HomeMy WebLinkAbout3115 MELROSE DR; ; AS130203; Permit12/13/24, 4:17 PM AS 130203 Permit Data
City of Carlsbad
Sprinkler Permit
Permit No: AS130203
Job Address: 3115 MELROSE DR Status: ISSUED
Permit Type: SPRINK Applied 11/13/2013
Parcel No: 2218801300 Approved: 11/22/2013
Lot #: 0
Reference No.: Issued: 11/22/2013
PC #: Inspector:
Project Title: VALUATION VISION TI—INSTALLATION OF NEW FIRE
SPRINKLER HEADS IN PREPARATION FOR NEW WALLS. FIRE
SPRINKLERS WILL BE SUPPLIED FORM EXISTING FIRE
SPRINKLER PIPING ABOVE SUSPENDED CEILING.
Applicant:
A& D FIRE SPRINKLERS
11465 WOODSIDE AV
SANTEE, CA
619-448-1962
Owner:
H R MELROSE LLC
11990 SAN VICENTE BLVD #200
LOS ANGELES CA
Fees ($) Add'I Fees ($) Total ($) Balance ($)
268 0 268 0
about:blank 1/1
•
FIRE SPRINKLERS INC.
VALUATION VISION
3115 MELROSE DR SUITE 120
CARLSBAD, CA
FIRE SPRINKLER SUBMITTAL
MANUFACTURER'S DATA SHEETS
** Materials of equal design, utility, and performance may be substituted for submitted materials so as to avoid delays in
the construction schedule and shall be deemed accepted by the Purchaser.
AS13020014
O FIRE SPRINKLER SUBMITTAL
TABLE OF CONTENTS
FIRE SPRINKLERS.
PIPE.
HANGERS.
S
0
1).- FIRE SPRINKLERS
0
[I
QUICK RESPONSE
UPRIGHT CONVENTIONAL
QUICK RESPONSE
PENDENT VERTICAL
SIDEWALL
QUICK RESPONSE
HORIZONTAL LPC/CE
SIDEWALL HORIZONTAL
SIDEWALL
Oman
um No
FIRE SPRINKLER CORPORATION
QUICK RESPONSE
A UTOMA TIC SPRINKLERS
GL SERIES
UPRIGHT* PENDENT
VERTICAL SIDEWALL
HORIZONTAL SIDEWALL
CONVENTIONAL (OLD STYLE)
DESCRIPTION AND OPERATION
The Globe Quick Response GL Series Sprinklers are a low
profile yet durable design which utilizes a 3mm frangible glass
ampule as the thermosensitive element. This provides sprinkler
operation approximately six times faster than ordinary sprinklers.
While the Quick Response Sprinkler provides an aesthetically
pleasing appearance, it can be installed wherever standard spray
sprinklers are specified when allowed by the applicable standards.
It offers the additional feature of greatly increased safety to life and
is available in various styles, orifices, temperature ratings and
finishes to meet many varying design requirements. Quick
Response Sprinklers should be used advisedly and under the
direction of approving authorities having jurisdiction.
The heart of Globe's GL Series sprinkler proven actuating
assembly is a hermetically sealed frangible glass ampule that
contains a precisely measured amount of fluid. When heat is
absorbed, the liquid within the bulb expands increasing the internal
pressure. At the prescribed temperature the internal pressure
within the ampule exceeds the strength of the glass causing the
glass to shatter. This results in water discharge which is distributed
in an approved pattern depending upon the deflector style used.
TECHNICAL DATA
See reverse side for Approvals and Specifications.
