HomeMy WebLinkAbout5781 VAN ALLEN WAY; ; FA100012; Permit4/4/25, 11:23 AM FAI000I2 Permit Data
City of Carlsbad
Fire Alarm Permit
Permit No: FAI 00012
Job Address: 5781 VAN ALLEN WY Status: ISSUED
Permit Type: FALARM Applied 3/17/2010
Parcel No: 2121304400 Approved: 3/17/2010
Lot #: 0
Reference No.: Issued: 3/17/2010
PC #: Inspector:
Project Title: LIFE TECHNOLOGIES T.I. ALARM PLAN CHECK &
INSPECTIONS
Applicant:
ADT SECURITY SERVICES, INC.
3830 CALLE FORTUNADA
SAN DIEGO, CA
(858) 654-3224
Owner:
GRIFFIN CAPITAL CARLSBAD POINTE
INVESTORS L L C
C/O INVITROGEN CORPORATION
1600 FARADAY AVE
CARLSBAD CA
Fees ($) Add'I Fees ($) Total ($) fBalance ($)
125 0 125 0
about:blañk 1/1
INVITROGEN
CP-24 T.I.
5781 VAN ALLEN WAY
CARLSBAD, CA. 92008
FIRE ALARM T.I. SUBMITTAL
Lou plfltflL
,,,III he irwuui apik cndeS in loice
w
Th OWu1 or cfliflu aLlof
I IL suppurt t an IC attnt1 ttll a
h the e spre 0 der 1udtrg that this I Cl
iehe' cc the 0et or ctllltractor or their
al 1 nCCC or anItitC tor sote respIkhdY
lP' with %aid codes and standart
the huitdiilg cede or br any re nthuttY b
crru'I%. o S°t1 or i gtigefl in
hethCr or not 0ied in ibis ruviCw.
/j' /O viewCrt
RECYM1 AP'l(t
ri RFC0MMENDAPPO As NOTED
Submitted By: FILE copy
3830 Calle Fortunada
San Diego, CA 92123
(858) 654-3133
Lie. # 707408
I,
INVITROGEN
CP-24 T.I.
FIRE ALARM SUBMITTAL
QIX DESCRIPTION MODEL # MANF. CSFM#
POWER SUPPLY FCPS-24FS8 FIRELITE 7315-0075:206
2 INPUT MODULE MMF-300 FIRE LITE 7300-0075:185
2 RELAY MODULE CRF-300 FIRE LITE 7300-0075:185
6 HORN/STROBE MULTI-CD AS-24MCC WHEELOCK 7125-0785:131
5 STROBE MULTI-CD RSS-24MCC WHEELOCK 7125-0785:141
CONNECTION TO 2 DUCT DETECTORS
LOT 14/2 FIRE CABLE ADT/GENESIS 7161-1487:100
LOT 18/4 FIRE CABLE ADT/GENESIS 7161-1487:100
p
FCPS-24FS8
8-Amp, 24-Volt Power Supply
General
The Fire-Lite FCPS-24FS8(CIE) is a compact, cost-effec-
tive, 8-amp remote power supplies with battery charger. The
FCPS-24FS8C/E) may be connected to any 12 or 24 volt fire
alarm control panel (FACP) or may stand-alone. Primary appli-
cations include notification appliance (bell) circuit (NAC)
expansion (to support ADA requirements and NAC synchroni-
zation) or auxiliary power to support 24 volt system accesso-
ries. The FCPS provides regulated and filtered 24 VDC power
to four notification appliance circuits configured as either two
Class B (Style Y) and Class A (Style Z, with ZNAC-4 option
module) or four class B only. Alternately, the four outputs may
be configured as any combination of resettable/non-resettable
power outputs (optimal for powering four-wire smoke detec-
tors. The FFCPS-24FS8(C/E) also contains a battery charger
capable of charging up to 18.0 Amp hour batteries. FCPS-
24FS8C/E) is ULC-listed.
NOTE: Unless otherwise specified, the term FCPS-24FS8 used in
this document refers to the standard FCPS-24FS8, FCPS-
24FS8C, FCPS-24FS8E
Features
UL-Listed Notification Appliance Circuit (NAC) synchroniza-
tion using System Sensor, Wheelock, or Gentex
Commander2" appliances.
Operates as a sync-follower" or as a "sync-generator"
(default). See note on page 2.
Contains two fully-isolated input/control circuits - triggered
from FACP NAC (NAC expander mode) or jumped perma-
nently "ON" (stand-alone mode).
Two Class B (Style Y) or Class A (Style Z, with ZNAC-4
module) NACs (circuits 1 & 3)
8-amp full load output, with 3 amps maximum/circuit, in
NAC expander mode (UL 864).
6-amp continuous output in stand-alone mode (UL 1481).
Compatible with coded inputs; signals passed through.
Optional power-supervision relay (EOLR-1).
In stand-alone mode, output power circuits may be config-
ured as: resettable, (reset line from FACP required),
non-resettable, or a mix of two and two.
Fully regulated and filtered power output - optimal for pow-
ering four-wire smoke detectors, annunciators, and other
system peripherals requiring regulated/filtered power.
Power-limiting technology meets UL power-limiting require-
ments.
Form-C normally-closed trouble relay.
Fully supervised power supply, battery, and NACs.
Selectable earth fault detection.
AC trouble report selectable for immediate 2-hour delay.
Works with virtually any UL 864 fire alarm control which uti-
lizes an industry-standard reverse-polarity notification cir-
cuit (including unfiltered and unregulated bell power).
Requires input trigger voltage of 9 - 32 VDC.
Self-contained in compact, locking cabinet - 15"H x 14.5W
x 2.75"D (cm: 38.1 H x 36.83W x 6.985D).
df-5231 0:A • 0-050
(2) FlreuTe®Atarms
by Honeywell
Includes integral battery charger capable of charging up to
18 AH oatteries. Cabinet capable of housing 7.0 AH batter-
ies.
Battery charger may be disabled via DIP switch for applica-
tions reqJiring larger batteries.
Fixed, :Imp-type terminal blocks accommodate up to 12
AWG (3.1mm2) wire.
Specifications
Primary (AC) Power:
FCPS-2r 120 VAC, 60 Hz, 3.2A maximum.
FCPS-2cFS8/E: 240 VAC, 50 Hz, 1.6A maximum.
Wire Size: minimum #14 AWG (2.0mm2) with 600 V insula-
tion.
Control input Circuit:
Trigger Input Voltage: 9 to 32 VDC.
Triggei Current: 2.0 mA (16-32 V); Per Input: 1.0 mA (9
- 16 V).
Trouble Contact Rating: 5 A at 24 VDC.
Auxiliary Power Output: Specific application power 500 mA
maximum.
Output Circuits:
+24 VCC filtered, regulated.
3.0 A it aximum for any one circuit.
Total ccnhinuous current for all outputs (stand-alone mode):
- FCPS-24FS8: 6.0 A maximum.
Total shot-term current for all outputs (NAC expander mode):
- FCPS-24FS8: 8.0 A maximum.
df-5231 OA • 04/30/09 - Page 1 of 4
Secondary Power (Battery) Charging Circuit:
Supports lead-acid batteries only.
Float-charge voltage: 27.6 VDC.
Maximum current charge: 250 mA.
Maximum battery capacity: 7.0 AH.
Applications
Example 1: Expand notification appliance power an additional
8.0 A. Use up to four Class B (Style Y) outputs or four Class A
(Style Z) outputs (using ZNAC-4). For example, the FACP noti-
fication appliance circuits will activate the FCPS when reverse-
polarity activation occurs. Trouble conditions on the FCPS are
sensed by the FACP through the notification appliance circuit.
Example 2: Use the FCPS to expand auxiliary regulated 24-
volt system power up to 6.0 A. Both resettable and non-reset-
table power options are available. Resettable outputs are cre-
ated by connecting the resettable output from the FACP to one
or both of the FCPS inputs.
Example 3: Use addressable control modules to activate the
FCPS instead of activating it through the FACP notification
appliance circuits. This typically allows for mounting the FCPS
at greater distances* away from the FACP while expanding
system architecture in various applications.
