4/4/25, 11:24 AM AS 100039 Permit Data
City of Carlsbad
Sprinkler Permit
Permit No: AS100039
Job Address: 5781 VAN ALLEN WY
Permit Type: SPRINK
Parcel No: 2121304400
Lot #: 0
Status: ISSUED
Applied 3/31/2010
Approved: 3/31/2010
Reference No.: Issued: 3/31/2010
PC #: Inspector:
Project Title: LIFE TECHNOLOGY TWO FIRE SPRINKLER INSPECTIONS @
$65/00
Fees ($) Add'IFees($) Total ($)
130
Balance
130 0
about:blank 1/1
HYDRAULIC CALCULATIONS
FOR
Life Technology
5781 Van Allen Way
Carlsbad, CA.
DATE: 3-24-2010
FILE NO: life
-DESIGN DATA-
(Office)
OCCUPANCY CLASSIFICATION: Light Hazard
DENSITY: 0.10 gpm/sq. ft.
AREA OF APPLICATION: 1500 sq. ft.
COVERAGE PER SPRINKLER: 20' x 20'
MINIMUM FLOW PER SPRINKLER: 40 gpm
NUMBER OF SPRINKLERS CALCULATED: 10
TOTAL SPRINKLER WATER FLOW REQUIRED: 407.9 gpm
TOTAL WATER REQUIRED (including hose): 507.9 gpm
FLOW AND PRESSURE (@ BOR) : 507.9 gpm @ 57.6 psi
SPRINKLER ORIFICE SIZE: 3/4"
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2
DATE: 3/24/2010 I:\DATA\LIFE.SDF
JOB TITLE: Life Technology
WATER SUPPLY DATA
SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D
NODE PRESS. PRESS. @ PRESS. @ DEMAND PRESS.
TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI)
BOR 90.0 89.0 1989.0 89.9 507.9 57.6
AGGREGATE FLOW ANALYSIS:
TOTAL FLOW AT SOURCE 507.9 GPM
TOTAL HOSE STREAM ALLOWANCE AT SOURCE 100.0 GPM
OTHER HOSE STREAM ALLOWANCES 0.0 GPM
TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 407.9 GPM
NODE ANALYSIS DATA
NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE
(FT) (PSI) (GPM)
1 35.0 - - - - 35.8 - - -
2 36.0 - - - - 34.7 - - -
3 36.0 K= 7.35 31.6 41.3
4 36.0 K= 7.35 31.3 41.1
5 36.0 K= 7.35 31.3 41.1
6 36.0 - - - - 32.9 - - -
7 35.0 - -
- -
33.6
8 35.0 - -
- - 35.8
9 36.0 - - - - 34.5 - - -
10 36.0 K= 7.35 30.1 40.3
11 36.0 K= 7.35 29.6 40.0
12 36.0 K= 7.35 29.6 40.0
12A 36.0 K= 7.35 29.8 40.1
13 36.0 - - - - 32.6 - - -
14 35.0 - - - - 33.6 - - -
15 35.0 - - - - 35.9 - - -
16 36.0 - - - - 34.8 - - -
17 36.0 K= 7.35 31.7 41.4
18 36.0 K= 7.35 31.4 41.2
19 36.0 K= 7.35 31.5 41.2
20 36.0 - - - - 32.9 - - -
21 35.0 - - - - 33.6 - - -
22 35.0 - - - - 36.0 - - -
23 36.0 - - - - 35.4 - - -
24 36.0 - - - - 33.3 - - -
25 35.0 - - - - 33.7 - - -
26 35.0 - - - - 36.2 - - -
27 36.0 - - - - 34.8 - - -
28 36.0 - - - - 34.3 - - -
29 35.0 - - - - 33.8 - - -
30 35.0 - - - - 36.5 - - -
31 36.0 - - - - 35.9 - - -
32 36.0 - - - - 33.5 - - -
33 35.0 - - - - 33.8 - - -
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3
DATE: 3/24/2010 I:\DATA\LIFE.SDF
JOB TITLE: Life Technology
NODE ANALYSIS DATA
NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE
(FT) (PSI) (GPM)
A 35.0 - - - - 41.2 - - -
TOR 35.0 - - - - 42.0
BOR 0.0 SOURCE 57.6 407.9
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4
DATE: 3/24/2010 I:\DATA\LIFE.SDF
JOB TITLE: Life Technology
PIPE DATA
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (PT) SUM.
NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe: 1 78.3 2.067 PL 1.00 PF 0.7
1 35.0 0.0 35.8 0.0 7.5 120 FTG T RE -0.4
2 36.0 0.0 34.7 0.0 0.060 TL 11.00 PV
Pipe: 2 78.3 2.067 PL 41.00 PF 3.0
2 36.0 0.0 34.7 0.0 7.5 120 FTG T FE 0.0
3 36.0 7.3 31.6 41.3 0.060 TL 51.00 PV
Pipe: 3 37.0 2.067 PL 20.00 PF 0.3
3 36.0 7.3 31.6 41.3 3.5 120 FTG ---- PE 0.0
4 36.0 7.3 31.3 41.1 0.015 TL 20.00 PV
Pipe: 4 -4.2 2.067 FL 20.00 PF 0.0
4 36.0 7.3 31.3 41.1 0.4 120 FTG ---- PE 0.0
5 36.0 7.3 31.3 41.1 0.000 TL 20.00 PV
Pipe: 5 -45.3 2.067 PL 63.00 PP 1.6
5 36.0 7.3 31.3 41.1 4.3 120 FTG T PE 0.0
6 36.0 0.0 32.9 0.0 0.022 TL 73.00 PV
Pipe: 6 -45.3 2.067 PL 1.00 PF 0.2
6 36.0 0.0 32.9 0.0 4.3 120 FTG T PE 0.4
7 35.0 0.0 33.6 0.0 0.022 TL 11.00 PV
Pipe: 7 78.3 4.260 FL 10.50 PF 0.0
8 35.0 0.0 35.8 0.0 1.8 120 FTG ---- FE 0.0
1 35.0 0.0 35.8 0.0 0.002 TL 10.50 PV
Pipe: 8 87.3 2.067 PL 1.00 PF 0.8
8 35.0 0.0 35.8 0.0 8.3 120 FTG T FE -0.4
9 36.0 0.0 34.5 0.0 0.073 TL 11.00 PV
Pipe: 9 87.3 2.067 FL 51.00 PF 4.5
9 36.0 0.0 34.5 0.0 8.3 120 FTG T PE 0.0
10 36.0 7.3 30.1 40.3 0.073 TL 61.00 PV
Pipe: 10 47.0 2.067 FL 20.00 PF 0.5
10 36.0 7.3 30.1 40.3 4.5 120 FTG ---- FE 0.0
11 36.0 7.3 29.6 40.0 0.023 TL 20.00 PV
Pipe: 11 6.9 2.067 FL 11.00 PP 0.0
11 36.0 7.3 29.6 40.0 0.7 120 FTG ---- FE 0.0
12 36.0 7.3 29.6 40.0 0.001 TL 11.00 PV
Pipe: hA -33.1 2.067 FL 14.00 PF 0.2
12 36.0 7.3 29.6 40.0 3.2 120 FTG ---- FE 0.0
12A 36.0 7.3 29.8 40.1 0.012 TL 14.00 PV
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5
DATE: 3/24/2010 I:\DATA\LIFE.SDF
JOB TITLE: Life Technology
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM.
NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe: 12 -73.2 2.067 PL 43.00 PF 2.8
12A 36.0 7.3 29.8 40.1 7.0 120 FTG T FE 0.0
13 36.0 0.0 32.6 0.0 0.053 TL 53.00 PV
Pipe: 13 -73.2 2.067 PL 1.00 PF 0.6
13 36.0 0.0 32.6 0.0 7.0 120 FTG T PE 0.4
14 35.0 0.0 33.6 0.0 0.053 TL 11.00 PV
Pipe: 14 45.3 4.260 FL 10.50 PF 0.0
14 35.0 0.0 33.6 0.0 1.0 120 FTG ---- FE 0.0
7 35.0 0.0 33.6 0.0 0.001 TL 10.50 PV
Pipe: 15 165.6 4.260 FL 10.50 PF 0.1
15 35.0 0.0 35.9 0.0 3.7 120 FTG ---- PE 0.0
8 35.0 0.0 35.8 0.0 0.007 TL 10.50 PV
Pipe: 16 72.8 2.067 PL 1.00 PF 0.6
15 35.0 0.0 35.9 0.0 7.0 120 FTG T PE -0.4
16 36.0 0.0 34.8 0.0 0.052 TL 11.00 PV
Pipe: 17 72.8 2.067 PL 51.00 PF 3.2
16 36.0 0.0 34.8 0.0 7.0 120 FTG T PE 0.0
17 36.0 7.3 31.7 41.4 0.052 TL 61.00 PV
Pipe: 18 31.5 2.067 FL 20.00 PF 0.2
17 36.0 7.3 31.7 41.4 3.0 120 FTG ---- PE 0.0
18 36.0 7.3 31.4 41.2 0.011 TL 20.00 PV
Pipe: 19 -9.8 2.067 PL 25.00 PF 0.0
18 36.0 7.3 31.4 41.2 0.9 120 FTG ---- FE 0.0
19 36.0 7.3 31.5 41.2 0.001 TL 25.00 PV
Pipe: 20 -51.0 2.067 PL 43.00 PF 1.4
19 36.0 7.3 31.5 41.2 4.9 120 FTG T PE 0.0
20 36.0 0.0 32.9 0.0 0.027 TL 53.00 PV
Pipe: 21 -51.0 2.067 FL 1.00 PF 0.3
20 36.0 0.0 32.9 0.0 4.9 120 FTG T PE 0.4
21 35.0 0.0 33.6 0.0 0.027 TL 11.00 PV
Pipe: 22 118.5 4.260 PL 10.50 PF 0.0
21 35.0 0.0 33.6 0.0 2.7 120 FTG ---- FE 0.0
14 35.0 0.0 33.6 0.0 0.004 TL 10.50 PV
Pipe: 23 238.4 4.260 FL 10.50 PF 0.1
22 35.0 0.0 36.0 0.0 5.4 120 FTG ---- FE 0.0
15 35.0 0.0 35.9 0.0 0.014 TL 10.50 FV
Pipe: 24 35.2 2.067 FL 1.00 PP 0.1
22 35.0 0.0 36.0 0.0 3.4 120 FTG T FE -0.4
23 36.0 0.0 35.4 0.0 0.014 TL 11.00 PV
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 6
DATE: 3/24/2010 I:\DATA\LIFE.SDF
JOB TITLE: Life Technology
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM.
NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe: 25 35.2 2.067 PL 136.00 PF 2.1
23 36.0 0.0 35.4 0.0 3.4 120 FTG 2T PE 0.0
24 36.0 0.0 33.3 0.0 0.014 TL 156.00 PV
Pipe: 26 35.2 2.067 PL 1.00 PF 0.0
24 36.0 0.0 33.3 0.0 3.4 120 FTG ---- PE 0.4
25 35.0 0.0 33.7 0.0 0.014 TL 1.00 PV
Pipe: 27 169.5 4.260 PL 10.50 PF 0.1
25 35.0 0.0 33.7 0.0 3.8 120 FTG ---- PE 0.0
21 35.0 0.0 33.6 0.0 0.007 TL 10.50 PV
Pipe: 28 273.6 4.260 PL 10.50 PF 0.2
26 35.0 0.0 36.2 0.0 6.2 120 FTG ---- PE 0.0
22 35.0 0.0 36.0 0.0 0.018 TL 10.50 PV
Pipe: 29 96.6 2.067 PL 1.00 PF 1.0
26 35.0 0.0 36.2 0.0 9.2 120 FTG T PE -0.4
27 36.0 0.0 34.8 0.0 0.088 TL 11.00 PV
0''
Pipe: 30 96.6 360 PL 136.00 PF 0.5
27 36.0 0.0 34.8 0.0 2.2 120 FTG 2T PE 0.0
28 36.0 0.0 34.3 0.0 0.003 TL 188.00 PV
Pipe: 31 96.6 2.067 PL 1.00 PF 1.0
28 36.0 0.0 34.3 0.0 9.2 120 FTG T PE 0.4
29 35.0 0.0 33.8 0.0 0.088 TL 11.00 PV
Pipe: 32 134.2 4.260 PL 10.50 PF 0.1
29 35.0 0.0 33.8 0.0 3.0 120 FTG ---- PE 0.0
25 35.0 0.0 33.7 0.0 0.005 TL 10.50 PV
Pipe: 33 370.2 4.260 PL 10.50 PF 0.3
30 35.0 0.0 36.5 0.0 8.3 120 FTG ---- PE 0.0
26 35.0 0.0 36.2 0.0 0.031 TL 10.50 PV
Pipe: 34 37.7 2.067 PL 1.00 PF 0.2
30 35.0 0.0 36.5 0.0 3.6 120 FTG T PE -0.4
31 36.0 0.0 35.9 0.0 0.015 TL 11.00 PV
Pipe: 35 37.7 2.067 PL 136.00 PF 2.4
31 36.0 0.0 35.9 0.0 3.6 120 FTG 2T PE 0.0
32 36.0 0.0 33.5 0.0 0.015 TL 156.00 PV
Pipe: 36 37.7 2.067 PL 1.00 PF 0.2
32 36.0 0.0 33.5 0.0 3.6 120 FTG T PE 0.4
33 35.0 0.0 33.8 0.0 0.015 TL 11.00 PV
Pipe: 37 37.7 4.260 PL 10.50 PF 0.0
33 35.0 0.0 33.8 0.0 0.8 120 FTG ---- PE 0.0
29 35.0 0.0 33.8 0.0 0.000 TL 10.50 PV
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 7
DATE: 3/24/2010 I:\DATA\LIFE.SDF
JOB TITLE: Life Technology
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (PT) SUM.
NODES (PT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe: 38 -407.8 4.260 PL 126.00 PF 4.7
30 35.0 0.0 36.5 0.0 9.2 120 FTG ---- RE 0.0
A 35.0 0.0 41.2 0.0 0.037 TL 126.00 PV
Pipe: 39 -407.8 6.357 PL 110.00 PF 0.8
A 35.0 0.0 41.2 0.0 4.1 120 FTG 2E PE 0.0
TOR 35.0 0.0 42.0 0.0 0.005 TL 146.00 PV
Pipe: 40 -407.9 6.357 PL 35.00 PF 0.4
TOR 35.0 0.0 42.0 0.0 4.1 120 FTG BA PE 15.2
BOR 0.0 SRCE 57.6 (N/A) 0.005 TL 83.00 PV
NOTES (HASS)
Calculations were performed by the HASS 8.0 computer program
under license no. 38021611 granted by
HRS Systems, Inc.
208 South Public Square
Petersburg, TN 37144
The system has been calculated to provide an average
imbalance at each node of 0.004 gpm and a maximum
imbalance at any node of 0.155 gpm.
Total pressure at each node is used in balancing the system.
Maximum water velocity is 9.2 ft/sec at pipe 29.
