HomeMy WebLinkAbout2787 STATE ST; ; FPC2022-0154; PermitPER]tT REPORT ity (_C of Cdr-isbad I 1L$ kwi $1I W Print Date: 04/23/2025 Permit No: FPC2022-0154 Job Address: 2787 STATE ST, CARLSBAD, CA 92008-1629 Status: Closed - Finaled Permit Type: FIRE-Construction Commercial Work Class: Fire Alarm Parcel #: 2032950101 Track #: Applied: 08/19/2022 Valuation: $217,341.23 Lot #: Issued: 11/30/2022 Occupancy Group: Project #: DEV2021-0040 Finaled Close Out: 12/01/2023 #of Dwelling Units: Plan #: Bedrooms: Construction Type: Final Inspection: Bathrooms: Orig. Plan Check #: INSPECTOR: Salcedo, Felix Plan Check #: Project Title: NEW VILLAGE ARTS THEATRE Description: NEW VILLAGE ARTS THEATRE -NEW MANUAL FIRE ALARM SYSTEM (ADDRESSABLE, 39 DEVICES) Applicant: FPContractor: FIVE ALARM SECURITY AGORA HOLDINGS INC SEAN HAMM 2794 LOKER AVE W, #108 2794 W LOKER AVE, # STE 108 CARLSBAD, CA 92010-6616 CARLSBAD, CA 92009-2284 (760) 930-9099 (760) 930-9099 FEE AMOUNT FIRE Hourly Services (each additional hour) $160.00 FIRE Hourly Services (first hour) $188.00 FIRE New Alarm System $1,499.00 FIRE Plan Resub (3rd&Subsequent Submittal/hr) $240.00 FIRE Plan Resub (3rd&Subsequent Submittal/hr) $240.00 Total Fees: $2,327.00 Total Payments To Date: $2,327.00 Balance Due: $0.00 Fire Department Page 1 of 1 1635 Faraday Avenue, Carlsbad CA 92008-7314 1 442-339-2665 1 Inspections: 442-339-2660 1 www.carlsbadca.gov True North 71 COMPLIANCE SERVICES November 22, 2022 City of Carlsbad Community Development Department - Building Division 1635 Faraday Ave. Carlsbad, CA 92008 Plan Review: Revision Address: 2787 State Street, Carlsbad, CA Applicant Name: Zahra Kharrazi Applicant Email: zahra@twinstepsarch.com OCCUPANCY AND BUILDING SUMMARY: Occupancy Groups: B, A-3, A-i Occupant Load: N/A Type of Construction: V-B Sprinklers: No Stories: 1 Area of Work (sq. ft.): 9,600 sq. ft. City of Carlsbad - FINAL REVIEW City Permit No: PREV2022-0 133 True North No.: 22-018-389 The plans have been reviewed for coordination with the permit application. Valuation: Confirmed Scope of Work: Confirmed Floor Area: Confirmed Attn: Building & Safety Department, True North Compliance Services, Inc. has completed the final review of the following documents for the project referenced above on behalf of the City of Carlsbad: 1. Drawings: One (1) copy dated October 28, 2022,,y Twinsteps Architecture, Oil The 2019 California Building, Mechanical, Plumbing, and Electrical Codes (i.e., 2018 IBC, UMC, UPC, and 2017 NEC, as amended by the State of California), 2019 California Green Building Standards Code, 2019 California Existing Building Code, and 2019 California Energy Code, as applicable, were used as the basis of our review. Please note that our review has been completed and we have no further comments, however, we bring the following to your attention: Approved on the following conditions: Provide 48" between Door 126A and 126F when in open position. Inspector will verify in field Applicant to update the city and owner set of plans at the counter to reflect the new door Applicant will provide updated structural sheets to the Building Inspector to reflect the updated trellis design. True North Compliance Services, Inc. 3939 Atlantic Avenue Suite 116, Long Beach, CA 90807 TI 562.733.8030 SALA SO'BRIE N 3220 Executive Ridge I Suite 210 Vista, CA 92081 expect a difference 1 760.560.0100 I www.salasobrien.com Delta D CC#2 Narrative Date: 10/28/2022 From: Salas O'Brien Subject: New Village Arts Carlsbad Description: Delta D CC#2 Project No: 20144 DELTA D CC#2 Item No. Description Electrical: EO.2 Revised Fixture Lighting Fixture Schedule per Interior Designer and Architect's direction Added detail 2 EO.3 Revised T-24, quantity of fixtures and added new fixtures EO.5 Added new sheet EO.6 Added new sheet E2.1 Revised Lighting in building Exterior, Existing Hallways, and Bathrooms per Interior Designer and Architect's direction Added detail 1 and revised keynotes Deleted previous building exterior lights Added power for trellis lighting E2.2 Added receptacles in Box Office per Owner's direction Deleted FC-2 Added power for expresso machine and IT/UPS Added power Fire Smoke Dampers E2.3 Added string lights Type G per Architect's direction Added power for Signage Deleted HP-2 Relocated receptacle in Hallway 116 E2.4 Added new sheet for AV in Theatre E4.1 Revised Panel loads End of Narrative Page lofi PLAN CHECK REVISION OR Development Services cTCitY of DEFERRED SUBMITTAL Building Division Carlsbad APPLICATION 1635 FaradayAvenue 442-339-2719 B-I 5 www.carlsbadca.gov C Original Plan Check Number CBuPREV20220043 Plan Revision Number 2 to Project Address 2787 State Street, Carlsbad CA 92008 General Scope of Revision/Deferred Submittal: minor revisions to plans per site conditions or client direction CONTACT INFORMATION: Name Zahra Kharrazi Phone 9253210614 F Address 18872 MacArthur Boulevard Suite 100 City Irvine Zip 92612 Email Address zahra(@twinstepsarch.com Original plans prepared by an architect or engineer, revisions must be signed & stamped by that person. 1 . Elements revised: • Plans Calculations Li Soils fl Energy Li Other 2. Describe revisions in detail 3. List page(s) where each revision is shown wall location at box office revised, wall & sound door added at theater, & note #5 A2.1 exterior trellis layout change A3.1,A4.1, A5.1 exterior soffit details #14 added - il & 12 updated A8.1 see attached electrical revisions narrative Does this revision, in any way, alter the exterior of the project?A_Yes No Does this revision add ANY new floor area(s)? Yes U No Does this revision affect any fire related issues? IN No C for Is this a complete set? Yes U No £Signature 4..L - Date 10-31-27 1635 Faraday Avenue, Carlsbad, CA 92008 : 442-339- 2719Email: building@carlsbadca.gov www.carlsbadca.gov 0 FIRE ALARM DATA SUBMITTAL AND LISTING SHEETS CONTRACTOR Five Alarm Security 2794 Loker Ave W Ste 108 Carlsbad CA 92010 760.930.9099 CA License 939772 i .0 NAME OF PROJECT nNEW VILLAGE b ARTS New Village Arts 2787 State St Carlsbad CA 92008 760.433.3245 SUBMITTAL FOR New Fire Alarm System October 2022 Model Number Description CSFM Number FL-255FACP-LTEVI Fire Alarm Control Panel with Integral Communicator 7165-0992:0501 GEMC-NAC7S NAC Extender Panel 7315-0992:0135 Remote Fire Keypad 7300-0992:0136 .GEMC-FK1 FWC-FSLC-SM K Addressable Photoelectric Smoke Detector 7272-0992:0130 FWC-FSLC-SMK613 Smoke/Heat Detector Base, 6" 7300-0992:0132 GEMC-WL-SM K Wireless Commercial Photoelectric Smoke Detector 7272-0992:0142 FWC-FSLC-PULL Addressable Manual Pull Station 7150-0992:0140 FWC-FSLC-EZM2 Addressable Dual Zone Module 7300-0992:0134 GEMC-RECV Wireless Commercial Receiver 7300-0992:0136 D4120 Duct Smoke Detector 3242-1653:0207 RTSKEY151 Remote Indicator and Test Switch 7300:1653:0212 P2GRL Horn/Strobe, Red 7135-1653:0503 SGRL Strobe, Red 7125-1653:0504 4506 Wire, 18/2 FPLP 7161-1487:0100 4513 Wire, 14/2 FPLP 7161-1487:0100 4507 Wire, 18/4 FPLP 7161-1487:0100 4508 Wire, 18/6 FPLP 7161-1487:0100 ACE-11 System Record Documents 7300-0553:0110 ELOCK-FA Circuit Breaker Lockout Kit N/A N P7-12 Battery, 12VDC 7AH N/A C Ograted Addressable 255 FEATURING: Lowest Equipment Cost Available for Any Full-Featured Cellular Reporting Fire Alarm Solution Saves Both Installation Time & Money Award-Winning All-in-One Design - Cellular Alarm Reporting, with Nation's largest multibillion dollar, extensively deployed cyberprotected networks nationwide Proven NAPCO StarLink Fire® Sole or Dual Path or Cell/lP High-Performance Dual Diversity Twin Antennas & Signal Boost" Circuitry for greater range & reliability Powerful FACP Addressable 128 to 255 Point Fire Alarm Control Panel, 128 addressable points fire zones, expandable to 255 w/ one module Cloud-based Programming from any smart device. Eliminates the need for software, training or lugging a PC Powerful 7A/24V Onboard Power Supply NFPA & UL Code Compliant FIRELINK SYSTEM SPECIFICATIONS: FACP: Addressable 128 to 255 Point Fire Alarm Control Panel; 4 programmable NAC circuits, 2A max @ 24V each or 4 programmable NAC circuits, 6,5A max @ 24V Built-In Annunciator: Menu-driven operation with backlit custom alphanumeric display and functionality for Reset, Acknowledge, ence (with disable). Also Remote Annunciator, matching functionality _____K1, red) oard Cellular &/or lP Communicator, Commercial Fire (StarLink Fire®): Reports on cyberprotected multibillion-dollar cellular network replaces 2 POTs lines Sole or Dual Path, Reports to any Central Station, via dial up or IP, without any special equipment. Integrated sync and smart operation support on each NAC for System Sensor" and Wheelock® Notification Devices Power Supply, 7A @ 24V 2 Onboard serial ports - one for high-speed local downloading New! Fully Cloud Programmable - mobile friendly, Preprogrammed, or optional Quickloader® Software custom programmable. Locking Mercantile Enclosure for surface mount* or recess mounting (between the studs) 16"x 25" x 5.2" (H x W x D) without cover. Houses up to 32Ah @ 24V battery backup capacity. * Note: For flush mount applications, use external antennas (see ordering info.) 36-Month Napco Warranty FACP EXPANSION OPTIONS Expandable to 255 Pts. (with one module (GEMC-FWSLC); SLC addressable or conventional fire devices Main FACP board supports 1 Addressable Fire SLC (addressable Signaling Line Circuit controllers) Fire 4-wire bus for annunciators and non-SLC (conventional) devices, including 12V devices Supports up to 6 additional Red FireLink fire annunciators, FL-FK1 or GEMC-FK1s, mounted anywhere on the bus lashable/updatable firmware) 'Plop SLC Loop Isolator (optional use - for fire applications iring increased circuit integrity, e.g., meets Class A, Style loop requirements. SLC Fire Devices supported: Analog smoke detector, analog heat detector, duct detector, pull station, conventional zone module & short circuit isolator Optional FireLink Remote Arnunciator, FL-K1 shown FACP INPUTS Up to 255 Zones/Points from a wide range of initiating devices (see ordering info.) Addressable SLC Loop - supports 128Pts., expandable to 255 SLC Fire Devices supported: analog smoke detector, analog heat detector, duct detector, pull station, conventional zone module & short circuit isolator Conventional 1- to 4-zone EZM Expansion modules on the 4-wire fire bus orSLC loops Conventional 2-wire or 4-wire smoke detector inputs FACP OUTPUTS Up to 96 outputs Four onboard Class B or 1 Class A NAG circuits, 2 amps each, total 2A@24V; Up to 24 Onboard Wheelock and System Sensor NAC sync/strobe/horn protocol allows initial silence of audible appliances while maintaining visual notification, without the use of additional modules Addressable SLC Fire Devices: Supervised relay, unsupervised relay Fire 4-wire bus devices: 8 zone form C relay (GEMC-RM3008), 8 open collector output (GEMC-OUT8) Support for Legacy and Existing Notification Appliances -Two NAG outputs configurable for 12V for easy retrofit compatibility Automatic drift compensation for SLC smoke detectors Programmable obscuration level by smoke detector device Tr-Mode Smoke Obscuration Report (for addressable detectors) generated remotely or locally (see W12309LF instructions) Pt. Fire Alarm Control Panel & Cellular/IP Communicator SOLE/DUAL PATH CELLULAR/IP COMMUNICATOR SPECS Integrated StarLink Fire Cellular Communicator® - Code-compliant, replaces 2 POTS lines to save thousands of dollars per year over leased landlines. Sole or Dual Path Cell/IP for redundant reporting (selectable when choosing plan). Reports to any Central Station, via dial up or IP, without any special equipment. Broadest coverage footprint available, using LTE CAT1, for the best, fastest coast-to-coast StarLink coverage Communicates critical life and safety alarm reports on cyberprotected multibillion-dollar cellular networks, for maximum security & liability protection Easy, flexible 24/7 activation & online account management - Ultra-affordable plans are available to meet various codes and requirements, with supervisory check-ins from 200 seconds, ORDERING INFO L-FACP-255-LTVI New FireLink FACP XL 255 4ith sole /dual path cell nnunciator builtin. (4 on board NACs providing up to 6.5A notification power). Locking, Mercantile Red Enclosure, (sur- face or flush mount*), removable 16" x 25" door, with 14.25" x 16" base. Houses up to 32Ah battery backup. * Note: For flush mount applications, use external antennas (see SLE-ANTEXT75..., below) FL-FACP-255LTA1 As above but with AT&T Network. Optional Extended Antenna (pro-grade conical shape), with 4'- 100' cable. With 30' cable (SLE-ANTEXT30). For full line go to: www.napcosecurity.com/media/pdfs/A745B.SLE.ANTEX.pdf Also see Original FireLink 32 Zone Conventional FL-FACP32 LTEVS & -LTEAS models (VZ & ATT) & additional peripherals below GEMC-FW-SLC Addressable SLC Fire Module, supports up to 128 addressable SLC fire devices, below, up to 2 connect to Panel. FWC-FSLC-SMK Addressable Analog SLC Smoke, photoelectric, head** FWC-FSLC-HEAT Addressable Analog SLC Heat, 135- 150F, head** FWC-FSLC-DUCT Addressable SLC Duct smoke detector, photoelectric (Requires use of GEMC-24VR Voltage Regulator) lnclds 2 onboard relays that follow state of detector. FWC-FsLc-DUcTRA Remote Indicator Plate with LEO indicator & key reset. FWC-FSLC-EZM2 Addressable SLC 2-zone conventional expansion module, uses one address on SLC loop, but yields 2 indep. contact monitoring circuits, for pull stations, water flow and other dry contact alarm initiating devices. Fwc-FsLc-EzM1 Addressable SLC 1-input conventional module, similar to usage above. FWC-FSLC-CZM Addressable SLC Conventional Zone module, for monitoring of dry contacts, i.e., pull stations and cony, smokes (Requires use of GEMC-24VR Voltage Regulator) Creates a 24V 2-wire fire zone on the SLC loop, selectable Class A or B zone wiring. Fwc-FsLc-RM2 Addressable SLC 2-output module (requires 2 SLC addresses) FWC-FsLC-ISO Addressable SLC Short Circuit Module (Optional: For special applications, meets Class A, Style 7 loop reqts.) FWc-FSLc-soMl Addressable SLC