HomeMy WebLinkAbout5781 VAN ALLEN WAY; ; FA090050; Permit4/4/25, 3:14 PM FA090050 Permit Data
City of Carlsbad
Fire Alarm Permit
Job Address: 5781 VAN ALLEN WY
Permit Type: FALARM
Parcel No: 2121304400
Lot #: 0
Permit No: FA090050
Status: ISSUED
Applied 11/4/2009
Approved: 11/4/2009
Reference No.: Issued: 11/4/2009
PC #: Inspector:
Project Title: LIFE TECHNOLOGY FIRE ALARM PLAN CHECK &
INSPECTIONS
Applicant:
ADT SECURITY SERVICES, INC.
3830 CALLE FORTUNADA
SAN DIEGO, CA
(858) 654-3224
Owner:
GRIFFIN CAPITAL CARLSBAD POINTE
INVESTORS L L C
C/O INVITROGEN CORPORATION
1600 FARADAY AVE
CARLSBAD CA
Fees ($)
1
Add'I Fees ($) I Total ($) Balance ($)
125 0 125 0
about:blank 1/1
INVITROGEN
CP-21 T.I.
5781 VAN ALLEN WAY
CARLSBAD, CA. 92008
FIRE ALARM T.I. SUBMITTAL
[
CITY OF CARLSBAD
FIRE DEPARTMENT
Submitted By: APPROVED
SubjeCt to field inspection and required
tests, notations hereon, conditions in
correspondence and conformance with
applicable regulations. The stamping
of these plans shall not be held to permit
violation of any law. 3830 Calle Fortunada orappr ye the
San Diego, CA 92123 By
Lic. #707408
(858) 654-3133
INVITROGEN CP-21
T.I.
FIRE ALARM SUBMITTAL
OTY DESCRIPTION MODEL # MANF. CSFM#
5 HORN/STROBE MULTI-CD CLG AS-24MCC WHEELOCK 7125-0785:131
3 STROBE MULTI-CD CLG RSS-24MCC WHEELOCK 7125-0785:141
LOT 14/2 FIRE CABLE ADT/GENESIS 7161-1487:100
LOT 18/4 FIRE CABLE ADT/GENESIS 7161-1487:100
Series AS Audible Strobe Appliances and Series AH Audibles
SERIES AH
Description
The Wheelock patented 2-wire Series AS Audible Strobe
Appliances and Series AH Audibles offer more features with
low current draw.
Strobe options for wall mount models include 1575cd or the
Wheelock patented MOW multi-candela wall strobes with field
selectable candela settings of 15/30/75/110cd or the high
intensity MCWH strobe with field selectable 135/185cd.
Ceiling mount models incorporate Wbeelock's patented MCC
multi-candela ceiling strobe with field selectable intensities of
15130/75/95cd or the high intensity MCCH strobe with field
selectable 115/177cd.
The audible provides a selectable choice of either a
continuous horn or temporal pattern (Code 3) when
constant voltage from a Fire Alarm Panel (FACP) is
applied. Each tone has 3 dBA settings to choose from.
When used with the Wheelock Series SM,DSM Sync
Modules, Wheelock Power Supplies or other manufacturers
panels incorporating the Wheelock Patented Sync Protocol,
synchronization of the continuous horn tone provides the
temporal (code 3) tone (mandated by NFPA 72) simultaneously
for all audible appliances. This ensures a distinct temporal
(code 3) pattern when 2 or more audibles are within hearing
distance. If not synchronized the temporal sound could overlap
and not be distinctive. At the same time the strobes will be
synchronized. This provides the ability to comply with ADA
guidelines concerning photosensitive epilepsy and the NFPA
standards when installing 2 or more visual appliances within
the field of view all of this plus the ability to silence the audible
is achieved by using only 2 wire.
Features
Approvals include: UL Standard 1971 UL Standard 464
New York City (MEA), California State Fire Marshal (CSFM),
Factory Mutual (FM), and Chicago (BFP). See approvals by
model in Specifications and Ordering Information
ADA/NFPNUFC/ANSI Compliant
Wall mount models are available with Field Selectable
Candela Settings of 15/30/75/110cd or 135/185cd (Multi-
Candela models) or 1575cd (single candela model)
Ceiling mount models are available with field selectable
candela settings of 15/30175/95cd or 115/177cd (multi-candela
ceiling models)
Selectable Continuous Horn or Temporal (Code 3).
3 Selectable dBA settings (99, 95 and 90 dBA) in both tones
Patented 2-Wire Audible Strobe Appliance.