oTemperature Ratings - 135°F (57°C), 155°F (68°C),
175°F (79°C), 200°F (93°C), 286°F (141°C)
oWater Working Pressure Rating - 175 psi (12 Bars)
0 Factory tested hydrostatically to 500 psi (34 Bars)
0 Maximum low temperature glass bulb rating is -67°F (-55°C)
Frame - bronze • Deflector - brass o Screw - brass
Lodgement Wire - stainless steel
Bulb seat - copper 0 Spring - nickel alloy • Seal - teflon
Bulb - glass with alcohol based solution, 3mm size
SPRINKLER TEMPERATURE RATING/CLA5SII-IUAIIUN ana UULUK uuuiivu
AVAILABLE SPRINKLER N. F.P.A. MAXIMUM
CLASSIFICATION TEMPERATURES BULB COLOR CEILING TEMPERATURE
ORDINARY 136'F 1°F 57 C168 C ORANGE/RED 100 F 38°C
INTERMEDIATE 17 F F1200 791C/931C YELLOW/GREEN 150 6 c
HIGH 286F 141°C BLUE 25°F 107°C
4077AIRPARK DRIVE, STANDISH, MICHIGAN 48658 989-846-4583 • FAX 989-846-9231
JULY 2012 A-20 BULLETIN GL5615, REV. #9
FIRE SPRINKLER CORPORATION
QUICK RESPONSE
A U TOMA TI C SPRINKLERS
GL SERIES
RECESSED PENDENT
RECESSED HORIZONTAL SIDEWALL
I
DESCRIPTION AND OPERATION
The Globe Quick Response GL Series Sprinkler is a low profile
yet durable design which utilizes a 3mm frangible glass ampule as
the thermosensitive element. This provides sprinkler operation
approximately six times faster than ordinary sprinklers. While the
Quick Response Sprinkler provides an aesthetically pleasing
appearance, it can be installed wherever standard spray sprinklers
are specified but offers the additional feature of greatly increased
safetyto life. Quick Response Sprinklers should be used advisedly
and under the direction of approving authorities having jurisdiction.
The heart of Globe's GL Series sprinkler proven actuating
assembly is a hermetically sealed frangible glass ampule that
contains a precisely measured amount of fluid. When heat is
absorbed, the liquid within the bulb expands increasing the internal
pressure. At the prescribed temperature the internal pressure
within the ampule exceeds the strength of the glass causing the
glass to shatter. This results in water discharge which is distributed
in an approved pattern depending upon the deflector style used.
The sprinkler and escutcheon are not factory assembled.
Assembly is done in the field.
TECHNICAL DATA
0See reverse side for Approvals and Specifications.
oTemperature Ratings - 135°F (57°C), 155°F (68°C),
175°F (79°C), 200°F (93°C), 286°F (141°C)
0 Water Working Pressure Rating - 175 psi (12 Bars)
0 Factory tested hydrostatically to 500 psi (34 Bars)
Maximum low temperature glass bulb rating is -67°F (-55°C)
0Frame - bronze o Deflector - brass o Screw - brass
Bulb seat - copper o Spring - nickel alloy • Seal - teflon
Lodgement Wire - stainless steel
Bulb - glass with alcohol based solution, 3mm size
Escutcheon Assembly - steel
QUICK RESPONSE
RECESSED PENDENT
QUICK RESPONSE
RECESSED
HORIZONTAL SIDEWALL
QUICK RESPONSE
LPC!CE RECESSED
HORIZONTAL SIDEWALL
SPRINKLER TEMPERATURE RATING/CLASSIFICATION and COLOR CODING
AVAILABLE SPRINKLER N.F.P.A. MAXIMUM
CLASSIFICATION TEMPERATURES BULB COLOR CEILING TEMPERATURE
ORDINARY 135?Fi55°F 57°C/68°C ORANGE/RED 38"C
INTERMEDIATE 174F -/200'F 39 GI9 C YELLOW/GREEN 15O 66 0
HIGH 286 F 141C BLUE L 225F 107 C
4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658 989-846-4583 • FAX989-846-9231
JULY 2012 A-24 BULLETIN GI-2801, REV.#10
QUICK RESPONSE
A UTOMA TIC SPRINKLERS
GL SERIES
UPRIGHT. PENDENT. VERTICAL SIDEWALL
HORIZONTAL SIDEWALL. CONVENTIONAL (OLD STYLE)
SPECIFICATIONS
NOMINAL "K" FACTOR THREAD SIZE LENGTH' FINISHES
2.8 (39 metric) 1/2" NPT 2 1/4" (5.7cm)
Factory Bronze
4.2 (59 metric) 1/2 NPT 2 1/4 (5.7cm)
Chrome
5.6 (80 metric) 1/2 NPT 2 1/4 (5.7cm) White Polyester
7.8 (111 metric) 1/2 NPT 2 1/4 (5.7cm)
Black Polyester 2,3
8.1 (116 metric) 3/4' NPT 2 7/16" (6.2cm)
METRIC CONVERSIONS ARE APPROXIMATE.
I HORIZONTAL SIDEWALL IS 2 9/16.
