HomeMy WebLinkAbout2525 EL CAMINO REAL; 146; FPC2019-0084; Permit11:214 i r1Pl ii .] JI
(ity Of
Carlsbad
Print Date: 02/12/2025
Job Address: 2525 EL CAMINO REAL, # 146,
Permit Type: FIRE-Construction Commercial
Parcel #: 1563020900
Valuation: $34,353.60
Occupancy Group:
#of Dwelling Units:
Bedrooms:
Bathrooms:
CARLSBAD, CA 92008-1206
Work Class: Fire Sprinklers
Track #:
Lot U:
Project U:
Plan U:
Construction Type:
Orig. Plan Check U:
Plan Check U:
Permit No: FPC2019-0084
Status: Closed - Finaled
Applied: 04/02/2019
Issued: 04/15/2019
Finaled Close Out: 02/14/2022
Final Inspection:
INSPECTOR: Salcedo, Felix
Fieri, Dominic
Project Title:
Description: SURF CITY SQUEEZE - 10 NEW SPRINKLER HEADS
Applicant: FPContractor:
MARCUS ENGLISH JOHNSON CONTROLS FIRE PROTECTION LP
3568 RUFFIN RD P0 BOX 3042
SAN DIEGO, CA 92123-2597 BOCA RATON, FL 33431-0942
(858) 633-9125 (561) 341-7780
FEE AMOUNT
FIRE NFPA 13 or 13R System 7 - 100 heads
-
$553.00
Total Fees: $553.00 Total Payments To Date: $553.00 Balance Due: $0.00
Fire Department Page 1 of 1
1635 Faraday Avenue, Carlsbad CA 92008-7314 1 442-339-2665 1 Inspections: 442-339-2660 1 www.carlsbadca.gov
tI Worldwide I I,CU Contacts www.tyco-fire.com
Series RFII - 56 K-factor
Flush II" Concealed Pendent Sprinklers
Aguick,A SL1Ja,0 Response, Standard Coverage
General
Description
The TYCO Series RFII 5.6 K-factor,
"Royal Flush II" Concealed Pendent
Sprinklers Quick Response (3-mm
bulb) and Standard Response (5-mm
bulb), are decorative sprinklers fea-
turing a flat cover plate designed to
conceal the sprinkler. These sprinklers
are optimal for architecturally sensi-
tive areas such as hotel lobbies, office
buildings, churches, and restaurants.
Each sprinkler includes a Cover Plate!
Retainer Assembly and a Sprinkler/
Support Cup Assembly. The separa-
ble, two-piece assembly design pro-
vides the following benefits:
Allows installation of the sprinklers
and pressure testing of the fire pro-
tection system prior to installation of
a suspended ceiling or application of
the finish coating to a fixed ceiling.
Permits the removal of suspended
ceiling panels for access to building
service equipment without having
to first shut down the fire protection
system and remove sprinklers.
Provides for 1/2 in. (12,7 mm) of ver-
tical adjustment to allow a measure
of flexibility in determining the length
of fixed piping to cut for the sprinkler
drops.
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 4
The Series RFll Sprinklers are shipped
with a Disposable Protective Cap. The
Protective Cap is temporarily removed
during installation and replaced to help
protect the sprinkler during ceiling
installation or finish. The tip of the Pro-
tective Cap can be used to mark the
center of the ceiling hole into plaster
board or ceiling tiles by gently pushing
the ceiling product against the Pro-
tective Cap. When ceiling installa-
tion is complete, the Protective Cap is
removed and the Cover Plate/Retainer
Assembly is installed.
As an option, the Series RFII Standard
Response (5-mm bulb) "Royal Flush II"
Concealed Pendent Sprinklers can be
fitted with a silicone Air and Dust Seal.
(Refer to Figure 5.) The Air and Dust
Seal is intended for sensitive areas
where it is desirable to prevent air and
dust from the area above the ceiling to
pass through the cover plate.
