HomeMy WebLinkAbout2100 PALOMAR AIRPORT RD; 214; AS110172; Permit12/28/2020 AS110172 Permit Data
City of Carlsbad
Sprinkler Permit
2100 PALOMAR
Job Address:
AIRPORT RD
Permit Type: SPRINK
Parcel No: 2130201800
Lot #: 0
Reference No.:
PC #:
Permit No: AS110172
Status: APPROVED
Applied 11/21/2011
Approved: 12/22/2011
Issued: 12/22/2011
Inspector:
Project Title: SWAIN COLLINS AVIATION PROP. T.I. STE 214
Applicant:
PACIFIC FIRE SYSTEMS, INC.
13142 NELSON LANE
POWAY, CA
858-722-9865
Owner:
COUNTY OF SAN DIEGO
PUBLIC AGENCY
Fees ($) Add'l Fees ($) Total ($) Balance ($)
262 0 262 0
1/1
Contractor's Material and Test Certificate for Aboveground Piping FILE COPY
PROCEDURE
Upon completion of work, inspection and tests shall be made by the Contractor's representative and witnessed by an owner's representative. All defects
shall be corrected and system left in service before contractor's personnel finally leave the job.
A certificate shall be filled out and signed by both representatives. Copies shall be prepared for approving authorities, owners, and contractor. It is
understood the owner's representative's signature in no way prejudices any claim against contractor for faulty material, poor workmanship, or failure to
comply with approving authority's requirements or local ordinances.
PROPERTY NAME SL-Al 1¼) C_O(v ) I DATE IZ_k-7/1i
PROPERTY ADDRESS 2100 4po.-r tQA
ACCEPTED BY APPROVING AUTHORITIES (NAMES) D I2
RESS
PLANS INSTALLATION CONFORMS TO ACCEPTED PLANS 0 YES El NO
EQUIPMENT USED IS APPROVED YES 0 NO
IF NO, EXPLAIN DEVIATIONS
INSTRUCTIONS
HAS PERSON IN CHARGE OF FIRE EQUIPMENT BEEN INSTRUCTED AS TO LOCATION 0 YES
OF CONTROL VALVES AND CARE AND MAINTENANCE OF THEIS NEW EQUIPMENT?
IF NO, EXPLAIN
U NO
HAVE COPIES OF THE FOLLOWING BEEN LEFT ON THE PREMISES Z YES
SYSTEM COMPONENTS INSTRUCTIONS 9 YES
CARE AND MAINTENANCE INSTRUCTIONS 0 YES
NFPA 25 0 YES
El NO
El NO U NO
0 NO
LOCATION SUPPLIES BUILDINGS
SPRINKLERS
MAKE MODEL
YEAR OF
MANUFACTURE
ORIFICE
SIZE QUANTITY
TEMPERATURE
RATING
________________ f -F3 I vz, - 1 / S-S-
01(
PIPE AND
FITTINGS
TYPE OF PIPE
TYPE OF FITTINGS
ALARM VALVE ALARM DEVICE
MAXIMUM TIME TO OPERATE
THROUGH TEST CONNECTION
OR TYPE MAKE I MODEL MIN SEC
FLOW
INDICATOR i\J
MAKE MODEL I SERIAL NO. MAKE MODEL SERIAL NO.
DRY PIPE
OPERATING
TEST
TIME TO TRIP
THROUGH TEST
CONNECTION
WATER
PRESSURE
AIR TRIP
PRESSURE
POINT
AIR PRESSURE
TIME WATER
REACHED
TEST OUTLET
ALARM
OPERATED
PROPERLY
MIN
WITH SEC PSI PSI PSI MIN I SEC YES I NO
NJ/ O.O.D.
W/O
Q.O.D.
IF NO, EXPLAIN
OPERATION El PNEUMATIC El ELECTRIC El HYDRAULIC
PIPING SUPERVISED El YES El NO DETECTING MEDIA SUPERVISED El YES El NO
DELUGE &
DOES THE VALVE OPERATE FROM THE MANUAL TRIP AND/OR REMOTE
CONTROL STATIONS El YES El NO
PREACTION
VALVES
IS THERE AN ACCESSIBLE FACILITY IN EACH CIRCUIT IF NO, EXPLAIN
FOR TESTING? El YES El NO
' fr MAKE
I
MODELI
DOES EACH CIRCUIT OPERATE
SUPERVISION LOSS ALARM
DOES EACH CIRCUIT
OPERATE VALVE RELEASE
MAXIMUM TIME TO
OPERATE RELEASE I\J YES NO YES NO MIN SEC
REDUCING
WL,M I IJIN
& FLOOR
IvitiNt a, Ot 1 I ii'
MODEL
I A I It, t-'htbbIJht MIUU/kL VSUI-th LUW HA I It
(FLOWING)
VALVE TEST INLET (PSI) OUTLET (PSI) INLET (PSI) OUTLET (PSI) FLOW (GPM)
PILE COPY \ ( ô (1
FILE COPY
HYDROSTATIC: Hydrostatic tests shall be made at not less than 200 psi (13.6 bars) for two hours or 50 psi (3.4 bars) above static
TEST pressure in excess of 150 psi (10.2 bars) for two hours. Differential dry-pipe valve clappers shall be left open during test to prevent
DESCRIPTION damage. All aboveground piping leakage shall be stopped.