For example, an addressable control module is used to acti-
vate the FCPS, and an addressable monitor module is used to
sense FCPS trouble conditions. Local auxiliary power output
from the FCPS provides power to the addressable control
module.
*NOTE: Addressable FACPs are capable of locating control and
monitor modules at distances of up to 10,000 feet (3,046 meters).
Sync Follower/Generator Note
In some installations, it is necessary to synchronize the flash
timing of all strobes in the system for ADA compliance.
Strobes accomplish this by monitoring very short timing pulses
on the NAC power which are created by the FACP. When
installed at the end of a NAC wire run, the FCPS-24FS8 can
track (i.e. follow") the strobe synchronization timing pulses on
the existing NAC wire run. This maintains the overall system
flash timing of the additional strobes attaches to the FCPS.
When the FCPS-24FS8 is configured (via DIP switch settings)
as a 'sync follower;' the FCPS's NAC outputs track the strobe
synchronization pulses present at the FCPS's sync input ter-
minal. The pulses originate from an upstream FACP or other
power supply.
When the FCPS-24FS8 is configured (via DIP switch settings)
as a sync generator," the FCPS's sync input terminals are not
used. Rather, the FCPS is the originator of the strobe synchro-
nization pulses on the FCPS's NAC outputs. In "sync genera-
tor" mode, the sync type (System Sensor, Wheelock, or
Gentex) is selectable via DIP switch settings.
Standards and Codes
The FCPS-24FS8 complies with the following standards:
NFPA 72 National Fire Alarm Code.
UL 864 Standard for Control Units for Fire Alarm Systems
(NAC expander mode).
UL 1481 Power Supplies for Fire Alarm Systems.
Page 2 of 4— df-52310:A • 04/30/09
Agency Listings and Approvals
These listings and approvals apply to the modules specified in
this document. In some cases, certain modules or applications
may not be listed by certain approval agencies, or listing may
be in process. Consult factory for latest listing status.
UL Listed: S2424
ULC Listed: S2424
CSFM Approved: 7315-0075:206
MEA:219-02E
Ordering Information
FCPS-24FS8: 6.0 A, 120 VAC remote charger power supply.
Includes main printed circuit board, transformers, enclosure
(15"H x 14.5W x 2.75"D [cm: 38.1H x 36.83W x 6.985D]), and
installation instructions.
FCPS-24FS8 is ULC-Iisted.
FCPS-24FS8E: 6.0 A, 240 VAC remote charger power supply.
Includes main printed circuit board, transformers, enclosure
(15"H x 14.5W x 2.75"D [cm: 38.1 H x 36.83W x 6.985D]), and
installation instructions.
ZNAC-4: Class A (Style Y) NAC option module.
EOLR-1: 12/24 VDC end-of-line relay for monitoring four-wire
smoke detector power.
BAT-1270: Battery, 12-volt, 7.0 AH (two required).
PS-1270: Battery, 12-volt, 7.0 AH (two required).
90286: Optional module mounting kit, is required to install an
addressable module on the power supply main circuit board.
AC
POWE
NOTE: All NAC outputs can
be converted to Style Z with
Style Y NAC or ZNAC-4 option module. FCPS Door Holder Trouble
Power Style Y NAC Style Y NAC Style Y NAC Contact
Output #4 Output #3 Output #2 Output #1 Output
24VDC
Specific
Application
Power
NAC Control
Input #2
(from FACP)
NAC Control
Input #1
(from FACP)
Sync Input
Battery Charger
Simplified Block Diagram
df-5231 OA • 04/30/09 - Page 3 of 4
IOU 0
CL '-5
I-
0
-S. Auxiliary Output: 111al
Application Power 9 rJ,-+-
-, • •
4 NO
I........ .
111)15CC) 14
SW1:
Programming
DIP Switches
TB2: Power-Limited, NAC/Out 1 + Supervised in NAC Mode NAC/Out 1 -
with Jumpers J5, JP6, NAC/Out 2 +
TB1: Supervised JPT, & JP8 In positions NAC/Out 2—
- Earth
shown below. NAC/Out 3 + NAC/Out 3 - — AC Neutral NAC/Out 4 +
AC Hot NAC/Out 4
_
182____
-EW AW ~j Lj
ILEr
Non-Power-Limited
J2: To Transformer #2
Ji: To Transformer #1
0 0
F1
0
0
10
II Fl:
Battery Fuse
lEA, 30 V
JP4
Im @ (9 (9 (5
a D __
- Battery LEDs (L to R):
L._ . AC Power (green) + Battery Ground Fault (yellow)
JP4: Supervised, Battery Trouble (yellow)
Non-Power-Limited . NAC Trouble (yellow)
18AH, 24 VDC Charger Trouble/AC Loss (yellow)
Normally Open
Normally Closed
Common
TB5: Trouble Relay o Form-C Fail-Safe
o (shown energized)
JRj a) I
3 2 TB5
JP1:
Ground Fault
Detection
jpi j (cut to disable)
J3: ZNAC-4
JP2 Connector
I
JP3 JP2 & JP3:
Coded/Non-Coded
Input Selection
—Aux. Common
+ Aux. 24
- Control Input 2
+ Control Input 2
- Out Common
+ Out/Trouble Contact
- Control Input 1
+ Control Input 1
- Sync Input
+ Sync Input
a) 1ftJo Auxiliary Power
01 Output is power-limited
but NOT supervised.
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. 7315-0075:206 Page 1 of 1
CATEGORY: Power Units
LISTEE: Fire-Lite Alarms, Inc., One Fire-Lite Place, Northford, CT 06472-1653
Contact: Brian Reynolds *(203) 484-7161 FAX (203) 484-7309
DESIGN: Models FCPS-24FS6 and FCPS-24FS8 are power limited power supply/battery chargers
used for supervision and expanded power driving capability of up to four Notification
Appliance Circuits (FACP Fire Circuits, Signaling Devices) or resettable/non resettable
outputs. Model ZNAC-4 Class A converter. Refer to listee's data sheet for additional detailed
product description and operational considerations.
RATING: 120 VAC, 24VDC
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and
ordinances and in a manner acceptable to the authority having jurisdiction.
MARKING: Listee's name, product designation, electrical rating and UL label.
APPROVAL: Listed as a Power Supply/Battery Charger for use with separately listed compatible fire
alarm control units.
*Rev. 05-06-05JW
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results
and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or
recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation
criteria. Refer to listee's data sheet, installation instructions and/or other suitable information sources.
Date Issued: JUNE 16, 2009 Listing Expires June 30, 2010
Authorized By: FRANCIS MATEO, Program Coordinator
Fire Engineering Division
df-52121:b • E-325
MMF.300(A) Series,
MDF.300(A)
Addressable Monitor Modules
General
Four different monitor modules are available for FiresLite's
intelligent control panels to suit a variety of applications. Moni-
tor modules are used to supervise a circuit of dry-contact input
devices, such as conventional heat detectors and pull stations,
or monitor and power a circuit of two-wire smoke detectors
(MMF-302(A)).
MMF-300(A) is a standard-sized module (typically mounts to a
4" [10.16 cm] square box) that supervises either a Style 0
(Class A) or Style B (Class B) circuit of dry-contact input
devices.
MMF-301 (A) is a miniature monitor module a mere 1.3 (3.302
cm) H x 2.75 (6.985 cm) W x 0.5 (1.270 cm) D used to super-
vise a Style B (Class B) circuit of dry-contact input devices. Its
compact design allows the MMF-301 (A) to often be mounted
in a single-gang box behind the device it monitors.
MMF-302(A) is a standard-sized module used to monitor and
supervise compatible two-wire, 24 volt, smoke detectors on a
Style D (Class A) or Style B (Class B) circuit.
MDF.300(A) is a standard-sized dual monitor module used to
monitor and supervise two independent two-wire Style B
(Class B) dry-contact initiating device circuits (IDCs) at two
separate, consecutive addresses in intelligent, two-wire systems.