Patented Universal Mounting Piate
Weatherproof models are available for outdoor use
Strobes produce 1 flash per second over the regulated
voltage range
12 and 24 VDC models with wide UL Regulated Voltage
Range' using filtered DC or unfiltered FWR input voltage
Synchronize using the Wheelock Sync Modules or panels with
built-in Wheelock Patented Sync Protocol
Fast installation with IN/OUT screw terminals using
#12 to #18 AWG wires
For Weatherproof Series AS, See Datasheet S9004
nYLLLI A.. <S_>
NOTE: All CAUTIONS and WARNINGS are identified by the symbol A. All warnings are printed in bold capital letters.
WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR
APPLYING THIS PRODUCT. VISIT WWW.COOPERWHEELOCK.COM OR CONTACT COOPER WHEELOCK FOR THE CURRENT INSTALLATION INSTRUCTIONS.
FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR
OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU
AND/OR OTHERS.
General Notes:
Strobes are designed to flash at 1 flash per second minimum over their 'Regulated Voltage Range". Note that NFPA-72 specifies a flash rate of 1
to 2 flashes per second and ADA Guidelines specify a flash rate of 1 to 3 flashes per second.
All candela ratings represent minimum effective Strobe intensity based on UL Standard 1971
Series NS Strobe products are listed under UL Standard 1971 for indoor use with a temperature range of 32°F to 120°F (0°C to 49°C) and
maximum humidity of 93% (± 2%).
Series NH horns are listed under UL Standard 464 for audible signal appliances (Indoor use only).
"Regulated Voltage Range" is the newest terminology used by UL to identity the voltage range. Prior to this change UL used the
terminology "Listed Voltage Range".
Table 1: Ratings Per UL 1971
Model
Number
Input
Voltage
VDC
Regulated
Voltage Range
VDC/FWR
Strobe
Candela (Cd)
AS-24MCW 24 16.0-33.0 15/30175/110
AS-24MCCH 24 16.0-33.0 115/177
AS-241575W 24 16.0-33.0 15 (75 on Axis)
AS-121575W 12 8.0-17.5 15 (75 on Axis)
AS-24MCC 24 16.0-33.0 15/30175/95
AS-24MCWH 24 16.0-33.0 135/185
ASWP-2475W 24 16.0-33.0 75 @ -31°F
Table 2: dBA Ratings for 12 VDC and 24 VDC Series AS/
AH 12 and 24 VDC Audible
Reverberant Anechoic
Description Volume dBA dBA Per UL 464 @10 ft. 10 ft.
High 91 99
Continuous Medium 88 95
Horn
Low 83 90
High 87 99
Code 3 Horn Medium 84 95
Low 79 90
Table 3: Average RMS Current
Audible Wall Mount Audible Strobe Models Ceiling Mount Audible Strobe Models
24 VDC Models AH-24 AS-241575W AS-24MCW AS-24MCWH AS-244CC AS-24MCCI-$
1575cd 15cd 30cd 75cd llOcd 1 35c 185cd 15cd 3Ocd 75cd 95cd 11 Sod 177ad
High (99) 24 vdc 0.062 1 0.100 0.080 0.102 0.150 0.194 0.250 0.320 0088 0114 0.165 0.205 0.250 0.320
dBA ULmax° 0.080 0.121 0.088 0.125 0.200 0.267 0.355 0.480 0.095 0.138 0.221 0.285 0.355 0.480
Med (95) 24 vdc 0.033 0.080 0.060 0.084 0.132 0.173 0.230 0.306 0.066 0.092 0.145 0.186 0.230 0.305
dBA UL max* 0.043 0.107 0.074 0.110 0.190 0.253 0.340 0.465 0.080 0.122 0.201 0.269 0.340 0.465
Low (90) 24 vdc 0.017 0.072 0.052 0.076 0.121 0.158 0.220 0.295 0.066 0.082 0.132 0.173 0.220 0.295
dBA UL max* 0.021 0.100 0.068 0.105 0.182 0.245 0.335 0.460 0.074 0.113 0.198 0.263 0.335 0.460
Wall Mount
Audible Audible
12 VDC Models Strobe Table 4:Average Current* (AMPS) For Series ASWP# 1
High dBA Medium dBA Low dBA Aft12 AS-121676W Voltage Setting Setting Setting
(99) dBA (95) dBA (90) dBA
High 99) 12 vdc 0.163 0.260
24.0 VDC 0.128 0.105 0.098
ULmax° 0.192 0.320 dBA ULMax* 0.168 0.155 0.150
Med (95) 12 vdc 0.076 0.195
UL max 0.108 0.275 dBA * RMS current ratings are per UL average RMS method. UL max current
rating is the maximum RMS current Within the listed voltage range (16-33v
Low (90) 12 vdc 0.039 0.175 for 24v units). For strobes the UL max current is usually at the minimum
dBA listed voltage (16V for 24v units). For audibles the max current is usually UL max* 0.058 0
.