Fire supervised output module. Application examples: elevator recall, HVAC shutdown, add'l NAC output w/ power supply (Requires use of GEMC-24VR Voltage Regulator) FWC-FSLC.PULL Addressable SLC Fire Pull Station, standard hex-key reset. Fwc-FsLc-puLLK Addressable SLC Fire Pull Station, with key reset. FWC-FSLC-PULL2 Dual action, pull station with hex-key reset. FWC-FSLC-PULL2K Dual action pull station, with key reset. FWC-FSLC-PROG2 Tool for address-programming SLC devices F'tNC-FSLC-SMK6B ** Smoke/Heat 6" Base, required for FWC-FSLC- SMK and -HEAT devices, above Conventional Fire System Pe!jpherals GEMC-FK1 LCD Fire Red Annunciator (Menu-driven operation, functionality for Reset, Acknowledge, Silence (with disable) FL-FK1 FireLink-Branded version of above (red) GEMC-EZM8 8-point Expansion Module FWC-CNV-PULL Conventional Single Action Pull Station, with Hex Reset FINC-CNV-PULLI( Conventional Single Action Pull Station, with Key Reset FWC-cNV-PULL2 Conventional Dual Action Pull Station, with Hex Reset FWC-CNV-PULL2K Conventional Dual Action Pull Station. with Key Reset S IMAPCD www.napcosecurity.com • 1.800.645.9445 333 Bayview Ave, Amityville, NY 11701 USA Product specifications subject to change without notice. FireLinke, Start-ink Fire*, Signal toost & Firewolfe are trademarks of NAPCO Security Technologies, Inc. Other trademarks, remnair, intellectual property of their respective companies and are unaffiliated with Napco. A812 4.2022 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING & INVESTIGATIONS DIVISION BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No.: 7165-0992:0501 CATEGORY: 7165 - FIRE ALARM CONTROL UNIT (COMMERCIAL) LISTEE: Napco 333 Bayview Avene, Amityville, NY, 11701 Contact: Lemma, Frank (631) 842-2726 Email: flemma@napcosecurity.com DESIGN: Models FL-32FACP, FL-96FACP, FL-I28FACP, FL-255FACP; FL-32FACP-A, FL- 96FACP-A, FL-128FACP-A, FL-255FACP-A, *FL..32FACP..LTEAI *FL.96FACP..LTEAI *FL.128FACP.LTAI *FL..255FACP..LTAI *FL..32FACP.LTEVI *FL..96FACP..LTEVI *FL I28FACP-LTVl, *FL..255FACP.LWI *FL..32FACP..LTEAS *FL..96FACP..LTEAS *FL.. 128FACP-LTAS, *FL.255FACP.LTAS *FL..32FACP..LTEVS *FL..96FACP..LTEVS *FL.. I28FACP-LTVS and *FL..255FACP..LWS fire alarm control units. Automatic, manual, waterflow and sprinkler supervisory service, local, remote station (PPU) and central station (PPU). Models with Suffix 'A" indicate integral GSM radio and models without suffix "A" integral CDMA radio. All Models may be followed by three alphanumeric characters. *Models with suffix LTEVS/LTEAS/LTVS/LTSA are Sole Path radios. *Models with suffix LTEVI/LTEAI/LTVl/LTAl are Dual Path radios. System components: GEMC-HSKIT1416, HSK1T1425; Enclosure GEMC-32MB, GEMC-96MB, GEMC-128MB, GEMC-255MB; Main Boards GEMC-P524V4A, GEMC-PS24V7A; Power Supply GEMC--FW-SLC; Fire Signaling Line Circuit Modules GEMC-F8ZCP1M; Zone Expander Modules GEMC-24VR; 24V Output Module GEMC-FKI; Keypad 9SLECDMAIPSLD or 9SLEGSMDPPSLD; SLE Duel Path Communicators Refer to listee's data sheet for detailed product description and operational considerations. RATING: 120 VAC, 12 and 24 VDC Page 1 of 2 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING & INVESTIGATIONS DIVISION BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE INSTALLATION: In accordance with listee's printed installation instructions and applicable codes and ordinances, NFPA 72 and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, electrical rating and UL label. APPROVAL: Listed as fire alarm control units for use with separately listed compatible initiating and indicating devices. Refer to manufacturer's Installation Manual for details. NOTES: For Fire Alarm Verification Feature, the maximum Retard/Reset/Restart must be adjusted to 30 sec. or less. *Rev 10-03-19 gt This listing is based upon technical data submitted by the applicant. OSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other suitable information sources. Date Issued: 07/05/2022 Listing Expires: 06/30/2023 Authorized By: Victor Wong, Program Coordinator Fire Engineering & Investigations Division Page 2 of 2 0 NAPCD I COMMERCIAL OFIREWOLF FEATURES • 4-Supervised Outputs suitable as 24V, maximum 2A • each, combined 6.5A maximum regulated Notification • Appliance Circuits. These outputs can be configured as: 4 Class B or I Class A and 2 Class B or 2 Class A • 3-Unsupervised Form-C Dry relay outputs activated by a programmed event generated by the Gemini C-Series control panel • One supervised, isolated GEMC-Remote Bus interface • One normally-closed (N/C) housing tamper input, identi- fied by trouble on dedicated integral EZM zone • Isolated integral ground-fault detection circuit • One isolated input (terminals 1-2) to synchronize • "Smart" outputs (Listed Wheelock or System Sensor horns/strobes) with other outputs from the C-Series motherboard or other GEMC-NACXX devices • Power supply contains integral battery charger capable of charging up to 4 pairs of 7AH / 7.5AH / 8AH sealed lead S acid or gel type 12V batteries. • The system monitors for low battery, no battery, brown- out and monitors battery charging circuit voltage, identi- fied by battery trouble on dedicated integral EZM zone • Remote bus interface and two Inputs are isolated, thus allowing for separate ground fault detection and annun- ciation • Allows audible notification appliances (horns) to be si- lenced while visual appliances (strobes) continue to oper- ate • Input allows synchronized Wheelock/System Sensor op- eration between the motherboard or other C-Series NAC circuits, allowing for multiple NAC circuits to be used within the same area • Each of the 4 NAG circuits are individually supervised for opens or shorts, and will annunciate and report sepa- rately • Solid State over-current protection on the four NAG's OVERVIEW The GEMC-NAC7S or GEMC-NAC7L (referred to as "GEMC- NACXX" throughout this data sheet) can be used as either: A UL864 9th edition accessory to a Gemini C-Series Combination Fire & Burglary Alarm control panel Power Supply—NAC GEMC-NACXX AGENCY LISTINGS UL864 9th adition: UL Listed Control Units and Accessories for Fire Alarm Systems CSFM: Cal fornia State Fire Marshall NFPA 72 National Fire Alarm Code I • UL864 9th Edition: Commercial Fire NFPA 72 National Fire Alarm Code NYCFD: NYC Fire Department --or-- A UL864 9th edition NAG Extender for use with any listed Fire Alarm Control Panel (FACP) Notification Appliance Circuits (NAC's) A Notification ApDliance Circuit is a circuit or path directly con- nected to a notification appliance, i.e. any audible, tactile or visual signal--or any combination thereof--employed to indi- cate a fire, supervisory or trouble condition. The Gemini C- Series control panels comply with National Fire Protection Association (NFPA) requirements for temporal pulse sounding of fire notification appliances. Use only the specified UL Listed notification appliances. Napco Security Technologies, Inc., 333 Bayview Ave, Amityville, NY 11701(800)645-9445; fax (631) 789-9292 SPECIFICATIONS Electrical Ratings Input Power: • Primary input power: I20VAC, 50/601-1z, 3A, maximum 15A dedicated branch circuit. Secondary power: 24V operation, up to eight 12V / 7AH I 7.5AH / 8AH batteries in pairs (7AH-32AH standby). Fire Bus Input Power Rating: 12.OV Nominal, 8mA. Output Power: Total Output Power: 24VDC, 7A maximum, power limited outputs. Each NAC circuit output rated @ 2A maximum. Optional Auxiliary Output Power: 2A maximum per circuit in alarm; 1.IA @ 24V maximum standby current (depending on batteries utilized) for 24 hours. Any of the 4 NAC's can be used for auxiliary outputs by programming the output with the feature "Reverse Polarity" (see the "NAC/Output Assignment" screen in PCD-Windows Quickloader software). Auxiliary power is 24V Special Applications for use with the GEMC-24VR; these auxiliary outputs are then 24V Regulated. Supervision: AC fail supervision local annunciation, approximate I minute delay to prevent nuisance swingers Battery presence, low battery supervision and battery charger voltage supervision; combined to generate a common battery trouble Remote bus supervised for opens, shorts or ground faults Additional GEMC-NACXX Specifications: NAC End-of-Line Resistor: 2.2K ohms (NAPCO EOL2.2K). Common Trouble Relay ("Out Relay 5"): 30VDC @ 1A, 30VAC @ IA Resistive, connect to power limited circuits only. Common Trouble Relay ("Out Relay 6"): 30VDC @ 1A, 30VAC @ IA Resistive, connect to power limited circuits only. Common Trouble Relay ("Out Relay 7"): 1 O / 120VAC; 2.5A / 30VAC / DC Resistive Load. Input control circuit: 10-30VDC @ 20mA maximum. Operating Temperature: 32°F to 120°F (0°C to 490C). Operating Humidity: Maximum 85% relative humidity @ 30°C. PHYSICAL Housing The GEMC-NACXX comes complete with 7A power supply, enclosure and ample room for standby batteries. Two models are available, as determined by the size of the enclosure: Enclosure Dimensions (W x H x D, Inches): The GEMC-NAC7S uses the small housing with sufficient room for two pair of 12V standby batteries (model GEMC- HSKITI4I6, size 14.25" x 16" x 5.25") The GEMC-NAC7L uses the large housing with room for four pairs of 12V standby batteries (model GEMC- H5K1T1425, size 14.25" x 24" x 5.25") ORDERING INFORMATION GEMC-NACXX: Remote NAC Extender. NARCO SECURITY SYSTEMS, INC WIRING DIAGRAM GEMC-NAC7L I GEMC-NAC7S SUPERVISED NAC EXTENDER AMITYVILLE, N.Y. 11701 22 B) BAIT REFER TO INSTALLATION NAC NAC NAC 1 NAC 2 NAC 3 NAC 4 FAULT TRB AC 05 INSTRUCTIONS W11821 NAPCO EZM ADD ADD OPTIONS IJ EJ IJ J6 123456 J4123 REPLACE BATTERY FUSE FSOO WITH WARNING: UL LISTED 12.5A, 250V FUSE RELAY CIRCUITS CARRY (NAPCO PART NO. F5126) i-IICJ-1 VOLTAGE (1212 0513 = (=1 INPUT I INPUT 2 05 ON SUPERViSED I INPUT INPUT 1 2 SUPERVISED BY FACP GEMC—XXMB UL LISTED UL LISTED UL LISTED UL USTED NOTES: EOL2.21( EOI2.2I( ECI.2.21( E12.2.21( ALL TERMINALS ARE POWER LIMITED OR FOR CONNECTION TO POWER LIMITED CIRCUITS. (EXCEPTION: TERMINALS 25 —28. SEE WI 1821 FOR WIRING METHOD'S) NAC'S 1, 2 & 3: 2A MAXIMUM CURRENT REGULATED NOTIFICATION APPLIANCE CIRCUIT. NAC 4: 2A MAX CURRENT, ADJUSTABLE TO 24V OR 12V REGULATED NOTIFICATION APPLIANCE CIRCUIT. MAX. 2 WIRES PER TERMINAL, 12-24 AWG MAX. 2A CHARGING CURRENT. USE ONLY 7AH, 7.5AH, BAH BATTERIES. LA2971 Napco Security Technologies, Inc., 333 Bayview Ave, Amityville, NY 11701 (800) 645-9445; fax (631) 789-9292 © NAPCO 2013 A646 04/13 PRESS TO RESET =051 RELAY 7 OEER51ZED ( NO TROUBLE Ji I 2 3 4 5 DSB 056 0510 DSII 0S14 DSI DS1 o o o o I J13 ON—J X [l o o o o POWER PULSINC=NAC TROUBLE p0-, py OFF=NORMAL t,) 054 INDOOR/DRY LOCATION USE fl ONLY. J15 o0 025 (126 c:i ' '.' RELAY 5 ENERGIZED RELAY 6 INERGIZED REMOTE -< 0 0 (AC ON) (BATTERY FIRE BUSS ° ° [.2] lA. JOY MAX. TA, 30V MAX SUPERI,I26D BY NOT 1—NOT SUPERViSED-1 — FACP SUPERVISED JP1 ICOMT N/C N/OIIcOM N/C N/ER LCU LOUT I I, I I I I -'-- CUT JUMPER ro ENABLE RRELAY5_J RELAY 6 (AC ON) (BAIT GOOD) i TAMPER CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM O LISTING SERVICE LISTING No. 7315-0992:0135 Page 1 of I CATEGORY: 7315-- POWER UNITS LISTEE: Napco333 Bayview Avene, Amityville, NY 11701 Contact: Frank Lemma (631) 842-9400 Fax (631) 842-2726 Email: flemma@napcosecurity.com DESIGN: Models GEMC-NAC7, GEMC-NAC71- and GEMC-NAC7S notification appliance circuit extenders/24V aux. power supply. Unit are power limited and are intended for use with separately listed compatible fire alarm control units. Refer to manufacturer's installation instructions for detailed product description and operational considerations. RATING: 24 VDC, 7A Regulated INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name or UL File number, model designation, electrical rating and UL label. APPROVAL: Listed as notification appliance circuit extenders for use with separately listed compatible fire alarm control units. S 11-29-10 bh This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2022 Listing Expires June 30, 2023 Authorized By: VICTOR WONG, Program Coordinator Fire Engineering Division Annunciator/Keypad SIGNALING ( - ® LISTED AGENCY LISTINGS UL864 9th Editicn: Commercial Fire UL985: Household Fire Warning System Units NFPA 72 Nation 31 Fire Alarm Code Security Industry Association (SIA) False Alarm Reduc- tion Standard CP-01 CSFM: California State Fire Marshall NYCFD: NYC Fi-e Department FIREWOLF Series NAPCD FEATURES: e. Listed per ANSI/UL Standard 864, 9th Edition Full English Language Display 32 Character Alphanumeric display Backlit LCD alphanumeric display Microprocessor controlled Allows for remote System Control Full English Language Keypad Local Piezo sounder Displays custom descriptions 7 Fully Supervised Remote Annunciator Keypads per System DESCRIPTION: The GEMINI 4 wire bus GEMC-FKI keypad features a two-line, 32-character alphanumeric LCD display and is compatible with the NAPCO GEMINI C-Series Control Panels. See the Gemini C-Series Installation instructions (WI 1653) for more information. KEYPAD AS PRIMARY USER INTERFACE For primary user interface, mount label 01343 adja- cent to keypad. For keypad address and option jumpers, see product label. Annunciator/Keypad Operations Features: User code required Key switch activation No code/key required POWER RATINGS GEMC-FK1 is powered by the Fire bus of the Gemini C-Series (GEMC) motherboard, GEMC-12V2APS or • an appropriately rated UL Listed power limited power supply suitable for Fire alarm service. Deduct these values from the system standby current, as described in the control panel wiring diagram. WIRING Connect the keypad wires to the control panel terminals shown in the accompanying table, "GEMC-FKI KEY- PAD WIRING". ELECTRICAL RATINGS Input Power: 12VDC nominal, 115mA maximum, 35mA if backlighting is disabled (cut jumpers WI, W2 & W3). PHYSICAL Dimensions: 5 W x 4 %" x 1" (WxHxD) ORDERING INFORMATION GEMC-FKI: Fire Keypad with a two-line, 32-character alphanumeric LCD display for the Gemini C-Series (GEMC) System, Red. Napco Security Technologies, Inc., 333 Bayview Ave, Amityville, NY 11701(800: 645-9445; fax (631) 789-9292 FRONT TAMPER BACK