LiteSpeedTM is a communication protocol developed by
Fire'Lite Engineering that greatly enhances the speed of com-
munication between analog intelligent devices. Intelligent
devices communicate in a grouped fashion. If one of the
devices within the group has new information, the panel CPU
stops the group poll and concentrates on single points. The
net effect is response speed greater than five times that of
other designs.
MMF-300(A) Monitor Module
Built-in type identification automatically identities this device
as a monitor module to the control panel.
Powered directly by two-wire SLC loop. No additional power
required.
High noise (EMF/RFl) immunity.
SEMS screws with clamping plates for ease of wiring.
Direct-dial entry of address: 01 —159 on MS-9600 series
panels, 01 - 99 on other compatible systems.
LED flashes during normal operation and latches on steady
to indicate alarm.
The MMF-300(A) Monitor Module is intended for use in intelli-
gent, two-wire systems, where the individual address of each
module is selected using the built-in rotary switches. It pro-
vides either a two-wire or four-wire fault-tolerant Initiating
Device Circuit (lDC) for normally-open-contact fire alarm and
supervisory devices. The module has a panel-controlled LED
indicator. The MMF-300(A) can be used to replace M300(A)
modules in existing systems.
11#11417-300(A) APPLICATIONS
Use to monitor a zone of four-wire smoke detectors, manual
fire alarm pull stations, waterflow devices, or other normally-
open dry-contact alarm activation devices. May also be used
to monitor normally-open supervisory devices with special
supervisory indication at the control panel. Monitored circuit
(a AreLuTeALarms
by Honeywell
MMF-300(A) (Type H)
may be wired as an NFPA Style B (Class B) or Style D (Class
A) Initiating Device Circuit. A 47K ohm End-of-Line Resistor
(provided) terminates the Style B circuit. No resistor is
required for supervision of the Style D circuit.
11411417-300(A) OPERATION
Each MMF-300(A) uses one of the available module
addresses on an SLC loop. It responds to regular polls from
the control panel and reports its type and the status (open/nor-
mal/short) of its Initiating Device Circuit (lDC). A flashing LED
indicates that the module is in communication with the control
panel. The LED latches steady on alarm (subject to current
limitations on the loop).
MMF-300(A) SPECIFICATIONS
Nominal operating voltage: 15 to 32 VDC.
Maximum current draw: 5.0 mA (LED on).
Average operating current: 350 pA (LED flashing), 1 com-
munication every 5 seconds, 47k EOL.
Maximum IDC wiring resistance: 40 ohms.
EOL resistance: 47K ohms.
Temperature range: 32°F to 120°F (0°C to 490C).
Humidity range: 10% to 93% noncondensing.
Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x
1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x
2.125" (5.398 cm) deep box.
MMF.301 (A) Mini Monitor Module
Built-in type identification automatically identifies this device
as a monitor module to the panel.
Powered directly by two-wire SLC loop. No additional power
required.
High noise (EMF/RFI) immunity.
Tinned, stripped leads for ease of wiring.
df-52121:b.11/19/09—Page 1 0t4
Direct-dial entry of address: 01 - 159 on MS-9600 series
panels, 01 - 99 on other compatible systems
1415 0 1 ADDRESS
13
R :
TENS ONES
The MMF-301(A) Mini Monitor Module can be installed in a
single-gang junction directly behind the monitored unit. Its
small size and light weight allow it to be installed without rigid
mounting. The MMF-301(A) is intended for use in intelligent,
two-wire systems where the individual address of each module
is selected using rotary switches. It provides a two-wire initiat-
ing device circuit for normally-open-contact fire alarm devices.
The MMF-301(A) can be used to replace M301 (A) modules in
existing systems.
MMF-301(A) APPLICATIONS
Use to monitor a single device or a zone of four-wire smoke
detectors, manual fire alarm pull stations, waterflow devices, or
other normally-open dry-contact devices. May also be used to
monitor normally-open supervisory devices with special super-
visory indication at the control panel. Monitored circuit/device
is wired as an NFPA Style B (Class B) Initiating Device Circuit.
A 47K ohm End-of-Line Resistor (provided) terminates the cir-
cuit.
MMF-301(A) OPERATION
Each MMF-301(A) uses one of the available module
addresses on an SLC loop. It responds to regular polls from
the control panel and reports its type and the status (open/nor-
mal/short) of its Initiating Device Circuit (IDC).
MMF-301(A) SPECIFICATIONS
Nominal operating voltage: 15 to 32 VDC.
Average operating current: 350 pA, 1 communication every
5 seconds, 47k EOL; 600 pA Max. (Communicating, IDC
Shorted).
Maximum IDC wiring resistance: 40 ohms.
Maximum IDC Voltage: 11 Volts.
Maximum IDC Current: 400 pA.
EOL resistance: 47K ohms.
Temperature range: 32°F to 120°F (0°C to 49°C).
Humidity range: 10% to 93% noncondensing.
Dimensions: 1.3" (3.302 cm) high x 2.75° (6.985 cm) wide x
0.65 (1.651 cm) deep.
Wire length: 6° (15.24 cm) minimum.
MMF.302(A) Interface Module
Supports compatible two-wire smoke detectors.
Supervises IDC wiring and connection of external power
source.
High noise (EMF/RFI) immunity.
SEMS screws with clamping plates for ease of wiring.
Direct-dial entry of address: 01 - 159 on MS-9600 series
panels, 01 - 99 on other compatible systems.
LED flashes during normal operation.
LED latches steady to indicate alarm on command from
control panel.
The MMF-302(A) Interlace Module is intended for use in intelli-
gent, addressable systems, where the individual address of
each module is selected using built-in rotary switches. This
module allows intelligent panels to interface and monitor two-
wire conventional smoke detectors. It transmits the status (nor-
mal, open, or alarm) of one full zone of conventional detectors
back to the control panel. All two-wire detectors being moni-
tored must be UL compatible with the module. The MMF-
302(A) can be used to replace M302(A) modules in existing
systems.
MMF-302 (A) APPLICATIONS
Use the MMF-302(A) to monitor a zone of two-wire smoke
detectors. The monitored circuit may be wired as an NFPA
Style B (Class B) or Style D (Class A) Initiating Device Circuit.
A 3.9 K ohm End-of-Line Resistor (provided) terminates the
end of the Style B or D (class B or A) circuit (maximum IDC
loop resistance is 25 ohms). Install ELR across terminals 8
and 9 for Style D application.
MMF-302(A) OPERATION
Each MMF-302(A) uses one of the available module
addresses on an SLC loop. It responds to regular polls from
the control panel and reports its type and the status (open/nor-
mal/short) of its Initiating Device Circuit (IDC). A flashing LED
indicates that the module is in communication with the control
panel. The LED latches steady on alarm (subject to current
limitations on the loop).
11411417-302(A) SPECIFICATIONS
Nominal operating voltage: 15 to 32 VDC.
Maximum current draw: 5.1 mA (LED on).
Maximum IDC wiring resistance: 25 ohms.
Average operating current: 300 pA, 1 communication and 1
LED flash every 5 seconds, 3.9k eol.
EOL resistance: 3.9K ohms.
External supply voltage (between Terminals T3 and T4):
DC voltage: 24 volts power limited. Ripple voltage: 0.1 Vrms
maximum. Current: 90 mA per module maximum.
Temperature range: 32°F to 120°F (0°C to 490C).
Humidity range: 10% to 93% noncondensing.
Dimensions: 4.5° (11.43 cm) high x 4' (10.16 cm) wide x
1.25" (3.175 cm) deep. Mounts to a 4° (10.16 cm) square x
2.125" (5.398 cm) deep box.
MDF.300(A) Dual Monitor Module
The MDF-300(A) Dual Monitor Module is intended for use in
intelligent, two-wire systems. It provides two independent two-
wire initiating device circuits (lDCs) at two separate, consecutive
addresses. It is capable of monitoring normally open contact fire
alarm and supervisory devices. The module has a single panel-
controlled LED.