265 at the maximum listed voltage (33v for 24v un(ts). For unfiltered FWR
ratings, see installation instructions.
Wiring Diagrams *
SERIES AS APPLIANCES NON-SYNCHRONIZED
FRO [T0 NEXT[]
PRECEDING:
OR EOLREJ OR FACPE:J
APPLIANCEEJ _PPLIJ\NCED
SERIES AS & RSS APPLIANCES SYNCHRONIZED WITH
PS-12124-SCP and PS-12124-8MP
CUTPUTSO EOLRO
F1 1-40
- 4-CLASSO
A: 050 A.S0 aS 0
c:
AM RSSO
Series PS-12/24-4 SO
or PS-12/24-8!{E(
SERIES AS APPLIANCES SYNCHRONIZED WITH DSM MODULE
CLASS"A" NAC CIRCUIT WITH NO AUDIBLE SILENCE FEATURE
SERIES AS APPLIANCES SYNCHRONIZED WITH SM MODULE SIN-
GLE CLASS "B" NAC CIRCUIT WITH AUDIBLESILENCE FEATURE
50RE0
OSTROBEO StrObeO
NACO
circuitc
*ud5b aD
EOLRD PEI
E~A.~dibleD -5.idsb aD
15CC]
CircuitO
SERIES AS APPLIANCES SYNCHRONIZED WITH MULTIPLE DSM
MODULES __DSM #10
DSM Interconnecting wiring shown. Maximum
twenty (20)0
'For detail using SM or DSM Sync Module refer to Data Sheet
S3000 or Installation lnstruct:ons P83123 for SM and P83177
for DSM. For wiring informationon the power supplies refer to
Installation Instructions P84662 for PS-24-8MC.
Specifications and Ordering Information
Model Number Order
Code
Strobe
Candela
Non-
Sync
Syncw/SM,
DSM or
PS..24..81VIC
24
VDC
12
VDC
Wall
Mount
Ceiling
Mount Mounting Options***
AgencyApprovals
U TLMEA CSFM FM BFI
S-24MCW-FR 9024 15/30175/110 X X X - - A,BDEF,G,H,JNOR,X X X X X X
S-24MCW-FW 9025 15/30/75/110 X X X - X - A,B,DE,F,G,H,J,NO,RX X X X X X
.S-24MCW)--FR 3468 135/185 X X X - X - AB,D,EFGHJN,O,R,X X X X X *
S-24MCWH-FW 3469 135/185 X X X - - ABDEFGH,j,NOR,X X X X X *
AS-241575W-FR 7405 15(75onAxis) X X X - X - A,B,D,EF,G,H,J,NO,R,X X X X X X
AS-121575W-FR 7410 15(75onAxis) X X - X X - A,BD,E,F,G,H,J,NO,R,X X X X X X
S-24MCC-FR 3161 15/30175/95 X X X - - X A,BDE,F,G,H,JNO,R,X X X X X *
IS-24MCC-FW 3162 15/30175/95 X X X - - X A,B,D,EFG,H,JN,OR,X X X X X
S-24MCCH-FW 3467 115/177 X X X - - X A,BD,EFGHJ,N,O,R,X X X X X *
SWP-2475W-FR 9012 75 @ -31°F X X X - X - I(see Data Sheet S9004) X X X X X
H-24-R 7892 - X X X - X X A,BD,EF,GH,J,NO,R,X X X X X X
H-24-W 7893 - X X X - X X AB,DEFG,H,JN,OR,X X X X X X
H-12-R 7891 - X X - X X X AB,D,E,F,GHJ,NOR,X X X X X X
H-12-W 7894 - X X - X X X A,B,DE,FG,HJ,NO,R,X X X X X X
H24WPR** 7416 - X X X - X X K X X X
-
X
H12WPR** 7415 - X X - X X X K X X X X
**For Weatherproof Series AS/AH specifications see data sheet S9004. *PENDING
Refer to Data Sheet S7000 for Mounting Options.
Note: Models are available in either Red or White. Contact Customer Service for Order Code and Delivery.
Arc nitects and Engineers Specifications
The notification appliances shall be Wheelock Series AS Audible Strobe appliances and Series AH Audible appliances or approved
equals. The Series AS Audible be listed for UL Standard 1971 (Emergency Devices for the Hearing-Impaired) for Indoor Fire Protection
Service. The Series AH Audible shall be UL Listed under Standard 464 (Fire Protective Signaling). Both shall meet the requirements
of FCC Part 15 Class B. All inputs shall be compatible with standard reverse polarity supervision of circuit wiring by a Fire Alarm
Control Panel (FACP).