2 FINISHES AVAILABLE ON SPECIAL ORDER.
3 AVAILABLE AS cULus LISTED CORROSION RESISTANT WHEN SPECIFIED ON ORDER.
APPROVALS
SIN K 135°F 155°F 175°F 200°F 286°F cULus FM LPC CE NYC - DOB
STYLE MODEL FACTOR HAZARD 57°C 68°C 79°C 93°C 141°C MEA 101-92-E
GL2815 2.8 LH X X X X X X - - - X
GL4215 4.2 LH X X X X X X - - - x
UPRIGHT GL5615 5.6 LH/OH X X X X X X X X X X
GL8115 7.8* LH/OH X X X X X X - - - X
GL8118 8.1 LH/OH X X X X X X X X X X
GL2801 2.8 LH X X X X X X - - - X
GL4201 4.2 LH X X X X X X - - - X
PENDENT GL5601 5.6 LH/OH X X X X X X X X X X
GL8101 7.8° LH/OH X X X X X X X - - X
GL8106 8.1 LH/OH X X X X X I X X X X X
VERTICAL GL5632 5.6 LH X X X X X X X - - -
SIDE WALLt GL8133 8.1 LH X X X X X X - - - -
GL2826 § 2.8 LH X X X X X X - - - x
GL4226 § 4.2 LH X X X X X X - - - X
HORIZONTAL GL5626 § 5.6 LH/OH X X X X X X X - - X
SIDEWALL GI-5627a 5.6 LH/OH X X X X X - - X X -
GL8127 § 8.1 LH/OH X X X X X I X - - - -
CONVENTIONAL GL5624 5.6 LH/OH X X X X X - - X X -
(OLD STYLE) GL8125 8.1 LH IOH X X X X X - - X X -
1SPRINKLERS SHALL BE LIMITED AS PER THE REQUIREMENTS OF NFPA13 AND ANY OTHER RELATED DOCUMENTS.
§HORIZONTAL SIDEWALL cULus LISTED FOR DEFLECTOR 4" TO 12" BELOW THE CEILING, FM APPROVED 4 TO 6" BELOW THE CEILING.
DINSTALL IN ACCORDANCE TO 6S5306 AND ANY OTHER RELATED DOCUMENTS.
tPENDENT VERTICAL SIDEWALL cULus LISTED FOR 6 MIN. SPACING.
tUPRIGHT VERTICAL SIDEWALL cULus LISTED FOR 9 MIN. SPACING.
OH: ORDINARY HAZARD
LH: LIGHT HAZARD
°112' NPT
n
ORDERING INFORMATION
SPECIFY
'Quantity • Model Number • Style
Orifice • Thread Sizes • Temperature
Finishes desired
'Quantity - Wrenches - P/N 325390 (1/2");
P/N 312366 (L.O.)
glio mo a
FIRE SPRINKLER CORPORATION
JUNE2012
GLOBE® PRODUCT WARRANTY
Globe agrees to repair or replace any of its own manufactured
products found to be defective in material or workmanship for a
period of one year from date of shipment.
For specific details of our warranty please refer to Price List
Terms and Conditions of Sale (Our Price List).
4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658
FAX 989-846-9231
www.globesprinkler.com
BULLETIN GI-5615, REV. #9
989-846-4583
1-800-248-0278
PRINTED U.S.A.
QUICK RESPONSE
AUTOMATIC SPRINKLERS
GL SERIES
O RECESSED PENDENT
RECESSED HORIZONTAL SIDEWALL
NOMINAL "K" FACTOR THREAD SIZE LENGTH FINISHES
2.8 (39metric) 1/2' NPT 2 1/4' (5.7cm) Factory Bronze
4.2 (59metr1c) 1/2" NPT 2 1/4' (5.7cm) Chrome
5.6 (80 metric) 1/2' NPT 2 1/4' (5.7cm) White Polyester3
7.8 (111 metric) 1/2' NPT 2 1/4' (5.7cm) Black Polyester23
8.1 (116 metric) 3/4" NPT 2 7/16" (6.2cm)
METRIC CONVERSIONS ARE APPROXIMATE
1 HORIZONTAL SIDEWALL IS 2 9/16.
2 FINISHES AVAILABLE ON SPECIAL ORDER.
3AVAILABLE AS cULus LISTED CORROSION RESISTANT WHEN SPECIFIED ON ORDER.