Page 2 of 4— df-521 21:b • 11/19/09
NOTE: The MDF-300(A) provides two Style B (Class B) IDC cir- MDF-300(A): Monitor module, dual, two independent Class B
cuits ONLY. Style 0 (Class A) IDC circuits are NOT supported in circuits.
any application. SMB500: Optional surface-mount backbox.
MDF300(A) SPECIFICATIONS NOTE: See installation instructions and refer to the SLC Wiring
Normal operating voltage range: 15 to 32 VDC. Manual, PN 51309.
Maximum current draw: 6.4 mA (LED on).
Average operating current: 750 pA (LED flashing).
Maximum IDC wiring resistance: 1,500 ohms.
Maximum IDC Voltage: 11 Volts.
Maximum IDC Current: 240 pA
EOL resistance: 47K ohms.
Maximum SLC Wiring resistance: 40 Ohms.
Temperature range: 32° to 120°F (00 to 490C).
Humidity range: 10% to 93% (non-condensing).
Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x
2.125" (5.398 cm) deep.
MDF-300(A) AUTOMATIC ADDRESSING
The MDF-300(A) automatically assigns itself to two address-
able points, starting with the original address. For example, if
the MDF-300(A) is set to address "26", then it will automati-
cally assign itself to addresses "26" and "27".
NOTE: "Ones" addresses on the MDF-300(A) are 0, 2, 4, 6, or 8
only. Terminals 6 and 7 use the first address, and terminals 8 and
9 use the second address.
CAUTION:
Avoid duplicating addresses on the system.
Architects/Engineers' Specifications
Specifications of these devices and all FireLite products are
available from FireLite.
Installation
MMF-300(A), MMF-302(A), and MDF-300(A) modules mount
directly to a standard 4" (10.16 cm) square, 2.125" (5.398 cm)
deep, electrical box. They may also be mounted to the
SMBSOO surface-mount box. Mounting hardware and installa-
tion instructions are provided with each module. All wiring
must conform to applicable local codes, ordinances, and regu-
lations. These modules are intended for power-limited wiring
only.
The MMF-301 (A) module is intended to be wired and mounted
without rigid connections inside a standard electrical box. All
wiring must conform to applicable local codes, ordinances, and
regulations.
Agency Listings and Approvals
In some cases, certain modules may not be listed by certain
approval agencies, or listing may be in process. Consult fac-
tory for latest listing status.
UL: S2424
ULC: S2424
FM Approved
CSFM: 7300-0075-185
MEA:72-01-E
Product Line Information
NOTE: "A" or suffix indicates ULC-listed model.
MMF-300(A): Monitor module.
MMF-301(A): Monitor module, miniature.
MMF-302(A): Monitor module, two-wire detectors.
df-52121 :b • 11/19/09 -Page 3 of 4
Fire-Lite® and LiteSpeed® are registered trademarks and FireWatch is a
trademark of Honeywell International Inc.
02009 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.
ISO 9001
This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate. _________
We cannot cover all specific applications or anticipate all requirements.
INGIRE11111111 & MANUFACTUMNS
QUALITY SYSTEMS
All specifications are subject to change without notice.
Made in the U.S. A.
For more information, contact Fire-Lite Alarms. Phone: (800) 627-3473, FAX: (877) 699-4105.
www.firelite.com
Page 4of4—df-52121:b. 11/19/09
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS USTING PROGRAM
LISTING SERVICE
LISTING No. 7300-0075:185 Page 1 of 1
CATEGORY: Misc. Devices/Control Unit Accessories
LISTEE: Fire-Lite Alarms, Inc., One Fire-Lite Place, Northford, CT 06472-1653
Contact: Brian Reynolds *(203) 484-7161 FAX (203) 484-7309
DESIGN: Models MDF-300, MMF-301, MMF-300, MMF-302, MCF-300 monitor modules; Models
CRF-300 and CMF-300 control modules; and MMF-302-6 six zone interface signaling
device module. Refer to listee's data sheet for additional detailed product description and
operational considerations.
RATING: 15-32VDC
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and
ordinances and in a manner acceptable to the authority having jurisdiction.
MARKING: Listee's name, model designation, electrical rating, and UL label.
APPROVAL: Listed as control unit accessories for use with listee's separately listed electrically
compatible fire alarm control units.
*Rev. 05-06-05 JW
1•0. This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results
and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or
recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation
criteria. Refer to listee's data sheet, installation instructions and/or other suitable information sources.
Date Issued: JUNE 16, 2009 Listing Expires June 30, 2010
Authorized By: FRANCIS MATEO, Program Coordinator
Fire Engineering Division
COOPER Notification
Series AS Audible Strobe Appliances and Series AH Audibles
-,
r
SERIES AS SERIES AH
Description
The Wheelock patented 2-wire Series AS Audible Strobe
Appliances and Series AH Audibles offer more features with
low current draw.
Strobe options for wall mount models include 1575cd or the
Wheelock patented MCW multi-candela wall strobes with field
selectable candela settings of 15/30/75/110cd, or the high
intensity MCWH strobe with field selectable 135/185cd.
Ceiling mount models incorporate Wheelock's patented MCC
multi-candela ceiling strobe with field selectable intensities of
15/30175/95cd or the high intensity MCCH strobe with field
selectable 115/177cd.
The audible provides a selectable choice of either a
continuous horn or temporal pattern (Code 3) when
constant voltage from a Fire Alarm Panel (FACP) is
applied. Each tone has 3 dBA settings to choose from.
When used with the Wheelock Series SM,DSM Sync
Modules, Wheelock Power Supplies or other manufacturers
panels incorporating the Wheelock Patented Sync Protocol,
synchronization of the continuous horn tone provides the
temporal (code 3) tone (mandated by NFPA72) simultaneously
for all audible appliances. This ensures a distinct temporal
(code 3) pattern when 2 or more audibles are within hearing
distance. If not synchronized the temporal sound could overlap
and not be distinctive. At the same time the strobes will be
synchronized. This provides the ability to comply with ADA
guidelines concerning photosensitive epilepsy and the NFPA
standards when installing 2 or more visual appliances within
the field of view all of this plus the ability to silence the audible
is achieved by using only 2 wire.
Features
Approvals include: UL Standard 1971, UL Standard 464
New York City (MEA), California State Fire Marshal (CSFM),
Factory Mutual (FM), and Chicago (BFP). See approvals by
model in Specifications and Ordering Information
ADA/NFPA/UFC/ANSI Compliant
Wall mount models are available with Field Selectable
Candela Settings of 15/30/75/11Ocd or 135/185cd (Multi-
Candela models) or 1575cd (single candela model)
Ceiling mount models are available with field selectable
candela settings of 15/30/75/95cd or 115/177cd (multi-candela
ceiling models)
Selectable Continuous Horn or Temporal (Code 3).
3 Selectable dBA settings (99, 95 and 90 dBA) in both tones
Patented 2-Wire Audible Strobe Appliance.
Patented Universal Mounting Plate
Weatherproof models are available for outdoor use
Strobes produce 1 flash per second over the regulated
voltage range
12 and 24 VDC models with wide UL Regulated Voltage
Range" using filtered DC or unfiltered FWR input voltage
Synchronize using the Wheelock Sync Modules or panels with
built-in Wheelock Patented Sync Protocol
Fast installation with IN/OUT screw terminals using
#12 to#18AWG wires
For Weatherproof Series AS, See Datasheet S9004
0 :--:~ It <g>
MEA APPROVED
E5946 151-92-E 7125-0785:131
S5391
AH-12 I AS-121575W
High (99) c 0.163 0.260
~ULmax. 0.192 0.320 dBA
Med (95) 12 vdc 0.076 0.195
UL max* 0.108 0.275 dBA
(90) Fd
l2vdc 0.039 0.175
UL max* 0.058 0.265 BA
Table 4: Average Current* (AMPS) For Series ASWP#
Voltage
High dBA
Setting
(99) dBA
Medium dBA
Setting
(95) dBA
Low dBA
Setting
(90) dBA
24.0 VDC 0.128 0.105 0.098
ULMax* 0.168 0.155 0.150
* RMS current ratings are per UL average RMS method. UL max current
rating is the maximum RMS current within the listed voltage range (16-33v
for 24v units). For strobes the UL max current is usually at the minimum
listed voltage (16v for 24v units). For audibles the max current is usually
at the maximum listed voltage (33v for 24v units). For unfiltered FWR
ratings, see installation instructions.