The audible portion of the appliance shall have a minimum of three (3) field selectable settings for dBA levels and shall have a choice
of continuous or temporal (Code 3) audible outputs.
The strobe portion of the appliance shall produce a flash rate of one (1) flash per second over the Regulated Voltage Range and
shall incorporate a Xenon flashtube enclosed in a rugged Lexan® lens. The Series AS shall be of low current design. Where Multi-
Candela appliances are specified, the strobe intensity shall have field selectable settings and shall be rated per UL Standard 1971 at
.15/30/75/110 or 135/185 candela for wall mount and 15/30/75/95 or 115/177 candela for ceiling mount. The selector switch for selecting
the candela shall be tamper resistant. The 1575 candela strobe shall be specified when 15 candela UL Standard 1971 Listing with 75
candela on-axis is required (e.g. ADA compliance).
When synchronization is required, the appliance shall be compatible with Wheelock's SM, DSM Sync Modules, Wheelock Power Supplies
or other manufacturers panels with built-in Wheelock Patented Sync Protocol. The strobes shall not drift out of synchronization at any
time during operation. If the sync module or Power Supply fails to operate, (i.e., contacts remain closed), the strobe shall revert to a
non-synchronized flash-rate. The appliance shall also be designed so that the audible signal may be silenced while maintaining strobe
activation when used with Wheelock synchronization.
The Series AS Audible Strobe and Series AH Audible shall incorporate a Patented Universal Mounting Plate that shall allow mounting
to a single-gang, double-gang, 4-inch square, 100mm European type backboxes, or the SHBB Surface Backbox. If required, an NATP
(Notification Appliance Trimplate) shall be provided.
All notification appliances shall be backward compatible.
WE ENCOURAGE AND SUPPORT NICET CERTIFICATION
3 YEAR WARRANTY
Made in USA
S8100 AS/AH 10/07
CAUFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECHON -
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIAlS LISTING PROGRAM -
LISTING SERVICE
LISTING No. 7i25-0785131 Page 1 of 2
CATEGORY: FirAlarm Devices for the Hearing-Impaired
LISTEE: Whéelock Inc., 273 Branchport Ave., Long Branch NJ 07740
Contact: Deborah Piserchia (732) 433-6001 Fax (732) 222-5607
DESIGN: Models AS-1215, -2415, -1230, -2430, -121575, -241575, -2475 and -24110 audible/strobes for
the hearing impaired followed by any three alpha/numeric characters indicating lens
orientation, lettering and color.
Models AS-1 215W, -2415W, -1230W, -2430W, -1 21 575W, -241575W, -2475W and -24110W
audible/strobes for the hearing impaired followed by any three alpha/numeric characters
indicating lens orientation, lettering and color. These units with suffix -W are for wall mount
only. *Models AS-121575W and AS-241575W lens color may be white, red, blue, green, or
amber.
Models AS-2415C, -2430C, -2475C and -241 OOC audible/strobes for the hearing impaired
followed by two alpha/numeric characters indicating lens lettering, orientation and color. These
units are intended for ceiling mount only.
Model AH-12, -24, AH-12WP, -24WP audible appliances (no strobe), followed by an alpha or
numeric character indicating product color.
Model AS-24MCW and AS-24MCC audible/strobe, followed by any two alpha or numeric
character indicating lettering and product color. *Lens color may be white, red, blue, green, or
amber.
Models ASWP-2475W and *AswP..2475c audible/strobe with integral private mode
fire/emergency visual signaling for non-hearing impaired applications. Lens color may be white,
red, blue, green, and amber. Both models are suitable for outdoor use when mounted on the
Model WPBB back box.
Models AS-24MCWH, AS-24MCCH, *ASwp.24Mc and *ASWP..24MCCH
audible/strobes for the hearing impaired followed by two alpha/numeric characters
indicating lens lettering and product color. Units with suffix CH are for ceiling mount only.
Units with suffix WH are for wall mount only. *Lens color may be white, red, blue, green,
or amber.
Refer to the listee's data sheet for detailed product description and operational considerations.
RATING: Electrical: 8-17.5/16-33 VDCNFWR
Flash Rate: 60 flashes/minute
Candela: 15:15cd, 1575:15175cd, 30:30cd, 75:75cd, 95:95cd, 100:100cd, 110:110cd
MCW: Selectable 15cd, 30cd, 75cd, 110cd
MCC: Selectable 15cd, 30cd, 75cd, 95cd
MCWH: Selectable 1 35cd, 185cd (65cd, 90cd at -40 C)
MCCH: Selectable 115cd, 177cd (50cd, 75cd at-40 C)
Listing No. 7125-0785:131
Page 2 of 2
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances and
in a manner acceptable to the authority having jurisdiction. Models ASWP-2475W, ASWP-
24MCWH, AS-24MCW and AS-24MCWH are for wall mount only. Models ASWP-2475C,
ASWP-24MCCH, AS-24MCCH, ANDAS-24MCC are for ceiling mount only. Models with suffix -
W or WH are for wall mount only. Models with suffix -c or -CH are for ceiling mount only.