PIPE FITTINGS TABLE
Pipe Table Name: STANDARD.PIP
PAGE: A MATERIAL: S40 HWC: 120
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D N
Eli Tee LngEll ChkVlv BfyVlv GatVlv AlmChk DPVlv NPTee
2.067 5.00 10.00 3.00 11.00 6.00 1.00 10.00 10.00 10.00
PAGE: B MATERIAL: THNWL HWC: 120
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D N
Ell Tee LngEll ChkViv BfyVlv GatVlv AlmChk DPVlv NPTee
4.260 13.00 26.00 8.00 29.00 16.00 3.00 26.00 26.00 26.00
6.357 18.00 38.00 11.00 40.00 13.00 4.00 35.00 35.00 38.00
100. 0
A
U
G
E
60.0
R
E
S
S
U
R E 40.0
p
S
i
20.0
WATER SUPPLY ANALYSIS
Static: 90.00 psi Resid: 89.00 psi Flow: 1989.0 gpm
H
400 600 800 1000 1200 1400 1600 1800 2000
FLOW (GPM)
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 9
DATE: 3/24/2010 I:\DATA\LIFE.SDF
JOB TITLE: Life Technology
SPRINKLER SYSTEM DIAGRAM WITH FLOWPLOT
2 3 4 5 6
ijurc 401.9
7
<14>
45.3
14
<22>
118.5
21
<39>
407.8
1
2
3
12
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 11
DATE: 3/24/2010 I:\DATA\LIFE.SDF
JOB TITLE: Life Technology
Utility Report:
Equivalent K-Factor Calculator
Node Sprinkler Pres. Dia. Pipe Ftgs. Total H-W Equivalent
Name K-Factor (psi) (in) Len. (ft) Len. (ft) coef. K-factor -----------------------------------------------------------------------
eqk 11.20 12.80 1.049 22.00 2T2E 36.00 120.00 7.35
tqcu Fire & Building
liProducts
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
Customer Service/Sales:
Tel: (414) 570-5000 /(800) 558-5236
Fax: (414) 570-5010 / (800) 877-1295
Series EC-1 I & EC-14 - 112 and 14.0 K-factor
Extended Coverage (Light and Ordinary Hazard)
Upright, Pendent, and Rec. Pendent Sprinklers
General
Description
The Series EC-11 and EC-14 Ex-
tended Coverage Upright and Pendent
Sprinklers are decorative glass bulb
sprinklers designed for use in light or
ordinary hazard occupancies. They
are intended for use in automatic
sprinkler systems designed in accord-
ance with standard installation rules
(e.g., NFPA 13) for a maximum cover-
age area of 400 ft2 (37,2 m2), as com-
pared to the maximum coverage area
of 130 ft2 (12,1 m2) for standard cover-
age sprinklers used in ordinary haz-
ard occupancies or 225 ft2 (20,6 m2)
for standard coverage sprinklers used
in light hazard occupancies.
The Series EC-11 and EC-14 Sprin-
klers feature a UL and C-UL Listing
that permits their use with unob-
structed or non-combustible ob-
structed ceiling construction as de-
fined and permitted by NFPA 13, as
well as a specific application listing for
use under concrete tees.
The Series EC-11 and EC-14 Ex-
tended Coverage Sprinklers have
been fire tested to compare their per-
formance to that of standard coverage
spray sprinklers. These tests have
shown that the protection provided is
equal to or more effective than stand-
ard coverage spray sprinklers.
IMPORTANT
Always refer to Technical Data
Sheet TFP 700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 8
Corrosion resistant coatings, where
applicable, are utilized to extend the
life of copper alloy sprinklers beyond
that which would otherwise be ob-
tained when exposed to corrosive at-
mospheres. Although corrosion resis-
tant coated sprinklers have passed the
standard corrosion tests of the appli-
cable approval agencies, the testing is
not representative of all possible cor-
rosive atmospheres. Consequently, it
is recommended that the end user be
consulted with respect to the suitability
of these corrosion resistant coatings
for any given corrosive environment.
The effects of ambient temperature,
concentration of chemicals, and
gas/chemical velocity, should be con-
sidered, as a minimum, along with the
corrosive nature of the chemical to
which the sprinklers will be exposed.
WARNINGS
The Series EC-11 and EC-14 Ex-
tended Coverage Sprinklers described
herein must be installed and main-
tained in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association, in addition to the
standards of any other authorities hav-
ing jurisdiction. Failure to do so may
impair the performance of these de-
vices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
SEPTEMBER, 2004
Model/Sprinkler
Identification
Number
TY5137 - Upright, 112K
TY5237 - Pendent, 11.2K
1Y6137 - Upright, 14.0K
TY6237 - Pendent,14.OK
TY5137 is a redesignation for C5137,
G1894, and S2510.
TY5237 is a redesignation for C5237,
G1893, and S2511.
TY6137 is a redesignation for C6137,
G1896, and S2610.
TY6237 is a redesignation for C6237,
G1895, and S2611.
TFP22O
ESCUTCHEON PLATE
SEATING SURFACE
!/
1-11/16"
(42,7 mm
3/40 **
NPT
6"
irn)
-IT &
ENT
WRENCH
FLAT
Page 2 of 8 TFP22O
1 - Frame
2 - Button
3 - Sealing Assembly
4 - Bulb
5 - Compression Screw
6- Deflector*
Temperature rating is
indicated on deflector
** Pipe thread
connections per ISO
7/1 can be provided
on special request.
