Series EC-8 ā 8.0 K-factor
Extended Coverage (Light Hazard)
Pendent and Recessed Pendent Sprinklers
General
Description
The Series EC-8 Extended Coverage
Pendent Sprinklers are decorative
glass bulb sprinklers designed for use
in light hazard occupancies. They are
intended for use in automatic sprinkler
systems designed in accordance with
standard installation IUICS (e.g., NFPA 13) for a maximum coverage area of
400 ft2 (37,2 m2), as compared to the
maximum coverage area of 225 ft2 (20,6 m2) for standard coverage sprin-
klers used in light hazard occupancies.
The recessed version of the EC-6, in-
tended for use in areas with a finished
ceiling, uses either the two-piece Style
30 or All Oarocoad rer,,trhanr, The Style 30 Recessed Escutcheon pro-
vides up to 1/2 inch (12,7 mm) of total
adjustment from the flush pendent po-
sition, whereas, the Style 40 provides
3/4 inch (19,1 mm) of vertical adjust-
ment from the flush pendent position.
The adjustment provided by the Re-
cessed Escutcheons reduces the ac-
curacy to which the fixed pipe drops to
the sprinklers must be cut.
Corrosion resistant coatings, where
applicable, are utilized to extend the
life of copper alloy sprinklers beyond
that Which would otherwise be ob-
tained when exposed to corrosive at-
mospheres. Although corrosion resis-
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can, permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 6
tant coated sprinklers have passed the
standard corrosion tests of the appli-
cable approval agencies, the testing is
not representative of all possible cor-
rosive atmospheres. Consequently, it
is recommended that the end user be
consulted with respect to the suitability
of these corrosion resistant coatings
for any given corrosive environment.
The effects of ambient temperature,
concentration of chemicals, and
gasichemicai velocity, should be con-
sidered, as a minimum, along with the
corrosive nature of the chemical to
which the sprinklers w-1411 be exposed.
WARNINGS
The Series EC-8 Extended Coverage
Sprinklers described herein must be
installed and maintained in compli-
ance with this document, as well as
with the applicable standards of the
National Fire Protection Association,
in addition to the standards of any
other authorities having jurisdiction.
Failure to do so may impair the per-
formance of these devices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
Model/Sprinkler
Identification
Number
TY4232 - Pendent, 8.0K
TY4232 is a redesignation for C4232.
MARCH, 2007
Technical
Data
Approvals
UL and C-UL Listed. FM and NYC Ap-
proved. (Refer to Table Afor complete
approval information including corro-
sion resistant status. The approvals
apply to the service conditions indi-
cated in the Design Criteria section.)
Maximum Working Pressure
175 psi (12,1 bar)
Pipe Thread Connection
3/4 inch NPT
Discharge Coefficients
K = 8.0 GPM/ps1112
(115,2 LPM/barll2)
TFP223
Page 2 of 6 TFP223
Components: 3/4 ** ESCUTCHEON PLATE
1 - Frame SEATING SURFACE
2 - Button
3 - Sealing Assembly
NPT
ā7 Bulb
Compression
___________ Screw
________ ________ (54,0 mm) Deflector* 3
J 11MAKE-IN
1/2 _______
* Temperature rating is NOMINAL
12,7 mm) /16"
indicated on Deflector. (36,5 mm)
** Pipe thread
connections per ISO
7/1 can be provided 6*
on special request.
FIGURE 1
SERIES EC-8 (TY4232) EXTENDED COVERAGE PENDENT SPRINKLERS
SPRINKLER FINISH (See Note 4)
HAZARD TYPE TEMP. BULB NATURAL I CHROME WHITE*
LIQUID BRASS PLATED POLYESTER
I
LIGHT PENDENT 135"F/57"C Orange
Refer to Table B for UL and C-UL
1,2,3,5 155°F/68°C Red _______________
REC. PEN DENT 135"F/57"C Orange Sensitivity Rating
and WI Style 30 Esc. 1, 2, 3, 5 Refer to Table C for FM
155"17168C Red
REC. PENDENT 135°F/57°C Orange Sensitivity Rating
wl Style 40 Esc. 1,2,5 155117I1 Red
NOTES:
Listed by Underwriters Laboratories, Inc. (UL).
Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL).