LL.)tL.i
The Series RFII Concealed Pendent
Sprinklers described herein must be
installed and maintained in compliance
with this document and with the appli-
cable standards of the NATIONAL FIRE
PROTECTION ASSOCIATION (NFPA),
in addition to the standards of any
authorities having jurisdiction. Failure
to do so may impair the performance
of these devices.
The owner is responsible for maintain-
ing their fire protection system and
devices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted with
any questions.
Sprinkler
Identification
Number (SIN)
TY3531 - 3 mm bulb
TY - mmulb
SEPTEMBER 2018
Technical
Data
Sprinkler Approvals
Approvals apply only to the service
conditions indicated in the Design Criteria
section.
TY3531 (3 mm Bulb) is UL Listed, C-UL
Listed and NYC Approved (MEA 353-
01-E) as Quick Response.
TY3531 (3 mm Bulb) is VdS Approved
(Certificate No. G4090007).
1Y3531 (3 mm Bulb) is FM and
LPCB Approved (Ref. No. 094a/1 0) as
Standard Response.
Note: FM and LPCB do not approve
concealed sprinklers for quick
response.
TY3551 (5 mm Bulb) is UL Listed, C-UL
Listed, FM Approved, LPCB Approved
(Ref. No. 094a/9), and NYC Approved
(MEA 353-01-E) as Standard Response.
Approvals for Air and Dust Seal
UL and C-UL Listed for use with the RFll
Standard Response Concealed Sprinkler
(TY3551)
Maximum Working Pressure
Maximum 250 psi (17,3 bar) by UL,
C-UL, and NYC
Maximum 175 psi (12,1 bar) by FM, VdS,
and LPCB
Temperature Rating
155°F (68°C) Sprinkler with
139°F (59°C) Cover Plate
200°F (93°C) Sprinkler with
165°F (74°C) Cover Plate
TFPISI
THREAD INTO U RETAINER
SUPPORT f WITH THREAD
CUP UNTIL 0 0 _- DIMPLES
MOUNTING
SURFACE IS EJECTION
FLUSH WITH SPRING
CEILING
SOLDER' COVER
TABS (3) COVER PLATE/RETAINER PLATE
ASSEMBLY
FIGURE 1
MODEL RFII CONCEALED SPRINKLER
ASSEMBLY
1/2 NPT
FRAME
SUPPOR1
CUP WITF
ROLL FORIV
THREADS
GUIDE
PINS (2)
DEFLECTOR
SPRINKLER/SUPPORT CUP
ASSEMBLY
EALING
SEMBLY
CAP
BULB
PRESSION
CREW
FLECTOR
ROPPED
POSITION)
TFPI8I
Page 2 of 4
Discharge Coefficient
K= 5.6 GPM/ps1112 (80,6 LPM/barl'2)
Adjustment
1/2 inch (12,7 mm)
Finishes
See the Ordering Procedure section.
Physical Characteristics
Frame ............................Bronze
Support Cup ...................Plated Steel
Guide Pins..................Stainless Steel
Deflector ...........................Bronze
Compression Screw ..................Brass
Bulb...............................Glass
Cap .....................Bronze or Copper
Sealing Assembly. . Beryllium Nickel w/TEFLON
Cover Plate .........................Brass
Retainer ............................ Brass
Election Spring ..............Stainless Steel
Design
Criteria
The TYCO Series RFII 5.6 K-factor,
"Royal Flush II" Concealed Pendent
Sprinklers are intended for fire protec-
tion systems designed in accordance
with the standard installation rules
recognized by the applicable Listing
or Approval agency; for example, UL
Listing is based on NFPA 13 and VdS
Approval is based on the CEA 4001.
For more information on LPCB and VdS
Approvals, contact Johnson Controlss
at the following office:
Enschede, Netherlands
Telephone: 31-53-428-4444
Fax: 31-53-428-3377
The Series RFII Concealed Pendent
Sprinklers are only listed and approved
with the Series RFII Concealed Cover
Plates having a factory applied finish.