MARKING: Listee's name, model number, electrical/candela rating, and UL label.
APPROVAL: Listed as audible and audibleMsual signaling devices suitable for the hearing impaired when used
in conjunction with separately listed electrically compatible fire alarm control units. For indoor use
only except Models AH-12WP, AH-24WP, *Aswp..2475w ASWP-2475C, ASWP-24MCWH, and
ASWP-24MCCH audible appliances are suitable for indoor/outdoor. For synchronization, Models
AS Series must be used with Model SM-12/24, SMX-12/24, DSM-12/24 or DSMX-12/24 sync
control module (CSFM Listing No. 7300-0785:132). Refer to listee's Installation Instruction Manual
for details.
These appliances can generate a distinctive three-pulse Temporal Pattern Fire Alarm
Evacuation Signal (for total evacuation) in accordance with NFPA 72, 2002 Edition.
NOTE: Models AH-12, AH-24, -12WP and -24WP audible devices are not suitable for the hearing
impaired applications.
*Rev. 10-01-07
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results
and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or
recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation
criteria. Refer to listee's data sheet, installation instructions and/or other suitable information sources.
Date Issued: JUNE 18, 2009 Listing Expires June 30,2010
Authorized By: FRANCIS MA TEO, Program Coordinator
Fire Engineering Division
RSS Round
Series RSS and RSSP Strobes and Strobe Plates
Description
The Wheelock patented Series RSS Strobe Appliances and
Series RSSP Strobe Plates have lower current draw while
maintaining outstanding performance, reliability and cost
effectiveness. These versatile appliances will satisfy virtually all
requirements for indoor, wall or ceiling mount applications.
Strobe options for wall mount models include 1575 or the
Wheelock Patented MCW multi-candela strobe with field
selectable candela settings of 15/30175/110cd or the high
intensity MCWH strobe with field selectable 1351185cd.
Ceiling mount models include the patented MCC multi-candela
ceiling strobe with field selectable intensities of 15/30175/95cd
or the high intensity MCCH strobe with field selectable
115/177cd.
All models may be synchronized using the Wheelock SM,
DSM Sync Modules, Wheelock Power Supplies or other
manufacturers panels incorporating the Wheelock Patented
Sync Protocol. Synchronized strobes can eliminate possible
restrictions on the number of strobes in the field of view.
Wheelocks synchronized strobes offer an easy way to comply
with ADA recommendations concerning photosensitive epilepsy
as well as meeting the requirements of NFPA72.
The Wheelock Series RSS Strobes employ a Patented Integral
Strobe Mounting Plate that can be mounted to a single gang,
double gang, 4" square, 1 00m European backboxes or the
SHBB surface backbox. If the flush backbox has side or top
space between it and the finished wall, the NATP (Notification
Appliance Trimplate) may be used. It provides an additional .65"
of trim for the Appliance. An attractive cover plate is provided
for a clean, finished appearance on all models.
The Series RSSP Multi-Candela Strobe Plates are a cost
effective way to retrofit required wall strobe appliances to
bells, horns, chimes, multitones or speakers and easily mounts
to standard 4" backboxes or for surface mount use with the
Wheelock SBL2 surface backbox.
Features
Approvals include: UL Standard 1971, New York City (MEA),
California State Fire Marshal (CSFM), Factory Mutual (FM), and
Chicago (BFP) See approvals by model in Specifications and
Ordering Information
ADNNFPA/UFC/ANSI compliant. Meets OSHA 29 Part
1910.165
%fII mount Multi-Candela models are available with Field
Selectable Candela Settings of 15130/75/110cd or 135/185cd.
Single Candela models are available in 1575cd
Ceiling mount Multi-Candela models are
available with field selectable candela settings of 15/30/75/95cd
or 115/177cd. (Round or Square)
Strobes produce 1 flash per second over the regulated voltage
range
12 and 24 VDC models with wide UL Regulated Voltage" us-
ing filtered (DC) or unfiltered VRMS input voltage
Synchronize using the Wheelock sync modules or panels with
built-in Wheelock Patented Sync Protocol
Fast installation with IN/OUT screw terminals using #12 to #18
AWG wire
For Weatherproof Series RSS See Datatsheet S9004
NOTE: All CAUTIONS and WARNINGS are identified by the symbol A. All warnings are printed in bold capital letters.