APPROVALS
STYLE SIN K HAZARD' 135°F 155°F 175°F 200°F **286F cULus FM LPC CE NYC - DOB
MODEL FACTOR 57°C 68°C 79°C 93°C 141°C MEAIOI-92-E
GL2801 2.8 LH X X X X X X - - - X
GL4201 4.2 LH X X X X X X - - - X
PENDENT GL5601 5.6 LH/OH X X X X X X X X X X
RECESSED
GL8101 7.8° LH/OH X X X X X X X - - X
GL8106 8.1 LH/OH X X X X X X X X X X
GL2826 2.8 LH X X X X X X - X
HORIZONTAL GL4226fl 4.2 LH X X X X X X - - - X
SIDEWALL GL5626 5.6 LH/OH X X X X X X - - - X
RECESSED GL5627a 5.6 LH/OH X X X X X - - X X -
GL8127 8.1 LH/OH X X X X X X I -
11
1SPNKLERS SHALL BE LIMITED AS PER THE REQUIREMENTS OF NFPA13 AND ANY OTHER RELATED DOCUMENTS.
MIN. MP.X.
PENDENT
ORDERING INFORMATION
SPECIFY
Quantity . Model Number . Style
Orifice • Thread Sizes • Temperature • Finishes desired
Quantity - Recessed Wrenches - P/N 325391 (1/2"); PIN 325401 (3/4")
Quantity - Protective Caps - P/N 327109-CAP (Friction Fit Recessed)
014MM
FIRE SPRINKLER CORPORATION
JULY 2012
**2860F cULus LISTED ONLY
BRASS FINISH ONLY
OR ORDINARY HAZARD
LH: LIGHT HAZARD *1/2 NPT
LPCICE
HORIZONTAL SIDEWALL
GLOBE® PRODUCT WARRANTY
Globe agrees to repair or replace any of its own
manufactured products found to be defective in material
or workmanship for a period of one year from date of
shipment.
For specific details of our warranty please refer to Price
List Terms and Conditions of Sale (Our Price List).
§ HORIZONTAL SIDEWALL cULus LISTED FOR DEFLECTOR 4" TO 12' BELOW THE CEILING.
U INSTALL IN ACCORDANCE TO BS5306 AND ANY OTHER RELATED DOCUMENTS.
tt 1/2" RECESSED ESCUTCHEONS ARE REQUIRED FOR FM APPROVED SPRINKLERS
CROSS SECTIONS
HORIZONTAL SIDEWALL
4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658
989-846-4583 FAX 989-846-9231
1-800-248-0278 www.globesprinkIer.com
PRINTED U.S.A BULLETIN GL2801, REV.#10
ci (.)•• •fl
FIRE SPRINKLER CORPORATION
,,THE INCH"
QUICK RESPONSE
A U TO MA TIC SPRINKLERS
MODEL GL5606
ONE INCH ADJUSTABLE
DESCRIPTION AND OPERATION CONCEALED PENDENT
The Globe Quick Response GL5606 Adjustable Concealed Pendent Sprinkler has a low profile,
aesthetically pleasing design. It provides sprinkler operation approximately six times faster than
ordinary sprinklers and can be installed wherever standard concealed spray sprinklers are
specified when allowed by the applicable standards. It offers the additional feature of greatly
increased safety to life and should be used advisedly and under the direction of approving
authorities having jurisdiction. The sprinkler is available with a nominal 1" of adjustment and a low
profile cover plate assembly. All that is seen at the ceiling is a 3 5/16" diameter ceiling plate or an
optional 2%" diameter ceiling plate colorfinished to match the specifier's exact requirements. The
GL Series Concealed Sprinkler may be virtually invisible as it does not interrupt the "smooth flow"
of the ceiling. Globe's Concealed Sprinkler utilizes its 3mm frangible glass ampule which is located
above the ceiling and concealed from view by the ceiling plate.
The provided protective cap needs to be removed in order to install the sprinkler with the proper
wrench. The protective cap must be replaced on the sprinkler until the time the cover plate is to be
installed. The "push on - screw off' designed cover plate is easily installed and with a nominal 1"
inch of adjustment makes it easier to get a proper fit at the ceiling.
