A Hoo-
tqco IF/re & Building
/ Products
Technical Services: Tel: (800) 381-9312 I Fax: (800) 791-5500
Series EC-8 — 8.0 K-factor
Extended Coverage (Light Hazard)
Pendent and Recessed Pendent Sprinklers
General
Description
The Series EC-8 Extended Coverage
Pendent Sprinklers are decorative
glass bwo sprinklers designed for use
in light hazard occupancies. They are
intended for use in automatic sprinkler
Systems designed Wi accordance with
standard installation rules (e.g., NFPA
13) for a maximum coverage area of
W ,h paru LU We
maximum coverage area of 225 ft2
(20,6 m2) for standard coverage sprin-
The recessed version of the EC-8, in-
tended for use in areas with a finished
ceiling, uses either the two-piece Style
30 or 40 Recessed Escutcheon. The
Style 30 Recessed Escutcheon pro-
viu up to ti iui, ,,, 11"111 UI toldl
adjustment from the flush pendent po-
sition, whereas, the Style 40 provides
..,,-t
ment from the flush pendent position.
The adjustment provided by the Re-
, C .2..t_trt2r n,I:,r,z
curacy to which the fixed pipe drops to
the sprinklers must be cut
Corrosion resistant coatings, wnere
applicable, are utilized to extend the
life of copper alloy sprinklers beyond
that which would otherwise be ob-
tained when exposed to corrosive at-
mospheres. Although corrosion resis-
IMPORTANT
Always refer to Technical Data
Sheet TFP 700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause The sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 6
tant coated sprinklers have passed the
standard corrosion tests of the appli-
cable approval agencies, the testing is
not representative of all possible cor-
rosive atmospheres. Consequently, it
is recommended that the end user be
consulted with respect to the suitability
of these corrosion resistant coatings
for any given corrosive environment
The effects of ambient temperature,
concentration of chemicals, and
gas/chemical velocity, should be con-
sidered, as a minimum, along with the
corrosive nature of the chemical to
which the sprinklers will be exposed.
WARNE
The Series EC-8 Extended Coverage
Sprinklers described herein must be
irsta-il;d, and maintained in seraph-
arise with This document, as well as
with the applicable standards of the
Natio'a' Firs Protsstis slk
in addition to the standards of any
other authorities having jurisdiction.
F-Ikkir-In in fin en snsI imnr iha
fonnance of these devices.
The owner is responsible for maintain-
tlt*J UfCI UI pIU t,4RfII Wilt U47-
vices in proper operating condition.
The installing contractor or sprinkler
with any questions.
Model/Sprinkler
Identification
Number
TY4232- Pendent;80K
TY4232 isa redeigation for C4232.
MARCH, 2007
Technical
Data
PppTo'4as
UL and C-UL Listed. FM and NYC Ap-
proved. (Refer to Table A for complete
approval information including corro-
sion resistant status. The approvals
apply to the service conditions indi-
cated in the Desiga CUterta sectio
Maximum Working Pressure
175 psi (12,1 bar)
Pipe Thread Connection
3/4 inch NPT
DisvbaTge Cocient
K = 8.0 GPM/psi112
(115,2 LPM/bar112)
TFP223
Page 2 of 6 TFP223
Components: 3/4 ** ESCUTCHEON PLATE
1 - Frame SEATING SURFACE
Button
Sealing Assembly
NPT _____
Bulb _____
2J/6" Compression ________ Screw (54,0 mm)
6-Deflector *1/2
TiL
_____
* Temperature rating is 12,7mm) 1J116' I
6-1
indicated on Deflector.MAKE-IN (36,5mm)
** Pipe thread
cormedum per ISO
7/1 can be provided
on special request.
FIGURE 1
SERIES EC-8 (TY4232) EXTENDED COVERAGE PENDENT SPRINKLERS
SPRINKLER FINISH (See Note 4)
HAZARD TYPE TEMP. BULB NATURAL CHROME WHITE*
LIQUID BRASS PLATED JPOLYESTER
LIGHT PENDENT 135F/57C Orange
Refer to Table B for UL and C-UL _______________
1,2,3,5 155°F/68°C Red
REC. PENDENT 135F167"C Orange Sensitivity Rating
and wl Style 30 Esc. 1,2,3,5
Refer to Table C for FM
155°F/68"C Red
REC. PENDENT 135°F?57"C Orange Sensitivity Rating
w/ Style 4OEsc. 1,2,5 155°F/68°C Red
NOTES:
Listed by Underwriters Laboratories, Inc. (UL).
Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL).
Apprnved by Factory Mutual Resea"ch Corporation (FM).
Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as Corrosion
Resistant Sprinklers.
Approved by the City of New York under MEA 113-04-E.
Frame and Deflector only. Listings and approvals apply to color (Special Order).
TABLE A
LABORATORY LISTINGS AND APPROVALS
(Refer to the Design Criteria Section)
Temperature Ratings
135°F/57°C and 155°F/680C
Finish
Sprinkler: Refer to Table A
Recessed Escutcheon: White Coated,
Chrome Plated, and Brass Plated
Physical Characteristics
Frame .............Bronze
Button .............Bronze
Sealing Assembly ..........
Beryllium Nickel w/Tefiont
Bulb ........Glass (3 mm dia.)
Compression Screw .........
........Bronze
Deflector ............Brass
t Registered trademark of DuPont
Operation
The glass bulb contains a iluid Thai
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass bulb, allowing the sprinkler to
activate and flow water.
Design
Criteria
The Series EC-8 Extended Coverage
Pendent Sprinklers must only be In-
stalled in accordance with the applica-
ble UL and C-UL Listing or FM Ap-
proval requirements as indicated
below. Only the Style 30 or 40 Re-
cessed Escutcheon is to be used for
recessed installation, as applicable
(Ref. Table A, B, and C)..
IlL and C-UL Listing
Requirements
The Series EC-8 Sprinklers may be
used for the coverage areas shown
in Table D, based on maintaining the
minimum specified flow rate as a
function of coverage area and haz-
ard group for all of the sprinklers in
the design area.
With respect to heat sensitivity, the
Series EC-8 Sprinklers can be used
With unobstructed construction con-
sisting of flat, smooth ceilings (in-
cluding bar joists) with a maximum
pitch of one in six as defined and
permitted by NFPA 13.
. The n mm'i spats be-
TFP223
135°F 155°F
AREA STYLE
16x16 Pendent OR OR
16x16 Style 30Recessed OR OR
16x16 Style 40 Recessed OR QR
-
18x18 Pendent QR OR
18 x. iS Style 30 Recessed OR SR.
1808 18 Style 40 Recessed OR SR
20 x 20 Pendent OR SR
20 x 20 Style 30 Recessed OR SR
20 x 20 Style 40 Recessed SR SR
OR: Quick Response
SR: Standard Response
N/A: Not Applicable
TABLE B
SENSITIVI-TY RATIND FOR. UL AND C-UL LISTING-
OF SERIES EC-8 SPRINKLERS
135F- 155F-
AREA STYLE
16x16 Pendent OR QR
16 x 16 Style 30 Recessed OR N/A
16 x 16 Style 40 Recessed N/A N/A
18x18 Pendent QR OR
18 x 18 Style 30 Recessed QR N/A
18 x 18 Style 30 Recessed N/A N/A
20x20 Pendent OR OR
20 x 20 Style 30 Recessed OR N/A
20 x 20 Style 40 Recessed N/A N/A
OR: Quick Response
SR: Standard Response--
N/A: Not Applicable
TABLE C
SENSITIVITY RATING FOR FM APPROVAL
OF SERIES i EC-8 SPRINKLERS
Page 3 of 6
Installation
The Series EC-8 Sprinklers must be
installed in accordance with the follow-
ing instructions:
NOTES
Do not install any bulb type sprinkler if
the Iii/b is cracked or there ,s a loss of
liquid from the bulb. With the sprinkler
held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 inch
(1,6mm).
A leak tight 3/4 inch NPTsprinkler joint
should be obtained with a torque of 10
to 20 ft.lbs. (13)4 to-26,8 Nm-i A maxi-
mum of 30 tUbs. (40,7 Nm) of torque
is to be used to install sprinklers.
Higher levels of torque may distort the
sprinkler iri/et wft/r consequent leak-
age or impairment of the sprinkler.
Do-not attempt - to-compensate- for-in-
sufficient adjustment of an Escutcheon
Plate by under- or over-tightening the
Sprinkler. Readjust the position of the
sprinkler fitting to suit.
Step 1. The sprinkler must be installed
with the deflector parallétto the mount-
ing surface. Pendent sprinklers must
be installed in the pendent position.
Step 2. After installing the Style 30 or
40 mounting plate (or other escutch-
eon, as applicable), over the sprinkler
pipe threads, and with pipe Thread
sealant applied to the pipe threads,
hand tighten the sprinkler into the
sprinkler fitting.