NOTE: All CAUTIONS and WARNINGS are identified by the symbol A. All warnings are printed in bold capital letters.
A. WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR
APPLYING THIS PRODUCT. VISIT WWW.COOPERWHEELOCK.COM OR CONTACT COOPER WHEELOCK FOR THE CURRENT INSTALLATION INSTRUCTIONS.
FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR
OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU
AND/OR OTHERS.
General Notes:
Strobes are designed to flash at 1 flash per second minimum over their 'Regulated Voltage Range". Note that NFPA-72 specifies a flash rate of I
to 2 flashes per second and ADA Guidelines specify a flash rate of 1 to 3 flashes per second.
All candela ratings represent minimum effective Strobe intensity based on UL Standard 1971.
Series NS Strobe products are listed under UL Standard 1971 for indoor use with a temperature range of 32°F to 120°F (0°C to 49°C) and
maximum humidity of 93% (± 2%).
Series NH horns are listed under UL Standard 464 for audible signal appliances (Indoor use only).
"Regulated Voltage Range" is the newest terminology used by UL to identify the voltage range. Prior to this change UL used the
terminology "Listed Voltage Range".
Table 1: Ratings Per UL 1971
Model
Number
Input
Voltage
VDC
Regulated
Voltage Range
VDC/FWR
Strobe
Candela (Cd)
AS-24MCW 24 16.0-33.0 15/30/75/110
AS-24MCCH 24 16.0-33.0 115/177
AS-241575W 24 16.0-33.0 15(75onAxis)
AS-121575W 12 8.0-17.5 15 (75 on Axis)
AS-24MCC 24 16.0 -33.0 15/30/75/95
AS-24MCWH 24 16.0-33.0 135/185
ASWP-2475W 24 16.0-33.0 75@-31°F
Table 2: dBA Ratings for 12 VDC and 24 VDC Series AS/
AH 12 and 24 VDC Audible
Reverberant Anechoic
Description Volume dBA
Per UL 464 dBA
@10 ft.
@10 ft.
High 91 99
Continuous Medium 88 95
Horn
Low 83 90
High 87 99
Medium 84 95 Code 3 Horn
Low 79 90
Table 3: Average RMS Current
24 VDC Models
Audible
AH-24 AS-241575W
1575cd
High (99)
dBA
24 vdc 0.062 0.100
UL max* 0.080 0.121
Med (95)
dBA
24 vdc 0.033 0.080
UL max* 0.043 0.107
Low (90)
dBA
24 vdc 0.017 0.072
UL max* 0.021 0.100
12 VDC Models
Audible
Wall Mount
Audible
Strobe
Wall Mount Audible Strobe Models Ceiling Mount Audible Strobe Models
AS-24MCW AS-24MCWH AS-24MCC AS-24MCCH
15cd 30cd 75cd llocd 135cd 185cd 15cd 30cd 75cd 95cd 11 5c 177cd
0.080 0.102 0.150 0.194 0.250 0.320 0.088 0.114 0.165 0.205 0.250 0.320
0.088 0.125 0.200 0.267 0.355 0.480 0.095 0.138 0.221 0.285 0.355 0.480
0.060 0.084 0.132 0.173 0.230 0.305 0.066 0.092 0.145 0.186 1 0.230 0.305
0.074 0.110 0.190 0.253 0.340 0.465 0.080 0.122 0.201 0.269 0.340 0.465
0.052 0.076 0.121 0.158 0.220 0.295 0.056 0.082 0.132 0.173 0.220 0.295
0.068 0.105 0.182 0.245 0.335 0.460 0.074 0.113 1 0.198 0.263 0.335 0.460
Wiring Diagrams
SERIES AS APPLIANCES NON-SYNCHRONIZED
FROMLTI 0T0 NEXTO
PRECE DINGO _PPL IANCEE
APPLIANCEE OR EOLRE
OR FACPLI
SERIES AS & RSS APPLIANCES SYNCHRONIZED WITH
PS-12124-8CP and PS-12/24-8MP
OUT P UT SC = CaL RD
FE 1-40
- 4-CLASSO
AS 000 QUO
cLi "AD
PE
ASD
i
Or1eo P5-12/24-8 PD
or PS-12/24--UMPC
SERIES AS APPLIANCES SYNCHRONIZED WITH DSM MODULE
CLASS"A" NAC CIRCUIT WITH NO AUDIBLE SILENCE FEATURE
Specifications and Ordering Information
DSM Interconnecting wiring shown. Maximum
twenty (20)11
For detail using SM or DSM Sync Module refer to Data Sheet
S3000 or Installation Instructions P83123 for SM and P83177
for DSM. For wiring informationon the power supplies refer to
Installation Instructions P84662 for PS-24-8MC.
SERIES AS APPLIANCES SYNCHRONIZED WITH SM MODULE SIN-
GLE CLASS "B" NAC CIRCUIT WITH AUDIBLESILENCE FEATURE
smo
+OSTROBED
050RoBED StrobeD AL NACC
CircUit AS
co dib cC
p EOLRD
AsdibleD -UOdib eD
85CC
circuita
SERIES AS APPLIANCES SYNCHRONIZED WITH MULTIPLE DSM
MODULES
- ......SM#lD
Strobe SAC Cir.t
FLI
Audible SAC
AES NAC .YflcO
CLII
Audl SAC SM 3D
P LI SyncO
Strobe SAC C
Model Number Order
Code
Strobe
Candela
Non-
Sync
Sync w/SM,
DSM or 24
VDC
12
VDC
Wall
Mount Mount
Ceiling Agency
Mounting Options*
Approvals
AS-24MCW-FR 9024 15/30/75/110 X X X - X - A,BD,E,FG,HJ,N,O,R,X X X X X X
AS-24MCW-FW 9025 15/30/75/110 X X X - X - A,B,D,E,F,G,H,J,N,O,R,X X X X X X
AS-24MCWH-FR 3468 135/185 X X X - X - A,B,D,E,F,G,H,J,N,O,R,X X X X X *
AS-24MCWH-FW 3469 135/185 X X X - X - A,B,D,E,F,G,H,J,N,O,R,X X X X X *
AS-241575W-FR 7405 15(75onAxis) X X X - X - A,B,D,E,F,G,H,J,N,O,R,X X X X X X
AS-121575W-FR 7410 15(75onAxis) X X - X X - A,B,D,EFG,H,J,N,O,R,X X X X X X
AS-24MCC-FR 3161 15/30/75/95 X X X - - X A,B,D,E,FG,H,JN,OR,X X X X X *
AS-24MCC-FW 3162 15/30/75/95 X X X - - X AB,D,E,F,G,H,J,N,O,R,X X X X X *
AS-24MCCH-FW 3467 115/177 X X X - - X A,B,D,E,F,G,H,J,N,O,R,X X X X X *
ASWP2475WFR** 90 75 @ -31°F X X X - X - I(see Data Sheet S9004) X X X X X
AH-24-R 7892 - X X X - X X A,B,D,E,F,G,H,J,N,O,R,X X X X X X
AH-24-W 7893 - X X X - X X A,B,D,E,F,G,HJ,N,O,R,X X X X X X
AH-12-R 7891 - X X - X X X A,B,D,E,F,G,H,J,N,O,R,X X X X X X
AH-12-W 7894 - X X - X X X A,B,D,E,F,G,H,J,N,O,R,X X X X X X
AH24WPR** 7416 - X X X - X X K X X X X
AH12WPR** 7415 - X X - X X X K X X X X
**For Weatherproof Series AS/AH specifications see data sheet S9004. *PENDING
***Refer to Data Sheet S7000 for Mounting Options.
Note: Models are available in either Red or White. Contact Customer Service for Order Code and Delivery.
NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in
accordance with Wheelock Inc. standard terms and conditions.
Architects and Engineers Specifications
The notification appliances shall be Wheelock Series AS Audible Strobe appliances and Series AH Audible appliances or approved
equals. The Series AS Audible be listed for UL Standard 1971 (Emergency Devices for the Hearing-Impaired) for Indoor Fire Protection
Service. The Series AH Audible shall be UL Listed under Standard 464 (Fire Protective Signaling). Both shall meet the requirements
of FCC Part 15 Class B. All inputs shall be compatible with standard reverse polarity supervision of circuit wiring by a Fire Alarm
Control Panel (FACP).
The audible portion of the appliance shall have a minimum of three (3) field selectable settings for dBA levels and shall have a choice
of continuous or temporal (Code 3) audible outputs.
The strobe portion of the appliance shall produce a flash rate of one (1) flash per second over the Regulated Voltage Range and
shall incorporate a Xenon flashtube enclosed in a rugged Lexan® lens. The Series AS shall be of low current design. Where Multi-
Candela appliances are specified, the strobe intensity shall have field selectable settings and shall be rated per UL Standard 1971 at
15/30/75/110 or 135/185 candela for wall mount and 15/30/75/95 or 115/177 candela for ceiling mount. The selector switch for selecting
the candela shall be tamper resistant. The 1575 candela strobe shall be specified when 15 candela UL Standard 1971 Listing with 75
candela on-axis is required (e.g. ADA compliance).
When synchronization is required, the appliance shall be compatible with Wheelock's SM, DSM Sync Modules, Wheelock Power Supplies
or other manufacturers panels with built-in Wheelock Patented Sync Protocol. The strobes shall not drift out of synchronization at any
time during operation. If the sync module or Power Supply fails to operate, (i.e., contacts remain closed), the strobe shall revert to a
non-synchronized flash-rate. The appliance shall also be designed so that the audible signal may be silenced while maintaining strobe
activation when used with Wheelock synchronization.
The Series AS Audible Strobe and Series AH Audible shall incorporate a Patented Universal Mounting Plate that shall allow mounting
to a single-gang, double-gang, 4-inch square, 1 00m European type backboxes, or the SHBB Surface Backbox. If required, an NATP
(Notification Appliance Trimplate) shall be provided.
All notification appliances shall be backward compatible.
WE ENCOURAGE AND SUPPORT NICET CERTIFICATION
3 YEAR WARRANTY
Made in USA
S8100 AS/AH 10/07
Cooper Notification is Wheelock (MEDCJ SAFEPATH wAAEPS COOPER Notification
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. 7125-0785:131 Page 1 of 2
CATEGORY: Fire Alarm Devices for the Hearing-Impaired
LISTEE: Wheelock Inc., 273 Branchport Ave., Long Branch NJ 07740
Contact: Deborah Piserchia (732) 433-6001 Fax (732) 222-5607
DESIGN: Models AS-1215, -2415, -1230, -2430, -121575, -241575, -2475 and -24110 audible/strobes for
the hearing impaired followed by any three alpha/numeric characters indicating lens
orientation, lettering and color.
Models AS-1215W, -2415W, -1230W, -2430W, -121575W, -241575W, -2475W and -24110W
audible/strobes for the hearing impaired followed by any three alpha/numeric characters
indicating lens orientation, lettering and color. These units with suffix -W are for wall mount
only. *Models AS-121575W and AS-241575W lens color may be white, red, blue, green, or
amber.
Models AS-2415C, -2430C, -2475C and -24100C audible/strobes for the hearing impaired
followed by two alpha/numeric characters indicating lens lettering, orientation and color. These
units are intended for ceiling mount only.
Model AH-12, -24, AH-12WP, -24WP audible appliances (no strobe), followed by an alpha or
numeric character indicating product color.
Model AS-24MCW and AS-24MCC audible/strobe, followed by any two alpha or numeric
character indicating lettering and product color. *Lens color may be white, red, blue, green, or
amber.
Models ASWP-2475W and *AsWP..2475c audible/strobe with integral private mode
fire/emergency visual signaling for non-hearing impaired applications. Lens color may be white,
red, blue, green, and amber. Both models are suitable for outdoor use when mounted on the
Model WPBB back box.
Models AS-24MCWH, AS-24MCCH, *ASWP24MCWH and *ASWP24MCCH
audible/strobes for the hearing impaired followed by two alpha/numeric characters
indicating lens lettering and product color. Units with suffix CH are for ceiling mount only.
Units with suffix WH are for wall mount only. *Lens color may be white, red, blue, green,
or amber.
Refer to the listee's data sheet for detailed product description and operational considerations.
RATING: Electrical: 8-17.5/16-33 VDCNFWR
Flash Rate: 60 flashes/minute
Candela: 15:15cd, 1575:15/75cd, 30:30cd, 75:75cd, 95:95cd, 100:100cd, 110:11ocd
MCW: Selectable 15cd, 30cd, 75cd, 110cd
MCC: Selectable 15cd, 30cd, 75cd, 95cd
MCWH: Selectable 135cd, 185cd (65cd, 90cd at -40 C)
MCCH: Selectable 11 5cd, 177cd (50cd, 75cd at -40 C)
Listing No. 7125-0785:131
Page 2 of 2
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances and
in a manner acceptable to the authority having jurisdiction. Models ASWP-2475W, ASWP-
24MCWH, AS-24MCW and AS-24MCWH are for wall mount only. Models ASWP-2475C,
ASWP-24MCCH, AS-24MCCH, AND AS-24MCC are for ceiling mount only. Models with suffix -
W or WH are for wall mount only. Models with suffix -c or -CH are for ceiling mount only.
MARKING: Listee's name, model number, electrical/candela rating, and UL label.
APPROVAL: Listed as audible and audible/visual signaling devices suitable for the hearing impaired when used
in conjunction with separately listed electrically compatible fire alarm control units. For indoor use
only except Models AH-12WP, AH-24WP, *Aswp2475w ASWP-2475C, ASWP-24MCWH, and
ASWP-24MCCH audible appliances are suitable for indoor/outdoor. For synchronization, Models
AS Series must be used with Model SM-12/24, SMX-12/24, DSM-12/24 or DSMX-12/24 sync
control module (CSFM Listing No. 7300-0785:132). Refer to listee's Installation Instruction Manual
for details.
These appliances can generate a distinctive three-pulse Temporal Pattern Fire Alarm
Evacuation Signal (for total evacuation) in accordance with NFPA 72, 2002 Edition.
NOTE: Models AH-12, AH-24, -12WP and -24WP audible devices are not suitable for the hearing
impaired applications.
*Rev. 10-01-07
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results
and/or other data but does not make an independent verification of any claims. This listing is not, an endorsement or
recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation
criteria. Refer to listee's data sheet, installation instructions and/or other suitable information sources.
Date Issued: JUNE 18, 2009 Listing Expires June 30, 2010
Authorized By: FRANCIS MATEO, Program Coordinator
Fire Engineering Division
COOPER Notification
Series RSS and RSSP Strobes and Strobe Plates
I
Series RSS Series RSS Series RSSWP RSS Round
Description
The Wheelock patented Series RSS Strobe Appliances and
Series RSSP Strobe Plates have lower current draw while
maintaining outstanding performance, reliability and cost
effectiveness. These versatile appliances will satisfy virtually all
requirements for indoor, wall or ceiling mount applications.
Strobe options for wall mount models include 1575 or the
Wheelock Patented MCW multi-candela strobe with field
selectable candela settings of 15/30/75/110cd or the high
intensity MCWH strobe with field selectable 135/185cd.
Ceiling mount models include the patented MCC multi-candela
ceiling strobe with field selectable intensities of 15/30175/95cd
or the high intensity MCCH strobe with field selectable
115/177cd.
All models may be synchronized using the Wheelock SM,
DSM Sync Modules, Wheelock Power Supplies or other
manufacturers panels incorporating the Wheelock Patented
Sync Protocol. Synchronized strobes can eliminate possible
restrictions on the number of strobes in the field of view.