!L•1tLI1
Do not use the Series RFII in applica-
tions where the air pressure above the
ceiling is greater than that below. Down
drafts through the Sprinkler/Support
Cup Assembly can delay sprinkler
operation in a fire situation.
Operation
When exposed to heat from a fire, the
Cover Plate, normally soldered to the
Retainer at three points, falls away to
expose the Sprinkler/Support Cup
Assembly.
The Deflector - supported by the
Guide Pins - then drops down to its
operational position.
The glass bulb contains a fluid that
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass bulb, activating the sprinkler and
allowing water to flow.
Installation
The TYCO Series RFIl 5.6 K-factor,
"Royal Flush II" Concealed Pendent
Sprinklers must be installed in accor-
dance with this section.
General Instructions
Do not install any bulb-type sprinkler
if the bulb is cracked or there is a loss
of liquid from the bulb. With the sprin-
kler held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 inch
(1,6 mm) for the 155'F (68'C) and 3/32
inch (2,4 mm) for the 200°F (93°C) tem-
perature ratings.
A leak-tight 1/2 inch NPT sprinkler
joint should be obtained by applying a
minimum to maximum torque of 7 to 14
ft.-Ibs. (9,5 to 19,0 Nm). Higher levels
of torque can distort the sprinkler Inlet
with consequent leakage or impairment
of the sprinkler.
Do not attempt to compensate for
insufficient adjustment in the Sprinkler
by under- or over-tightening the Sprin-
kler/Support Cup Assembly. Re-adjust
the position of the sprinkler fitting to
suit.
Step 1. Install the sprinkler only in the
pendent position with the center-line
of the sprinkler perpendicular to the
mounting surface.
Step 2. Remove the Protective Cap.
Step 3. With pipe thread sealant
applied to the pipe threads, hand-
tighten the sprinkler into the sprinkler
fitting.
Step 4. Wrench-tighten the sprinkler
using only the RFII Sprinkler Wrench.
(Refer to Figure 3.) Apply the RFII
Sprinkler Wrench to the Sprinkler as
shown in Figure 3.
B: 3/16 inches (4,8 mm) D: 1-3/4 to 2-1/4 inches (44,5 to 57,2 mm)
FIGURE 2
SERIES CONCEALED SPRINKLER INSTALLATION DIMENSIONS
TFPI8I
Page 3 of 4
FACE OF
SPRINKLER
FITTING
SPRINKLER
SUPPORT CUP
ASSEMBLY
1/2' (12,7 mm)
THREADED
D ADJUSTMENT
FACE
OF CEILING,
RETAINING RING
MOUNTING
SURFACE
CLEARANCE HOLE
- DIAMETER -
DIMENSION C
3/16 to 11/16 MANUFACTURER DEFLECTOR COVER PLATE
(4,8 to 17,5 mm) PRESET GAP IN DROPPED RETAINER
REFERENCE 3/32 (2,4 mm) POSITION ASSEMBLY
COVER PLATE COVER PLATE
PROFILE DEPTH DIAMETER
DIMENSION B DIMENSION A
Step 5. Replace the Protective Cap
by pushing it upwards until it bottoms
out against the Support Cup. (Refer
to Figure 4.) The Protective Cap helps
prevent damage to the Deflector and
Arms during ceiling installation and/or
finish. You can also use the Protective
Cap to locate the center of the clear-
ance hole by gently pushing the ceiling
material up against the center point of
the Protective Cap.
A: 3-1/4 inches (82,6 mm) C: 2-3/8 to 2-5/8 inches (60,3 to 66,7 mm) U I
As long as the Protective Cap remains
in place, the system is considered "Out
of Service".
Step 6. After the ceiling has been
completed with the 2-1/2 in. (63,5 mm)
diameter clearance hole and in prep-
aration for installing the Cover Plate!
Retainer Assembly, remove and discard
the Protective Cap. Verify that the
Deflector moves up and down freely.
If the Sprinkler is damaged and the
Deflector does not move up and down
freely, replace the entire Sprinkler.