TAMPER PRIMARY USER INTERFACE S MOUNTING THE KEYPAD To open the case, insert a screwdriver into either slot at the bottom and push up with a slight twisting motion to re- lease the retainer tab. Repeat for the other slot. Pull out at the bottom and lift off the two hooks at the top. The key- pad features a handy pull-up reference label. Before mounting the keypad onto the wall, push the Sliding Label Plate (with label and felt backing affixed and handle facing forward) down the guides at the rear of the keypad until it snaps into place. Once installed, the Sliding Label Plate cannot be removed without first removing the keypad from the wall. If installing onto a double-gang box, insert mounting screws through the two vertical elongated holes on the left side of the case and into the box. If the box is visible when viewed from the front, adjust the keypad vertically and tighten the screws. Then, using hardware suitable for the mounting surface, add one or two screws at the right side of the keypad case directly into the wall to ensure a secure installation. Note: Do not over tighten the screws! Uneven walls may cause the keypad case to distort. INDOOR / DRY LOCA- TION USE ONLY INSTALLING A REMOTE KEYSWITCH A UL-Listed remote momentary keyswitch can be used for unlocking the GEMC-FK1 Fire keypad #1. Operation In UL Commercial Fire installations, mount the keyswitch next to the GEMC-FK1 Fire keypad #1 and install the key- switch wiring within 20 feet from the control panel and within rigid conduit; the keyswitch switch must be mounted securely to a secured metal box. Note: The keyswitch reports as user 0, if "Open/Close Reporting" is enabled (see Zone Options in the control panel programming instructions). The keypad will flash "Keypad Unlocked" and allow all Fire options to be accessed. Motherboard Wiring for the Remote Keyswitch Install the keyswitch as follows: Connect one side of the keyswitch to the control panel terminal #17 (marked "KEYSW") and connect the other side of the switch to terminal 19 (marked "REM PWR (—]"). If you are using the tamper, ensure it is connected to a zone programmed as a Fire "Monitor" zone. MAXIMUM 2 WIRES PER TERMINAL, WIRE RANGE 12-24 AWC. Napco Security Technologies, Inc., 333 Bayview Ave, Amityville, NY 11701 (800)645-9445; fax (631)789-9292 ©NAPCO 2013 A622 04/13 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM S LISTING SERVICE LISTING No. 7300-0992:0136 Page 1 of I CATEGORY: 7300 -- FIRE ALARM CONTROL UNIT ACCESSORIES/MISC. DEVICES LISTEE: Napco333 Bayview Avene, Amityville, NY 11701 Contact: Frank Lemma (631) 842-9400 Fax (631) 842-2726 Email: flemma@napcosecurity.com DESIGN: Models EOL2.2K, EOL180K end of line resistors, GEMC-EZM8 zone expansion module, GEMC-FK1 keypad, GEMC-RM3008 relay module, GEMC-RECV RF receiver, GEMC-WL-WD2 transmitter, GEMC-R5232 control panel/computer converter, GEMC-FPRINT printer interface and GEMC-OUT8 output module. Refer to listees data sheet for detailed product description and operational considerations. INSTALLATION: In accordance with listees printed installation instructions, applicable codes & ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listees name or UL file number, model designation, electrical rating and UL label. APPROVAL: Listed as control unit accessories for used with separately listed compatible fire alarm control units. S 11-29-10 bh This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2022 Listing Expires June 30, 2023 Authorized By: VICTOR WONG, Program Coordinator Fire Engineering Division I%IARCD I COMMERCIAL Addressable OFIREWOLF Photoelectric Smoke Detector S FEATURES: . Low Profile - Only 2.0" high, including base Simple and reliable device addressing method Automatic compensation for sensor contamination Built-in fire test feature Uses noise immune communication protocol that utilizes interrupts for fast response to fires Two built-in power/alarm LEDs Programmable Non-polling LEDs Non-directional smoke chamber Vandal-resistant security locking feature Removable smoke labyrinth for cleaning or replace- ment DESCRIPTION: 1w he detection chamber consists of a light emitting diode (LED) and photodiode arrangement. The chamber is designed such that light emitted by the LED cannot nor- mally reach the photo diode. In the event of fire, parti- cles of smoke enter the chamber and scatter the light. As the smoke level increases, the scattering effect in- creases, causing more light to hit the photodiode. The chamber contains a unique baffle design that allows smoke to enter the chamber while preventing external light from affecting the photodiode. The photodiode in- put level is sampled to sense smoke density. When the smoke density exceeds a preset threshold, the sensor transmits an interrupt to the fire alarm control panel indicating a fire condition. The fire alarm control panel can adjust the sensor threshold to compensate for contamination. Up to 127 devices are permitted on each loop. A sensor address can be set by a hand held programming unit. The sensor mounts to an electronics-free base and in- corporates a locking mechanism for secure installation. The base provides mounting slots, terminals for field viring and a third contact for a remote indicator/LED. he sensor incorporates dual LEDs for easy viewing of sensor status. SIGNALING LISTED NFPA® LISTINGS: UL268: Smoke Detectors for Fire Alarm Signal- ing Systems UL268A: Smoke Detectors for Duct Application replacement head for the DUCT NFPA 72 National Fire Alarm Code . CSFM: California State Fire Marshall APPLICATION: The Napco FWC-FSLC-SMK Photoelectric Smoke Sensor is particularly suited to detecting optically dense smoke typical of fires involving materials such as soft furnishings, plastic, foam or other similar ma- terials that tend to smolder and produce large visible smoke particles. Napco's unique design allows fast response to flaming fires as well as smoldering fires while eliminating false alarms. ENGINEERING SPECIFICATION: The contractor shall furnish and install where indicat- ed on the plans, photoelectric sensors FWC-FSLC- SMK. The combination sensor head and twist lock base shall be UL Listed compatible with a UL Listed fire alarm control panel. The base shall permit direct interchange with the FWC-FSLC-HEAT heat sensor. The sensitivity of the sensor shall be capable of being measured by the control panel. The vandal-resistant, security locking feature shall be used in those areas as indicated on the drawing. The locking feature shall be optional and can be implemented when required. Napco Security Technologies, Inc., 333 Bayview Ave, Amityville, NY 11701 (800) 645-9445; fax (631) 789-9292 SPECIFICATIONS Operating Voltage Range (VH) (S-SC) 22.9 39.5 VDC; 39.5 VDC Max Current Consumption (S-SC) Normal Mode 390p.A Typical; 8001.LA Maximum Current Consumption (S-SC) when polled 2mA Device Type Code 88 Hex Operating Temperature 14°F to 122°F (-10°C to 50°C) UL Listed Temperature 32°F to 100°F (0°C to 37.8°C) Storage Temperature -4°F to 140°F (-20°C to 60°C) Dimensions 3-15/16°D x 1-1/2"H Environment Indoor Use Only Visual Alarm / Power Indicator Dual LED Coverage . One smoke detector covers 450 to 900 square feet (42 to 84 square meters) WARNING: HEAT DETECTORS ARE NOT LIFE SAFETY DEVICES. WHERE LIFE SAFETY IS A FACTOR SMOKE DETECTORS ARE RECOMMENDED. Examples: You may use 30 foot (9.1 m) spacing on smooth ceilings for smoke detectors. Beams and other obstructions extending more than 18" (45.7cm) below the ceiling reduce the effective range of the detectors. Such obstructions should desig- nate a new separation point, and be considered a border for a new section. Beams or other obstructions extending more than 8" (20.3cm) but less than 18" (45.7cm) require reduced spacing at the perpendicular of the obstructions. NOTE: FOR INFORMATION ON DIFFERING STYLES OF CONSTRUCTION, CONSULT THE NFPA HANDBOOK, SECTION 72. WARNING: DO NOT INSTALL SMOKE DETECTORS IN THE FOLLOWING AREAS: Where temperatures are likely to exceed 100°F (37.8°C) or fall below 32°F (0°C) is • Closer than 4 inches to any side wall • Where forced ventilation can dilute the smoke from a fire • In known areas of combustion such as kitchens or furnace rooms Napco Security Technologies, Inc., 333 Bayview Ave, Amityville, NY 11701 (800) 645-9445; fax (631) 789-9292 © NAPCO 2016 A632A 08/16 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE S LISTING No. 7272-0992:0130 Page 1 of 1 CATEGORY: 7272 -- SMOKE DETECTOR-SYSTEM TYPE-PHOTOELECTRIC LISTEE: Napco333 Bayview Avene, Amityville, NY 11701 Contact: Frank Lemma (631) 842-9400 Fax (631) 842-2726 Email: flemma@napcosecurity.com DESIGN: Model FWC-FSLC-SMK analog addressable photoelectric type smoke detector with listed compatible Models FWC-FSLC-SMK6B and FWC-FSLC-SMK4B detector bases. Unit consists of resistors, capacitors, diodes, transistors, LED, photo diode, mounted on a printed wiring board inside an enclosure. Refer to listee's data sheet for additional detailed product description and operational considerations. RATING: 22.9-39.5 VDC INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listees name, model designation, electrical rating and UL label. APPROVAL: Listed as photoelectric smoke detector for use with separately listed compatible fire alarm control units. Also suitable for in-duct use in air velocities up to 4000 ft/mm. XLF: 7272-0410:0173 10-08-10 bh This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff the test results and/or other data but does not make an independent verification of any claims. This has reviewed listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct S operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2022 Listing Expires June 30, 2023 Authorized By: VICTOR WONG, Program Coordinator Fire Engineering Division 0 I'JARCD OFIREWOLF S I COMMERCIAL Addressable 6" Mounting Base FWC-FSLC-SMK6B FEATURES: UL Listed Designed for use with all NS analog sensors Available in 4 and 6 inch models Contains a security locking tab for tamper protection DESCRIPTION: The Napco FWC-FSLC-SMK6B bases are designed specifically for use with the Napco Analog models FWC- FSLC-SMK and FWC-FSLC-HEAT. The FWC-FSLC-SMK6B common mounting base allows for complete compatibility for all of the Napco Address- able Series Analog sensors. The bases are lightweight and very thin, providing a low profile once installed. The solder-less screw terminals enable quick and easy wir- ing connections. *APPLICATION: The Napco FWC-FSLC-SMK6B mounting base is elec- tronics free and features a simple rugged design with screw terminals for wiring connections. A common mounting base allows for easy sensor interchanges while maintaining loop continuity when sensors are re- moved. A simple anti-tamper head locking system is provided that is enabled by removing a small plastic tab on the back of the sensor. Once locked, the head can only be removed using a small diameter screwdriver. SIGNAUNG @ I LSTED NFPA® IIIR[eT. UL268: Smoke Detectors for Fire Alarm Signaling Systems (FWC-FSLC-SMK, FWC-FSLC-SMK6B) UL268A: Smoke Detectors for Duct Application (FWC-FSLC-SMKALG replacement head for the FWC-FSLC-DUCT) UL521: Heat Detectors for Fire Protective Signaling Systems (FWC-FSLC-HEAT) . NFPA 72: National Fire Alarm Code . CSFM: California State Fire Marshall ENGINEERING SPECIFICATION: The base shall permit direct interchange with the NAPCO FSLC-SMK Photoelectric Smoke Sensor, and FSLC-H EAT Heat Sensor. The vandal-resistant, security locking feature shall be used in those areas as indicated on the drawing. The locking feature shall be optional and can be imple- mented when required. I* Security Feature Plastic Tamper-lock Color & Materia Bone PC / ABS Blend Dimensions FWC-FSLC-SMK6B: 6 inches Compatible with FWC-FSLC-SMK, FWC-FSLC-HEAT Napco Security Technologies, Inc., 333 Bayview Aye, Amityville, NY 11701 (800) 645-9445; fax (631) 789-9292 FWC-FSLC-SMK6B BASE SPECIFICATIONS Operating Voltage Range (VH) (S-SC) 24 40.7 VDC; 41 VDC Max )perating Temperature 14°F to 122°F (-10°C to 50°C) UL Listed Temperature 32°F to 115°F (0°C to 47°C) Storage Temperature -4°F to 140°F (-20°C to 60°C) Dimensions 5-7/8D x 15/32H Environment Indoor Use Only Visual Alarm / Power Indicator See Sensor U.L. LISTEI COMPATIE CONTROL OR SLCIC t VL-LLL-1VI1Sbb US COMPATII CONT PA LIS PO LIMI SE-Jr 8niA MAX. rWL-tLL1V110J 8mA MAX. OUTPUT OUTPUT * - OPTIONAL WIRING CONFIGURATIONS FOR REMOTE OUTPUT Napco Security Technologies, Inc., 333 Bayview Ave, Amityville, NY 11701 (800) 645-9445; fax (631) 789-9292 0 NAPCO 2013 A631 04/13 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM O LISTING SERVICE LISTING No. 7300-0992:0132 Page 1 of 1 CATEGORY: 7300 -- FIRE ALARM CONTROL UNIT ACCESSORIES/MISC. DEVICES LISTEE: Napco333 Bayview Avene, Amityville, NY 11701 Contact: Frank Lemma (631) 842-9400 Fax (631) 842-2726 Email: flemma@napcosecurity.com DESIGN: Models FWC-FSLC-SMK6B and FWC-FSLC-SMK4B detector bases. Unit is intended for use with a separately listed compatible detector head. Refer to listee's data sheet for detailed product description and operational considerations. INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, electrical rating and UL label. APPROVAL: Listed as bases for use with listee's separately listed compatible smoke and heat detectors. Refer to heat or smoke detector listings for compatibility. XLF: 7300-0410:0132 10-11-10 bh This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2022 Listing Expires June 30, 2023 Authorized By: VICTOR WONG, Program Coordinator Fire Engineering Division ISJARCD OFIREWOLF 0 COMMERCIAL Commercial Wireless - FIRE GEMC-WL-SMK, GEMC-WL-HEAT, GEMC-WL-WD2 319.5 MHz Frequency Smoke Detection . Heat detection Single- or Dual-input monitor modules Extended range transmitters 5 year battery life (estimated) DESCRIPTION: The GEMC-WL-SMK is a high-quality photoelectric smoke detector with built-in supervised digitally- coded radio transmitter. It is compatible with Napco's GEMC-RECV supervised receivers that monitor alarms, restores, low battery, tamper and status. • During