Step 3. Wrench tighten pendent sprin-
klers-using only-the W-Type 3- (End -A) -
Sprinkler Wrench. Wrench tighten the
recessed pendent sprinklers using
only the W-Type 23 Sprinkler Wrench.
The wrench recess of the applicable
sprinkler wrench (Ref. Figure 4 and 5)
is to be applied to the sprinkler wrench
flats tRei. Figure f).
tween the Series EC-8 Sprinklers, to
prevent cold soldering, is 8 feet (2,4
M).
4. The Series EC-8 Sprinklers are to be
installed in accordance with all other
requirements of NFPA 13 for ex-
tended coverage pendant sprin-
klers.
FM Approval
Requirements
The Series EC-8 Extended Coverage
Sprinklers aretabe installed in accord-.
ance with the applicable Factory Mu-
tual Loss Prevention Data Sheet. Infor-
mation provided in the FM Loss
Prevention Data Sheets relate to, but
are not limited to, hydraulic design,
ceiling slope and obstructions, mini-
mum and maximum atlawabte spec-
ing, and deflector-to ceiling distance.
Page 4 of 6 TFP223
DESCRIPTION AREA GPM PSI
TY4232 (K=8.0) PENDENT 16 x 16 26 10.6
18x18
20 x 20 5.O
1 ft. = 0.3048 m
1 ft2 = 0.093 m2
I gpm=3.785 1pm
1 psi = 0.06895 bar
I gpm/ft2 = 40.74 mm/mm
TABLED
FLOW-CRITERIA-FOR-UL AND C1JL LISTING
OF SERIES EC-8 SPRINKLERS
2-7/8 DIA.
1/2±1/8 (73,0 mm) 1/2' (12,7 mm) r (12,7t3,2 mm) 2-AW DIA. 1/4" (6,4 mm)
FACE OF (57,2 mm)
FITTING (3,2 mm) SPRINKLER 1/8"
/
MOUNTING /
SURFACE /7 MOUNTING
CLOSURE ________
PLATE
1-1I4"(31,8mm)
1" (25,4 mm)
FIGURE 2
SERIES EC-8 RECESSED PENDENT SPRINKLER ASSEMBLY
WITH iWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 30 RECESSED ESCUTCHEON
• 2-7/8" DIA.
9/16±1/4" (73,0 mm) 3/4"(19,1 mm)
(14,3±6,4 mm) 2-114" DIA. 114(6,4 mm)
FACE OF (57,2 mm)
SPRINKLER 1/8"
FITTING (3,2 mm)
T \
MOUNTING /
SURFACE MOUNTING
PLATE
CLOSURE I
1-5/16(33,3 mm) 1
13/16(20,6mm)
FIGURE 3
SERIES EC-8 RECESSED PENDENT SPRINKLER ASSEMBLY
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 40 RECESSED ESCUTCHEON
"FITTING SIDE"
TOWARDS SPRINKLER
FITTING
/ WRENCH
RECESS
(END "A")
FIGURE 4
W-TYPE 3 SPRINKLER
WRENCH.,
WRENCH
RECESS
'----I
FIGURE 5
W-TYPE 23 RECESSED
SPRINKLER WRENCH
Care and
Maintenance
The Series EC-8 Sprinklers must be
maintained and serviced in accord-
ance with the following instructions:
NOTE
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, permission to shut down
the affected fire protection systems
must be obtained from the proper
authorities and all personnel who may
be affected by ffiis act/on must be no-
tified.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or otherwise
altered after leaving the factory. Modi-
fied sprinklers must be replaced.
Sprinklers that have been exposed to
TFP223 Page 5 of 6
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid dam-
age to the sprinklers - before, during,
and after installation. Sprinklers dam-
aged by dropping, striking, wrench
twist/slippage, or the like, must be re-
placed. Also, replace any sprinkler that
has a cracked bulb or that has lost
liquid from its bulb. (Ref. Installation
Section).
Frequent visual inspections are rec-
ommended to be initially performed for
corrosion resistant coated sprinklers,
after the installation has been com-
pleted, to verify the integrity of the cor-
rosion resistant coating. Thereafter,
snni*l insnetinnq mar NFPA 21,
should suffice; however, instead of in-
specting from the floor level, a random
sampling of close-up visual inspec-
tions should be made, so as to better
determine the exact sprinkler condi-
tion and the long term integrity of the
corrosion resistant coating, as it may
be affected by the corrosive conditions
present.