Do not attempt to modify or repair a
damaged sprinkler.
Step 7. When installing an Air and
Dust Seal, refer to Figure 5; otherwise,
proceed to Step 8. To attach the Air
and Dust Seal, verify the angle of the
outside edge of the seal is oriented
according to Figure 5. Start the edge of
the Retainer in the grooved slot of the
Air and Dust Seal and continue around
the retainer until the entire Air and Dust
Seal is engaged.
TFPI8I
Page 4 of 4
SUPPORT SPRINKLER FACE OF ORIENT
CUP CEILING —\ SEAL
BEVEL AS
\ SHOWN COVER
PLATE
RETAINER
ASSEMBLY
S S S
\) AIR
AND DUST
LIP OF COVER SEAL
RETAINER PLATE
FIGURE 5
OPTIONAL AIR AND DUST SEAL FOR SERIES RFII (TY3551)
Step 8. Screw on the Cover Plate!
Retainer Assembly until the Retainer
(shown in Figure 2) or the Air and Dust
Seal (shown in Figure 5) contacts the
ceiling. Do not continue to screw on the
Cover Plate/Retainer Assembly so that
it lifts a ceiling panel out of its normal
position. If you cannot engage the
Cover Plate/Retainer Assembly with
the Support Cup or you cannot engage
the Cover Plate/Retainer Assembly suf-
ficiently to contact the ceiling, you must
reposition the Sprinkler Fitting.
Care and
Maintenance
The TYCO Series RFII 5.6 K-factor,
"Royal Flush II" Concealed Pendent
Sprinklers must be maintained and
serviced in accordance with this
section.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
that it controls, obtain permission to
shut down the affected fire protection
system from the proper authorities
and notify all personnel who may be
affected by this action.
Absence of the Cover Plate/Retainer
Assembly can delay sprinkler opera-
tion in a fire situation.
When properly installed, there is a
nominal 3/32 in. (2,4 mm) air gap
between the lip of the Cover Plate and
the ceiling, as shown in Figure 2.
This air gap is necessary for proper
operation of the sprinkler. If the ceiling
requires repainting after sprinkler
installation, ensure that the new paint
does not seal off any of the air gap.
Do not pull the Cover Plate relative to
the Enclosure. Separation may result.
Sprinklers which are found to be
leaking or exhibiting visible signs of
corrosion must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or other-
wise altered after leaving the factory.
Modified sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid
damage to the sprinklers - before,
during, and after installation. Sprin-
klers damaged by dropping, striking,
wrench twist/slippage, or the like, must
be replaced. Also, replace any sprin-
kler that has a cracked bulb or that has
lost liquid from its bulb. (Ref. Installa-
tion Section.)
Exercise care to avoid damage to sprin-
klers' before, during, and after instal-
lation. Replace sprinklers damaged
by dropping, striking, wrench twist-
ing, wrench slipping, or the like. Also,
replace any sprinkler that has a cracked
bulb or that has lost liquid from its bulb.
(Refer to the Installation section.)
If you must remove a sprinkler, do not
reinstall it or a replacement without
reinstalling the Cover Plate/Retainer
Assembly. If a Cover Plate/Retainer
Assembly becomes dislodged during
service, replace it immediately.
The owner is responsible for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards
of the NATIONAL FIRE PROTECTION
ASSOCIATION, for example, NFPA 25,
in addition to the standards of any other
authorities having jurisdiction. Contact
the installing contractor or sprinkler
manufacturer regarding any questions.
Automatic sprinkler systems should be
inspected, tested, and maintained by a
qualified Inspection Service in accor-
dance with local requirements and/or
national code.
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.
Ordering
Procedure
Contact your local distributor for
availability. When placing an order,
indicate the full product name.
