HomeMy WebLinkAbout2110 RUTHERFORD RD; ; FA090004; Permit4/10/25, 8:39 AM FA090004 Permit Data
City of Carlsbad
Fire Alarm Permit
2110 RUTHERFORD
Job Address:
RD
Permit Type: FALARM
Parcel No: 2120702200
Lot #: 0
Permit No: FA090004
Status: VOID
Applied 1/8/2009
Approved: 1/8/2009
Reference No.: Issued: 1/8/2009
PC #: Inspector:
Project Title: GENOPTIX MONITORING SYSTEM PLAN CHECK &
INSPECTIONS
Applicant: Owner:
JMG SECURITY BLACKMORE AIRPORT CENTRE
17150 NEWHOPE C/O ALLEN J BLACKMORE
SUITE 109 P0 BOX 424
RANCHO SANTA FE CA
800-900-4564 EXT.316
Fees ($) Add'I Fees ($) Total ($) I Balance ($)
L 125 L ü 125 j 125
about:blank 1/1
Mar 26 09 02:28p p.2
FIRE ALARM SYSTEM
RECORD OF COMPLETION
Nam ofprotected property: Genoptix Medical Laboratory - Genoptix Lab Expansion
Aadreast 2110 Rutherford Road, Carlsbad, Ca. 92008
Representative of protected property (name/phone):
Authority kavingjnrisdiction: Carlsbad Safety Center
Address/telephone nurnber. 2560 Orion Way, Carlsbad, Ca. 92010, Phone (760) 931-2141
Org w.eeor r4rulphone Reprser2etve name/phone
Installer 3MG Security Systems, Inc Ph, 714-545-8882 Mike Tremblay
Supplier 3MG Security Systems, Inc Ph.714-545-8882 Mike Tremblav
Service organization 3MG Security Systems, Inc Ph.714-545-8882 Mike Tremblay
Location ofrecord(as.built)drawings: 2110 Ru:herfort Road, Carlsbad, Ca. 92008
Location ofoperation and maintenance manuals: Same a*ove
Location oftestreports: 2113 Rutherford Road, Cerltbad, Ca. 92008
A contract for test and inspection in accordance with A standard(s)
Contract No(s): Et date: Expiration date:
System Software
Operating system (executive) software revision level(s):
Site..epecific software revision date:
Revision completed by.
name) (firm)
1.Type(s) of System or Service
NFPA 72, Chapter 6 — Local
If alarm is transmitted to location(s) off premises list where received:
_____NFPA 72, Chapter -Remote Station
Telephone numbers ofthe organization receiving alarm:
Alarm:
Supervimrv:
Trouble:
If alarms ate retransmitted to public tire service communications centers or others, indicate location and telephone
numbers of the organization receiving alarm:
Indicate how alarm is retransmitted:
_____NFPA 72, Chapter S —Proprietary
Telephone numbers of the organization receiving alarm:
Alarm:_____
Sapervisor#:
Trot.ble:
If alarms are retransmItted to public fire service communications centers or others, indicate location and telephone
numbers of the organization receiving alarm:
Indicate how alarm is retransmitted:
X Nb'PA 72, Chapter 8—Central Station
Prime contractor: DBA National Monitoring Center N4C).
Centralstationlocation: 26800 Laguna Hills Drive, Suite 250. Aliso Viejo, CA. 92656
V.PA 72.1 of 41
Mar 26 09 02:28p p.3
Means oftransmisaion of signals from the pintmted premises to the central station:
______McCulloh ______Multiplex —One-way radio
X Digital alarm communicator —Two-way radio ______Others
Means oftransmission of alarms to the public fire service communications center:
System location:
NFPA72, Chapter 9—Auxiliary
Indicate type of connection: ______ Local energy -Shunt ______Parallel telephone
Location of telephone number for receipt of signals:______________________________________
2. Record 01 System Installation
(Pill out after installation is complete and wiring is checked for opens, short ground faults, and improper branching,
but prior to conducting operational acceptance tests.)