Approved by Factory Mutual Research Corporation (FM).
Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as Corrosion
Resistant Sprinklers.
Approved by the City of New York under MEA 113-04-E.
"Frame and Deflector only. Listings and approvals apply to color (Special Order).
TABLE A
LABORATORY LISTINGS AND APPROVALS
(Refer to the Design Criteria Section)
Temperature Ratings
135°F157°C and 155°F/68°C
Finish
Sprinkler: Refer to Table A
Recessed Escutcheon: White Coated,
Chrome Plated, and Brass Plated
Physical Characteristics
Frame .............Bronze
Button .............Bronze
Sealing Assembly ..........
Beryllium Nickel w/Teflont
Bulb ........Glass (3 mm dia.)
Compression Screw .........
.......Bronze
Deflector ............Brass
t Registered trademark of DuPont
Operation
The glass bulb contains a fluid that
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass bulb, allowing the sprinkler to
activate and flow water.
Design
Criteria
The Series EC-8 Extended Coverage
Pendent Sprinklers must only be in-
stalled in accordance with the applica-
ble UL and C-UL Listing or FM Ap-
proval requirements as indicated
below. Only the Style 30 or 40 Re-
cessed Escutcheon is to be used for
recessed installation, as applicable
(Ref. Table A, B, and C)..
UL and C-UL Listing
Requirements
The Series EC-8 Sprinklers may be
used for the coverage areas shown
in Table D, based on maintaining the
minimum specified flow rate as a
function of coverage area and haz-
ard group for all of the sprinklers in
the design area.
With respect to heat sensitivity, the
Series EC-8 Sprinklers can be used
with unobstructed construction con-
sisting of flat, smooth ceilings (in-cluding bar joists) with a maximum
pitch of one in six as defined and
permitted by NFPA 13.
The minimum allowable spacing be-
Page 3 of 6 TFP223
135°F 155°F
AREA STYLE
16x16 Pendent OR OR 16x16 Style 30 Recessed OR OR
16x16 Style 40 Recessed OR OR
18x18 Pendent OR OR 18x18 Style 30Recessed OR SR 18 x 18 Style 40 Recessed OR SR
20 x 20 Pendent OR SR 20 x 20 Style 30 Recessed OR SR
20 x 20 Style 40 Recessed SR SR
OR: Quick Response
SR: Standard Response
N/A: Not Applicable
TABLE B
SENSITIVITY RATING FOR UL AND C-UL LISTING
OF SERIES EC-8 SPRINKLERS
135°F 155°F
AREA STYLE
16x16 Pendent OR OR 16X 16 Style 30 Recessed OR N/A
16 x 16 Style 40 Recessed N/A N/A
18x18 Pendent OR OR 18x18 Style 30 Recessed OR N/A 18 x 18 Style 30 Recessed N/A N/A
20 x 20 Pendent OR OR 20 x 20 Style 30 Recessed OR N/A
20 x 20 Style 40 Recessed N/A N/A
OR: Quick Response
SR: Standard Response
N/A: Not Applicable
TABLE C
SENSITIVITY RATING FOR FM APPROVAL
OF SERIES EC-8 SPRINKLERS
Installation
The Series EC-8 Sprinklers must be
installed in accordance with the follow-
ing instructions:
NOTES
Do not install any bulb type sprinkler if
the bulb is cracked or there is a loss of
liquid from the bulb. With the sprinkler
held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 inch
(1,6mm).
A leak fight 3/4 inch NPTsprinklerjoini
should be obtained with a torque of 10
to 20 ft.lbs. (13,4 to 26,8 Nm). A maxi-
mum of 30 ft. lbs. (40,7 Nm) of torque
is to be used to install sprinklers.
Higher levels of torque may distort the
sprinkler inlet with consequent leak-
age or impairment of the sprinkler.
Do not attempt to compensate for in-
sufficient adjustment ofan Escutcheon
Plate by under- or over-tightening the
Sprinkler. Readjust the position of the
sprinkler fitting to suit.
Step 1. The sprinkler must be installed
with the deflector parallel to the mount-
ing surface. Pendent sprinklers must
be installed in the pendent position.
Step 2. After installing the Style 30 or
40 mounting plate (or other escutch-
eon, as applicable) over the sprinkler
pipe threads, and with pipe thread
sealant applied to the pipe threads,
hand tighten the sprinkler into the
sprinkler fitting.