Sprinkler/Support Cup Assembly
Specify: Series RFII (specify SIN),
K=5.6, "Royal Flush II" Pendent Sprin-
klers (specify) temperature rating, P/N*
(specify):
155°F (68'Cl 200°F (93°C
TY3531 51-792-1-155 51-792-1-200
1Y3551 51-790-1-155 51-790-1-200
* Use Suffix "I" for ISO 7-1 connection; for example,
51-792-1-155-I
Separately Ordered Cover Plate/
Retainer Assembly:
Specify: (temperature rating from
below) Series RFII Concealed Cover
Plate with (finish), P/N (specify).
139°F (59°C)(a) 165°F (74°C)(b)
Grey White
(RAL9002) 56-792-0-135 56-792-0-165
Brass...... 56-792-1-135 56-792-1-165
Pure White (c)
(RAL9010) .... 56-792-3-135 56-792-3-165
Signal White
(RAL9003) .... 56-792-4-135 56-792-4-165
Jet Black
(RAL9005) ... 56-792-6-135 59-792-6-165
Brushed
Chrome...... 56-792-8-135 56-792-8-165
Chrome........ 56-792-9-135 56-792-9-165
Custom...... 56-792-X-135 56-792-X-165
For use with 155°F (68°C) sprinklers.
For use with 200°F (93°C) sprinklers.
(C) Eastern Hemisphere sales only.
Sprinkler Wrench
Specify: RFII Sprinkler Wrench,
P/N 56-000-1-075
Air and Dust Seal
Specify: Air and Dust Seal,
P/N 56-908-1-001
1400 Pennbrook Parkway, Lansdale, PA 194461 Telephone +1-215-362-0700
a 2018 Johnson Controls. All rights reserved. All specifications and Other information shown were Current as of document revision dale and are sublect to change without notice. Johnson '/,! kill NATIONAL FIRE PROTECTION ASSOCIATION and NFPAa,u roglotn,nd trodo,na,lns of National Fire Protection Association; Controls TEFLON 55 rogiutered trudomsokof OePcnt
Worldwide I tqC170 Contacts www.tyco-fire.com W
Series TY-FRB, 56 K-factor
Upright, Pendent, and Recessed Pendent Sprinklers
Quick Response, Standard Coverage
General
Description
The TYCO Series TY-FRB, 5.6 K-factor,
Upright (TY313) and Pendent (TY323)
Sprinklers described in this data sheet
are quick response, standard coverage,
decorative 3 mm glass bulb-type spray
sprinklers designed for use in light or
ordinary hazard, commercial occupan-
cies such as banks, hotels, and shop-
ping malls.
The recessed version of the Series
TY-FRB Pendent Sprinkler, where
applicable, is intended for use in areas
with a finished ceiling. This recessed
pendent sprinkler uses one of the
following:
A two-piece Style 15 Recessed
Escutcheon with recessed adjust-
ment up to 5/8 in. (15,9 mm) from
the flush pendent position.
A two-piece Style 20 Recessed
Escutcheon with recessed adjust-
ment up to 1/2 in. (12,7 mm) from
the flush pendent position.
The adjustment provided by the
Recessed Escutcheon reduces the
accuracy to which the fixed pipe drops
to the sprinklers must be cut.
Intermediate level versions of Series
TY-FRB Sprinklers are described in
Technical Data Sheet TFP357. Sprin-
kler guards and shields are described
in Technical Data Sheet TFP780.
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fall
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 4
I(.)tLi1
The TYCO Series TY-FRB Sprinklers
described herein must be installed
and maintained in compliance with
this document, as well as with the
applicable standards of the National
Fire Protection Association, in addition
to the standards of any other authori-
ties having jurisdiction. Failure to do so
may impair the performance of these
devices.
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any
questions.
Sprinkler
Identification
Number (SIN)
TY31 Up4ht-&6K, lJir., NPT
jY323 .... Pendent5.6K, 1/2 in. NI
Technical
Data
Approvals
Refer to Table A
Maximum Working Pressure
175 psi (12.1 bar)
250 psi (17.2 bar)*
* The maximum working pressure of 250 psi (17.2 bar)
only applies to the listing by Underwriters Laborato-
ries, Inc. (UL).