This system has been installed in accordance with the NPPA standards as shown below, was inspected by
on , includes the devices shown
in S and 8, and has been in service since
...2i_NPPA 72, Chapters 1 2 3 ®® 6 () 8 9 11. (circle all that apply)
NF.PA 70, National Electrical Cie,Article 760
Manufacturer's instructions
Other (speci4,):
Signed: Date:
Organiration:
. Record 01 System Operation
Documentation in accordance with Inspection Testing Form, Figure 10.6.2.3, is attached -
All operational features and functions of this system were tested by date
and found In be operating properly in accordance with the requirements o
...L...NFPA 72, Chapters 1 2 3 () ® C 0 8 9 (Ij) ii (circle all that apply)
..JL NFPA 70, National Electrical Code, Article 760
jLMarnifactuxex's instructions
- Other (specify):
Signed:............... Date:
Organization:
4. Signaling Line Circuits
Quantity and class of signaling line circuits connected to system (see NPPA 72, Table 6.6.1):
Quantity: 1 Style: _4 Class: B
(1':FPA 72.2014)
Mar 26 09 02:28p p.4
S. Alarm-initiating Devices and Circuits
Quantity and class of initiating device circuits (see NIPA 72, Table 6.5):
Quantity: 17 Style:B Class:
MANUAL
(a) Manual stations Noncoded________ Transmitters_
(b) Combination manual fire alarm and guard's tour coded stations
B
Coded______ Addressable 11
AUTOMATIC
Coverage: Complete Paatial
Selective. No nreq aired
Smoke detectors ' Ion Photo Addressable X
Duct detectors _5 Ion Photo X Addressable_______
Heat detectors _2 F'l' ER FT,RR_______ BC______ Addressable______
Sprinkler waterfiow indicators: Tranmftters 1 Noncoded X Coded _______ Addressable_______
The alarm verification feature is disabled ______ orenabled______ ,chauged from ______ seconds to______ seconds.
(0 Other (list):
6. Supervisory Signal-initiating Devices and Circuits (use blanks to indicate quantity of devices)
GUARD'S TOUR
(a)—Coded stations
(b)_Noncoded stations
(c) Compulsory guard's tour system comprised of_________ transmitter stations and intermediate stations
Note: Combination devices are recorded under 5(b), Manual, and ma), Guard's Tout
SPRINKLER SYSTEM
Check if provided
(a)2Valve supervisory switches
__Building temperature points
Site water temperature points
(d)___ Site water supply level points
Electric fire pump:
(e) ._Fire pump power
(1) .__.Fire pump running
(g—Phase reversal
Engine-driven fire pump:
(h)_ Selector in ado position
(1) _...Engine or control panel trouble
(j) __Fire pump running
ENGINE-DRiVEN GENERATOR:
(a)_Selecbr in auto position
(b)_......Control panel trouble
(c) _Transfer switches
(d)—Engine running
Other supervisory function(s) specify):
(NFPA 72,3 of 4)
Mar 26 09 02:28p P.5
7. Annunciator(s)
Nunber. 1 Type: LCD Location: ByLobby
& Alarm Notification Appliances and Circuits
NFPA 72, Chapter 6— Emergency VoiceiAlarm Service
Quantity of voice/alarm channels: Single:
Quantity of speakers installed: Quantity of speaker zones:
Quantity of telephones or telephone jacks included in systems:
Multiple:
Quantity and the class of notification appliance circuits connected to system (see NFPA 72 Table 67):
Quantity:15 Style: Class: B
Types and quantities of notification appliances installed:
Bells ____________________ With Visible
Speakers With Visible__________________
Horns _55 With Visible Yes
Chimes With Visible
Other: With Visible
Visible appliances without audible: 35
9. System Power Supplies
Fire Alarm Control Panel: Nominal voltage: 24VDC Current rating:
Overcurrent protection: Type: Current rating-
Location: NDFRoom
Secondary (standby):
Storage battery: 17.2Ah Amp-hour rating. 17.2Ah
Calculated capacity to drive system, in hours: 24hrs
Engine-driven generator dedicated to fire alarm system:_____________________________________
Location of fuel storage:
Emergency system used as backup to primary power supply: Bacrupbatteries
Emergency system described in NFPA 70, Article 700:-
10. Comments
Frequency of routine tests and inspections, ifother than in accordance with the referenced NFPA standard(s)
System deviations (rum the referenced NFPA standard(s) are:_______________________________________
(si ned risailation contractor/supplier (title) (date)
P?-&r,cr 1LLA
(signed) foricr alarm seriice company (ltIt (dale)
(signed) br cenlial station . (title) (date)
Upon completion ofthe system(s) satisfactory test(s) witnessed (if required by the authority having jurisdiction):
(519n9d) representative of the authority having juisdictio (liVe) (date)
(NF72.4 of 4)