2
3
4
5
6*
1/2(12,7mIT) 1
NOMINAL MAKE-IN
UPRIGHT PENDENT
FIGURE 1
SERIES EC-1 1 AND EC-14 EXTENDED COVERAGE SPRINKLERS
11.2 K-FACTOR (TY5137) UPRIGHT AND (TY5237) PENDENT
14.0 K-FACTOR (TY6137) UPRIGHT AND (TY6237) PENDENT
CROSS
SECTION
SPRINKLER FINISH (See Note 5)
HAZARD TYPE TEMP. BULB NATURAL I CHROME I WHITE LEAD
LIQUID BRASS PLATED IPOLYESTER COATED
135°F/57"C Orange
LIGHT
UPRIGHT
K=11.2 (TY5137)
1,2,3"",4 155°F/68°C Red
175°F/79°C Yellow PENDENT
Refer to Table B for
K=11.2 (TY5237)
K14.0 (TY6237)
1,2,4 1,2,4 200°F/93°C Green
286°F/141°C Blue UL and C-UL
135"F/57°C Orange Sensitivity Rating
and
Refer to Table C for
FM
REC. PENDENT
K=1 1.2 (TY5237)
K=14.0 (TY6237)
1, 2, 3, 4
N/A
155°F/66"C Red
175°F/79°C Yellow
Sensitivity Rating With Style 30
Escutcheon
1, 2, 4 200"F/93"C Green
286°F/141"C Blue
UPRIGHT 135°F/57°C Orange
ORDINARY
K=11.2(TY5137)
K=14.0(TY6137)
and
1,2,3,4
1,2,3,4 155°F/68°C Red
175"F/79"C Yellow
Refer to Table B for
UL and C-UL
PENDENT
K11.2 (TY5237)
1, 2, 4 2000F/93°C Green
286"F/141"C Blue Sensitivity Rating K14.0 (TY6237)
REC. PENDENT 135°F/57"C Orange and
Refer to Table C for
FM
Sensitivity Rating
K=1 1.2 (TY5237)
K=14.0 (TY6237)
With Style 40 1, 2, 4 N/A
155°F/68°C Red
175°F/79°C Yellow
Escutcheon 200°F/93°C Green
NOTES:
11isted by Underwriters Laboratories, Inc. (UL).
21isted by Underwriters Laboratories, Inc. for use in Canada (C-UL).
Approved by Factory Mutual Research Corporation (FM).
Approved by the City of New York under MEA 177-03-E.
Where Polyester Coated or Lead Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as
Corrosion Resistant Sprinklers.
*Frame and Deflector only. Listings and approvals apply to color (Special Order).
Pendent Only.
N/A: Not Available
TABLE A, LABORATORY LISTINGS AND APPROVALS
TFP220 Page 3 of 8
LIGHT HAZARD
135°F 155°F 175°F 200°F 286°F
ORDINARY HAZARD
135°F 155°F 175°F 200°F 286°F
AREA STYLE
14 x 14 Up. or Pend. - - - - - SR SR SR SR
14 x 14 Style 30 Recessed - - - - - SR SR SR SR
14 x 14 Style 40 Recessed - - - - - SR SR SR SR
16x16 Up. orPend. QR* QR QR* QR* QR* SR SR SR SR
16x16 Style 30 Recessed QR* QR* QR- QR* QR* SR SR SR SR
16 x 16 Style 40 Recessed N/A N/A N/A N/A N/A SR SR SR SR
18x18 Up. orPend. QR* OR* QR' QR* QR* SR SR SR SR
18x18 Style 30 Recessed QR* QR* QR* QR* QR* SR SR SR SR
18 x 18 Style 40 Recessed N/A N/A N/A N/A N/A SR SR SR SR
20x20 Up. orPend. QR* QR* QR* SR* SR* SR SR SR SR
20 x 20 Style 30 Recessed QR* SR* QR* SR* SR* SR SR SR SR
20 x 20 Style 40 Recessed N/A N/A N/A N/A N/A SR SR SR SR
OR: Quick Response
SR: Standard Response
N/A: Not Applicable
* Does not apply to Upright K 14.0
TABLE B
SENSITIVITY RATING FOR UL AND C-UL LISTING OF SERIES EC-Il OR EC-14 SPRINKLERS
-
(SEE TABLED FOR PERMITTED K-FACTOR/AREA COMBINATIONS)
LIGHT HAZARD ORDINARY HAZARD
135°F 155°F 175°F 200°F 286°F 135°F 155°F 175°F 200°F 286°F
AREA STYLE
14 x 14 Up. or Pend. - - - - - SR SR SR SR SR
14 x 14 Style 30 Recessed - - - - - N/A N/A N/A N/A N/A
14 x 14 Style 40 Recessed - - - - - N/A N/A N/A N/A N/A
16x16 Up. orPend. QR* QR* N/A N/A N/A SR SR SR SR SR
16x16 Style 30 Recessed OR OR N/A N/A N/A N/A N/A N/A N/A N/A
16 x 16 Style 40 Recessed N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
18 x 18 Up. or Pend. OR* QR* N/A N/A - N/A SR SR SR SR SR
18x18 Style 30 Recessed OR OR N/A N/A N/A N/A N/A N/A N/A N/A
18x18 Style 40 Recessed N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
20x20 Up. orPend. OR* OR* N/A N/A N/A SR SR SR SR SR
20 x 20 Style 30 Recessed OR OR N/A N/A N/A N/A N/A N/A N/A N/A
20 x 20 Style 40 Recessed N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
OR: Quick Response
SR: Standard Response
N/A: Not Applicable
* Pendent Only
TABLE C
SENSITIVITY RATING FOR FM APPROVAL OF SERIES EC-1 1 OR EC-14 SPRINKLERS
(SEE FM LOSS PREVENTION DATA SHEET 2-8N FOR PERMITTED K-FACTOR/AREA COMBINATIONS)
SR
N/A
N/A
SR
N/A
N/A
SR
N/A
N/A
SR
N/A
N/A
Page 4 of 8 TFP220
Technical
Data
Approvals
UL and C-UL Listed. FM Approved.
(Refer to Table A for complete approval
information including corrosion resis-
tant status. The approvals apply to the
service conditions indicated in the De-
sign Criteria section.)
