
M ______
m
--
-
------
10'
3,0 m
8
2,4
6
1,8
4
1,2
2
0,6
0
7psi
48 kPa
15 psi
103 kPa
30 psi -------
207 kPa
DISTRIBUTION PATTERNS
MODELS V2707, V2708
K5.6 STANDARD PENDENT AND RECESSED PENDENT
DISTRIBUTION PATTERNS - TRAJECTORY
10' I I I I I I I I I 3,0 m
8'
2,4 m
7ps1
48 kPa
6
1,8 m
15 psi
103 kPa
4,
I,2m
30 psi -------
207 kPa
2-
0,6 m
0 2' 4' 6' 8' 10' 12' 14
0,6 m 1,2w 1.8 m 2,4 m 3,0 in 3,7 m 4,3 m
MODELS V2103, V2704
K5.6 STANDARD UPRIGHT DISTRIBUTION PATTERNS - TRAJECTORY
0,6m 1,2m 1,8m 2,4m 3,0m 3,7m 4,3rn 4,9m
NOTES:
Data shown Is approximate and can vary due to differences in installation.
These graphs illustrate approximate trajectories, floor-wetting, and wall-wetting patterns for these specific Victaulic FireLock Automatic Sprinklers. They are
provided as information for guidance in avoiding obstructions to sprinklers and should not be used as minimum sprinkler spacing rules for installation. Refer to
the appropriate NFPA National Fire Code and the authority having jurisdiction for specific information regarding obstructions, spacing limitations and area of
coverage requirements. Failure to follow these guidelines could adversely affect the performance of the sprinkler and will void all Listings, Approvals and War-
ranties.
All patterns are symmetrical to the centerline of the waterway.
WARRANTY Refer to the Warranty section
of the current Price List or
contact Victaulic for details.
This product shall be manufactured by Victaulic Company. Al products to be installed in accordance with cutent Victaulic installationlassembly instructions.
Victaulic reserves the right to change product specifications, designs and standard equipment without notice and without incurring obligations.
40.10-4