normal operation, when unit is in standby mode and is within proper sensitivity limits, the green LED on the GEMC-WL-SMK flashes once every 10 seconds. As soon as smoke is detected, the GEMC-WL-SMK sounds a local alarm and the transmitter sends an alarm signal to the supervised receiver (Operating Fre- quency: 319.5MHz). The alarm signal is repeated as long as smoke is still present. A restore report is sent when the smoke detection chamber clears. Supervi- sion status reports are sent from the GEMC-WL-SMK every hour. The GEMC-WL-HEAT is a high-quality wireless 135°F (57°C) fixed-temperature heat detector with Rate of Rise. It is compatible with Napco's GEM-RECV super- vised receivers that monitor alarms, restores, low bat- tery, tamper and status. The GEM-WL-HEAT incorpo- rates circuitry that will transmit an alarm signal upon an alarm condition, generate an hourly supervision test signal to the receiver and also monitor and annunciate low battery. Coding switches are not required or used in the GEMC-WL-HEAT. Each transmitter is assigned a unique identification code number at the factory. The transmitters are powered by one 3V Lithium battery (supplied) that can power the unit for up to two years. If the battery voltage drops below normal, a low-battery SIGNAUNG LISTED NFPA® LISTINGS: . UL864 9th Edition: Commercial Fire UL985: Household Fire Warning System Units UL268: Smoke Detectors for Fire Protective Sig- naling Systems NFPA 72 National Fire Alarm Code CSFM: California State Fire Marshall (excluding the GEMC-WL-HEAT) NYCFD: NYC Fire Department (excluding the GEMC- WL-SMK and GEMC-WL-HEAT) report will be sent to the receiver with any status or alarm transmission. The GEMC-FW-WD2 is a 2 point transmitter designed for use in Napco FIREWOLF Series wireless systems, and with the Napco GEMC-RECV series wireless re- ceivers. Terminals are provided for supervised exter- nal contacts. A jumper (JI) allows the use of external fire alarm pull stations, thermal detectors, waterfiow tamper switches, etc. For Fire installations use 22-18 AWG. In addition, the GEMC-WL-WD2 includes a rear tamper to protect against the removal of the transmitter from the wall. The GEMC-FW-WD2 is powered by a 3- volt lithium battery that will power the transmitter for up to 5 years. When battery voltage drops below normal, a low-battery report will be sent to the receiver. The transmitter has a unique factory-programmed code that distinguishes itself to the receiver. (Note: A fire condi- tion sends a fire alarm signal; this signal will be sent until the condition clears). Napco Security Technologies, Inc., 333 Bayview Ave, Amityville, NY 11701(800)645-9445; fax (631) 789-9292 GEMC-WL-SMK GEMC-WL-H EAT GEMC-WL-WD2 Battery 3-Volt lithium 3-Volt lithium 3-Volt lithium Dimensions 5-1/8 Diameter x 2° Depth 4-5/8°Diameter x 3° Depth 1.5Width x 3.125"Height x 1'Depth Temperature n/a Fixed 135°F (57°C) 15 *F or more per minute Rate-of-Rise n/a Frequency 319.5 MHz 319.5 MHz 319.5 MHz Max Zone Length n/a n/a 3' maximum (#18-22 AWG) Max Loop Resistance n/a n/a 300 Ohms EOL Resister n/a n/a 180 K Ohm CONTROL PANEL S Single Fire N initiating /O device GEMC-WL-SMK I I LJ GEMC-WL-WD2 GEMC-WL-HEAT How to Order: GEMC-WL-SMK UL Commercial Wireless Smoke Detector GEMC-WL-HEAT UL Commercial 135 degree Fixed Temperature Heat detector GEMC-WL-WD2 Wireless Input Alarm Transmitter (2 inputs) Napco Security Technologies, Inc., 333 Bayview Ave, Amityville, NY 11701 (800)645-9445; fax (631) 789-9292 © NAPCO 2013 A635 04/13 I CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM S LISTING SERVICE LISTING No. 7272-0992:0142 Page 1 of I CATEGORY: 7272 -- SMOKE DETECTOR-SYSTEM TYPE-PHOTOELECTRIC LISTEE: Napco333 Bayview Avene, Amityville, NY 11701 Contact: Frank Lemma (631) 842-9400 Fax (631) 842-2726 Email: flemma@napcosecurity.com DESIGN: Model GEMC-WL-SMK photoelectric smoke detector with sounder and R.F. transmitter. Refer to listee's data sheet for additional detailed product description and operational considerations. RATING: 3 Vdc Battery. Duracell DLI23A, Varta CR123A or Panasonic CR123A INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number and UL label. APPROVAL: Listed as a photoelctric smoke detector when used with listee's listed GEMC-RECV receiver unit (CSFM No. 7300-0992:0136) and compatible listed FACP. Refer to listee's Installation Instruction Manual for details. S 01-15-15 gt This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff the test results and/or other data but does not make an independent verification of any claims. This has reviewed listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct S operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2022 Listing Expires June 30, 2023 Authorized By: VICTOR WONG, Program Coordinator Fire Engineering Division 0 I%IARCD OFIREWOLF S I COMMERCIAL Addressable Manual Fire Pull Stations FWC-FSLC-PULL, FWC-FSLC-PULLK, FEATURES: FWC-FSLC-PULL2K, FWC-FSLC-PULL2 Addressable integrated design All metal construction Single- and dual-action models available Extremely easy to operate Bi-colored status LED indicates Standby and Alarm conditions Address is programmable in the EEPROM Address can be programmed when installed Key lock or hex key lock models available Terminals accept up to 14AWG wire ADA compliant (except D models) DESCRIPTION: SIGNAUN .-. - LISTED NFPA® LISTINGS: S The FWC-FSLC-PULL series are the Napco series of addressable manual pull stations that provide a fast and practical means of manually initiating a fire alarm signal. Both single-action and dual-action manual pull stations are available. Resetting of the pull station requires either a Cat 30 key or a 1/8" hex key (depending upon the model used). An alarm condition is actuated by pulling down on the handle of the FWC-FSLC-PULL and FWC-FSLC -PULLK single action models. On the dual-action models FWC-FSLC-PULL2 and FWC-FSLC- PULL2K, the Lift and Pull cover must be lifted before pulling down on the pull station handle. Once the pull station is activated, the handle cannot be put back into a normal standby condition without using the key operated reset feature. The FWC-FSLC-PULL series is electronically ad- dressable and includes a bi-colored status LED. The LED blinks green indicating normal communication with the DCP compatible SLC loop. When an alarm condition is actuated by pulling the handle, the LED will latch red to indicate the alarm condition. UL38: Manual Signaling Boxes for Fire Alarm Systems NFPA 72 National Fire Alarm Code CSFM: California State Fire Marshall NYCFD: NYC Fire Department APPLICATION: Manual pull stations shall be Napco addressable PULL-series single or dual action models, FWC-FSLC -PULL, FWC-FSLC-PULLK, FWC-FSLC-PULL2, or FWC-FSLC-PULL2K. Models shall be made of 14 AWG CRS and painted with red enamel. The words Fire Alarm shall be in a contrasting color and be embossed text 1/2" tall. The electronics shall be fully integrated into the manual pull station requir- ing only connection to the SLC loop of the control pan- el. Programming of the manual pull station address must be possible with the manual pull station fully in- stalled. Manual pull stations shall be Underwriters Laborato- ries Inc. Listed, CSFM Approved, and be installed within the limits defined in the Americans With Disabili- ties Act. Napco Security Technologies, Inc., 333 Bayview Ave, Amityville, NY 11701 (800) 645-9445 Fax (631) 789-9292 iL Lis111rt Nspco Dcp Conspsii SLC M. oHo SINGlY. GANG rjjtcmlcni 115CC £1115 MODEL DESCRIPTIQN WC-FSLC-PULL Single Action Hex Key Lock FWC-FSLC-PULL2 Dual Action Hex Key Lock FWC-FSLC-PULLK Single Action Key Lock FWC-FSLC-PULL2K Dual Action Key Lock SPECIFICATIONS SIC Applied Voltage Rated Range 25.3 - 39VDC SLC Current Consumption Max 660pA Surge current: 30mA (in 5 ms.); Alarm: 8mA with Alarm LED Latched. Nominal 550pA (isual Indicator Bi-Color LED (green/red) Operating Temperature 32F to 120F (0CC to 49CC) Indoor Use Only Storage Temperature -22F to 70F (-30CC to 158CC) Maximum Relative Humidity Up to 90% RH Non-Condensing Dimensions 3.4W x 4.8H x 2.0"D Weight Approximately 19 oz. rxpwnr.o VII'AIIFCKC, SIOUN11AC. 0111011 Note: Only the same size wire from Class B (Style 4) 12 to 22 AWG may be connected to terminal block T131 when more than S one conductor is being connected -7 Sp-, h,. .apco Sriy Syms, Inc. inpco Sccms1ySym. I under each terminal. Maximum of 2 i.ec_rSlc_l1ItJ. PC.FSLC.PtLL 1WC.IS1C-Pt'11. conductors per terminal. MP1155,nunc 5IncIPIS,nc,, Mrnc Ic,IPn5S,.n 511. \.. S. No, P.. Only P.. Uly 1n4 U.. Only my 1,~ U.. Only M-C. L__ -- _.Usted sc Napco DCP Compatible + S j Panel or I SLC Module SC — — — — — — — — — — — — I J — — — — — — — — — — — — — — — — — - FIGURE3A 'NClass A Return (Style 6) Class A (Style 7) r--------1 r---1 &j It Ton 0 Napoo M -1 "'E Mk DCP Compatible Panel or SLC Module L----------JL---------] :c E1IGUR 38 Napco Security Technologies, Inc., 333 Bayview Ave, Amityville, NY 11701 (800) 645-9445 Fax (631) 789-9292 © NAPCO 2020 A629A 3/20 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL I - FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM . LISTING SERVICE LISTING No. 7150-0992:0140 Page 1 of I CATEGORY: 7150-- FIRE ALARM PULL BOXES LISTEE: Napco333 Bayview Avene, Amityville, NY 11701 Contact: Frank Lemma (631) 842-9400 Fax (631) 842-2726 Email: flemma@napcosecurity.com DESIGN: Model FWC-FSLC-PULL maunual pull box. Refer to listee's data sheet for additional detailed product description and operational considerations. INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number and UL label. APPROVAL: Listed as fire alarm pull box for use with separately listed compatible fire alarm control units. Refer to listee's Installation Instruction Manual for details. These manual pull boxes meet the requirements of UL Standard 38, 1999 Edition with California amendments which the controls and operating mechanisms required to be operable at no more than 51bs. force with one hand and shall not require tight grasping, pinching, or twisting of the wrist. XLF: 7150-0410:0169 04-05-11 bh This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct S operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2022 Listing Expires June 30, 2023 Authorized By: VICTOR WONG, Program Coordinator Fire Engineering Division NAPCD INFIREWOLF S COMMERCIAL Addressable Contact Monitoring Modules FWC-FSLC-EZM 1 FWC-FSLC-EZM2 FEATURES: . UL 864 9th Edition Listed Single input contact monitor Fast, reliable contact monitoring 127 devices can be used per SLC loop Can be programmed to monitor Normally Open (NO) or Normally Closed (NC) contacts Operates on Class A or Class B SLC loop DESCRIPTION: rL_J1 INAPC L1i' F INAPCDI _ Lri _ SIGNALING - :ç (] LISTED NFPA® I The Napco FWC-FSLC-EZMI Fast Response Con- tact Module and FWC-FSLC-EZM2 Dual Input Moni- tor Module are designed to be used with pull stations, water flow switches, and other applications requiring the monitoring of dry contact devices. The interrupt driven communications protocol combines maximum communication reliability and fast response to emer- gency conditions. The FWC-FSLC-EZM1 and FWC- FSLC-EZM2 contact monitoring modules do not re- quire a separate 24VDC power source. Each addressable contact monitoring module is pro- grammed with its own unique Signaling Line Circuit (SLC) loop address. The FSLC-EZM2 utilizes only a single address for two (2) distinctive initiating points. The device address is electrically programmable and stored in the onboard EEPROM. Up to 127 devices can be placed on the Napco SLC loop. The module supervises the wiring to the contact with an End Of Line (EOL) resistor. It can be programmed to moni- tor Normally Open (NO) or Normally Closed (NC) contacts. If a fault condition occurs in the wiring, the module sends a trouble status signal to the fire alarm control panel. When a change of status (contact changes state) is sensed by the FWC-FSLC-EZMI or FWC-FSLC-EZM2 it sends an interrupt to the con- trol panel indicating that an alarm has occurred. LISTINGS: UL864 9th Edition: Commercial Fire NFPA 72 National Fire Alarm Code CSFM: California State Fire Marshall NYCFD: NYC Fire Department SPECIFICATION: FWC-FSLC-EZM I The contractor shall furnish and install where indicated on the plans, addressable contact monitoring modules Napco FWC-FSLC-EZMI. The modules shall be UL Listed and compatible with the Napco communication protocol supporting control panel. The device address shall be electrically programmable and stored in the EEPROM. The FWC-FSLC-EZMI shall fit inside a single gang electrical back box. FWC-FSLC-EZM2 The FWC-FSLC-EZM2 addressable SLC two zone conventional input module provides two independent contact monitoring circuits while only utilizing one ad- dress on the SLC loop. Designed to be used with pull stations, water flow switches, and other applications requiring the monitoring of dry contact alarm initiating devices. The FWC-FSLC-EZM2 shall fit inside a sin- gle-gang electrical back box. Napco Security Technologies, Inc., 333 Bayview Ave, Amityville, NY 11701(800)645-9445; fax (631) 789-9292 cLJcc Nopco Socorny Sororm,. lny FX1C-FSLC-EZM2 DmI Inpur Mnnnor 74oduln MR. NO. XXXXXXX)CX + TB! Inpu A — s+ + sc_ 10pm B — Fur Dr) ISO.,, U.rOuly It+puil.rur,. SlIM 1k I'rkF.AI_ORM IIQL'tPMlINT ru1o o Wiring Limitations: Maximum line impedance between input and initiating devices: 3.500 + I U.L LISTED COMPATIBLE FIRE CONTROl PANEL OR SLC MODULE 00110 NFXT MODUlE + I —' FIGURE 3. TYPICAL WIRING DIAGRAM TIM SHOWN IS SUPERVISED AND INHERENTLY POWER LIMITED. FWC-FSLC-EZM 1 Maximum Applied Voltage S, SC: 41 VDC Nominal Supply Voltage S, SC: 33 VDC Average Current Consumption 5501JA (Typical) mm Current Consumption Surge Current 30mA (in 5 ms.) Alarm and response: 30mA (in 20 ms.) No Alarm and no response: 660pA End of Line Device for Input Napco part #0400-02350 10KO Visual Indicator Bi-Color LED (green/red) Maximum Relative Humidity Up to 90% RH Non-Condensing Dimensions 2.8W x 07H x 0.7"D Weight Approx 3 oz. Operating Temperature 32F to 120F (0CC to 49C) Indoor Use Only C FWLCEZM29 SLC Applied Voltage Rated SIC Current Consumption Max 720pA; Nominal 600pA IDC Circuit Rating 3.2VDC, lOOpA End of Line Device for Input Napco part #0400-02370 22KC) Visual Indicator Bi-Color LED (green/red) Maximum Relative Humidity Up to 90% RH Non-Condensing Dimensions 4.2W x 4.7"H x .850 Weight Approx 3 oz. Storage Temperature -227 to 70F (-30CC to 158T) Operating Temperature 32SF to 120F (0CC to 49CC) Indoor Use Only INITIATING DEVICE CIRCUIT (IDE) - XFPA STYLE B (FOR WIRING LENGTH REFER TO TABLE TABLE I: WIRING LIMITATIONS Maximum Distance Between Module and EOL Device 14 AWG 1500 Ft. 16 AWG 900 Ft. 18 AWG 550 Ft. CONTROL Uf) if -r - NEL TYPICAL WIRING FOR N/() CONTACTS ONLY E.O.L. DEVICE PART NUMBER ANY NUMBER OF UI LISTED N/U CONTACT ULOSERF. 