Wheelock's synchronized strobes offer an easy way to comply
with ADA recommendations concerning photosensitive epilepsy
as well as meeting the requirements of NFPA 72.
The Wheelock Series RSS Strobes employ a Patented Integral
Strobe Mounting Plate that can be mounted to a single gang,
double gang, 4" square, 1 00m European backboxes or the
SHBB surface backbox. If the flush backbox has side or top
space between it and the finished wall, the NATP (Notification
Appliance Trimplate) may be used. It provides an additional .65"
of trim for the Appliance. An attractive cover plate is provided
for a clean, finished appearance on all models.
The Series RSSP Multi-Candela Strobe Plates are a cost
effective way to retrofit required wall strobe appliances to
bells, horns, chimes, multitones or speakers and easily mounts
to standard 4" backboxes or for surface mount use with the
Wheelock SBL2 surface backbox.
® 10 <g> IYIEA APPROVED
S5391 151-92-E 7125-0785:141
7300-0785:154
Features
Approvals include: UL Standard 1971, New York City (MEA),
California State Fire Marshal (CSFM), Factory Mutual (FM), and
Chicago (BFP) See approvals by model in Specifications and
Ordering Information
ADA/NFPA/UFC/ANSI compliant. Meets OSHA 29 Part
19 10.165
Wall mount Multi-Candela models are available with Field
Selectable Candela Settings of 15/30/ 75/1Ood or 135/185cd.
Single Candela models are available in 1575cd
Ceiling mount Multi-Candela models are
available with field selectable candela settings of 15/30175/95cd
or 115/177cd. (Round or Square)
Strobes produce 1 flash per second over the regulated voltage
range
12 and 24 VDC models with wide UL "Regulated Voltage" us-
ing filtered (DC) or unfiltered VRMS input voltage
Synchronize using the Wheelock sync modules or panels with
built-in Wheelock Patented Sync Protocol
Fast installation with IN/OUT screw terminals using #12 to #18
AWG wire
For Weatherproof Series RSS See Datatsheet S9004
NOTE: All CAUTIONS and WARNINGS are identified by the symbol A. All warnings are printed in bold capital letters.
A. WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR
APPLYING THIS PRODUCT. VISIT WWW.COOPERWHEELOCK.COM OR CONTACT COOPER WHEELOCK FOR THE CURRENT INSTALLATION INSTRUCTIONS.
FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR
OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU
AND/OR OTHERS.
General Notes:
Strobes are designed to flash at 1 flash per second minimum over their "Regulated Voltage Range". Note that NFPA-72 specifies a flash rate of 1
to 2 flashes per second and ADA Guidelines specify a flash rate of ito 3 flashes per second.
All candela ratings represent minimum effective Strobe intensity based on UL Standard 1971.
Series NS Strobe products are listed under UL Standard 1971 for indoor use with a temperature range of 32°F to 120°F (0°C to 49°C) and
maximum humidity of 93% (± 2%).
Series NH horns are listed under UL Standard 464 for audible signal appliances (Indoor use only).
"Regulated Voltage Range" is the newest terminology used by UL to identify the voltage range. Prior to this change UL used the
terminology "Listed Voltage Range".
Table 1: Average RMS Current*
RSSIRSSP -Wall Mount Ceiling Mount
RSS/RSSP I 241575W 24VDC
Models
24MCW I 24MCWH 24MCC I 24MCCH
1575cd I 15cd I 30cd I 75cd I hOod I 135cd I 185cd I 15cd I 30Cd I 75cd I 95cd I 115cd I 177cd
UL max* 0.090 0.060 0.092 0.165 10.220 10.300 10.420 10.065 10.105 10.189 10.249 1 0.300 1 0.420
RSS/RSSP
RSS/RSSP Wall Mount 24VDC ____________ * RMS current ratings are per UL average RMS method. UL max current Models 121575W rating is the maximum RMS current within the listed voltage range (16-33v
for 24v units). For strobes the UL max current is usually at the minimum
12 vdc 0.152 listed voltage (16v for 24v units). For audibles the max current is usually at
UL max 0.255 the maximum listed voltage (33v for 24v units). For unfiltered FWR ratings,
see installation instructions.
Table 2: Audibles/Speakers for RSSP Strobe Plate
Product Series
Multitone Appliances AMT, MT
Horns AH, NH, HIS
Motor Bells MB-G6/G10
Speakers ET-1010/1080, E70, E170
Chimes CH70
Wiring Diagrams #
SERIES RSS/RSSP APPLIANCE
FROM TO NEXT
PRECEDING APPLIANCE
APPLIANCE, SYNC OR EOLR MODULE, POWER
SUPPLY OR FACP
SERIES RSS/RSSP APPLIANCES SYNCHRONIZED
WITH DSM MODULE SINGLE CLASS "A" NAC CIRCUIT
DSM STROBE 0 NAC SYNC
- 0 CIRCUIT
OUT 0°OUT1
O+IN1 RSS RSS RSS
0 MINUS I 0+
]ROBE
AUDIBLE
MINUS 2
+ IN 2 RSS SRSS
NAC 0 * OUT 2
CIRCUIT
RETURN
SERIES RSS/RSSP APPLIANCES SYNCHRONIZED
WITH MULTIPLE DSM MODULES
DSM #1
DSM Interconnecting wiring shown. Maximum of
twenty (20)
SERIES RSS/RSSP APPLIANCE SYNCHRONIZED WITH
SM MODULE SINGLE CLASS "B" NAC CIRCUIT
SM
F + STROBE
0 - STROBE Strobe 0 A NAC
C
Circuit
A
0—
diblel
P EOLR -Audible
SERIES RSS/RSSP APPLIANCES SYNCHRONIZED
WITH PS-12124-8CP or PS-12/24-8MP
Series PS-12/24-81VIP
AS RES OUTPUTS EOLR
1 F -4
- 4-CLASS
A "B"
AS OR RSS
C 2-CLASS
"A"
P
AS RSS
Series PS-12124-8MP
STROBE/PLATE ASSEMBLY
AUDIBLE & VISIBLE APPLIANCE OPERATE IN UNISON
TO NEXT
FROM _____ _______ ______
+ APPLIANCE
PRECEDING II t II i - OR EOLR
APPLIANCE, SYNC
MODULE, POWER
SUPPLY OR FACP +
- + -
STROBE AUDIBLE
STROBE/PLATE ASSEMBLY
AUDIBLE & VISIBLE APPLIANCE OPERATE INDEPENDENTLY
FROM + + TO NEXT PRECEDING
APPLIANCE OR APPLIANCE- - OR OUR FACP
FROM + - - - + TO NEXT
PRECEDING STROBE OR
STROBE, SYNC — - - fl i r EOLR - —
MODULE, POWER
SUPPLY OR FACP
STROBE APPLIANCE
For detail using SM or DSM Sync Module refer to Data
Sheet S3000 or Installation Instructions P83123 for SM
and P83177 for DSM. For wiring information on the power
supplies refer PS-24-8MC.