Operation of the sprinkler occurs when heat build up causes the solder holding the cover plate
to the support shell to melt allowing the cover plate to fall clear. Continued heat build up causes
the 3mm glass bulb to burstallowing the deflectorto drop down and distributewater in an approved
pattern to extinguish or control the fire.
TECHNICAL DATA
See reverse side for Approvals and Specifications.
oTemperature Ratings -
135°F (57°C) Sprinkler, 135°F (57°C) Cover Plate
155°F (68°C) Sprinkler, 135°F (57°C) Cover Plate
155°F (68°C) Sprinkler, 155°F (68°C) Cover Plate 35/16" diameter plate
175°F (79°C) Sprinkler, 155°F (68°C) Cover Plate
200°F (93°C) Sprinkler, 155°F (68°C) Cover Plate
oWater Working Pressure Rating -175 psi (12 Bars)
0 low temperature glass bulb rating is -67°F (-55°C)
Factory tested hydrostatically to 500 psi (34 Bars)
0 Frame - bronze • Deflector - brass • Screw - brass
Bulb seat - brass o Spring - nickel alloy • Seal - teflon 23/4" diameter plate
Bulb - glass with alcohol based solution, 3mm size QUICK RESPONSE
Drop Pin - stainless steel WHITE ADJUSTABLE
0 Cover Plate - brass CONCEALED PENDENT
0 Upper Escutcheon Assembly - plated steel
NOTE: Globe's wrench PIN 332765 must be used to install this sprinkler.
SPRINKLER TEMPERATURE RATING/CLASSIFICATION and COLOR CODING
AVAILABLE BULB N.F.P.A. MAXIMUM CEILING CLASSIFICATION SIF SPRINKLER TEMPERATURES COLOR TEMPERATURE
ORDINARY 135TI15°F 5. 57°C/68°C. ORANGE/RED 00'F. 3851C
I INTERMEDIATE 175P1200F 79°C/93°C YELLOW/GREEN 150 F .- 666C
4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658 (989) 846-4583 • FAX 989-846-9231
MAY 2012 A-38 BULLETIN GL5606 REV#6
QUICK RESPONSE
A UTOMA TIC SPRINKLERS
MODEL GL5606 ONE INCH
ADJUSTABLE CONCEALED PENDENT
SPECIFICATIONS
NOMINAL "K" FACTOR THREAD SIZE LENGTH FINISHES
Bright Chrome
White Painted
5.6 (80 metric) 1/2 NPT 2 1/2" (6.4 cm) Bright Brass'
Satin Chrome'
Other Painted Finishes'
NOTE: METRIC CONVERSIONS ARE APPROXIMATE. 'FINISHES AVAILABLE ON SPECIAL ORDER. FOR PAINTED PLATES OTHER
THAN WHITE, CONTACT GLOBE FOR ORDERING SPECIFICATIONS.
APPROVALS
**1350F (57°C) 155°F (68°C) **1550F (68°C) 175°F (79°C) 200°F (93°C) NYC-DOB
STYLE SIN K with plate with plate with plate with plate with plate cULus *FM MEA MODEL FACTOR 135°F (57°C) 135°F (57°C) 155°F (68°C) 155°F (68°C) 155°F (68°C) 101-92-E
Adjustable
Concealed GL5606 5.6 X X X X X X X X
Pendent
*FM APPROVED AS STANDARD RESPONSE
**NO FM APPROVALS
CROSS SECTIONS
H- 2 1/4 DIR. MIN. I HOLE IN CEILING
NA.
1, x l/2
REDUCER
2 3f4 MAX.
17/8" MIN.
DROP PIN
SUPPORT SHELL-
CEILING COVER
OPTIONAL COVER
PLATE SIZE
WHITE 135°F
PART #
WHITE 155°F
PART #
CHROME 135°F
PART #
CHROME 155°F
PART #
23/4" 332726 332731 332724 332729
35/16" 332706 332711 332704 332709
522PM
CEIUE
ORDERING INFORMATION
SPECIFY
Quantity . Model Number • Style
Orifice • Thread Sizes • Temperature
Finishes desired
Quantity - Adjustable Concealed Wrenches - P/N 332765
gE,4 , D s,
FIRE SPRINKLER CORPORATION
GLOBE® PRODUCT WARRANTY
Globe agrees to repair or replace any of its own manufactured
products found to be defective in material or workmanship for
a period of one year from date of shipment.