0400-023-50 Dr-.\!](,F-',S NI AY BE I L I) DO NOT \II\ FIRE. I \it\I INITIATING OR SUPERVISORY ON THE SAME MODIII.F. IlGURE 3. TYPICAl. WIRING DIAGRAM EXAMI'I.E, CONNECTED TO A COMPATIBLE LISTED CONTROL PANEL OCNEXT TTO oL Jc c -o lul a fig 1 31 115 El -o --, ALL WIRING Sl-lO\XN IS SIJI'ERVlSEl) AND INHERENTLY POWER LiMITED. INITIATING DEVICE CIRCUIT ( (IDC) — NFPA STYLE B L° E.0.L DEVICE 22K PART NUMBER 04130-02370 II TYPICAL WIRING FOR NIO CONTACTS ONLY ANY NUMBER OF UL USrED N/O CONTACT CLOSURE DEVICES MAY BE USED. Note: SLC circuit is in reference to S, and SC. Note: Only the same size wire from 12 to 22 AWG may be connected to terminal block TB1 when more than S one conductor is being connected under each terminal. Maximum of 2 conductors per terminal.. Napco Security Technologies, Inc., 333 Bayview Ave, Amityville, NY 11701 (800) 645-9445; fax (631) 789-9292 © NAPCO 2013 A626 03/13 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE S LISTING No. 7300-0992:0134 Page 1 of 1 CATEGORY: 7300 -- FIRE ALARM CONTROL UNIT ACCESSORIES/MISC. DEVICES LISTEE: Napco333 Bayview Avene, Amityville, NY 11701 Contact: Frank Lemma (631) 842-9400 Fax (631) 842-2726 Email: flemma@napcosecurity.com DESIGN: Models FWC-FSLC-EZM1, FWC-FSLC-EZM2 Monitor Modules, FWC-FSLC-RM2 Analog Relay Module, FWC-FSLC-SOM1 Supervised Output Module, FWC-FSLC-ISO Short Circuit Isolator, and FWC-FSLC-CZM Conventional Zone Module. Refer to listee's data sheet for additional detailed product description and operational considerations. INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listees name, model number, electrical rating, and UL label. APPROVAL: Listed as control unit accessories for use with separately listed compatible fire alarm control units. Refer to listee's Installation Instruction Manual for details. XLF: 7300-0410:0150 S 10-25-10 bh This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff the test results and/or other data but does not make an independent verification of any claims. This has reviewed listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct S ' operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2022 Listing Expires June 30, 2023 Authorized By: VICTOR WONG, Program Coordinator Fire Engineering Division GFIREWOLF 0 Wireless RF Receiver GEMC-RECV FEATURES: SIGNALING X IT, LISTED AGENCY LISTINGS UL365: Police Station Alarm Units UL609: Local Burglar Alarm Units and Systems UL864 9th Edition: Commercial Fire UL985: Household Fire Warning System Units UL1 023: Household Burglar Alarm System Units ULI6I0: Central Station Burglar Alarm Units NFPA 72 National Fire Alarm Code Security Industry Association (SIA) False Alarm Re- duction Standard CP-01 CSFM: California State Fire Marshall NYCFD: NYC Fire Department connected to the Gemini C-Series control panel Fire bus (see the Gemini C-Series installation instructions W11653). The receiver monitors each transmitter, up- dating transmitter status as reports are received, and conveys this information to the control panel. Also moni- tored is the elapsed time since the last report from each transmitter. If no report of sufficient signal strength is received within a programmed time, a Supervision Fail- ure will result. ORDERING INFORMATION GEMC-RECV: Commercial Fire and Burg approved Wireless Receiver, supports 255 devices, maximum of (4) receive-s supported by GEMC system. 0 I%IAPCD I COMMERCIAL Commercial Security Commercial Fire Auto enroll Device feature 200 Wireless Zones All points programmable as Security All points programmable as Fire All points can be a mix of Security and Fire Four Receiver Capable - Full Supervision Signal Strength flashing LED Front Cover Tamper Rear mounting Tamper '1 *IsHIM[.i The Gemini GEMC-RECV RF Receiver is the hard- wired interface to Napco's Wireless-ReadyTM FIRE- WOLF C-Series control panels (see W11653 for in- stallation instructions). • The wireless system is comprised of a compatible GEMC-Series control panel, at least one GEMC- RECV receiver, and one or more companion GEMC- Series (Commercial) or GEM-Series (Residential Fire or Burglary only) transmitters. The transmitters may be wireless smoke detectors, space-protection de- vices, window/door sensors, or other listed devices that report zone status and supervision information to the receiver without the use of wires. There are three differences between the GEM-RECV and GEMC—REC V-Series wireless receivers: The Signal Strength level 5 is adjusted to 3dB greater than the Signal Strength level 4. The green Signal Strength LED is activated at SS3 on the GEMC—RECV instead of SS4 on the GEM-RECV Series. An additional back tamper has been added to the GEMC-RECV to detect removal from the mounting location. THE GEMC-RECV RECEIVER The GEMC-RECV can accommodate up to 200 wire- less zones. The number of transmitters is limited by the associated Gemini C-Series control panel se- lected, because only the number of zones supported by the panel can be mapped to transmitters. The • receiver is connected to the Gemini C-Series control panel 4-wire Fire bus (or Burglary bus for Burg-only applications). For Fire-only applications or Fire-Burg combination applications, the GEMC-RECV must be Napco Security Technologies, Inc., 333 Bayview Ave, Amityville, NY 11701 (800) 645-9445; fax (631) 789-9292 S "'AA GEMC-RECV kil WIRING DIAGRAM NAPCO REFER TO W11682 BACK TAMPER SWITCH RECEIVER NO. JUMPER 1 OR 2i 0 nI 210 2 1 DI 21° 3 110— 201 A -r 1DI 201 FRoNT__..ff PER CO SWiTCH I11uI AIL_ ADDRESS JUMPERS ONLY REQUIRED IF MORE THAN ONE D1 11213141 GEMC—RECV IS USED RED LED ANTENNAS (4 PLACES) - DS2 TO GREEN LED 4-WIRE MOUN11NG KEYPAD EARS BUS 2 PLS Rated 12.5-9.4VDC,70mA MAXIMUM 1 MRE PER TERMINAL. WIRE RANGE 14 TO 22 AWG. INDOOR/DRY LA2704 LOCATION USE ONLY MAXIMUM WIRE LENGTH 1000 FEET. CONTROL PANEL Napco Security Technologies, Inc., 333 Bayview Ave, Amityville, NY 11701 (800) 645-9445; fax (631) 789-9292 ©NAPCO2O13 A621 04/13 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM . LISTING SERVICE LISTING No. 7300-0992:0136 Page 1 of 1 CATEGORY: 7300 -- FIRE ALARM CONTROL UNIT ACCESSORIES/MISC. DEVICES LISTEE: Napco333 Bayview Avene, Amityville, NY 11701 Contact: Frank Lemma (631) 842-9400 Fax (631) 842-2726 Email: flemma@napcosecurity.com DESIGN: Models EOL2.2K, EOL180K end of line resistors, GEMC-EZM8 zone expansion module, GEMC-FK1 keypad, GEMC-RM3008 relay module, GEMC-RECV RF receiver, GEMC-WL-WD2 transmitter, GEMC-R5232 control panel/computer converter, GEMC-FPRINT printer interface and GEMC-OUT8 output module. Refer to listee's data sheet for detailed product description and operational considerations. INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name or UL file number, model designation, electrical rating and UL label. APPROVAL: Listed as control unit accessories for used with separately listed compatible fire alarm control units. S 11-29-10 bh This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct . operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2022 Listing Expires June 30, 2023 Authorized By: VICTOR WONG, Program Coordinator Fire Engineering Division 0 SYSTEM SENSOR D4120 Duct Smoke Detector The lnnovairF/exTM Series are the only duct smoke detectors flexible enough to fit configurations from square to rectangular and everything in between. inn ovaiu Features 4-Wire Photoelectric, integrated low-flow technology Air velocity rating from 100 ft/min to 4,000 ft/mm (0.5 m/s to 20.32 m/sec) Versatile mounting options: square or rectangular configuration Plug-in sensor offers superb false alarm immunity and the latest S sensor technology Broad ranges for operating temperature (-4°F to 158°F) and humidity (0% to 95% non-condensing) Patented sampling tube installs from front or back of the detector with no tools required Increased wiring space with a newly added 3/4-inch conduit knockout One easy-access Test/Reset button and improved LED status Patented interconnect feature for multi-fan shutdown New high contrast terminal designations Built-in short circuit protection from operator wiring errors Field selectable settings for configuring the detector Two DPDT Form-C relay contacts 24 VAC/DC or 120 VAC Backward compatibility with existing Innovair products, including remote accessories Agency Listings ® <~> 1I LISTED APPROVED S911 3033744 3242-16530207 The InnovairFiex D4120 4-wire photoelectric duct smoke detector features a pivoting housing that fits both square and rectangular footprints and mounts to round or rectangular ductwork. This unit senses smoke in the most challenging conditions, operating in airflow speeds of 100 to 4,000 feet per minute, temperatures of -4°F to 158oF, and a humidity range of 0 to 95 percent (non- condensing). A plug-in sensor head offers improved false alarm immunity and simple installation, testing, and maintenance. An improved cover design isolates the sensor head from the low-flow feature for simple maintenance. The InnovairFiex housing provides ample wiring space, a 34-inch conduit knockout, and built-in short circuit protection to prevent damage to sensitive components during installation. High contrast terminal designations make wiring easy. With its 2:1 sensor-to-power capability, the power board of the D4120 may be used to monitor a second sensor, D4S, simultaneously (i.e., supply and return side). As many as 50 InnovairFiex detectors can be interconnected. When one unit senses smoke, all interconnected detectors will switch their relays; only the detector sensing smoke will go into alarm, thus pinpointing the fire source. An easy-access Test/Reset button makes it possible to test the unit with the cover on. Three DIP switches can be used to configure field selectable settings: cover tamper delay, number of sensors to be controlled, and shut down on trouble option. Each power board has two LEDs that can be used to indicate the status of connected sensors, and a quick reference imprinted on the cover explains the LED status indications (Standby, Maintenance, Trouble, and Alarm). The InnovairFlex duct smoke detector can be customized to meet local codes and specifications without additional wiring. The new InnovairFIex product line is compatible with all previous Innovair models, including remote test accessories. WARNING: Duct smoke detectors are NOT a substitute for open area smoke detectors; NOT a substitute for early warning detection; NOT a replacement for a building's regular fire detection system. Refer to NFPA 72 and 90A for additional information. lnnovairFlexTM Duct Smoke Detector Specifications The air duct smoke detector shall be a System Sensor InnovairFleXTm D4120 Photoelectric Duct Smoke Detector. The detector housing shall be UL listed per UL 268A specifically for use in air handling systems. The flexible housing of the duct smoke detector fits multiple footprints from square to rectangular. The detector shall operate at air velocities of 100 feet per minute to 4000 feet per minute (0.5 to 20.32 meters/second). The unit shall be capable of controlling up to 50 air handling systems when interconnected with other detectors. The detector shall be capable of providing a trouble signal in the event that the front cover is removed. It shall be capable of local testing via magnetic switch, test button on the cover, or remote testing using the RTS2-AOS Multi-Signaling Accessory or the RTS151KEY Remote Test Station. Terminal connections shall be of the strip and clamp method suitable for 12-18 AWG wiring. Physical Specifications Size: (Rectangular Dimensions) 14.38 in (37 cm) Length; 5 in (12.74 cm) Width; 2.5 in (6.36 cm) Depth (Square Dimensions) 7.75 in (19.7 cm) Length; 9 in (22.9 cm) Width; 2.5 in (6.35 cm) Depth Weight: 2,5 lbs (1.14 kg) Operating Temperature Range: D4120 & D4S: 40 to 158°F (-20° to 70°C); D4P120: -40° to 158°F (-40° to 70°C) Storage Temperature Range: D4120 & D4S: -22° to 158°F (-30° to 70°C); D4P120: -40° to 158°F (40° to 70°C) Operating Humidity Range: 0% to 95% relative humidity non-condensing Air Duct Velocity: Electrical Ratings 100 to 4000 ft/mm (0.5 to 20.32 m/sec) Power supply voltage: 20-29 VDC 24 VAC 50-60 Hz 120 VAC 50-60 Hz Input capacitance: 270 pF max. 270 pF max. N/A Reset voltage: 3.0 VDC mm. 2.0 VAC mm. 10 VAC mm. Reset time: (with RTS151) .03 to 0.3 sec. .03 to 0.3 sec. .03 to 0.3 sec. Reset time: (by power down) 0.6 sec. max. 0.6 sec. max. 0.6 sec. max. Power up time: 35 sec. max. 35 sec. max. 35 sec. max. Alarm response time: 15 sec. 15 sec. 15 sec. Sensitivity Test: See detector label See detector label See detector label Current Requirements: (Using No Accessories) Max. standby current: 21 mA @ 24VDC 65 mA RMS @ 24VAC 60Hz 20 mA RMS © 120VAC 60Hz Max. alarm current: 65 mA @ 24VDC 135 mA RMS © 24VAC 60Hz 35 mA RMS © 120VAC 60Hz S tContact TIRatings Alarm initiation contacts: 2.OA © 30 VDC (resistive) (SPST) Alarm auxiliary contacts: 10A @30 VDC (resistive); 10A @250 VAC (resistive); ½ HP @240 VAC; 1/4 HP © 120 VAC (DPDT) Note: Alarm auxiliary contacts shall not be connected to initiating circuits of control panels. Use the alarm initiation contact for this purpose. Supervisory contacts: (SPDT) 2.OA @30 VDC (resistive); 2.OA © 125 VAC (resistive) Device Standby Trouble Alarm APA151 12.5 mA n/a 30mAMax. MHR/MHW 0 mA n/a 29 mA Max. RA100Z 0 mA n/a 12 mA