The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. The in-
stalling contractor or sprinkler manu-
facturer should be contacted relative
to any questions.
It is recommended that automatic
sprinkler systems be inspected,
tested, and maintained by a qualified
Inspection Service in accordance with
local requirements and/or national
codes.
Limited
Warranty
Products manufactured by Tyco Fire &
Building Products (TFBP) are war-
ranted solely to the original Buyer for
ten (10) years against defects in mate-
rial and workmanship when paid for
and properly installed and maintained
under normal use and service. This
warranty will expire ten (10) years
from date of shipment by TFBP. No
warranty is given for products or com-
ponents manufactured by companies
not affiliated by ownership with TFBP
or for products and components which
have been subject to misuse, improper
installation, corrosion, or which have
not been installed, maintained, modi-
fied or reeaired in accordance with a-
plicable Standards of the National Fire
Protection Association, and/or the
standards of any other Authorities
Having Jurisdiction. Materials found
by TFBP to be defective shall be either
repaired or replaced, at TFBP's sole
option. TFBP neither assumes, nor
authorizes any person to assume for it,
any other obligation in connection with
the sate of products or parts of prod-
ucts. TFBP shall not be responsible for
sprinkler system design errors or inac-
curate or incomplete information sup-
plied by Buyer or Buyer's repre-
sentatives.
In no event shall TFBP be liable, in
contract, tort, strict liability or under
any other legal theory, for incidental,
indirect, special or consequential dam-
ages, including but not limited to labor
charges, regardless of whether TFBP
was informed about the possibility of
such damages, and in no event shall
TFBP's liability exceed an amount
equal to the sales price.
The foregoing warranty is made in lieu
of any and all other warranties, ex-
press or implied, including warranties
of merchantability and fitness for a par-
ticular purpose.
This limited warranty sets forth the ex-
clusive remedy for claims based on
failure of or defect in products, materi-
als or components, whether the claim
is made in contract, tort, strict liability
or any other legal theory.
This warranty will apply to the full ex-
tent permitted by law. The invalidity, in
whole or part, of any portion of this
warranty will not affect the remainder.
Ordering
Procedure
When placing an order, indicate the
fult product name. Please spectf'j the
Sprinkler Identification Number (SIN),
quantity, and temperature rating. Re-
fer to the Price List for complete listing
of Part Numbers.
Contact your local distributor for avail-
ability.
Sprinkler Assemblies with NPT
Thread Connections
Specify: TY4232, (specify tempera-
ture rating), Extended Coverage Pen-
dent Sprinkler with (specify finish). PII'4
(specify)-
137w
ron .ju-ou I-
White Coated .............PSN 50-801-4-135
White (RAL9O1O). .......... PSN 50-801-3-135
Chrome Plated . .......... .PSN 50-801-9-135
155°FI68C
Natural Brass .............PSN 50-801-1-155
White Coated .............PSN 50-801-4-155
White (RAL90W) .........PSN 0.80?-3-155
Chrome Plated ............PSN 50-801-9-155
Eastern Hemisphere sales only.
Recessed Escutcheon:
Specify: Style (30 or 40) Recessed
Escutcheon with (specify finish), PIN
(specify).
Style 30 Recessed Escutcheon
Chrome Plated ............PSN 56-705-9-011
White Color Coated ........PSN 56-705-4-011
White (RAL901O) .........PSN 56-705-3-011
Brass Plated ......... ..... PSN 56-705-2-011
Style 40 Recessed Escutcheon
Chrome Plated ............PSN 56-700-9-010
White Color Coated ........PSN 56-700-4-010
White (RAL9OIO) ........... PSN 56-700-3-010
Brass Plated ..............PSN 56-700-2-010
*Eastern Hemisphere sales only.
Sprinkler Wrench:
Specify: W-Type 3 Sprinkler Wrench,
P/N 56-895-1-001.
Specify: W-Type 23 Recessed Sprin-
kler Wrench, P/N 56-000-6-838.