PNEUMATIC: Establish 40 psi (2.7 bars) air pressure and measure drop, which shall not exceed 11/2 psi (0.1 bars) in 24 hours. Test
pressure tanks at normal water level and air pressure and measure air pressure drop which shall not exceed 11/2 psi in 24 hours.
ALL PIPING HYDROSTATICALLY TESTED AT 200 FOR 2 HOURS IF NO, STATE REASON
DRY PIPING PNEUMATICALLY TESTED 0-YES El NO
EQUIPMENT OPERATES PROPERLY El YES El NO
DO YOU CERTIFY AS THE SPRINKLER CONTRACTOR THAT ADDITIVES AND CORROSIVE CHEMICALS, SODIUM SILICATE
OR DERIVATIVES OF SODIUM SILICATE, BRINE, OR OTHER CORROSIVE CHEMICALS WERE NOT USED FOR TESTING
SYSTEMS OR STOPPING LEAKS? El YES El NO
DRAIN READING OF GAGE LOCATED NEAR WATER RESIDUAL PRESSURE WITH VALVE IN TEST
TESTS TEST SUPPLY TEST CONNECTION PSI CONNECTION OPEN WIDE PSI
UNDERGROUND MAINS AND LEAD-IN CONNECTIONS TO SYSTEM RISERS FLUSHED BEFORE
CONNECTION MADE TO SPRINKLER PIPING.
VERIFIED BY COPY OF THE U FORM NO. 858 El YES []NO OTHER EXPLAIN
FLUSHED BY INSTALLER OF UNDERGROUND
SPRINKER PIPING El YES flNO
IF POWDER DRIVEN FASTENERS ARE USED IN CONCRETE IF NO, EXPLAIN
HAS REPRESENTATIVE SAMPLE TESTING BEEN COMPLETED? El YES El NO BLANK TEST NUMBER USED LOCATIONS NUMBER REMOVED
GASKETS
WELDED PIPING El YES
IF YES...
DO YOU CERTIFY AS THE SPRINKLER CONTRACTOR THAT WELDING PROCEDURES COMPLY
WITH THE REQUIREMENTS OF AT LEAST AWS D1 0.9. LEVEL AR3? El YES El NO
DO YOU CERTIFY THAT THE WELDING WAS PERFORMED BY WELDERS QUALIFIED IN COMPLIANCE
WELDING WITH THE REQUIREMENTS OF AT LEAST AWS D10.9. LEVEL AR 3? El YES El NO
DO YOU CERTIFY THAT WELDING WAS CARRIED OUT IN COMPLIANCE WITH A DOCUMENTED
QUALITY CONTROL PROCEDURE TO INSURE THAT ALL DISCS ARE RETRIEVED, THAT OPENINGS
IN PIPING ARE SMOOTH, THAT SLAG AND OTHER WELDING RESIDUE ARE REMOVED, AND THAT
THE INTERNAL DIAMETERS OF PIPING ARE NOT PENETRATED? El YES El NO
CUTOUTS DO YOU CERTIFY THAT YOU HAVE A CONTROL FEATURE TO ENSURE THAT ALL CUTOUTS (DISCS)
(DISCS) ARE RETRIEVED? 'YES El NO
HYDRAULIC
DATA
NAMEPLATE PROVIDED IF NO, EXPLAIN El YES NO
NAMEPLATE
DATE LEFT IN SERVICE WITH ALL CONTROL VALVES OPEN.
REMARKS
NAME OF SPRINKER CONTRACTOR:
SIGNATURES TESTS WITNESSED BY
FR f1QERTY OWNER (SIGNED) TITLE DATE i1J V \ t/\ Lc- L
F'bR TITLE DATE
ADDITIONAL EXPLANATIONS AND NOTES:
M
ASIIOI-~~-
Tfl •-r" 42 (I 4 JL
Pacific Fire Systems
13142 Nelson Lane
Poway, ca 92064
858-722-9865
Job Name : Swain Collins
Building
Location : 2100 Palomar Airport Road, Suite 214
System : Existing
Contract
Data File : proofcalc.WXF
Pacific Fire Systems Page 1
Swain Collins Date 12/21/11
Hydraulic Design Information Sheet
Name - Swain Collins Date - 12/21/11
Location - 2100 Palomar Airport Road, Suite 214
Building - System No. - Existing
Contractor - Pacific Fire Systems, Inc. Contract No. -
Calculated By - Pacific Fire Systems, Inc. Drawing No. -
Construction: ( ) Combustible (x) Non-Combustible Ceiling Height - 91 -0"
Occupancy - Light Hazard - Office
S (x) NFPA 13 (x) Lt. Haz Ord.Haz.Gp. ( ) 1 ( ) 2 ( ) 3 ( ) Ex.Haz.