Maximum Working Pressure
175 psi (12,1 bar)
Discharge Coefficients
K = 11.2 GPM/psi112
(161,3 LPM/bar1l2)
K = 14.0 GPM/psi112
(201,6 LPM/bar112)
Temperature Ratings
135°F/57°C to 286°F/141°C
Finish
Sprinkler: Refer to Table A
Recessed Escutcheon: White Coated,
Chrome Plated, and Brass Plated
Physical Characteristics
Frame .............Bronze
Button .............Bronze
Sealing Assembly ..........
Beryllium Nickel w/Teflonf
Bulb ........Glass (3 mm dia.)
Compression Screw .........
.........Bronze
Deflector .............Brass
Patents
U.S.A. Patent Numbers 5,366,022;
5,579,846; 5,584,344; 5,609,211;
5,862,994; and 5,865,256.
Operation
The glass bulb contains a fluid which
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass bulb, which then allows the sprin-
kler to activate and flow water.
Design
Criteria
The Series EC-11 and EC-14 Ex-
tended Coverage Sprinklers must only
be installed in accordance with the ap-
plicable UL and C-UL Listing or FM
Approval requirements as indicated
below. Only the Style 30 or 40 Re-
cessed Escutcheon is to be used for
recessed installation, as applicable
(Ref. Table A, B, and C).
The Series EC-il and EC-14Sprin-
kiers may be used for the coverage
areas shown in Table D, based on
maintaining the minimum specified
flow rate as a function of coverage
area and hazard group for all of the
sprinklers in the design area.
The Series EC-1 1 and EC-14 Sprin-
klers are permitted to be used with
unobstructed or non-combustible
obstructed ceiling construction as
defined and permitted by NFPA 13.
For example:
Unobstructed, combustible or non--
combustible, ceiling construction
with a deflector to ceiling/roof deck
distance of 1 to 12 inches (25 to 300
mm).
Obstructed, non-combustible, ceil-
ing construction with a deflector lo-
cation below structural members of
1 to 6 inches (25 to 150 mm) and a
maximum deflector to ceiling/roof
deck distance of 22 inches (550
mm).
The Series EC-1 1 and EC-14 Sprin-
klers having been specifically tested
and listed for non-combustible ob-
structed construction are permitted
to be used within trusses or bar joists
having non-combustible web mem-
bers greater than 1 inch (25.4 mm)
when applying the 4 times obstruc-
tion criteria rule defined under "Ob-
structions to Sprinkler Discharge
Pattern Development".
The minimum allowable spacing be-
tween the Series EC-li and EC-14
Sprinklers, to prevent cold solder-
ing, is 8 feet (2,4 m) for upright sprin-
klers and 9 feet (2,7 m) for pendent
sprinklers.
The Series EC-1 1 and EC-14 Sprin-
klers are to be installed in accord-
ance with all other requirements of
NFPA 13 for extended coverage up-
right and pendent sprinklers. For ex-
ample: obstructions to sprinkler dis-
charge, obstructions to sprinkler
pattern development, obstructions
to prevent sprinkler discharge from
reaching hazard, clearance to stor-
age, etc.
UL and C-UL Specific Application
Listing Requirements For
Installation Under Concrete Tees
The Series EC-11 and EC-14 Ex-
tended Coverage Upright and Pendent
Sprinklers (TY5 137, TY5237, TY61 37
& TY6237) have a UL and C-UL Spe-
cific Application Listing for use under
concrete tees when installed as fol-
lows:
The stems of the concrete tee con-
struction must spaced at less than
7.5 feet (2,3 m) on center but more
than 3 feet (0,9 m) on center. The
depth of the concrete tees must not
exceed 30 inches (762 mm). The
maximum permitted concrete tee
length is 32 feet (9,8 m); however,
where the concrete tee length ex-
ceeds 32 feet (9,8 m), non-combus-
tible baffles, equal in height to the
depth of the tees, can be installed so
that the space between the tees
does not exceed 32 feet (9,8 m) in
length.
The sprinkler deflectors are to be
located in a horizontal plane at or
above 1 inch (25,4 mm) below the
bottom of the concrete tee stems.
When the sprinkler deflectors are
located higher than a horizontal
plane 1 inch (251,4mm) beneath the
bottom of the concrete tee stems,
the obstruction to sprinkler dis-
charge criteria requirements of
NFPA 13 for extended coverage up-
right sprinklers applies.
FM Approval
Requirements
The Series EC-11 and EC-14 Ex-
tended Coverage Sprinklers are to be
installed in accordance with the appli-
cable Factory Mutuai Loss Prevention
Data Sheet for limited use in buildings
of specific roof construction and for the
protection of certain specific ordinary
hazard (non-storage and/or non-flam-
mable or combustible liquid) occupan-
cies. Information provided in the FM
Loss Prevention Data Sheets relate to,
but are not limited to, hydraulic design,
ceiling slope and obstructions, mini-
mum and maximum allowable spac-
ing, and deflector-to ceiling distance.
These criteria may differ from UL
and/or NFPA criteria, therefore the de-
signer should review and become fa-
miliar with Factory Mutual require-
ments before proceeding with design.
Pipe Thread Connection UL and C-UL Listing
3/4 inch NPT Requirements
TFP22O
2-7/8 DIA.