Max. RTS151/RTS151KEY 0mtV12mA n/a 12mAMax. RTS2/RTS2-AOS 3.0mA max 16 mA Max. with strobe: 55 mA max; without strobe 30 mA max Note: Any combination of accessories may be used such that the given accessory loads are: 110 mA or less at the Aux output, and 50 mA or less at the Alarm output Installing the InnovairFiex Sampling Tube The lnnovairFlex sampling tube may be installed from the front or back of the detector. The tube locks securely into place and can be Wiring for 4-wire Duct Smoke Detector and Accessories S I POWER INPUTS (NOTE 1) I I POWER INPUTS (NOTE 1) VAC/D1 -g- I I 9 10 I 9 10 I OR I I OR I AUXILIARY CONTACTS I I AUXILIARY CONTACTS I FOR FAN SHUTDOWN, ETC. (NOTE 2) FOR FAN SHUTDOWN, ETC. (NOTE 2) AUXA AUXB AUXA AUXB J" J., I SUPERVISORY CONTACTS SUPERVISORY CONTACTS (NOTE 3) I (NOTE 3) SUP NO. SUP C SUP NO. SUP C UL/FMIJSTED 4-W RE 14 3 14 3 CONTROL PANEL / - ALARM 5 ALARM N.O. ALARM 5 ALARM N.C. ALARM INITIATION A INITIATION INITIATION CONTACTS CONTACTS LOOP (NOTE 4) (NOTE 4) ARM C -AIRMC ----AL FIRST DETECTOR IN THE LOOP LAST DETECTOR IN THE LOOP EDL RESISTOR SPECIFIED BY PANEL MANUFACTURER 1 NOTE 1: 24V Power Inputs accept a non-polarized 24V00 or 24VAC 50-60Hz. 120VAC Power Inputs accept only 120VAC 50-60Hz. Connect power source to appropriate terminals of each detector. See specifications for additional power supply information. NOTE 2: Auxiliary contacts shown in standby position. Contacts switch during alarm as indicated by arrows. Auxiliary contacts are not to be used for connection to the control panel. See specifications for contact ratings. *Please refer to the corresponding installation manual for accessory wiring diagrams. NOTE 3: Supervisory contacts shown in standby position. Open contacts indicate a trouble condition to the panel. See specifications for contact ratings. NOTE 4: Alarm Initiation contacts shown in standby position. Closed contacts indicate an alarm condition to the panel. See specifications for contact ratings. S Important Notes on 2:1 Sensor-to-Power Capability 2:1 sensor-to-power capability is not available for all InnovairFIex models. The feature is only available on the 04120 4-wire conventional models. 2:1 sensor-to-power capability can be enabled Using one 04120 and one 04S, or two D4S and one 04P120. Important Interconnect Notes When Using the interconnect feature, all interconnected Units must be powered Using the same independent supply. Polarity must be maintained throughout the interconnect wiring. Connect the INT+ terminal on unit 1 to the lNT+ terminal on unit 2 and so on. Similarly, connect the INT/AUX— terminal on unit 1 to the INT/AUX- terminal on unit 2 and so on. Up to 50 04120 units, 50 04P120 units, or 50 units of combinatior may be interconnected. Up to 10 DH100ACDC units may be interconnected. Please note that each of the 9 DH100ACDC units interconnected may be replaced by three 04P120 units. Therefore, when using the interconnect feature a single DH100ACDC can drive either 9 DH100ACDCs or 27 04120 units. * NOTE: Alarm can be reset only at the initiating device and not at the devices interconnected. Accessories System Sensor provides system flexibility with a variety of accessories, including two remote test stations and several different means of visible and audible system annunciation. As with our duct smoke detectors, all duct smoke detector accessories are UL listed. SMOKE RTS151 UL S4011 RTS151 KEY UL S2522 APA151 UL S4011 RTS2-AOS UL S2522 VNPW MOM— RA100ZULS2522 MHWULS4O11 MHRULS4O11 AOS Ordering Information 4-wire photoelectric low-flow duct smoke detector D4S 4-wire photoelectric sensor component only D4P120 4-wire photoelectric power board cjmponent only, 24 VAC/DC, 120 VAC 2D51 4-wire conventional photoelectric sensor head DST1 Metal sampling tube duct width up tc itt (0.3m) DST1 .5 Metal sampling tube duct widths 1 ft :o 2 ft (0.3 to 0.6 m) DST3 Metal sampling tube duct widths 2 ft :o 4 ft (0.6 to 1.2m) DST5 Metal sampling tube duct widths 4 ft :o 8 ft (1.2 to 2.4 m) DST10 Metal sampling tube duct widths 8 ft to 12 ft (2.4 to 3.7 m) APA151 Remote annunciator with piezo alarm ETX Metal exhaust tube duct width 1 f (0.3m) M02-04-00 Test magnet MHR Mini Horn, Red MHW Mini Horn, White P48-21-00 End cap for metal sampling tubes RAiOOZ Remote annunciator alarm LED RTS1 Si Remote test station RTS151KEY Remote test station with key lock RTS2 - AOS Multi-signaling accessory with add on strobe ef~ SYSTEM $ SENSOR 3825 Ohio Avenue • St. Charles, IL 60174 02013 System Sensor. Phone: 800-SENSOR2 • Fax: 630-377-6495 Product specifications subject to change without notice. Visit systemsessorcorn for current product information, including the latest oeruion of this data sheet. www.systemsensor.com HVDS00502 • 10/13 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM O LISTING SERVICE LISTING No. 3242-1653:0207 Page 1 of 1 CATEGORY: 3242 -- DUCT SMOKE DETECTOR, PHOTO. (W/ OR W/O BASE) LISTEE: System Sensor, Unincorporated Div of Honeywell Int'l lnc.3825 Ohio Ave, St. Charles, IL 60174 Contact: Lisa Brant (203) 484-6105 Fax (203) 484-7309 Email: lisa.brant@honeywell.com DESIGN: Models D4120, D4240, RD4120, P270-3000PL, TD41203, TD41204, LD4S, LD412OX, LD4120H, D4S, D4P120, CD4PI20 LD4PI20X, LD4P120H, TD4C, PD4 120, YD4120, YD4P120, and AD4P120 four-wire conventional photoelectric duct smoke detectors and subassemblies. Unit consists of a duct detector housing, powerboard with electrical components and relays, exhaust tubes, and listed 2D51 detector head (CSFM Listing No. 7272-1653:203). Model AD4S sensor component. Models *TD4C LD412OX, LD4I20H, LD4P120X and LD4PI20H do not contain a 120 VAC transformer. Refer to listee's data sheet for additional detailed product description and operational considerations. RATING: 20-29 VDC, *24 VAC, 120 VAC (except Models *TD4C LD412OX, LD4120H, LD4P120X and LD4PI20H *do not have 120 VAC rating). INSTALLATION: In accordance with listee's printed installation instruction, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, rating, air velocity and UL label. I APPROVAL: Listed as conventional photoelectric duct smoke detector for use with separately listed fire alarm control units. Refer to listee's Installation Instruction Manual for details. Rev. 03-27-13 gt This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2022 Listing Expires June 30, 2023 Authorized By: VICTOR WONG, Program Coordinator Fire Engineering Division SYSTEM SENSOR® SMOKE Duct Smoke Detector Accessories - 0 Expand the versatility of the lnnovairF/exTM line of duct smoke detectors with System Sensor notification and test accessories. Available Accessories Duct smoke detector accessories add functionality to the duct APA151 Piezo Annunciator smoke detection system by allowing quick, convenient inspections at eye level and effective audible and visible notification options. All MHR Mini-Horn, Red System Sensor duct smoke detectors and accessories are UL listed. MHW Mini-Horn, White The APAI5I piezo annunciator, which replaces the APA451 with a RA100Z/RA100ZA Remote Annunciator RTS151 Remote Test Station new, improved look, provides an audible alarm signal, a red LED to indicate alarm status, and a green LED to indicate power status. It is RTS151KEY Remote Test Station with Key intended for use with System Sensor 4-wire conventional duct smoke detector applications without a system control panel, to comply with RTS2 Multi-Signaling Accessory NFPA 90A. AOS Add-On Strobe The MHR and MHW SpectrAlert® Advance mini-horns feature RTS2-AOS Multi-Signaling Accessory temporal or continuous tones at high and low volume settings. Their small footprint allows mounting to single-gang back boxes for applications where a small device is desired. The RAIOOZ and RAIOOZA remote annunciators are designed for both conventional and intelligent applications. Their red LED provides visual indication of an alarm condition. The RTSI 51 and RTSI 51 KEY remote test stations are automatic fire detector accessories designed to test duct smoke detectors from a convenient location. For 4-wire detectors, the FITS 151KEY test station features a multi-colored LED that alternates between steady green and red. For 2-wire detectors, the LED illuminates red for alarm. The RTS2 and RTS2.AOS multi-signaling accessories are designed to work with InnovairFIex 4-wire conventional duct smoke detectors. These accessories include a key switch that can be used Agency Listings to select one of two connected sensors to be tested, reset, or both by a push button switch. They also enable sensitivity measurements using the SENS-RDR sensitivity reader (sold separately). The ADS (Add-On Strobe) is an optional accessory included with the RTS2- C E ADS model. 7300-1653:0212 LISTED APPROVED 7300-1653:0211 S2522 3034401 7135.1653:0196 9080301 Specifications, Duct Smoke Detector Accessories APA151 Piezo Annunciator RTS151 Remote Test Station Regulated 24 VDC Power Requirements - Alarm LED: 2.8 to 32 VDC, 12 mA max. S Voltage Operating Voltage 16 to 33 VDC Total Current: 105 mA max. Maximum Alarm Current 30 mA Test Switch 10 VA @32 VDC Temperature Range 0°C to 49°C (32°F to 120°F) Reset Switch 10 VA @32 VDC Relative Humidity 10 to 93% non-condensing Alarm Response Time 40 seconds max. Wire Gauge 12 to 18 AWG Temperature Range —10°C to 60°C (14°F to 140°F) Dimensions 4.6" H < 2.9"W,< .45" D Relative Humidity 95% non-condensing • Wire Gauge 14 to 18 AWG Voltage Regulated 12 DC or FWR (Full Wave Dimensions 4.8"H x 2.90"W x 1.4"D Rectified) or Regulated 24 VDC or FWR RTS151 KEY Remote Test Station with Key Sounder Current Draw 22 mA RMS max. at to 17.5 Volts DC Power Requirements Power LED (Green): 14 to 35 VDC, 29 mA RMS max. at 16 to 33 Volts DC 12 mA max. Temperature Range 0°C to 49°C (32°F to 120°F) Alarm LED (Red): 2.8 to 32 VDC, Humidity Range 10 to 93% non-condensing 12 mA max. Total Current: 105 mA max, Nominal Sounder 3 kHz Frequency Alarm Response Time 40 seconds max. Wire Gauge 12 to 18 AWG Temperature Range —10°C to 60°C (14°F to 140°F) Dimensions 4.6-H x 2.9"W x 0.45"D Relative Humidity 95% non-condensing RA10OZtRA10OZA Remote Annunciator • Wire Gauge 14 to 18 AWG Voltage Range Conventional System: 3.1 to 32 VDC Dimensions 4.6-H x 2.75"W x 1.8"D Intelligent System: 18 to 32 VDC RTS2 and RTS2-AOS Multi -signaling Accessory Maximum Alarm Current 10 mA Voltage 20 to 29 VDC Dimensions 46 "H x 2.8-W x 1.3D Power Requirements Standby: 3.0 mA max. Trouble: 16.0 mA max. Alarm without strobe: 30 mA max. Alarm with strobe: 55 mA max. Sounder 85 dBA at ten feet S Temperature Range —10°C to 60°C (14°F to 140°F) Relative Humidity 95% non-condensing Wire Gauge 14 to 22 AWG Dimensions 4.8"W x 5.3" H x 1.6"D For the very latest product specifications and listing information, please visit the System Sensor Web site at www.systemsensor.com. tsr SMOKE . S 0 RTS151 ULS4011 3151 KEY UL S2522 APA151 ULS4011 RTS2-AOS UL S2522 Di RA100Z UL S2522 MHR UL S4011 AOS SYSTEM SENSOR 3825 Ohio Avenue • St. Charles, IL 60174 @2013 System Sensor. Phone: 800-SENSOR2 • Fax: 630-377-6495 Product specifications subject to change without notice. Visit systemsenssr.com for current product information, including the latest version of this data sheet. www.systemsensor.com HVDS20202 • 8/13 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE S LISTING No. 7300-1653:0212 Page 1 of I CATEGORY: 7300 -- FIRE ALARM CONTROL UNIT ACCESSORIES/MISC. DEVICES LISTEE: System Sensor, Unincorporated Div of Honeywell Intl Inc.3825 Ohio Ave, St. Charles, IL 60174 Contact: Lisa Brant (203) 484-6105 Fax (203) 484-7309 Email: lisa.brant@honeywell.com DESIGN: Models RTS1 51, RTS1 51 KEY and RA100Z Duct Smoke Detector accessories. Refer to listee's data sheet for detailed product description and operational considerations. RATING: Refer to the installation manuals. INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listees name, model number, electrical rating, and UL label. APPROVAL: Listed as control unit accessories for use with separately listed compatible fire alarm control units. Refer to listee's Installation Instruction Manual for details. 