Y ( ) NFPA 231 ( ) NFPA 231C ( ) Figure Curve
S Other Area reduced for ceiling heights of 9 1 -0"
T Specific Ruling Made By Date
E
M Area of Sprinkler Operation - 900 System Type Sprinkler/Nozzle
Density - .1 (x) Wet Make Tyco
D Area Per Sprinkler - 18'x18' ( ) Dry Model EC-8/ssp-qr
E Elevation at Highest Outlet - 201 9" ( ) Deluge Size 3/4TT/1/2!
S Hose Allowance - Inside - ( ) Preaction K-Factor 8.0/5.6
I Rack Sprinkler Allowance - ( ) Other Temp.Rat.135/155
G Hose Allowance - Outside - 150
N
Note PROOF CALC TO BASE OF RISER
Calculation Flow Required - 407.877 Press Required - 29.787
Summary C-Factor Used: 120 Overhead Underground
W Water Flow Test: Pump Data: Tank or Reservoir:
A Date of Test - Cap. -
T Time of Test - Rated Cap.- Elev.-
E Static Press - @ Press -
R Residual Press - Elev. - Well
Flow - Proof Flow
S Elevation -
U
P Location -
P
L Source of Information
Y
C Commodity Class Location
O Storage Ht. Area Aisle W.
M Storage Method: Solid Piled % Palletized % Rack
M
Single Row ) Conven. Pallet ( ) Auto. Storage ( ) Encap.
S R ( ) Double Row ( ) Slave Pallet ( ) Solid Shelf ( ) Non
T A ( ) Mult. Row ( ) Open Shelf
O C
R K Flue Spacing Clearance:Storage to Ceiling
A Longitudinal Transverse
G
E Horizontal Barriers Provided:
VVdLI OUFJFJIY L,UIVt IL#)
Pacific Fire Systems Page 2
Swain Collins Date 12/21/11
Demand: Dl - Elevation : -0.433
D2 - System Flow : 257.877
stem Pressure : 29.787 D2 -
SrDemand Hose Adj City) ________ Hose ) : 150 D3 - System Demand : 407.877
Safety Margin
02 ____ ______ _______ 30 -
28
26 i11____ p24
R22
E2°
S 18
S 16
u 14
R 12
E 10
50D1100 150 200 250 300 350 400 450 FLOW( N"1.85)
Comouter Proarams by Hvdratec Inc. Route 111 Windham NH. USA 03087
riuii iy utu OUItlllIdI
Pacific Fire Systems Page 3
Swain Collins Date 12/21/11
Fitting Legend
Abbrev. Name 1/2 % 1 1½ 11/2 2 21/2 3 31/2 4 5 6 8 10 12 14 16 18 20 24
B Generic Butterfly Valve 0 0 0 0 0 0 7 10 0 12 9 10 12 19 21 0 0 0 0 0
E 90StandardElbow 2 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61
Fsp Flow Switch Potter VSR Fitting generates a Fixed Loss Based on Flow
T 90' Flow thru Tee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121
Units Summary
Diameter Units Inches
Length Units Feet
Flow Units US Gallons per Minute
Pressure Units Pounds per Square Inch
Comouter Proarams by Hvdratec Inc. Route 111 Windham N.H. USA 03087
Pressure / Flow Summary - STANDARD
Pacific Fire Systems Page 4
Swain Collins Date 12/21/11
Node
No.
Elevation K-Fact Pt
Actual
Pn Flow
Actual
Density Area Press
Req.