Discharge Coefficient
K=5.6 GPM/pSi½ (80,6 LPM/bar½)
Temperature Rating
Refer to Table A
Finishes
Sprinkler: Refer to Table B
Recessed Escutcheon: White Coated,
Black Coated, Chrome Plated, or Brass
Plated
Physical Characteristics
Frame ............................Bronze
Button ......................Brass/Copper
Sealing Assembly ... Stainless Steel w/TEFLON
Bulb...............................Glass
Compression Screw .................Bronze
Deflector ..........................Bronze
AUGUST 2018
I'.
\ i...
ci
!
t%J;j44 2)
Operation
The glass bulb contains a fluid which
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass bulb, allowing the sprinkler to
activate and water to flow.
Design
Criteria
The TYCO Series TY-FRB, 5.6 K-factor,
Upright (TY313) and Pendent (TY323)
Sprinklers are intended for fire protec-
tion systems designed in accordance
with the standard installation rules
recognized by the applicable Listing or
Approval agency (such as, UL Listing
is based on the requirements of NFPA
13, and FM Approval is based on the
requirements of FM's Loss Prevention
Data Sheets). Only the Style 15 or Style
20 Recessed Escutcheon is to be used
for recessed pendent installations.
TFPI72
2-7/8 (73,0 mm) DIA.
TFPI72
Page 2 of 4
Components: * Temperature rating is ** Pipe thread connections per ISO 7-1 1 - Frame 4 - Bulb indicated on Deflector, can be provided on special request. 2 - Button 5 - Compression
3 - Sealing Screw ESCUTCHEON PLATE 1/2 7/16 (11,1 mm) Assembly 6 - Deflector* DEFLECTOR * SEATING SURFACE NPT** NOMINAL MAKE-IN
* 6
t 7/16
_______ .
MAKE-IN (50,8 mm)
\
\ FEE-
/ 2 I 13/8" :
NOMINAL
(11,1 mm)
______
"
(50,8 mm) (34,9 mm)
WF
Fl
/ I 1/2" NPT** DEFLECTOR*
STYLE 15 or 20
RECESSED
ESCUTCHEON
CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT
FIGURE 1
SERIES TY-FRB UPRIGHT (TY313) AND PENDENT (TY323) SPRINKLERS
5.6 K-FACTOR, 1/2 INCH NPT, QUICK RESPONSE
,,,//
^WRENCH RECESS
(USE ONLY
FIGURE 2
W-TYPE 6
SPRINKLER WRENCH
WRENCH
RECESS
PUSH WRENCH
IN TO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURE 3
W-TYPE 7 RECESSED
SPRINKLER WRENCH
Installation
The TYCO Series TY-FRB, 5.6 K-factor,
Upright (TY313) and Pendent (TY323)
Sprinklers must be installed in accor-
dance with this section.
General Instructions
Do not install any bulb-type sprin-
kler if the bulb is cracked or there is
a loss of liquid from the bulb. With the
sprinkler held horizontally, a small air
bubble should be present. The diam-
eter of the air bubble is approximately
1/16 in. (1,6 mm)forthe 135°F (57°C) and
3/32 in. (2,4 mm) for the 286°F (141°C)
temperature ratings.
A leak-tight 1/2 in. NPT sprinkler joint
should be obtained by applying a
minimum to maximum torque of 7 to
14 lb-ft (9,5 to 19,0 Nm). Higher levels
of torque can distort the sprinkler Inlet
with consequent leakage or impairment
of the sprinkler.
Do not attempt to compensate for
insufficient adjustment in the Escutch-
eon Plate by under- or over-tightening
the sprinkler. Re-adjust the position of
the sprinkler fitting to suit.
Upright and Pendent Sprinklers
The Series TY-FRB Upright and
Pendent Sprinklers must be installed
in accordance with the following
instructions.
Step 1. Install Pendent sprinklers in the
pendent position. Install upright sprin-
klers in the upright position.