Step 3. Wrench tighten pendent sprin-
klers using only the W-Type 3 (End A)
Sprinkler Wrench. Wrench tighten the
recessed pendent sprinklers using
only the W-Type 23 Sprinkler Wrench.
The wrench recess of the applicable
sprinkler wrench (Ref. Figure 4 and 5)
is to be applied to the sprinkler wrench
flats (Ref. Figure 1).
tween the Series EC-8 Sprinklers, to
prevent cold soldering, is 8 feet (2,4
M).
4. The Series EC-8 Sprinklers are to be
installed in accordance with all other
requirements of NFPP 13 for ex-
tended coverage pendent sprin-
klers.
FM Approval
Requirements
The Series EC-8 Extended Coverage
Sprinklers are to be installed in accord-
ance with the applicable Factory Mu-
tual Loss Prevention Data Sheet. Infor-
mation provided in the FM Loss
Prevention Data Sheets relate to, but
are not limited to, hydraulic design,
ceiling slope and obstructions, mini-
mum and maximum allowable spac-
ing, and deflector-to ceiling distance.
Page 4 of 6 TFP223
DESCRIPTION AREA GPM PSI
TY4232 (K8.0) PENDENT 16 x 16 26 10.6
18x18 33 17.0
20x20 40 25.0 1 ft. = 0.3048 m
1 ft2 = 0.093 m2
1 gpm = 3.785 1pm
1 psi = 0.06895 bar
1 gpm/ft2 = 40.74 mm/mm
TABLED
FLOW CRITERIA FOR UL AND C-UL LISTING
OF SERIES EC-8 SPRINKLERS
2-7/8" DIA.
(73,0 mm) 1/2" (12,7 mm)
(12,7±3,2 mm) 2-1/4" DIA. 1/4" (6,4 mm)
FACE OF (57,2 mm)
SPRINKLER 1/8"
FITTING (3,2 mm)
MOUNTING
MOUNTING
SURFACE
PLATE r CLOSURE
1-1/4"(31,8 mm)
1" (25,4 mm)
FIGURE 2
SERIES EC-8 RECESSED PENDENT SPRINKLER ASSEMBLY
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 30 RECESSED ESCUTCHEON
2-7/8" DIA.
9/16±1/4" (73,0 mm) 314"(19,1 mm) r (14,3±6,4 mm) 2-1/4',DIA. 1/4(6,4 mm)
e\/j
118"
FITTING
I (3 mm) I
I FACE OF (57,2 mm)
SPRINKLER
2
MOUNTING MOUNTING SURFACE PLATE
CLOSURE
1-5/16" (33,3 mm)
13/16" (20,6 mm)
FIGURE 3
SERIES EC-8 RECESSED PENDENT SPRINKLER ASSEMBLY
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 40 RECESSED ESCUTCHEON
"FITTING SIDE"
TOWARDS SPRINKLER
FITTING
WRENCH
RECESS
FIGURE 4
W-TYPE 3 SPRINKLER
WRENCH
WRENCH
RECESS
ri
uāf
FIGURE 5
W- TYPE 23 RECESSED
SPRINKLER WRENCH
Care and
Maintenance
The Series EC-8 Sprinklers must be
maintained and serviced in accord-
ance with the following instructions:
NOTE
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, permission to shut down
the affected fire protection systems
must be obtained from the proper
authorities and all personnel who may
be affected by this action must be no-
tified.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or otherwise
altered after leaving the factory. Modi-
fied sprinklers must be replaced.
Sprinklers that have been exposed to
TFP223 Page 5 of 6
corrosive products of combustion, but
have not operated, should be replaced
If they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid dam-
age to the sprinklers - before, during,
and after installation. Sprinklers dam-
aged by dropping, striking, wrench
twistfslippage, or the like, must be re-
placed. Also, replace any sprinkler that
has a cracked bulb or that has lost
liquid from its bulb. (Ref. Installation
Section).