4 WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR
APPLYING THIS PRODUCT. VISIT WWW.COOPERWHEELOCK.COM OR CONTACT COOPER WHEELOCK FOR THE CURRENT INSTALLATION INSTRUCTIONS. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR
OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU
AND/OR OTHERS.
General Notes:
Strobes are designed to flash at 1 flash per second minimum over their "Regulated Voltage Range". Note that NFPA-72 specifies a flash rate of 1
to 2 flashes per second and ADA Guidelines specify a flash rate of 1 to 3 flashes per second. All candela ratings represent minimum effective Strobe intensity based on UL Standard 1971.
Series NS Strobe products are listed under UL Standard 1971 for indoor use with a temperature range of 32°F to 120°F (0°C to 49°C) and
maximum humidity of 93% (± 2%).
Series NH homs are listed under UL Standard 464 for audible signal appliances (Indoor use only).
"Regulated Voltage Range" is the newest terminology used by UL to identify the voltage range. Prior to this change UL used the
terminology "Listed Voltage Range".
Table 1: Average RMS Current*
RSS!RSSP -Wall Mount Ceiling Mount
241575W 24MCW 24MCWH '24MCC 24MCCH
RSS/RSSP
Models
1575cd 15cd 30cd 75cd 110cd 135cd 185cdl . 15cd .30cd 75cd 95cd 11 5c 177cd
UL max* 0.090 0.060 0.092 0.165 0.220 0.300 0.420 0.065 0.105 0.189 0249 0.300 0.420
RSS/RSSP RSS!RSSP
Wall Mount 24VDC _____________ * RMS current ratings are per UL average RMS method. UL max current Models 121575W rating is the maximum RMS current within the listed voltage range (16-33v
for 24v units). For strobes the UL max current is usually at the minimum 12 vdc 0.152 listed voltage (16v for 24v units). For audibles the max current is usually at
the maximum listed voltage (33v for 24v units). For unfiltered FWR ratings, UL max* 0.255 see installation instructions.
Table 2: Audibles/Speakers for RSSP Strobe Plate
Product Series
Multitone Appliances AMT, MT
Horns AH, NH, HS
Motor Bells MB-G6/G10
Speakers ET-1010/1080, E70, ET70
Chimes CH70
Wiring Diagrams #
SERIES RSSIRSSP APPLIANCE
FROM + TO NEXT
PRECEDING - APPLIANCE
APPLIANCE, SYNC OR EOLR MODULE, POWER
SUPPLY OR FACP
SERIES RSS/RSSP APPLIANCES SYNCHRONIZED
WITH DSM MODULE SINGLE CLASS "A" NAC CIRCUIT
DSM STROBE
SYNC0 NAC
CIRCUIT -
OUT 0+OUT 1
0INl RSS RSS RSS
0MINUS
LI
1
AUDIBLE
2
ROBE
ØMINUS
IN 2 RSS RSS
NAC 0 + OUT 2
CIRCUIT
RETURN
SERIES RSS/RSSP APPLIANCES SYNCHRONIZED
WITH MULTIPLE DSM MODULES
DSM #1
Strobe NAC Cir. 0+ SS RSS I I I I F lsj#' - A sync Strobe NAC
C de
DSM #3 P ___
RSS RSS JLrr?-sr7-
Strobe NAC Cir.
DSM Interconnecting wiring shown. Maximum of
twenty (20)
STROBEIPLATE ASSEMBLY
AUDIBLE & VISIBLE APPLIANCE OPERATE IN UNISON
TO NEXT
FROM
____ _______ ______
+ APPLIANCE
PRECEDING 1 R - OR EOLR
APPLIANCE, SYNC
MODULE, POWER ____ ____
SUPPLY ORFACP
1+ -+-
STROBE AUDIBLE
SERIES RSSIRSSP APPLIANCE SYNCHRONIZED WITH
SM MODULE SINGLE CLASS "B" NAC CIRCUIT
SM
F STROBE
STROBE Strobe A NAG
ø Is'
Gircjit
Audible
P EOLR
Audible
STROBE/PLATE ASSEMBLY
AUDIBLE & VISIBLE APPLIANCE OPERATE INDEPENDENTLY
FROM + TO NEXT FR BC ED WE
APPLIANCE APPLIANCE OR - ___________________ __________________ - OR EOLR FAC?