04-03-09 bh This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct S operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2022 Listing Expires June 30, 2023 Authorized By: VICTOR WONG, Program Coordinator Fire Engineering Division SYSTEM $ SENSOR Indoor Selectable- Output Horns, Strobes, and Horn Strobes for Wall Applications System Sensor L -Series audible visible notification products are rich with features guaranteed to cut installation times and maximize profits with lower current draw and modern aesthetics. Features is 1 Updated Modern Aesthetics Small profile devices for Horns and Horn Strobes Plug-in design with minimal intrusion into the back box Tamper-resistant construction Automatic selection of 12- or 24-volt operation at 15 and 30 candela Field-selectable candela settings on wall units: 15, 30, 75, 95,110,135, and 185 Horn rated at 88+ dBA at 16 volts Rotary switch for horn tone and two volume selections Mounting plate for all standard and all compact wall units Mounting plate shorting spring checks wiring continuity before device installation Electrically Compatible with legacy SpectrAlert and SpectAlert Advance devices Compatible with MDL3 sync module Listed for wall mounting only Agency Listings SIGNALING ®eII APP ROVED LISTED S5512 FM approved except 7125-1653:0504 54011 for ALERT models 7135-1653:0503 3057363, 3057072 The System Sensor L.Series offers the most versatile and easy-to-use line of horns, strobes, and horn strobes in the industry with lower current draws and modern aesthetics. With white and red plastic housings, standard and compact devices, and plain, FIRE, and FUEGO-printed devices, System Sensor L-Series can meet virtually any application requirement. The L-Series line of wall-mount horns, strobes, and horn strobes irclude a variety of features that increase their application versatility while simplifying installation. All devices feature plug-in designs with minimal intrusion into the back box, making installations fast and foolproof while virtually eliminating costly and time-consuming ground faults. To further simplify installation and protect devices from constructior damage, the L-Series utilizes a universal mounting plate for all models with an onboard shorting spring, so installers can test wiring continuity before the device is installed. Installers can also easily adapt devices to a suit a wide range of application requirements using field-selectable candela settings, automatic selection of 12- or 24-volt operation, and a rotary switch for horn tones with two volume selections. AV00865-04 • 11/17/2017 • Page 1 L-Series Specifications S General L-Series standard horns, strobes, and horn strobes shall mount to a standard 2 x 4 x 1 7/8-inch back box, 4 x 4 x 11/2-inch back box, 4-inch octagon back box, or double-gang back box. L-Series compact products shall mount to a single-gang 2 x 4 x 17/8-inch back box. A universal mounting plate shall be used for mounting ceiling and wall products for all standard models and a separate universal mounting plate shall be used for mounting wall compact models. The notification appliance circuit wiring shall terminate at the universal mounting plate. Also, L-Series products, when used with the Sync.Circuit'° Module accessory, shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync.Circuit Module, 12-volt-rated notification appliancEf circuit outputs shall operate between 8.5 and 17.5 volts; 24-volt-rated notification appliance circuit outputs shall operate between 16.5 and 33 volts. Indoor L-Series products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or full-wave rectified unfiltered power supply. Strobes and horn strobes shall have field-selectable candela settings including 15, 30, 75, 95, 110, 135, and 185. Strobe The strobe shall be a System Sensor [-Series Model listed to UL 1971 and shall be approved for fire protective service. The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe's entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. Horn Strobe Combination The horn strobe shall be a System Sensor [-Series Model listed to UL 1971 and UL 464 and shall be approved for fire protective service. The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe's entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. The horn shall have two audibility options and an option to switch between a temporal three pattern and a non-temporal (continuous) pattern. These options are set by a multiple position switch. The horn on horn strobe models shall operate on a coded or non-coded power supply. Synchronization Module The module shall be a System Sensor Sync'Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service. The module shall synchronize Strobes at 1 Hz and horns at temporal three. Also, while operating the strobes, the module shall silence the horns on horn strobe models over a single pair of wires. The module shall mount to a 411/16 x 411/16 x 21/8-inch back box. The module shall also control two Style Y (class B) circuits or one Style Z (class A) circuit. The module shall synchronize multiple zones. Daisy chaining two or more synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power supply. Standard Operating Temperature 32°F to 120°F (0°C to 49°C) Humidity Range 10 to 93% non-condensing Strobe Flash Rate 1 flash per second Nominal Voltage Regulated 12 DC or regulated 24 DC/FWR1'2 Operating Voltage Range 8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal) Operating Voltage Range MDL3 Sync Module 8.5 to 17.5 V (12 V nominal) or 16.5 to 33 V (24 V nominal) Input Terminal Wire Gauge 12 to 18 AWG Wall-Mount Dimensions (including lens) 5.6" L x 4.7"W x 1.91" 0 (143 mm L x 119 mm W x 49 mm D) Compact Wall-Mount Dimensions (including lens) 5.26" Lx 3.46" W x 1.91" D (133 mm Lx 88 mm W x 49 mm D) Horn Dimensions 5.6"L x 4.7"W x 1.25"D (1143 mm Lx 119 mm W x 32 mm D) Compact Horn Dimensions 5.25" Lx 3.45" W x 1.25" D (133mm Lx 88mm W x 32mm D) Full Wave Rectified (FWR) voltage is a non-regulated, time-varying power source that is used on some power supply and panel outputs Strobe products will operate at 12 V nominal only for 15 cd and 30 cd. AVDS865-04 • 11/17/2017 • Page 2 UL Current Draw Data 8-17.5 Volts 16-33 Volts 8-17.5 Volts 16-33 Volts Candela S DC DC FWR Sound Pattern dB DC DC FWR Candela 15 88 43 60 Temporal High 39 44 54 Range 30 143 63 83 Temporal Low 28 32 54 75 N/A 107 136 Non-Temporal High 43 47 54 95 N/A 121 155 Non-Temporal Low 29 32 54 110 N/A 148 179 3.1 KHz Temporal High 39 41 54 135 N/A 172 209 3.1 KHz Temporal Low 29 32 54 185 N/A 222 257 3.1 KHz Non-Temporal High 42 43 54 3.1 KHz Non-Temporal Low 28 29 54 Coded High 43 47 54 3.1 KHz Coded High 42 43 54 tUL Max. Current1Draw znmi DC Input :1 i Horn 8-17.5 Volts 15cd Strobe, 30cd Cindela :fliTjI 16-33 Volts 15cd I-E$T 30cd 75cd 95cd llOcd 135cd 185cd Temporal High 98 158 54 74 121 142 162 196 245 Temporal Low 93 154 44 65 111 133 157 184 235 Non-Temporal High 106 166 73 94 139 160 182 211 262 Non-Temportal Low 93 156 51 71 119 139 162 190 239 3.lKTemporal High 93 156 53 73 119 140 164 190 242 3.lKTemporal Low 91 154 45 66 112 133 160 185 235 3.1K Non-Temporal High 99 162 69 90 135 157 175 208 261 3.1 K Non-Temporal Low 93 156 52 72 119 138 162 192 242 16-33 Volts Input 15cd 30cd 75cd 95cd llOcd 135cd 185cd S FWR Temporal High 83 107 156 177 198 234 287 Temporal Low 68 91 145 165 185 223 271 Non-Temporal High 111 135 185 207 230 264 316 Non-Temportal Low 79 104 157 175 197 235 283 3.1K Temporal High 81 105 155 177 196 234 284 3.lKTemporal Low 68 90 145 166 186 222 276 3.1K Non-Temporal High 104 131 177 204 230 264 326 3.1K Non-Temporal Low 77 102 156 177 199 234 291 Horn Tones and Sound Output Data Switch Position Sound Pattern dB 8-17.5 Volts DC 16-33 Volts DC FWR 1 Temporal High 84 89 89 2 Temporal Low 75 83 83 3 Non-Temporal High 85 90 90 4 Non-Temporal Low 76 84 84 5 3.1 KHz Temporal High 83 88 88 6 3.1 KHz Temporal Low 76 82 82 7 3.1 KHz Non-Temporal High 84 89 89 3.1 KHz Non-Temporal Low 77 83 83 S 8 9* Coded High 85 90 90 10* 3.1 KHz Coded High 84 89 89 * Settings 9 and 10 are not available on 2-wire horn be provided by the NAC. If the NAC voltage is held constantly on. strobes. Temporal coding must constant, the horn output remains AvDS865-04 • 11/17/2017 • Page 3 L-Series Dimensions 1.91" 3.46" ________ 125" -3.57"----- 1.55" 88mn1 125" 46.5 mm 88 min 32 mm (9.1 cm) )9 cm) 32 mm s•s•.•.•,•u• III 132.5mm 5.38" 5.27" .'4a!i!i!.'. III (13.7 cm) Q 5.27" 133.9 mm 111116111 A0548-00 A0547-00 A0557-00 Compact Strobe, Horn Strobe Compact Horn Compact Wall Surface Mount Back Box SBBGRL, SBBGWL b (4.85 cm) 1.91" 1.25" (3.18 mm) 5.61" 14.4 cm) Strobe, Horn Strobe A0550-00 125" 1 4.82" H k--- 1.85" 32 min (1224 cm) (4.69 cm) C OUP 5.79" 14.68 cm) CD 0 A0554.Ot A0549-00 Wall Surface Mount Back Box SBBRL/SBBWL Horn S L-Series Ordering Information Wall Horn Strobes P2RL 2-Wire, Horn Strobe, Red P2WL re Horn Strobe, White 2-Wire, Compact Horn Strobe, Red' 2-Wire, Compact Horn Stroce, vvniie P2RL-P 2-Wire, Horn Strobe, Red, Plain P2WL-P 2-Wire, Horn Strobe, White, Plain P2RL-SP 2-Wire, Horn Strobe, Red, FUEGO P2WL-SP 2-Wire, Horn Strobe, White, FUEGO P4RL 4-Wire, Horn Strobe, Red P4RW 4-Wire, Horn Strobe, White Wall Strobes SRL Strobe, Red S (ZaRL tr'' \A/hit Compact Strobe, SGWL Compact Strobe, White SRL-P Strobe, Red, Plain SWL-P Strobe, White, Plain SRL-SP Strobe, Red, FUEGO SWL-CLR-ALERT Strobe, White, ALERT r SYSTEM $ SENSOR Horns HRL Horn, Red HWL Horn, White HGRL Compact Horn, Red HGWL Compact Horn, White Accessories TR-2 Universal Wall Trim Ring Red TR-2W Universal Wall Trim Ring White SBBRL Wall Surface Mount Back Box, Red SBBWL Wall Surface Mount Back Box, White SBBGRL Compact Wall Surface Mount Back Box, Red SBBGWL Compact Wall Surface Mount Back Box, White Notes: All -P models have a plain housing (no "FIRE" marking on cover) All -SP models have "FUEGO" marking on cover All -ALERT models have "ALERT" marking on cover 3825 Ohio Avenue • St. Charles, )L 60174 @2017 System Sensor. Phone: 800-SENSOR2 • Fax: 630-377-6495 Product specifications subject to change e.ithout notice. Visit systerrrSensOr.cOm for current product information, includerg the latest version of this data sheet. www.systemsensor.com AVDS865-04 • 11/17/2017 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM . LISTING SERVICE LISTING No. 7135-1653:0503 Page 1 of 2 CATEGORY: 7135 --AUDIBLE DEVICES LISTEE: System Sensor, Unincorporated Div of Honeywell Int'l lnc.3825 Ohio Ave, St. Charles, IL 60174 Contact: Lisa Brant (203) 484-6105 Fax (203) 484-7309 Email: Iisa.brant@honeywell.com DESIGN: System Sensor Indoor 2-wire and *4..wire Models: HWL, HRL, HGWL and HGRL Horns; CHWL and CHRL Chimes; P2RL, P2WL, P2GRL, P2GWL, P2RL-P, P2WL-P, P2RL-SP, P2WL-SP, *P4RL and *P4WL Wall Horn Strobes; PC2RL, PC2WL, *PC4RL and *PC4WL Ceiling Horn Strobes; CHSRL and CHSWL Wall Chime Strobes; CHSCRL and CHSCWL Ceiling Chime Strobes; Wall Bezel Parts: BZR-F, BZR-AL, BZR-AG, BZR-EV, BZR-P, BZR-SP, BZR-PG, BZW-F, BZW-AL, BZW-AG, BZW-EV, BZW-P, BZW-SP, BZW-PG, BZGR-F, BZGR-AL, BZGR-AG, BZGR-EV, BZGR-P, BZGR-SP, BZGR-PG, BZGW-F, BZGW-AL, BZGW-AG, BZGW-EV, BZGW-P, BZGW-SP and BZGW-PG, . Ceiling Bezel Parts: BZRC-F, BZRC-AL, BZRC-AG, BZRC-EV, BZRC-P, BZRC-SP, BZRC-PG, BZWC-F, BZWC-AL, BZWC-AG, BZWC-EV, BZWC-P, BZWC-SP and BZWC-PG. Color Lens: LENS-A2, LENS-132, LENS-G2, LENS-R2, LENS-AC2, LENS-BC2, LENS-GC2 and LENS-RC2. WailTrim Rings: *TR2 and *TR2W CeilingTrim Rings: *TRC2 and *TRC2W Wall Surface Mounted Back Boxes: SBBRL, SBBGRL, SBBWL and SBBGWL, Ceiling Surface Mounted Back Boxes: Revision 08-21-2017 dcc This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct S V% operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2022 Listing Expires June 30, 2023 Authorized By: VICTOR WONG, Program Coordinator Fire Engineering Division Listing No. 7135-1653:0503 Page 2 of 2 SBBCRL and SBBCWL MP120KL 120 VAC Adapter Mounting Plate Refer to listee's data sheet for detailed product description and operational considerations. RATING: 12 VDC regulated and 24 VDC/FWR INSTALLATION: In accordance with listee's printed installation instructions, NFPA 72, applicable codes & ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, electrical rating, and UL label. APPROVAL: Listed as audible devices when used with separately listed compatible fire alarm control units. Suitable for indoor use, wall or ceiling mounted. Authority having jurisdiction should be consulted prior to installation. Refer to listee's Installation Instruction Manual for details. Revision 08-21-2017 dcc This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2022 Listing Expires June 30, 2023 Authorized By: VICTOR WONG, Program Coordinator Fire Engineering Division CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM O LISTING SERVICE LISTING No. 7125-1653:0504 Page 1 of 2 CATEGORY: 7125-- FIRE ALARM DEVICES FOR THE HEARING IMPAIRED LISTEE: System Sensor, Unincorporated Div of Honeywell Int'l lnc.3825 Ohio Ave, St. Charles, IL 60174 Contact: Lisa Brant (203) 484-6105 Fax (203) 484-7309 Email: lisa.brant@honeywell.com DESIGN: System Sensor Indoor 2-wire Models: SRL, SWL, SGRL, SGWL, SRL-P SWL-P, SRL-SP, SWL-CLR-ALERT and SWL-ALERT Wall Strobes; SCRL, SCWL and SCWL-CLR-ALERT Ceiling Strobes. Wall Bezel Parts: BZR-F, BZR-AL, BZR-AG, BZR-EV, BZR-P, BZR-SP, BZR-PG, BZW-F, BZW-AL, BZW-AG, BZW-EV, BZW-P, BZW-SP, BZW-PG, BZGR-F, BZGR-AL, BZGR-AG, BZGR-EV, BZGR-P, BZGR-SP, BZGR-PG, BZGW-F, BZGW-AL, BZGW-AG, BZGW-EV, BZGW-P, BZGW-SP and BZGW-PG, Ceiling Bezel Parts: BZRC-F, BZRC-AL, BZRC-AG, BZRC-EV, BZRC-P, BZRC-SP, BZRC-PG, BZWC-F, BZWC-AL, BZWC-AG, BZWC-EV, BZWC-P, BZWC-SP and BZWC-PG. . Color Lens: LENS-A2, LENS-B2, LENS-G2, LENS-R2, LENS-AC2, LENS-BC2, LENS-GC2 and LENS-RC2. WallTrim Rings: TR2 and TR2W CeilingTrim Rings: TRC2 and TRC2W. Wall Surface Mounted Back Boxes: SBBRL, SBBGRL, SBBWL and SBBGWL, Ceiling Surface Mounted Back Boxes: SBBCRL and SBBCWL Refer to listee's data sheet for detailed product description and operational considerations. *Rev 04-04-19 gt øri4, This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2022 Listing Expires June 30, 2023 Authorized By: VICTOR WONG, Program Coordinator Fire Engineering Division Listing No. 7125-1653:0504 Page 2 of 2 RATING: Regulated 12 VDC setting: 8-17.5 VDC Regulated 24 VDC/fwr setting: 16-33 VDC S INSTALLATION: In accordance with listee's printed installation instructions, NFPA 72, applicable codes & ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, electrical rating, and UL label. APPROVAL: Listed as two wire strobe units used for synchronous application when used with separately listed compatible fire alarm control units. Suitable for indoor use, vertical wall or horizontal ceiling mounted. *Listed with software code, S05-0048-001 for low temperature compensation. Authority having jurisdiction should be consulted prior to installation. Refer to listee's Installation Instruction Manual for details. *Rev 04-04-19 gt This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2022 Listing Expires June 30, 2023 Authorized By: VICTOR WONG, Program Coordinator Fire Engineering Division -GENESIS- arlenum Rated Power Limited Fire Alarm Cable art Number: 4513 14 AWG 2 Solid Conductors Ratings Approvals Construction Conductor Conductor Count Insulation Insulation Colors Lay Length Shielding Rip Cord Jacket Overall Diameter rint Legend Properties Operating Voltage DC Resistance Capacitance Impedance FPLP, CL3P, FT6 UL Listed 14 AWG Solid Bare Copper 2 Plenum PVC (0.008" nom.) Black, Red 5.25" nom. N/A Yes Plenum PVC (0.015" nom.) 0.206" nom. GENESIS P/N 4513 2C I4AWG E175105 (UL) FPLP OR CL3P FT6 75C (RoHS) W/O# XXXXXX-XXXXXXX XXXXFT A B C D E F 1 23456789 300 Volts max. 2.57 Ohms/1000' at 20°C 24.1 pF/ft. nom. 63 Ohms nom. Temperature -20°C to 75°C Flame Rating NFPA 262 (Plenum); CSA C22.2 No. 2556 (FT6) RoHS Compliant Yes Country of Origin USA S Published: 2018-10-19 -GENESIS- Plenum Rated Power Limited Fire Alarm Cable 4 art Number: 4506 18 AWG 2 Solid Conductors Ratings Approvals