For specific details of our warranty, please refer to Price List
Terms and Conditions of Sale (Our Price List).
4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658
989-846-4583 FAX 989-846-9231
1-800-248-0278 www.globesprinkler.com
MAY 2012 PRINTED U.S.A. BULLETIN GL5606 REV#6
QUICK RESPONSE
A U TO MA TI C SPRINKLERS
GL SERIES
UPRIGHT o PENDENT
FIRE SPRINKLER CORPORATION VERTICAL SIDEWALL
HORIZONTAL SIDEWALL
CONVENTIONAL (OLD STYLE)
DESCRIPTION AND OPERATION
The Globe Quick Response GL Series Sprinklers are a low profile
yet durable design which utilizes a 3mm frangible glass ampule as the
thermosensitive element. This provides sprinkler operation approxi-
mately six times faster than ordinary sprinklers. While the Quick
Response Sprinkler provides an aesthetically pleasing appearance, it
can be installed wherever standard spray sprinklers are specified when
allowed by the applicable standards. It offers the additional feature of
greatly increased safety to life and is available in various styles,
orifices, temperature ratings and finishes to meet many varying design QUICK RESPONSE requirements. Quick Response Sprinklers should be used advisedly UPRIGHT CONVENTIONAL and under the direction of approving authorities having jurisdiction.
The heart of Globe's GL Series sprinkler proven actuating
assembly is a hermetically sealed frangible glass ampule that contains
a precisely measured amount of fluid. When heat is absorbed, the
liquid within the bulb expands increasing the internal pressure. At the
prescribed temperature the internal pressure within the ampule ex-
ceeds the strength of the glass causing the glass to shatter. This results .
in water discharge which is distributed in an approved pattern depend-
ing upon the deflector style used.
QUICK RESPONSE
TECHNICAL DATA PENDENT VERTICAL
*See reverse side for Approvals and Specifications. SIDEWALL
oTemperature Ratings - 135°F (57°C), 155°F (68°C),
175°F (79°C), 200°F (93°C), 286°F (141°C)
oWater Working Pressure Rating - 175 psi (12 Bars)
oFactory tested hydrostatically to 500 psi (34 Bars)
oMaximum low temperature glass bulb rating is -67°F (-55°C)
0 Frame - bronze • Deflector - brass • Screw - brass
0 Bulb seat - copper o Spring - nickel alloy o Seal - teflon QUICK RESPONSE
oBulb - glass with alcohol based solution, 3mm size HORIZONTAL SIDEWALL
o SPRINKLER TEMPERATURE RATING/CLASSIFICATION and COLOR CODING
AVAILABLE SPRINKLER N.F.P.A. MAXIMUM
CLASSIFICATION TEMPERATURES BULB COLOR CEILING TEMPERATURE
ORDINARY 1350F/155°F 570C/680C ORANGE/RED 100°F 38°C
INTERMEDIATE 1750F/200°F 790C/930C YELLOW/GREEN 150°F 66°C
HIGH 286°F 141°C BLUE 225°F 107°C
4077 Al RPARK DRIVE, STANDISH, MICHIGAN 48658 989-8464583 9 FAX989-846-9231
MAY 2011 A-20 BULLETIN GL5615, REV. #7
I
I
QUICK RESPONSE
A U TO MA TI C SPRINKLERS
GL SERIES
UPRIGHT PENDENT VERTICAL SIDEWALL
HORIZONTAL SIDEWALL e CONVENTIONAL (OLD STYLE)
SPECIFICATIONS
NOMINAL K" FACTOR THREAD SIZE LENGTH ' FINISHES
2.8 (39 metric) 1/2 NPT 2 1/4 (5.7 cm) Factory Bronze
4.2 (59 metric) 1/2 NPT 2 1/4' (5.7 cm) Bright Chrome
Satin Chrome 2
5.6 (80 metric) 1/2' NPT 2 1/4" (5.7 cm) White Polyester
7.8 (111 metric) 1/2" NPT 2 1/4' (5.7 cm) Black Polyester 2.3
8.1 (116 metric) 3/4" NPT 2 7/16" (6.2 cm) Lead Coated 2.3
NOTE: METRIC CONVERSIONS ARE APPROXIMATE. hUIILON IP,L IUVVLL 1,)2W10 .