Frequent visual inspections are rec-
ommended to be initially performed for
corrosion resistant coated sprinklers,
after the installation has been corn- ...I..e .,.1 .. ., ,.A.H,... fllcl&%A, WI VOl 117 (tIC UI hOWl 1(7 JI 10 %fl.Jl
rosion resistant coating. Thereafter,
annual inspections per NFPA 25
should suffice; however, instead of in-
specting from the floor level, a random
sampling of close-up visual inspec-
tions should be made, so as to better
determine the exact sprinkler condi-
tion and the long term integrity of the
corrosion resistant coating, as it may
be affected by the corrosive conditions
present.
The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. The in-
stalling contractor or sprinkler manu-
facturer should be contacted relative
to any questions.
It is recommended that automatic
sprinkler systems be inspected,
tested, and maintained by a qualified
Inspection Service in accordance with
local requirements and/or national
codes.
Limited
Warranty
Products manufactured by Tyco Fire &
Building Products (TFBP) are war-
ranted solely to the original Buyer for
ten (10) years against defects in mate-
rial and workmanship when paid for
and properly installed and maintained
under normal use and service. This
warranty will expire ten (10) years
from date of shipment by TFBP. No
warranty is given for products or com-
ponents manufactured by companies
not affiliated by ownership with TFBP
or for products and components which
have been subject to misuse, improper
ip.staRation, corrosion, or which have
not been installed, maintained, modi-
fied or repaired in accordance with ap-
plicable Standards of the National Fire
Protection Association, and/or the
standards of any other Authorities
Having Jurisdiction. Materials found
by TFBP to be defective shall be either
repaired or replaced, at TFBP's sole
option. TFBP neither assumes, nor
authorizes any person to assume for it,
any other obligation In connection with
the sale of products or parts of prod-
ucts. TFBP shall not be responsible for
sprinkler system design errors or inac-
curate or incomplete information sup-
plied by Buyer or Buyer's repre-
sentatives.
In no event shall TFBP be liable, in
contract, tort, strict liability or under
any other legal theory, for incidental,
indirect, special or consequential dam-
ages, including but not limited to labor
charges, regardless of whether TFBP
was informed about the possibility of
such damages, and in no event shall
TFBP's liability exceed an amount
equal to the sales price.
This limited warranty sets forth the ex-
clusive remedy for claims based on
failure of or defect in products, materi-
als or components, whether the claim
is made in contract, tort, strict liability
or any other legal theory.
This warranty will apply to the full ex-
tent permitted bylaw. The invalidity, in
whole or part, of any portion of this
warranty will not affect the remainder.
Ordering
Procedure
When placing an order, indicate the
full product name. Please specify the
Sprinkler Identification Number (SIN),
quantity, and temperature rating. Re-
fer to the Price List for complete listing
of Part Numbers.
Contact your local distributor for avail-
ability.
Sprinkler Assemblies with NPT
Thread Connections:
Specify: 1Y4232, (specify tempera-
ture rating), Extended Coverage Pen-
dent Sprinkler with (specify finish), P/N
(specify).
135.FI5rc
Natural Brass .............PSN 50-801-1-135
White Coated .............PSN 50-801-4-135
White (RAL9010) ........... PSN 50-801-3-135
Chrome Plated ............PSN 50-801-9-135
155FI681C
Natural Brass .............PSN 50-801-1-155 White Coated .............PSN 50-801-4-155
White (RALQOIO). .......... PSN 50-801-3-155 Chrome Plated ............PSN 50-801-9-155
*Eastern hemisphere sales only.
Recessed Escutcheon:
Specify: Style (30 or 40) Recessed
Escutcheon with (specify finish), P/N
(specify).
Style 30 Recessed Escutcheon
Chrome Plated ............PSN 56-705-9-011
White Color Coated ........PSN 56-7054-011 White (RAL9OIO). .......... PSN 56-705-3-011
Brass Plated .. ............ PSN 56-705-2-011
Style 40 Recessed Escutcheon Chrome Plated ............PSN 56-700-9-010 White Color Coated ........PSN 56-700-4-010 White (RAL9010) .........PSN 56-700-3-010
Brass Plated ..............PSN 56-700-2-010
Eastern Hemisphere sales only.
Sprinkler Wrench:
Specify: W-Type 3 Sprinkler Wrench,
P/N 56-895-1-001,
Specify: W-Type 23 Recessed Sprin-
kler Wrench, P/N 56-000-6-838.
Page 6 of 6 TFP223