Step 2. With pipe-thread sealant
applied to the pipe threads, hand-
tighten the sprinkler into the sprinkler
fitting.
Step 3. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
6 Sprinkler Wrench (Figure 2). With ref-
erence to Figure 1, apply the W-Type 6
Sprinkler Wrench to the wrench flats.
Torque sprinklers 7 to 14 lb-ft (9,5 to
19,0 N'm).
Recessed Pendent Sprinklers
The Series TY-FRB Recessed Pendent
Sprinklers must be installed in accor-
dance with the following instructions.
Step A. After installing the Style 15
or Style 20 Mounting Plate over the
sprinkler threads, and with pipe-thread
sealant applied to the pipe threads,
hand-tighten the sprinkler into the
sprinkler fitting.
Step B. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
7 Recessed Sprinkler Wrench (Figure
3). With reference to Figure 1, apply the
W-Type 7 Recessed Sprinkler Wrench
to the sprinkler wrench flats. Torque
sprinklers 7 to 14 lb-ft (9,5 to 19,0 N.m).
Step C. After ceiling installation and
finishing, slide on the Style 15 or Style
20 Closure over the Series TY-FRB
Sprinkler and push the Closure over the
Mounting Plate until its flange comes in
contact with the ceiling.
TFPI72
Page 3 of 4
Care and
Maintenance
The TYCO Series TY-FRB, 5.6 K-factor,
Upright (TY313) and Pendent (TY323)
Sprinklers must be maintained and ser-
viced in accordance with this section.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
that it controls, obtain permission to
shut down the affected fire protection
systems from the proper authorities
and notify all personnel who may be
affected by this action.
Absence of the outer piece of an
escutcheon, which is used to cover
a clearance hole, can delay sprinkler
operation in a fire situation.
The owner must assure that the sprin-
klers are not used for hanging any
objects and that the sprinklers are only
cleaned by means of gently dusting
with a feather duster; otherwise, non-
operation in the event of a fire or inad-
vertent operation may result.
Sprinklers which are found to be
leaking or exhibiting visible signs of
corrosion must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or other-
wise altered after leaving the factory.
Modified sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid
damage to the sprinklers before,
during, and after installation. Sprin-
klers damaged by dropping, striking,
wrench twist/slippage, or the like, must
be replaced. Also, replace any sprin-
kler that has a cracked bulb or that has
lost liquid from its bulb. (Ref. Installa-
tion Section.)
The owner is responsible for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards
of the National Fire Protection Asso-
ciation (e.g., NFPA 25), in addition to
the standards of any other authorities
having jurisdiction. Contact the install-
ing contractor or product manufacturer
with any questions.
Automatic sprinkler systems are rec-
ommended to be inspected, tested,
and maintained by a qualified Inspec-
tion Service in accordance with local
requirements and/or national codes.
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.
Ordering
Procedure
Contact your local distributor for avail-
ability. When placing an order, indicate
the full product name and Part Number
(P/N).
Sprinkler Assemblies with NPT
Thread Connections
Specify: Series TY-FRB Upright or
Pendent (specify) Sprinkler, SIN
(specify), K=5.6, Quick Response,
(specify) temperature rating, (specify)
finish, P/N (specify, refer to Table A).
Recessed Escutcheon
Specify: Style 15 Recessed Escutch-
eon with (specify*) finish, P/N (specify*)
Specify: Style 20 Recessed Escutch-
eon with (specify*) finish, P/N (specify*)
* Refer to Technical Data Sheet TFP770
Sprinkler Wrench
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001
2-7/8' DIA.
(73,0 mm)
2-1/4" DIA.
FACE OF (57,2 mm)
5/8' (15,9 mm)
SPRINKLER
FITTING
FLUSH
3/8±5/16'
(9,5±7,9 mm) /
MOUNTING / 1/8' J
SURFACE/
-
(3,2 mm)
CLOSURE SERIES MOUNTING 1-3/8" (34,9 mm)
TY-FRB PLATE 3/4" (19,1 mm)
FIGURE 4
SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY (TY323)
WITH TWO PIECE 5/8 INCH TOTAL ADJUSTMENT STYLE 15
RECESSED ESCUTCHEON
2-7/8" DIA.