2FINISHES AVAILABLE ON SPECIAL ORDER.
3 AVAILABLE AS cULus LISTED CORROSION
APPROVALS RESISTANT WHEN SPECIFIED ON ORDER.
STYLE SIN K 135°F 155°F 175°F 200°F 286°F cULus F. M. LPC CE NYC - DOB MEA
MODEL FACTOR 57°C 68°C 79°C 93°C 141°C 101-92-E
GL2815 2.8 X X X X X X -- -- --- X
GL4215 4.2 X X X X X X -- - --- X
UPRIGHT GL5615 5.6 X X X X X X X X X X
GL8115 7.8* X X X X X X -- - -- X
GL8118 8.1 X X X X X X X X X X
GL2801 2.8 X X X X X X - -- X
GL4201 4.2 X X X X X X --- -- --- X
PENDENT GL5601 5.6 X X X X X X X X X X
GL8101 7.8* X X X X X X X - --- X
GL8106 8.1 X X X X X X X X X X
VERTICAL GL5632 5.6 X X X X X X X -- --- --
SIDEWALLt GL8133 8.1 X X X X X X - -- -- --
GL2826 2.8 X X X X X X -- -- --- X
HORIZONTAL GL4226 4.2 X X X X X X -- -- -- X
SIDEWALL § GL5626 5.6 X X X X X X X - --- X
GL8127 8.1 X X X X
CONVENTIONAL GL5624 5.6 X X X X X -- --- X X --
(OLD STYLE) GL8125 8.1 X X X X X -- -- X X -
S
ORDERING INFORMATION
SPECIFY
Quantity • Model Number . Style
Orifice • Thread Sizes • Temperature
Finishes desired
Quantity - Wrenches - P/N 325390 (1/2");
P/N 312366 (L.O.)
al4mm
FIRE SPRINKLER CORPORATION
MAY2011
*1/2 NPT
t VERTICAL SIDEWALL SPRINKLER cULus LISTED FOR LIGHT HAZARD ONLY.
PENDENT VERTICAL SIDEWALL cULus LISTED FOR 6' MIN. SPACING.
UPRIGHT VERTICAL SIDEWALL cULus LISTED FOR 9' MIN. SPACING.
§ HORIZONTAL SIDEWALL cULus LISTED FOR DEFLECTOR 4" TO 12" BELOW
THE CEILING, FM APPROVED 4" TO 6".
GLOBE® PRODUCT WARRANTY
Globe agrees to repair or replace any of its own manufac-
tured products found to be defective in material or workmanship
for a period of one year from date of shipment.
For specific details of our warranty please refer to Price List
Terms and Conditions of Sale (Our Price List).
4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658
989-8464583 FAX 989-846-9231
1-800-248-0278 www.globesprinkler.com
PRINTED U.S.A. BULLETIN GL5615, REV. #7
From: 01/13/2014 17:51 #129 P.005/007
n
Contractors Material and Test Certificate for Aboveground Piping
PROCEDURE
Upon completbn of work, Inspection and tests shall be made by the contractor's representative and witnessed by an owners representative.
AD dsfds shall be corrected and system left In service before contractors personnel finally leave the Job.
A certificate shalt be filled out and signed by both representatives. Copies shalt be prepared for approving authorities, owners, and
contractor. It Is understood the owner's representative's signature In no way prejudiceS ay claim against contractor for faulty material, poor
workmanship, or failure to comply with approving authority's requirements or local ordinances.
Propertynarne V;o IDate
Property address 35 /20
Accepted by approving authorities (names)
O'cC..i5 ã
Address
Plans
Installation conform to accepted plans )s E No
Equipment used Is approved f Yes 0 No
if no, explain deviations
Has person In charge of fire equipment been Instructed as [i'as ED No
to location of control valves and care and maintenance
of this new equipment?
If no, explain?
Instructions Have copies of the blowIng been left on the premises? 0 Yes Cl No
System components Instructions 0 Yes 0 No
Care and maintenance Instructions 0 Yes 0 No
NFPA2S C) v 0 No
Location of
system Supplies buildings
Year of orifice Temperature
Make Model manufacture size Quantity rating
GLbL 0.2. SL.til.. 2oi t/" __ ISIS,
Spriniders i
t,tS I
Pipe and Type of pipe 30
fittings Type of fittings %>,c.ê& 4r4.cJ
Maximum time to operate
Alarm
valve Or
flow
Alarm device through test connection
Type Make 'Model Minutes Seconds
iniôator
Dry valve Q.O.D,
Make Model Serial no. Make Model -Serial no.