Specifications and Ordering Information
Model Order
Code
Wall
Mount
Ceiling
Mount
Non-
Sync
Strobe
Candela
24
VDC
12
VDC
Color
RED
Color
WHITE Mounting Options***
Square
or
Round
Agency Approvals
-
UL MEA CSFM FM BFP
RSS-24MCW-FR 940 X - X 15/30/75/110 X - X - B,D,E,F,G,H,J,N,O,R,X Square X X X X X
RSS-24MCW-FW 9401 X - X 15/30/75/110 X - - X B,D,E,F,G,H,J,N,O,R,X Square X X X X X
RSS-241575W-FR 7471 X - X 15(75onAxis) X - X - B,D,E,F,G,H,J,N,O,R,X Square X X X X X
RSS-241575W-FW 7788 X - X 15(75onAxis) X - - X B,D,E,F,G,H,J,N,O,R,X Square X X X X X
RSS-121575W-FR 7476 X - X 15(75onAxis) - X X - B,D,E,F,G,H,J,N,O,R,X Square X X X X X
RSS-121575W-FW 7468 X - X 15(75onAxis) - X - X B,D,E,F,G,H,J,N,O,R,X Square X X X X X
RSS-24MCC-FW 3158 - X X 15/30/75/95 X - - X B,D,E,F,G,H,J,N,O,R,X Square X X X X *
RSS-24MCC-FR 3157 - X X 15/30/75/95 X - X - B,D,E,F,G,H,J,N,O,R,X Square X X X X *
RSS-24MCCR-FW 3160 - X X 15/30/75/95 X - - X B,D,E,F,G,H,J,N:o,R,x Round X X X X *
RSS-24MCCH-FW 3461 - X X 115/177 X - - X B,D,E,F,G,H,J,N,O,R,X Square X X X X *
RSS-24MCCHR-FW 3463 - X X 115/177 X - - X B,D,E,F,G,H,J,N,O,R,X Round X X X X *
RSS-24MCWH-FR 3465 X X 135/185 X X B,D,E,F,G,H,J,N,O,R,X Square X X X X *
RSS-24MCWH-FW 3464 X X 135/185 X X B,D,E,F,G,H,J,N,O,R,X Square X X X X *
RSSWP2475WFR** 9013 X - X 180@ 77-F X X X - B,D,E,F,G,H,J,N,O,R,X Square X X X X *
RSSWP2475WFW** 3034 X - X 180@ 77'F X X - X B,D,E,F,G,H,J,N,O,R,X Square X X X X *
RSSP-121575W-FR 7798 X - X 15(75onAxis) - X X - D,E,Z Square X X X X X
RSSP-24MCW-FR 9402 X - X 1 15/30/75/110 X - X - D,E,Z Square X X X X X
RSSP-241575W-FR 7793 X - X 15(75onAxis) - - X - D,E,Z Square X X X X X
*PENDING
All models sync with Wheelock SM, DSM or PS-12/24-8CP or PS-12/24-8MP.
# Models are available in either Red or White. Call Customer Service for Order Code & Delivery.
**For Weatherproof Series RSS Strobe specifications see data sheet S9004.
***Refer to data sheet S7000 for mounting options.
Architects and Engineers Specifications
The visual notification appliances shall be Wheelock Series RSS Strobe Appliances or approved equals. The Series RSS shall meet
and be listed for UL Standard 1971 (Emergency Devices for the Hearing-Impaired) for Indoor Fire Protection Service. The strobe shall
be listed for indoor use and shall meet the requirements of FCC Part 15 Class B. The strobe appliances shall produce a flash rate of
one (1) flash per second over the Regulated Voltage Range and shall incorporate a Xenon flashtube enclosed in a rugged Lexan® lens.
All inputs shall be compatible with standard reverse polarity supervision of circuit wiring by a Fire Alarm Control Panel (FACP). When
Strobe Plates are to be installed, they shall be the Wheelock Series RSSP Strobe Plate and shall have the same electronic circuitry
as the Wheelock Series RSS.
The Series RSS Strobe shall be of low current design. Where Multi-Candela appliances are specified, the strobe intensity shall have
field selectable settings and shall be rated per UL Standard 1971 at 15/30/75/110cd or 135/185cd for wall mount and 15/30/75/95cd or
115/177cd for ceiling mount. The selector switch for selecting the candela shall be tamper resistant. The 1575 candela strobe shall be
specified when 15 candela UL Standard 1971 Listing with 75 candela on axis is required (e.g. ADA compliance).
When synchronization is required, the appliance shall be compatible with Wheelock's SM, DSM Sync Modules, Wheelock Power Supplies
or other manufacturers panels with built-in Wheelock Patented Sync Protocol. The strobes shall not drift out of synchronization at any
time during operation. If the sync module or Power Supply fails to operate, (i.e., contacts remain closed), the strobe shall revert to a
non-synchronized flash rate. The strobes shall be designed for indoor surface of flush mounting.
The Series RSS Strobe Appliances shall incorporate a Patented, Integral Strobe Mounting Plate that shall allow mounting to single-
gang, double-gang, 4-inch square, 1 00m European type backboxes, or the SHBB Surface Backbox. If required, an NATP (Notification
Appliance Trimplate) shall be provided. An attaching cover plate shall be provided to give the Appliance and attractive appearance. The
Appliance shall not have any mounting holes or screw heads visible when the installation is completed.
The Series RSSP Multi-Candela or single candela Strobe Plate shall mount to either a standard 4 inch square backbox for flush mounting,
or the Wheelock SBL2 backbox for surface mounting.
All notification appliances shall be backward compatible.
NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Wheelock, Inc. standard terms and conditions.
LNEWA
1ru
WE ENCOURAGE AND SUPPORT NICET CERTIFICATION
3 YEAR WARRANTY
Made in USA
S0410 RSS/RSSP 02/08
Cooper Notification is Wheelock' IMEDCJ SAFEPATH WAV ?) * COOPER Notification
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
LISTING SERVICE
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM 00
LISTING No. 7125-0785:141 Page 1 of 1
CATEGORY: Fire Alarm Devices for the Hearing Impaired
LISTEE: Wheelock Inc., 273 Branchport Ave., Long Branch NJ 07740
Contact: Deborah Piserchia (732) 433-6001 Fax (732) 222-5607
DESIGN: Synchronized or non-synchronized Strobe Lights. Models are as follows:
RSS-##W RSSP-##W RSS-##C RSSP-##C RSS-##CR RSSP-##CR
2415 2415 2415 2415 2415 2415
2475 2475 2430 2430 2430 2430
241575 241575 2475 2475 2475 2475
2430 2430 *2495 *2495 *2495 *2495
24110 24110
1215 1215
121575 121575
Also, Models RSS-24MCW and RSSP-24MCW, RSS-24MCC, RSS-24MCCR, RSSP-
24MCC, RSS-24MCWH, RSS-24MCWHR, RSSP-24MCWH, RSS-24MCCH, RSS-
24MCCHR, RSSP-24MCCH, *ZRSMCC *ZRSMCW *ZRSMCCH and *ZRSMCWH
Model numbers may be followed by any two alpha/numeric character indicating lens
orientation, lettering and color. Refer to listee's data sheet for additional detailed product
description and operational considerations.
RATING: Electrical 12 = 8-17.5VDC/FWR OR 24 = 16-33VDC/FWR
Candela 15=5cd, 1575=15/75cd on axis, 30=30cd, 75=75cd, 110=110cd (Wall)
RSS-24MCW, RSSP-24MCW, *ZRSMCW: Selectable 15cd, 30cd, 75cd
orll0cd
RSS-24MCC, RSS-24MCCR, RSSP-24MCC, *ZRSMCC: Selectable
15cd, 30cd, 75cd and 95cd
RSS-24MCWH, RSS-24MCWHR, RSSP-24MCWH, *ZRSMCWH:
Selectable 135cd, 185cd
RSS-24MCCH, RSS-24MCCHR, RSSP-24MCCH, *zRS..MccH:
Selectable 115cd, 177cd
Flash rate 60 flashes/minute
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and
ordinances and in a manner acceptable to the authority having jurisdiction. Models with
suffix -W, wall mount only. Models with suffix -C, ceiling mount only. All models are for
indoor use only.
MARKING: Listee's name, model number, electrical/candela rating, and UL label.
APPROVAL: Listed as strobe light suitable for the hearing impaired when used with separately listed
electrically compatible fire alarm control units. For synchronization strobes, Models SM-
12/24, SMX-12/24, DSM-12/24 or DSMX-12/24 Sync Control Module (CSFM Listing No.
7300-0785:132) must be used. Refer to listee's Installation Instruction Manual for details.
*Rev. 12-13-2006 jw
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results
and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or
recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation
criteria. Refer to listee's data sheet, installation instructions and/or other suitable information sources.
Date Issued: JUNE 18, 2009 Listing Expires June 30, 2010
Authorized By: FRANCIS MATEO, Program Coordinator
Fire Engineering Division