(73,0 mm)
FACE OF
SPRINKLER 2-1/4" DIA.
FITTING - (57,2 mm)
1/2" (12,7 mm) 5/16±1/4"
(7,9±6,4 mm) FLUSH
MOUNTING
SURFACE/' (3,2 mm)
CLOSURE SERIES MOUNTING 1-3/8' (34,9 mm)
TYFRB PLATE 7/8" (22,2 mm)
FIGURE 5
SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY (TY323)
WITH TWO PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 20
RECESSED ESCUTCHEON
TFPI72
Page 4 of 4
SPRINKLER FINISH (See Note 7)
K
FACTOR TYPE TEMPERATURE BULB LIQUID
COLOR
NATURAL
BRASS
I CHROME
PLATED OLYESTERc
135°F (57°C) Orange
UPRIGHT
(TY313) 155°F (68°C) Red
175°F (79°C) Yellow
5.6
1/2 in. NPT
and
PENDENT
(TY323)
1, 2, 3, 4, 5, 6
200°F (93°C) Green
286°F (141°C) Blue
RECESSED
PENDENT
(TY323)
Figures 4a and 5b
135°F (57°C) Orange
1,2,3,4
155°F (68°C) Red
175°F (79°C) Yellow
200°F(93°C) Green
Notes:
Listed by Underwriters Laboratories, Inc., (UL) as Quick Response Sprinklers.
Listed by Underwriters Laboratories, Inc., for use in Canada (C-UL) as Quick Response Sprinklers.
Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers.
Approved by the City of New York under MEA 354-01-E.
VdS Approved (For details, contact Johnson Controls, Enschede, Netherlands, Tel. 31-53-428-4444/Fax 31-54-428-3377.)
Approved by the Loss Prevention Certification Board (LPCB Ref. No. 0945/06) as Quick Response Sprinklers.
Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as Corrosion-Resistant Sprinklers.
Installed with Style 15 (1/2 in. NPT) 5/8 in. Total Adjustment Recessed Escutcheon, as applicable.
Installed with Style 20 (1/2 in. NPT) 1/2 in. Total Adjustment Recessed Escutcheon, as applicable.
C. Frame and Deflector only. Listings and approvals apply to color (Special Order).
TABLE A
LABORATORY LISTINGS AND APPROVALS FOR
5.6 K-FACTOR SPRINKLERS
P/Na 77 —XXX - X - XXX
LI
9 CHROME PLATED
Notes:
a. Eastern Hemisphere sales only
TABLE B
SERIES TY-FRB UPRIGHT AND PENDENT SPRINKLERS
PART NUMBER SELECTION
I SPRINKLER
FINISH
1 NATURAL BRASS
PURE WHITE (RAL901O)a
POLYESTER
SIGNAL WHITE (RAL9003)
-
POLYESTER
JET BLACK (RAL9005)
POLYESTER
I TEMPERATURE
RATINGS
135 135-F (57-C)
155 155°F(68°C)
175 175-F (79-C)
200 200°F(93°C)
286 286-F (141-C)
SIN
370 1 5.6K UPRIGHT (1/2 in.NPT) I 1Y313
371 I 5.6K PENDENT (1/2 n.NPT) I TY323
Notes:
a. Use suffix "I" for ISO 7-1 connection; for example,
77-370-4-175-I
1400 Pennbrook Parkway, Lansdale, PA 194461 Telephone +1-215-362-0700 ,jjj r
0 2018 Johnson Controls. All tights reserved. All specifications and other Information shown wore current as at document revision date and are subject tn change without notice. Johnson '1.1 ('
NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are regIstered trademarks of National Fire Protection Association; cu registered nademwk,f Dupont