Page 6 of 6 TFP223
TYCO FIRE & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446
Sully Fire Protection
1975 Spanish Oak Way
Vista, California 92081
760-727-3444
HYDRAULIC CALCULATIONS
FOR
Suite 208 - Entire Room
Room Design - Hallway door to have automatic closer
Richard Sax Tenant Improvement
2150 Palomar Airport Road, Suite 208
Carlsbad, California
FILE NUMBER: HangerTl.sdf
April 19, 2011
-DESIGN DATA-
OCCUPANCY CLASSIFICATION: Light Hazard
DENSITY:
AREA OF APPLICATION:
COVERAGE PER SPRINKLER:
NUMBER OF SPRINKLERS CALCULATED:
TOTAL SPRINKLER WATER FLOW REQUIRED:
FLOW AND PRESSURE REQUIRED AT SOURCE
PRESSURE AVAILABLE AT SOURCE:
SPRINKLER ORIFICE SIZE:
0.10 gpm/sqft
1,315 square feet
256 sqft max.
7 sprinklers
174.20 gpm
174.20 gpm @ 17.5 psi
58.7 psi at 242.9 gpm
17/32"
NAME OF CONTRACTOR: Sully Fire Protection, C-16 701590
Note: Tenant improvement calculations for Suite 208 evaluated to
existing light hazard occupancy requirements for other more
remote light hazard occupancy requirements at base of riser.
CALCULATIONS BY MASS COMPUTER PROGRAM (LICENSE # 50110279
HRS SYSTEMS, INC.
ATLANTA, GA
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2
DATE: 4/20/2011 C:\HASS78\FILES\HANGERTI.SDF
JOB TITLE: Revised Office Space
WATER SUPPLY DATA
SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D
NODE PRESS. PRESS. @ PRESS. @ DEMAND PRESS.
TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI)
RISER 58.7 58.7 242.9 58.7 174.2 17.5
Required pressure is 41.2 psi (70%) less than available pressure.
AGGREGATE FLOW ANALYSIS:
TOTAL FLOW AT SOURCE 174.2 GPM
TOTAL HOSE STREAM ALLOWANCE AT SOURCE 0.0 GPM
OTHER HOSE STREAM ALLOWANCES 0.0 GPM
TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 174.2 GPM
NODE ANALYSIS DATA
DENSITY
NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE AREA REQ. ACT.
(FT) (PSI) (GPM) (FT-2) (GPM/FT"2)
1 8.8 K= 8.00 10.2 25.6 256.0 0.100 0.100
2 8.8 K= 8.00 10.4 25.8 256.0 0.100 0.101
3 8.8 K= 8.00 10.4 25.8 256.0 0.100 0.101
4 8.8 K= 5.60 10.7 18.3 150.0 0.100 0.122
5 8.8 K= 8.00 10.6 26.0 256.0 0.100 0.102
6 8.8 K= 8.00 10.8 26.2 256.0 0.100 0.102
7 8.8 K= 8.00 10.8 26.3 256.0 0.100 0.103
A 9.4 12.3 - - -
B 9.4 - - - - 12.3 - - -
C 9.4 - - - - 12.4 - - -
D 9.4 - - - - 12.4 - - -
E 9.4 - - - - 12.4 - - -
F 9.4 - - - - 12.4 - - -
G 9.4 - - - - 12.5 - - -
H 9.4 - - - - 12.5 - - -
TOR 9.4 - - - - 13.3 - - -
RISER 0.0 SOURCE 17.5 174.2
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3
DATE: 4/20/2011 C:\HASS78\FILES\HANGERTI.SDF
JOB TITLE: Revised Office Space
PIPE DATA
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM.
NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe: 1 -25.6 1.087 PL 5.25 PF 2.3
1 8.8 8.0 10.2 25.6 8.9 120 FTG ET PE -0.3
A 9.4 0.0 12.3 0.0 0.173 TL 13.55 PV
Pipe: 2 -25.8 1.087 PL 4.25 PF 2.2
2 8.8 8.0 10.4 25.8 8.9 120 FTG ET PE -0.3
B 9.4 0.0 12.3 0.0 0.175 TL 12.55 PV
Pipe: 3 -25.8 1.087 PL 4.25 PF 2.2
3 8.8 8.0 10.4 25.8 8.9 120 FTG ET PE -0.3
D 9.4 0.0 12.4 0.0 0.176 TL 12.55 PV
Pipe: 4 -18.3 1.087 PL 10.50 PF 2.0
4 8.8 5.6 10.7 18.3 6.3 120 FTG 2ET PE -0.3
E 9.4 0.0 12.4 0.0 0.093 TL 21.20 PV
Pipe: 5 -26.0 1.087 PL 3.25 PF 2.1
5 8.8 8.0 10.6 26.0 9.0 120 FTG ET PE -0.3
E 9.4 0.0 12.4 0.0 0.178 TL 11.55 PV
Pipe: 6 -26.2 1.087 PL 2.25 PF 1.9
6 8.8 8.0 10.8 26.2 9.1 120 FTG ET PE -0.3
F 9.4 0.0 12.4 0.0 0.181 TL 10.55 PV
Pipe: 7 -26.3 1.087 PL 2.25 PF 1.9
7 8.8 8.0 10.8 26.3 9.1 120 FTG ET PE -0.3
H 9.4 0.0 12.5 0.0 0.182 TL 10.55 PV
Pipe: 8 -25.6 3.314 PL 16.17 PF 0.0
A 9.4 0.0 12.3 0.0 1.0 120 FTG ---- PE 0.0
B 9.4 0.0 12.3 0.0 0.001 TL 16.17 PV
Pipe: 9 -51.4 3.314 PL 2.17 PF 0.1
B 9.4 0.0 12.3 0.0 1.9 120 FTG T PE 0.0
C 9.4 0.0 12.4 0.0 0.003 TL 21.87 PV
Pipe: 10 25.8 3.314 PL 14.00 PF 0.0
C 9.4 0.0 12.4 0.0 1.0 120 FTG T PE 0.0
D 9.4 0.0 12.4 0.0 0.001 TL 33.70 PV
Pipe: 11 -44.3 3.314 PL 16.70 PF 0.0
E 9.4 0.0 12.4 0.0 1.6 120 FTG ---- PE 0.0
F 9.4 0.0 12.4 0.0 0.002 TL 16.70 PV
Pipe: 12 -70.5 3.314 PL 2.17 PF 0.1
F 9.4 0.0 12.4 0.0 2.6 120 FTG T PE 0.0
G 9.4 0.0 12.5 0.0 0.005 TL 21.87 PV
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4
DATE: 4/20/2011 C:\HASS78\FILES\HANGERTI.SDF
JOB TITLE: Revised Office Space
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM.
NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe: 13 26.3 3.314 PL 14.00 PF 0.0
G 9.4 0.0 12.5 0.0 1.0 120 FTG T PE 0.0
H 9.4 0.0 12.5 0.0 0.001 TL 33.70 PV
Pipe: 14 -77.2 3.314 PL 20.40 PF 0.1
C 9.4 0.0 12.4 0.0 2.9 120 FTG ---- PE 0.0
G 9.4 0.0 12.5 0.0 0.006 TL 20.40 PV
Pipe: 15 -174.1 3.314 PL 15.00 PF 0.8
G 9.4 0.0 12.5 0.0 6.5 120 FTG 2E PE 0.0
TOR 9.4 0.0 13.3 0.0 0.026 TL 30.00 PV
Pipe: 16 -174.2 4.310 PL 9.50 PF 0.1
TOR 9.4 0.0 13.3 0.0 3.8 120 FTG CG PE 4.1
RISER 0.0 SRCE 17.5 (N/A) 0.007 TL 9.50 PV
NOTES (HASS)
Calculations were performed by the HASS 8.1 computer program
under license no. 50110279 granted by
HRS Systems, Inc.
208 South Public Square
Petersburg, TN 37144
(931) 659-9760
The system has been calculated to provide an average
imbalance at each node of 0.024 gpm and a maximum
imbalance at any node of 0.382 gpm.
Total pressure at each node is used in balancing the system.
Maximum water velocity is 9.1 ft/sec at pipe 7.
PIPE FITTINGS TABLE
Pipe Table Name: STANDARD.PIP
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5
DATE: 4/20/2011 C:\HASS78\FILES\HANGERTI.SDF
JOB TITLE: Revised Office Space
PAGE: W MATERIAL: DyThd HWC: 120
Diameter Equivalent Fitting Lengths in Feet
(in) E T L R B G A C
Eli Tee 45 RunTee Bfly Gate Alarm Check
1.087 2.40 5.90 1.20 2.30 0.00 0.00 0.00 4.80
PAGE: Y MATERIAL: DynaFi HWC: 120
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D
Eli Tee 45 Check BtrFly GateVi
3.314 7.50 19.70 0.00 0.00 0.00 0.00 0.00 0.00
4.310 9.60 22.70 0.00 0.00 0.00 0.00 0.00 0.00
WATER SUPPLY ANALYSIS
Static: 58.70 psi Resid: 58.69 psi Flow: 242.9 gpm
70.0
60.0
50.0
P
R
F:
S 40.0
S
U
R E 30.0
20.0
S
1
10.0
0.0
-14.7
200 300 400 500 600 700 800 900 1000
FLOW (GPM)