Construction Conductor Conductor Count Insulation Insulation Colors Lay Length Shielding Rip Cord Jacket Overall Diameter Orint Legend Properties Operating Voltage DC Resistance Capacitance Impedance FPLP, CL3P, FT6 UL Listed 18 AWG Solid Bare Copper 2 Plenum PVC (0.007" nom.) Black, Red 2.25" nom. N/A Yes Plenum PVC (0.015" nom.) 0.136" nom. GENESIS P/N 4506 2C 18AWG E175105 (UL) FPLP OR CL3P FT6 75C (RoHS) W/O# XXXXXX-XXXXXXX XXXXFT A B C D E F 1 2 3 4 5 6 7 8 9 300 Volts max. 6.52 Ohms/1000' at 20°C 32.1 pF/ft. nom. 58 Ohms nom. Temperature -20°C to 75°C Flame Rating NFPA 262 (Plenum); CSA C22.2 No. 2556 (FT6) RoHS Compliant Yes Country of Origin USA S Published: 2018-10-19 -GENESIS- Plenum Rated Power Limited Fire Alarm Cable 4 art Number: 4507 18 AWG 4 Solid Conductors Ratings Approvals Construction Conductor Conductor Count Insulation Insulation Colors Lay Length Shielding Rip Cord Jacket Overall Diameter Orint Legend Properties Operating Voltage DC Resistance Capacitance Impedance FPLP, CL3P, FT6 UL Listed 18 AWG Solid Bare Copper 4 Plenum PVC (0.007" nom.) Black, Red, Green, Yellow 4.50" nom. N/A Yes Plenum PVC (0.015" nom.) 0.157" nom. GENESIS P/N 4507 4C I8AWG E175105 (UL) FPLP OR CL3P FT6 75C (RoHS) WIO# XXXXXX-XXXXXXX XXXXFT A B C D E F 1 23456789 300 Volts max. 6.52 Ohms/1000' at 20°C 32.1 pF/ft. nom. 58 Ohms nom. Temperature -20°C to 75°C Flame Rating NFPA 262 (Plenum); CSA C22.2 No. 2556 (FT6) RoHS Compliant Yes Country of Origin USA Published: 2018-10-19 -GENESIS- Plenum Rated Power Limited Fire Alarm Cable 'art Number: 4508 18 AWG 6 Solid Conductors Ratings Approvals Construction Conductor Conductor Count Insulation Insulation Colors Lay Length Shielding Rip Cord Jacket Overall Diameter Orint Legend Properties Operating Voltage DC Resistance Capacitance Impedance FPLP, CL3P, FT6 UL Listed 18 AWG Solid Bare Copper 6 Plenum PVC (0.007" nom.) Black, Red, Green, Yellow, Brown, Blue 5.25" nom. N/A Yes Plenum PVC (0.015" nom.) 0.188' nom. GENESIS P/N 4508 6C 18AWG E175105 (UL) FPLP OR CL3P FT6 75C (RoHS) W/O# XXXXXX-XXXXXXX XXXXFT A B C D E F 1 23456789 300 Volts max. 6.52 Ohms/1000' at 20°C 32.1 pFlft. nom. 58 Ohms nom. Temperature -20°C to 75°C Flame Rating NFPA 262 (Plenum); CSA C22.2 No. 2556 (FT6) RoHS Compliant Yes Country of Origin USA Published: 2018-10-19 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 7161-1487:0100 Page 1 of 1 CATEGORY: 7161 -- CABLES-FIRE PROTECTIVE SIGNALING LISTEE: GENESIS CABLE SYSTEM7701 95TH Street, Pleasant Prairie, WI 53158 Contact: Mahinay Lovell (262) 947-0720 Fax (262) 947-0724 Email: Lovell.Mahinay@resideo.com DESIGN: Model FPL, FPLP and FPLR power limited fire protective signaling cable. Conductors: In accordance with the standard Insulation: GPT-150, Foam PP, HOPE or LOPE Assembly: 2 to 12 insulated conductors Shield (Optional): Aluminum polyester tape shield Braid (Optional): Metal braid over cable core Jacket: PVC compound Gitto/Global Corp., Grade GA-91-84, GPT-45, GA5033, GA93016 Refer to listee's data sheet for detailed product description and operational considerations. INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances, NEC Article 760, and in a manner acceptable to the authority having jurisdiction. MARKING: Listees name, Type 'FPL" and UL label. APPROVAL: Listed as power-limited fire protective signaling cables. Rev. 06-18-2003 This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct . VI operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2022 Listing Expires June 30, 2023 Authorized By: VICTOR WONG, Program Coordinator Fire Engineering Division laox 1" BY SPACE AGE ELECTRONICS FEATURES fowN4 18 gauge cold rolled steel construction with red powder coat and white lettering UL Dimensions are 12" wide x © 13" tall and 2 1/4" deep LISTED Stainless steel piano hinge Two key ring hooks to hold - system keys : Business card holder for key , contacts Slide tab allows user to select USB-C or Micro USB connector to download from 8GB digital flash memory DCD Computer Desk Kit (sold separately) holds enclosure door open at a 90 degree angle with a snap on cable for a convenient S working surface in the field. Includes velcro strap for securing your laptop. SRO ACE-11 System Record Documents Store important system documents in a secure location with a cabinet built specifically to meet the requirements of NFPA 727.7.2.4. The number one goal at Space Age is to manufacture code compliant solutions, and the SAD is just that. NFPA 72 7.7.2.1 states, "With every new system, a documentation cabinet shall be installed at the system control unit or other approved location at the protected premises." The SAD includes our innovative 8GB flash drive slide tab that allows the user to select a USB-C or Micro USB connector to access records electronically (See NFPA 72 7.5.6.7). SPECIFICATIONS The SRD System Record Documents Box shall be UL Listed, constructed of 18 gauge cold rolled steel. It shall have a powder coat finish. The cover shall be permanently screed with 1" high lettering "SYSTEM RECORD DOCUMENTS" with white indelible ink. The access door shall be locked with a 3/4" barrel lock and there will be a 12" stainless steel piano hinge. The SAD will have a minimum of 8 gigabyte digital flash memory drive with a slide tab that allows user to select USB-C or Micro USB connector for uploading and downloading information. The enclosure will supply 4 mounting holes. Inside will accommodate standard 8 1/2" x 11" manuals and document records. A legend sheet will be attached to the door for system required documentation, key contacts and system information. The enclosure shall also provide 2 key ring holders with a location to mount standard business cards for key contact personnel. CUSTOM COLORS AND BRANDING AVAILABLE Pg. 1/2 Ac OX 4klMENSIONS 2.35 'I II 1.63 1 -I--- SY87EN RECORD .88 12.59 1 13.00 316 11.75 7NO INFOR D System Record Documents =Box - Red P/N# SSU00690 SRD System Record Documents Box - Red with your custom screened logo PIN# SSU01689 SRD System Record Documents Box - Black P/N# SSU01690 SAD System Record Documents Box - Black with your custom screened logo P/N# SSU00616 DCD Computer Desk Kit S www.lsae.com I toll free 1.800.486.1723 1 fax 508.485.4740 E] © copyright 2018 Space Age Electronics, Inc. I This document subject to change without notice I LT1 0641 1 Rev. E NFPA• ADA Pg. 2/2 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM . LISTING SERVICE LISTING No. 7300-0553:0110 Page 1 of 1 CATEGORY: 7300 -- FIRE ALARM CONTROL UNIT ACCESSORIES/MISC. DEVICES LISTEE: SPACE AGE ELECTRONICS58 Chockett Road, Sterling, MA 01564 Contact: Robert Scholl (508) 485-0966 Fax (508) 485-4740 Email: bobs@lsae.com DESIGN: Models TC2-32, TC1-18, TCX/A 64, TCX/D 128, ACE/A, AC2, ACE/D, IF-2, IFi, lFX/A and IFXID enclosures. Models ACE-1 1, ACE-12 and ACE-13, *ACE2424, *ACE 3036, *ACE 2436, *ACE 3048 document cabinets. Refer to listee's data sheet for detailed product description and operational considerations. INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number and UL label. APPROVAL: Listed as fire alarm equipment enclosures and document cabinets for use with listee's fire alarm equipment. Refer to listee's Installation Instruction Manual for details. 02-09-16 dc This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct vt operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2022 Listing Expires June 30, 2023 Authorized By: VICTOR WONG, Program Coordinator Fire Engineering Division ftCEBOX .1" BY SPACE AGE ELECTRONICS ELOCK-FA CIRCUIT LOCKOUT KIT Circuit lockout tab Hex key Breaker, legend, and door labels NFPA 2016 CODE COMPLIANCE 10.6.5.2 Circuit Identification and Accessibility. 10.6.5.2.1 The location of the branch circuit disconnecting means shall be permanently identified at the control unit. 10.6.5.2.2 System circuit disconnecting means shall be permanently identified as to its purpose in accordance with the following: "FIRE ALARM" for fire alarm systems "EMERGENCY COMMUNICATIONS" for emergency communications systems "FIRE ALARM/ECS" for combination fire alarm and emergency communications systems 10.6.5.2.3 For fire alarm and/or signaling systems, the circuit disconnecting means shall have a red marking. 10.6.5.2.4 The red marking shall not damage the overcurrent protective devices or obscure the manufacturer's markings. 10.6.5.2.5 The circuit disconnecting means shall be accessible only to authorized personnel. 10.6.5.3 Mechanical Protection. The branch circuit(s) and connections shall be protected against physical damage. 10.6.5.4 Circuit Breaker Lock. Where a circuit breaker is the disconnecting means, a listed breaker locking device shall be installed. www.lsae.com I toll free 1.800.486.17231 fax 508.485.4740 ] NAM j © Copyright 2019 Space Age Electronics, Inc. I This document is subject to change without notice I SS10101 I Rev. 2 NFPK ADA Control of Gas Generation The design of Yuasa's NP batteries incorporates the very latest Layout oxygen recombination technology to effectively control the generation of gas during normal use. Low Maintenance Operation Due to the perfectly sealed construction and the recombination of gasses within the cell, the battery is almost maintenance free. ED Terminals Fason tab: 187 A Faston tab: 250 D uv INc4-1'Th'1 'l .250 B.5 ' .310 7.00 T 1 .185 4.10 .250 5.35 41 1.5G q .031 0.80 .004 0.10 .031 NP SERIES - NP7.5-12 Reliability is your Security ing the latest advance design Oxygen rwuombination Technology, Yuasa have applied their 80 years of experience in the lead acid battery field to produce the optimum design of Sealed Lead Acid batteries. FEATURES Superb recovery from deep discharge. Electrolyte suspension system. Gas Recombination. Multipurpose: Float or Cyclic use. Usable in any orientation Superior energy density. Lead calcium grids for extended life. Manufactured World wide. Application specific designs. Technica Features Sealed Construction Yuasa's unique construction and sealing technique ensures no electrolyte leakage from case or terminals. trolyte Suspension System batteries utilize Yuasa's unique electrolyte suspension incorporating a microfine glass mat to retain the maximum amount of electrolyte in the cells. The electrolyte is retained in the separator material and there is no free electrolyte to escape from the cells. No gels or other contaminants are added. Terminals NP batteries are manufactured using a range of terminals which vary in size and type. Please refer to details as shown. Operation in any Orientation The combination of sealed construction and Yuasa's unique electrolyte suspension system allows operation in any orientation, with no loss of performance or fear of electrolyte leakage. Valve Regulated Design The batteries are equipped with a simple, safe low pressure venting system which releases excess gas and automatically reseals should there be a build up of gas within the battery due to severe overcharge. Note. On no account should the battery be charged in a sealed container. General Specifications Nominal Capacity (Ah) NP7.5-12 20hr to I .75vpc 30°C 7.5 1 0hr to 1 .75vpc 20°C 6.4 5hrto 1.70vpc200C 5.9 1 hrtol .60vpc201C 4.2 Voltage 12 Energy Density (Wh.L.20hr) 91 Specific Energy (wh.kg20hr) 32 Int. Resistance (m.Ohms) 25 Maximum discharge (A) 40/75 Short Circuit current (A) 210 Dimensions (mm) Length 151 Width 65 Height overall 97.5 Weight (Kg) 2.65 Terminal AID Layout 4 Terminal Torque Nm - NP SERIES - NP7.5-12 Lead Calcium Grids [he heavy duty lead calcium alloy grids provide an extra margin of erformance and life in both cyclic and float applications and give .11 eled recovery from deep discharge. Long Cycle Service Life )epending upon the average depth of discharge, over a thousand lischarge/charge cycles can be expected. Float Service Life [he expected service life is five years in float standby applications. Separators [he use of the special separator material provides a very efficient nsulation between plates preventing inter-plate short circuits and )rohibiting the shedding of active materials. CYCLIC RECHARGE REGIME BUN, Ch4rge 84 SMHdSY Charge • 0.3 150 17 111,10.1 TI,no.U2 0.25 125 16 'CSU,gaVoB2n,. Change Voltage 14 12 0 DISCHARGE CHARACTERISTICS RVES AT 252C (772F) FOR 12V Fl 6'I Note: C Given capacity 88 stated on each battery in Ah BATTERY BATTERY NP AT 25.0 (7FF) 13.0 6.5---- - -- = - 12.0 6.0 - - - - - - lII \ ). t11.0- IN 10.0 5.5 - - - - -4-. - -- 9.0 4.0--- - 7-4---- 8.0 4.0_ - - - - - - - - - IC 2 8 010 20 40 80 2 4 6 1 20 MINUTES HOURS DISCHARGE TIME FLOAT SERVICE LIFE NP RANGE (AH%) TESTING CONDITIONS: FLOATING VOLTAGE: 2.275VPC AMBIENT TEMPERATURE. arC )ErFTO 721') 12(. bc, o 8). 6C <UJ 4). ZIM 2). Lii> a.< C 1 2 3 4 5 5.5 LIFE (YEARS) Long shelf Life The extremely low self discharge rate allows the battery to be stored for extended periods up to one year at normal ambient temperatures with no permanent loss of capacity. Operating Temperature Range The batteries can be used over a broad temperature range permitting considerable flexibility in system design and location. Charge - 15'C to 50'C Discharge - 201C to 601C Storage -20CC to 501C (fully charged battery) SELF DISCHARGE CHARACTERISTICS (5)100 S.0 (321') 75 0 (350 a 2S.0 40.C(104' (86.F)r 25 0 3 6 9 12 15 18 STORAGE TIME (MONTHS) FLOAT CHARGE CHARACTERISTICS 0 0.25CA- 2.275VPC CONSTANT VOLTAGE CHARGING (SI (.CA) (0) AT2O'C)68'F) 140 CHARG!Y''0_ - - - 5) 120 0.25 7.50 15.5 100 \ 7.00 - - - CHARGE VOLTAGE 14.0 80 so 6.50 AFTER 100% 13.0 RGE AFTER 50% RGE 40 :: 8.00 ,' ::: 20 :NT -.-. 5.50 )246 8'0 1214161820 CHARGING TIME (HOURS) TYPICAL DISCHARGE CHARAC- TERISTICS NP RANGE CYCLE SERVICE LIFE IN RELATION TO DEPTH OF DISCHARGE TESTING CONDITIONS: DISCHARGE CURRENT 0.17C AltO. (F.V 1.7V/CELL CHARGING CURRENT 0.09C Anp, CHARGING VOLUME, 125% OF DISCHARGED CAPACITY (Al-IS) AMBIENT TEMPERATURE, 20C TO 25C (68-F TO 77-F) 0 150% 55% 30%DEPT 000 DOD OF DISCHI ROE no NUMBER OF CYCLES ! Yuasa Battery Inc. Distributed by 2901 Montrose Ave Laureldale, PA 19605 www.yuasabatteries.com u ASA Registered number 1548820 Cat. No. I NP7.5-12 January 08