1/2±1/8 (73,0 mm) 1/2° (12,7 mm)
(12,7±3,2 mm) 2-1/4" DIA. 1/4' (6,4 mm)
FACE OF I (57,2 mm)
SPRINKLER I
4MOUNTING
1/8'
FITTING I (3,2 mm)
MOUNTING / SURFACE //
CLOSURE
PLATE
-
1-3/8' (34,9 mm)
1-1/8° (28,6 mm)
FIGURE 2
SERIES EC-1 1 AND EC-14 RECESSED PENDENT SPRINKLER ASSEMBLY
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 30 RECESSED ESCUTCHEON
Page 5 of 8
"FITTING SIDE"
TOWARDS SPRINKLER
FITTING
/\
WRENCH
/
(
RECESS
END "A")
FIGURE 4
W-TYPE 3 SPRINKLER
WRENCH
WRENCH
RECESS
WRENCH
HEX
FIGURE 5
W- TYPE 22 RECESSED
SPRINKLER WRENCH
2-7/8' DIA.
5/8±1/4" (73,0 mm) 3/4" (19,1 mm
(15,9±6,4 mm) 2-1/4' DIA. 1/4' (6,4 mm)
FACE OF (57,2 mm) I
SPRINKLER 1/8"
FITTING (3,2 mm)
MOUNTING MOUNTING t
SURFACE PLATE
rm
CLOSURE
1-3/8" (34,9 mm)
7/8' (22,2 mm)
FIGURE 3
SERIES EC-1 1 AND EC-14 RECESSED PENDENT SPRINKLER ASSEMBLY
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 40 RECESSED ESCUTCHEON
Page 6 of 8 TFP220
GROUPI GROUPII
LIGHT HAZARD ORDINARY HAZARD ORDINARY HAZARD
0.10 GPM/FT2 0.15 GPM/FT2 0.20 GPM/FT2
DESCRIPTION AREA GPM PSI GPM PSI GPM PSI
TY5137 (K=11.2) UPRIGHT 14 x 14 - - 30 7.2 39 12.1
16x16 30 7.2 39 12.1 51 20.7
18x18 33 8.7 49 19.1 65 33.7
20x20 40 12.8 60 28.7 80 51.0
TY5237 (K=1 1.2) PENDENT 14 x 14 - - 30 7.2 39 12.1
16x16 30 7.2 39 12.1 51 20.7
18x18 33 8.7 49 19.1 65 33.7
20 x 20 40 12.8 60 28.7 80 51.0
TV6137(K=14.0)UPRIGHT 14x14 N/A N/A - - - -
16x16 N/A N/A 39 7.8 51 13.3
18x18 N/A N/A 49 12.3 65 21.6
20 x 20 N/A N/A 60 18.4 80 32.7
TY6237 (K=14.0) PENDENT 14 x 14 - - - - -
16 x 16 37 7.0 39 7.8 51 13.3
18x18 37 7.0 49 12.3 65 21.6
20 x 20 40 8.2 60 18.4 80 32.7 1 ft. = 0.3048 m
1 It2 = 0.093 m2
1 gpm = 3.785 1pm
1 psi = 0.06895 bar
1 gpm/f12 = 40.74 mm/mm
TABLED
FLOW CRITERIA FOR UL AND C-UL LISTING OF SERIES EC-1 1 AND EC-14 SPRINKLERS
Step 1. The sprinkler must be installed Installation with the deflector parallel to the mount-
The Series EC-11 and EC-14 Sprin-
klers must be installed in accordance
with the following instructions:
NOTES
Do not install any bulb type sprinkler if
the bulb is cracked or there is a loss of
liquid from the bulb. With the sprinkler
held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 inch
(1,6 mm) for the 135°F/57°C to 3/32
inch (2,4 mm) for the 286°F/1411C
temperature ratings.
A leak tight 3/4 inch NPT sprinkler joint
should be obtained with a torque of 10
to 20 ft.lbs. (13,4 to 26,8 Nm). A maxi-
mum of 30 ft.lbs. (40.7 Nm) of torque
is to be used to install sprinklers.
Higher levels of torque may distort the
sprinkler inlet with consequent leak-
age or impairment of the sprinkler.
Do not attempt to compensate for in-
sufficient adjustment in an Escutcheon
Plate by under- or over-tightening the
Sprinkler. Readjust the position of the
sprinkler fitting to suit.
ing surface. Pendent sprinklers must
be installed in the pendent position,
and upright sprinklers must be in-
stalled in the upright position.
Step 2. After installing the Style 30 or
40 mounting plate (or other escutch-
eon, as applicable) over the sprinkler
pipe threads and with pipe thread
sealant applied to the pipe threads,
hand tighten the sprinkler into the
sprinkler fitting.
Step 3. Wrench tighten upright or pen-
dent sprinklers using only the W-Type
3 (End A) Sprinkler Wrench. Wrench
tighten the recessed pendent sprin-
klers using only the W-Type 22 Sprin-
kler Wrench. The wrench recess of the
applicable sprinkler wrench (Ref. Fig-
ure 4 and 5) is to be applied to the
sprinkler wrench flats (Ref. Figure 1).
TFP22O Page 7 of 8
Care and
Maintenance
The Series EC-11 and EC-14 Sprin-
klers must be maintained and serviced
in accordance with the following in-
structions:
NOTE
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, permission to shut down the
affected fire protection systems must
be obtained from the proper authori-
ties and all personnel who may be
affected by this action must be notified.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or otherwise
altered after leaving the factory. Modi-
fied sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid dam-
age to the sprinklers - before, during,
and after installation. Sprinklers dam-
aged by dropping, striking, wrench
twist/slippage, or the like, must be re-
placed. Also, replace any sprinkler that
has a cracked bulb or that has lost
liquid from its bulb. (Ref. Installation
Section).