Hi 20.75 5.6 65.61 na 45.36 0.1 30 7.0
H2
H3
20.75
20.75
5.6
8
66.38
36.9
na
na
45.63
48.59
0.1
1.0
204
1 1-7
H4 20.75 8 40.08 na 50.65 1.0 1 1-7
H5 20.75 5.6 38.31 na 34.66 0.1 166 7.0
H6 20.75 8 17.0 na 32.98 1.0 1 17.0
1 21.75 78.21 na
2 21.75 72.13 na
3 21.75 49.34 na
4 21.75 48.88 na
5 21.75 42.25 na
10 21.75 29.64 na
6 21.75 19.81 na
12 21.75 20.9 na
ii 21.0 21.69 na
13 21.0 21.57 na
15 21.0 20.91 na
16 21.0 19.83 na
TOR 0.0 28.85 na
BOR 0.0 29.79 na 150.0
The maximum velocity is 4959 and it occurs in the pipe between nodes 1 and 2
Final Calculations - Hazen-Williams
Pacific Fire Systems Page 5
Swain Collins Date 12/21/11
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "C" or Ftng's Pe Pv ******* Notes
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn
Hi 45.36 1.08 2E 4.61 15.000 65.613 K Factor = 5.60
to 120 iT 5.762 10.372 -0.433
1 45.36 0.5138 0.0 25.372 13.035 Vel= 15.89
0.0
45.36 78.215 K Factor = 5.13
H2 45.63 1.08 1 E 2.305 3.830 66.381 K Factor = 5.60
to 120 1 5.762 8.067 -0.433
2 45.63 0.5193 0.0 11.897 6.178 Vel= 15.98
0.0
45.63 72.126 K Factor = 5.37
H3 48.59 1.08 1E 2.305 14.000 36.896 K Factor = 8.00
to 120 iT 5.762 8.067 -0.433
3 48.59 0.5835 0.0 22.067 12.877 Vel= 17.02
0.0
48.59 49.340 KFactor= 6.92
H4 50.65 1.08 1 E 2.305 6.580 40.085 K Factor = 8.00
to 120 iT 5.762 8.067 -0.433
4 50.65 0.6300 0.0 14.647 9.227 Vet = 17.74
0.0
50.65 48.879 K Factor = 7.24
H5 34.66 1.08 1 2.305 5.920 38.310 K Factor =5.60
to 120 1 5.762 8.067 -0.433
5 34.66 0.3124 0.0 13.987 4.369 Vel= 12.14
0.0
34.66 42.246 KFactor= 5.33
H6 32.98 1.08 1 E 2.305 3.330 17.000 K Factor = 8.00
to 120 iT 5.762 8.067 -0.433
6 32.98 0.2849 0.0 11.397 3.247 Vel= 11.55
0.0
32.98 19.814 K Factor = 7.41
1 -362.52 1.728 0.0 2.500 78.215
to 120 0.0 0.0 0.0
2 -362.52 -2.4356 0.0 2.500 -6.089 Vel = 49.59
2 45.63 1.728 0.0 12.000 72.126
to 120 0.0 0.0 0.0
3 -316.89 -1.8988 0.0 12.000 -22.786 Vel = 43.35
3 48.59 1.728 0.0 0.330 49.340
to 120 0.0 0.0 0.0
4 -268.3 -1.3970 0.0 0.330 -0.461 Vel = 36.70
4 50.65 1.728 0.0 7.000 48.879
to 120 0.0 0.0 0.0
5 -217.65 -0.9476 0.0 7.000 -6.633 Vet = 29.78
Final Calculations - Standard
Pacific Fire Systems Page 6
Swain Collins Date 12/21/11
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "C" or Ftng's Pe Pv ******* Notes
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn
5 34.67 1.728 0.0 18.330 42.246
to 120 0.0 0.0 0.0
10 -182.98 -0.6875 0.0 18.330 -12.602 Vel = 25.03
10 0.0 1.728 iT 11.29 0.750 29.644
to 120 0.0 11.290 0.325
11 -182.98 -0.6875 0.0 12.040 -8.278 Vel= 25.03
0.0
-182.98 21.691 K Factor = -39.29
6 32.98 1.728 0.0 37.500 19.814
to 120 0.0 0.0 0.0
12 32.98 0.0289 0.0 37.500 1.084 Vel = 4.51
12 0.0 1.728 iT 11.29 0.750 20.898
to 120 0.0 11.290 0.325
13 32.98 0.0288 0.0 12.040 0.347 Vel = 4.51
0.0
32.98 21.570 K Factor = 7.10
Ii -182.98 4.31 0.0 15.000 21.691
to 120 0.0 0.0 0.0
13 -182.98 -0.0081 0.0 15.000 -0.121 Vel = 4.02
13 32.98 4.31 2E 27.874 90.500 21.570
to 120 0.0 27.874 0.0
15 -150.0 -0.0056 0.0 118.374 -0.657 Vel = 3.30
15 0.0 4.31 2E 27.874 168.000 20.913
to 120 0.0 27.874 0.0
16 -150.0 -0.0056 0.0 195.874 -1.088 Vel = 3.30
16 0.0 6.357 3E 52.808 29.000 19.825
to 120 0.0 52.808 9.095
TOR -150.0 -0.0008 0.0 81.808 -0.068 Vel = 1.52
TOR 0.0 6.357 1 12.573 10.000 28.852
to 120 iFsp 0.0 67.896 1.000 * Fixed loss = 1
BOR -150.0 -0.0008 1E 17.603 77.896 -0.065 Vel = 1.52
1 37.72
150.00 Qa= 150.00
0.0 29.787 K Factor =0