+ TO NEXT PRECEDING STROBE OR STROBE. SYNC - -
- 11 1 1 — — - EOLR MODULE. POWER
SUPPLY DI FACP
STROBE APPLIANCE
For detail using SM or DSM Sync Module refer to Data
Sheet S3000 or Installation Instructions P83123 for SM
and P83177 for DSM. For wiring information on the power
supplies refer PS-24-8MC.
SERIES RSS!RSSP APPLIANCES SYNCHRONIZED
WITH PS-12!24-8CP or PS-12124-8MP
Series PS-12124-8MP
F 1-4 :BMOUTPUTS EOLR
4-CLASS
A OR S A ASS C 2-CLASS
P
AS RSS
Series PS-12/24-SMP
Specifications and Ordering Information
Model Order
Code
Wall
Mount
Ceiling
Mount
Non-
Sync
Strobe
Candela
24
VDC
12
VDC
Color
RED
Color
WHITE Mounting Options
Square
or
Round
Agency Approvals — —
UL MEA
- -
CSFM FM BFP
RSS-24MCW-FR 940 X - X 15/30175/110 X - X - BDE,F,GH,J,N,OR,X Square X X X X X
RSS-24MCW-FW 9401 X - X 15/30175/110 X - - X BD,E,F,G,H,J,NO,R,X Square X X X X X
RSS-241575W-FR 7471 X - X 15(75onAxis) X - X - B,DE,F,GH,J,N,OR,X Square I X X X X X
RSS-241575W-FW 7788 X - X 15(75onAxis) X - - X BD,E,F,GHJ,N,OR,X Square X X X X X
RSS-121575W-FR 7476 X - X 15(75onAxis) - X X - B,D,E,FG,HJ,N,O,R,X Square X X X X X
RSS-121575W-FW 7468 X - X 15(75onAxis) - X - X B,D,E,FG,H,J,NO,R,X Square X X X X X
RSS-24MCC-FW 3158 - X X 15/30/75/95 X - X B,DE,FGHJN,OR,X Square X X X X
RSS-24MCC-FR 3157 - X X 15/30/75/95 X - X - B,D,E,FGH,J,NOR,X Square X X X X
RSS-24MCCR-FW 3160 - X X 15/30/75/95 X - - X BDE,FG,H,J,NO,R,X Round X X X X *
RSS-24MCCH-FW 3461 - X X 115/177 X - - X B,DEF,G,H,JN,O,R,X Square X X X X *
RSS-24MCCHR-FW 3463 - X X 115/177 X - - X B,D,EFG,H,JN,O,R,X Round X X X X
RSS-24MCWH-FR 3465 X X 135/185 X X B,DE,F,GHJ,N,OR,X Square X X I X X
RSS-24MCWH-FW 3464 X X 135/185 X X BDE,F,G,H,J,N,OR,X Square X X X X
RSSWP2475WFR** 9013 X - X 180@ 77*F X X X - B,D,E,F,G,H,J,NOR,X Square X X X X *
RSSWP-2475W-FW" 3034 X - X X X - X BD,EF,G,HJN,O,R,X Square X X X X
RSSP-121575W-FR 77981 X • X 15(75onAxis) - X X - D,E,Z Square X X X X X
RSSP-24MCW-FR 9402 X - X 15/30/75/110 X - X - D,E,Z Square X X X X X
R SSP-241 575W-FR 7793 X - X 15 (75 On Axis) - - X - D,E,Z Square X X X X I X
*PENDING
All models sync with Wheelock SM, DSM or PS-12124-8CP or PS-12/24-8MP.
# Models are available in either Red or White. Call Customer Service for Order Code & Delivery.
Architects and Engineers Specifications
The visual notification appliances shall be Wheelock Series RSS Strobe Appliances or approved equals. The Series RSS shall meet
and be listed for UL Standard 1971 (Emergency Devices for the Hearing-Impaired) for Indoor Fire Protection Service. The strobe shall
be listed for indoor use and shall meet the requirements of FCC Part 15 Class B. The strobe appliances shall produce a flash rate of
one (1) flash per second overthe Regulated Voltage Range and shall incorporate a Xenon flashtube enclosed in a rugged Lexan® lens.
All inputs shall be compatible with standard reverse polarity supervision of circuit wiring by a Fire Alarm Control Panel (FACP). When
Strobe Plates are to be installed, they shall be the Wheelock Series RSSP Strobe Plate and shall have the same electronic circuitry
as the Wheelock Series RSS.
The Series RSS Strobe shall be of low current design. Where Multi-Candela appliances are specified, the strobe intensity shall have
field selectable settings and shall be rated per UL Standard 1971 at 15/301751110cd or 135/185cd for wall mount and 15130/75/95cd or 115/177cd for ceiling mount. The selector switch for selecting the candela shall be tamper resistant. The 1575 candela strobe shall be
specified when 15 candela UL Standard 1971 Listing with 75 candela on axis is required (e.g. ADA compliance).