Frequent visual inspections are rec-
ommended to be initially performed for
corrosion resistant coated sprinklers,
after the installation has been com-
pleted, to verify the integrity of the cor-
rosion resistant coating. Thereafter,
annual inspections per NFPA 25
should suffice; however, instead of in-
specting from the floor level, a random
sampling of close-up visual inspec-
tions should be made, so as to better
determine the exact sprinkler condi-
tion and the long term integrity of the
corrosion resistant coating, as it may
be affected by the corrosive conditions
present.
The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. The in-
stalling contractor or sprinkler manu-
facturer should be contacted relative to
any questions.
It is recommended that automatic
sprinkler systems be inspected,
tested, and maintained by a qualified
Inspection Service in accordance with
local requirements and/or national
codes.
Limited
Warranty
Products manufactured by Tyco Fire
Products are warranted solely to the
original Buyer for ten (10) years
against defects in material and work-
manship when paid for and properly
installed and maintained under normal
use and service. This warranty will ex-
pire ten (10) years from date of ship-
ment by Tyco Fire Products. No war-
ranty is given for products or
components manufactured by compa-
nies not affiliated by ownership with
Tyco Fire Products or for products and
components which have been subject
to misuse, improper installation, corro-
sion, or which have not been installed,
maintained, modified or repaired in ac-
cordance with applicable Standards of
the National Fire Protection Associa-
tion, and/or the standards of any other
Authorities Having Jurisdiction. Mate-
rials found by Tyco Fire Products to be
defective shall be either repaired or
replaced, at Tyco Fre Products' sole
option. Tyco Fire Products neither as-
sumes, nor authorizes any person to
assume for it, any other obligation in
connection with the sale of products or
parts of products. Tyco Fire Products
shall not be responsible for sprinkler
system design errors or inaccurate or
incomplete information supplied by
Buyer or Buyer's representatives.
IN NO EVENT SHALL TYCO FIRE
PRODUCTS BE LIABLE, IN CON-
TRACT, TORT, STRICT LIABILITY OR
UNDER ANY OTHER LEGAL THE-
ORY, FOR INCIDENTAL, INDIRECT,
SPECIAL OR CONSEQUENTIAL
DAMAGES, INCLUDING BUT NOT
LIMITED TO LABOR CHARGES, RE-
GARDLESS OF WHETHER TYCO
FIRE PRODUCTS WAS INFORMED
ABOUT THE POSSIBILITY OF SUCH
DAMAGES, AND IN NO EVENT
SHALL TYCO FIRE PRODUCTS' LI-
ABILITY EXCEED AN AMOUNT
EQUAL TO THE SALES PRICE.
THE FOREGOING WARRANTY IS
MADE IN LIEU OF ANY AND ALL
OF MERCHANTABILITY AND FIT-
POSE.
TFP22O Page 8 of 8
Ordering
Procedure
When placing an order, indicate the full
product name. Please specify the
Sprinkler Identification Number (SIN),
quantity, and temperature rating. Refer
to the Price List for complete listing of
Part Numbers.
Contact your local distributor for avail-
ability.
Sprinkler Assemblies with NPT
Thread Connections:
Specify: (specify SIN), (specify K-Fac-
tor), (specify temperature rating),
(specify Pendent or Upright) Extended
Coverage Sprinkler with (specify fin-
ish), P/N (specify - from Table E, where
applicable).
Recessed Escutcheon:
Specify: Style (specify 30 or 40) Re-
cessed Escutcheon with (specify fin-
ish), P/N (specify).
Style 30 Recessed Escutcheon
Chrome Plated ............PSN 56-705-9-011
White Color Coated ........PSN 56-705-4-011
White (RAL9010)*PSN 56-705-3-011
Brass Plated ..............PSN 56-705-2-011
Style 40 Recessed Escutcheon
Chrome Plated ............PSN 56-700-9-010
White Color Coated ........PSN 56-700-4-010
White (RAL9010)*PSN 56-700-3-010
Brass Plated ..............PSN 56-700-2-010
*Eastern Hemisphere sales only.
Sprinkler Wrench:
Specify: W-Type 3 Sprinkler Wrench,
P/N 56-895-1-001
Specify: W-Type 22 Recessed Sprin-
kler Wrench, P/N 56-665-7-001
PIN 51 - AAA - B -CCC
AAA = 893 (for TY5237
Ki 1.2 Pendent)
AAA = 894 (for TY5 137
Ki 1.2 Upright)
AAA = 895 (for TY6237
K14.0 Pendent)
AAA = 896 (for TY6137
K14.0 Upright)
B = 1 (for Natural Brass)
B = 3 (for White [RAL9010])*
B = 4 (for White Polyester)
B = 7 (for Lead Coated
B = 9 (for Chrome Plated)
CCC = 135 (for 1350F/57°C)
CCC = 155 (for 155°F/68°C)
CCC = 175 (for 175°F/79°C)
CCC = 200 (for 200°F/93°C)
*Eastern Hemisphere sales only.
TABLE E
PART NUMBERS FOR
EC-1 1 AND EC-14 SPRINKLERS
TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446