Dry pipe
operating
test
-
-
Timetop
through test
connection'l
Water
pressure
Air
pressure
Trip point
air pressure
Time water
reached
tastoutlett
Alarm
operated
properly
- Minutes Seconds pal psi psi Minutes Seconds Yes I No
V11
out
Q________
If no, explain
FIRF PRflTIrTlfli\f lMr
From 01/13/2014 17:51 #129 P.006/007
Operation S [J Pneumatic E] Electric D Hydraulics
Piping supervised ED Yes [] No Detecting media supervIsed D Yes No
Does valve operate from the manual trip, remote, or both EJ Yea D No
control stations?
Deluge and
preactlon
valves
Is there an accessible facility in each circuit
for testing?
1:JYas C3 No
if no, explain
Make Model
Does each circuit operate
supervision loss alarm?
Does each circuit operate
valve release?
Maximum time to
operate release
Yes No Yes No Minutes Seconds
Pressure
Location
and floor
Make and
model
Setting Static pressure Residual pressure
(flowing)
Flow rate
valve test
reducing inlet (psi) Outlet (psi)
J
Inlet (psi) Outlet (psi) Flow (gpm)
Test
description
Hydrostatic: Hydrostatic tests shall be made at not less than 200 psi (13.6 bar) for 2 hours or 50 psi (3.4bsr)
above static pressure in excess of 150 psi (10.2 bat) for 2 hours. Differential thy-pipe valve clappers strati be left
open during the list to prevent damage. All aboveground piping leakage shall be stopped.
Pneumatic: Establish 40 psi (2.7 bar) air pressure and measure drop, which shall not exceed 1½ psi (0.1 bar)
In 24 hours. Test pressure tanks at normal water level and air pressure and measure air pressure drop, which shall
not exceed 1½ psi (0.1 bar) In 24 hours.
AN piping hydrostatically lasted at -psi (_ bar) for _. hours If no, state reason
Dry piping pneumatically tested D Yes El No
Equipment operates properly 0 Yes j) No
Do you certify as the sprinkler contractor that additives and corrosive chemicals, sodium silicate or derivatives
of sodium silicate, brle, or other corrosive chemicals were not used for testing systems or stopping leaks?
Elves No
Tests
Drain I
test
Reading of gauge located near water
supply test connor1• psi (_ bar)
Residual pressure with valve in test
I connection open wide_ psi (_ bat)
Underground mains and lead In connections to system risers flushed betori connection made
to sprinkler piping
Verified by copy of the U Form No. 858 0 Yes El No Other Explain
flushed by Installer of underground
sprinkler piping El Yes El No
If powder-driven fasteners are used In concrete, has Yes No if no, explain
representative sample testing be satisfactorily
completed?
Blank leafing Number used Locations Number removed
gaskets
Welding piping El Yes No
If yes.
Do you certify as the sprinkler contractor that welding procedures comply El Yes CJ No
with the requirements of at least AWS 82.1?
Welding Do you certify that the welding was performed by welders qualified In C3 Yes El No
compliance with the requirements of at least AWS 82.1?
Do you certify that the welding was carried out in compliance with a documented El Yea D No
quality control procedure to ensure that all discs are retrieved, that openings
In piping are smooth, that slag and other welding residue are removed, and that
the internal diameters of piping are not penetrated?
Cutouts
(discs)
Do you certify that you have a control feature to ensure that :Yes El No
all cutouts (discs) are retrieved?
I• fl r r fl — — a a n a • • a * fl
From: 01/13/2014 17:51 #129 P.007/007
Hyd rate
data
rtam
Nameplate provided
c:eplae Yes
S E] No
I If no, explain
Rernas
Date left In service with all control valves open
Signatuas
Name of sprinkler contractor ç cct. crY..t*_r5
.5
Tests witnessed by
For property owner (signed) Title . Date
. ned) TM%W; Date
Additional eplanatlons and noise
kfl
FIRE PROTECTION INC.
11465 Woodside Ave. 1st. Floor
Santee CA 92071 Office 6191448-1962 Fax 6191448-1265 E Mall: andcorpl@aol.com