When synchronization is required, the appliance shall be compatiblewith Wheelock's SM, DSM Sync Modules, Wheelock Power Supplies
or other manufacturers panels with built-in Wheelock Patented Sync Protocol. The strobes shall not drift out of synchronization at any
time during operation. If the sync module or Power Supply fails to operate, (i.e., contacts remain closed), the strobe shall revert to a
non-synchronized flash rate. The strobes shall be designed for indoor surface of flush mounting.
The Series RSS Strobe Appliances shall incorporate a Patented, Integral Strobe Mounting Plate that shall allow mounting to single-
gang, double-gang, 4-inch square, 100mm European type backboxes, orthe SHBB Surface Backbox. If required, an NATP (Notification
Appliance Trimplate) shall be provided. An attaching cover plate shall be provided to give the Appliance and attractive appearance. The
Appliance shall not have any mounting holes or screw heads visible when the installation is completed.
The Series RSSP Multi-Candela or single candela Strobe Plate shall mount to either a standard 4 inch square backbox for flush mounting,
or the Wheelock SBL2 backbox for surface mounting.
All notification appliances shall be backward compatible.
NOTE Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with tATheelock, Inc. standard terms and conditions.
WE ENCOURAGE AND SUPPORT NICET CERTIFICATION
3 YEAR WARRANTY
Made in USA
S0410 RSS/RSSP 02108
CALIFORNIA DEPARTMENT OF FOREST1Y & FIRE PROTECTION
OFFICE OF THE STATT, FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS IJSFING PROGRAM
LISTING SERVICE
LISTING No. 71250785:141 Page 1 of 1
CATEGORY: Fire Alarm Devices for the Hearing Impaired
LISTEE: Wheelock Inc., 273 Branchport Ave., Long Branch NJ 07740
Contact: Deborah Piserchia (732) 433-6001 Fax (732) 222-5607
DESIGN: Synchronized or non-synchronized Strobe Lights. Models are as follows:
RSS-##W RSSP-##W RSS-##C RSSP-C RSS-CR RSSP-#CR
2415 2415 2415 2415 2415 2415 2475 2475 2430 2430 2430 2430
241575 241575 2475 2475 2475 2475
2430 2430 *2495 *2495 *2495 *2495
24110 24110
1215 1215
121575 121575
Also, Models RSS-24MCW and RSSP-24MCW, RSS-24MCC, RSS-24MCCR, RSSP-
24MCC, RSS-24MCWH, RSS-24MCWHR, RSSP-24MCWH, RSS-24M CCH, RSS-
24MCCHR, RSSP-24MCCH, *ZRSMCC *ZRSMCW; *ZRSMCCH and *ZRSMCWH
Model numbers may be followed by any two alpha/numeric character indicating lens
orientation, lettering and color. Refer to listee's data sheet for additional detailed product
description and operational considerations.
RATING: Electrical 12 = 8-17.5VDC/FWR OR 24 =16-33VDC/FWR
Candela 15=5cd, 1575=15/75cd on axis, 30=30cd, 7575cd, 110=110cd (Wall)
RSS-24MCW, RSSP-24MCW, *ZRSMCW: Selectable 15cd, 30cd, 75cd
orll0cd
RSS-24MCC, RSS-24MCCR, RSSP-24MCC, *ZRS.MCC: Selectable
15cd, 30cd, 75cd and 95cd
RSS-24MCWH, RSS-24MCWHR, RSSP-24MCWH, *zRS.McJL:
Selectable 135cd, 185cd
RSS-24MCCH, RSS-24MCCHR, RSSP-24MCCH, *ZRSMCCH:
Selectable 115cd, 177cd
Flash rate 60 flashes/minute
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and
ordinances and in a manner acceptable to the authority having jurisdiction. Models with
suffix -W, wall mount only. Models with suffix -C, ceiling mount only. All models are for
indoor use only.
MARKING: Listees name, model number, electrical/candela rating, and UL label.
APPROVAL: Listed as strobe light suitable for the hearing impaired when used with separately listed
electrically compatible fire alarm control units. For synchronization strobes, Models SM-
12/24, SMX-12/24, DSM-12/24 or DSMX-12/24 Sync Control Module (CSFM Listing No.
7300-0785:132) must be used. Refer to listee's Installation Instruction Manual for details.
Rev. 12-13-20061w
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results
and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or
recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation
criteria. Refer to listee's data sheet, installation instructions and/or other suitable information sources.
Date Issued: JUNE 18, 2009 Listing Expires June-30,-2010
Authorized By: FRANCIS MATEG, Program Coordinator