HomeMy WebLinkAbout1373 MAGNOLIA AVE; ; AS120053; Permit5/30/25, 11:56 AM AS120053 Permit Data
City of Carlsbad
Sprinkler Permit
Job Address: 1373 MAGNOLIAAV
Permit Type: SPRINK
Parcel No: 2052808100
Lot #: 0
Reference No.:
Permit No: A5120053
Status: APPROVED
Applied 5/22/2012
Approved: 5/25/2012
Issued: 5/25/2012
PC #: Inspector:
Project Title: 1373 MAGNOLIA AVE-RESIDENCE NEW RESIDENTIAL
Applicant:
SYMONS FIRE PROTECTION
SUITE R
1050 PIONEER WAY
EL CAJON, CA
619-588-6364
Owner:
Fees ($) Add'I Fees ($) Total ($) Balance ($)
393 0 393 0
about:blank 1/1
HYDRONICS: RESIDENTIAL FIRE SPRINKLER HY
D
R
A
U
L
I
C
S
4
.
3
1
- SUBMITTAL.
ENGINEERS : SYMONS FIRE PROTECTION. (6
1
9
)
5
8
8
-
6
3
6
4
.
Oyu LICENSE : 682025
DESIGNER : CANDI CAUDILLO
DATE : '05-19-2012
9
FILE : 12-102
JOB NAME : MAGNOLIA LOT 2
16'FT FLAT LOCATION : 1373 MAGNOLIA AVENUE, CAR
L
S
B
A
D
,
C
A
DESIGN DATA.
DESIGN CRITERION:
MIN SPR FLOW
AREA PER SPRINKLER
TOTAL CALCULATED AREA
TOTAL SPRINKLERS CALCULATED
NFPA 13-D
13 Gpm
256 Sq Ft
512 Sq Ft
2 Heads
FLOW DATA.
TOTAL SPRINKLER FLOW
DOMESTIC DEMAND
TOTAL WATER REQUIRED
BASE OF RISER NODE: 11
26.0 Gpm
5.0 Gpm
31.0 Gpm
FLOW: 31.0 Gpm PRESSURE: 22.8 Psi
AWA AS 3. U,
AUTHORITY HAVING JURISDICTION : CARL
S
B
A
D
F
I
R
E
D
E
P
T
.
PHONE : 760-602-4666
HYbRONICS: RESIDENTIAL FIRE SPRINKLERHYDRAULICS 4.31
- SUBMITTAL.
ENGINEERS : SYMONS FIRE PROTECTION. (619) 588-6364. ADDRESS : 1050 Pioneer Way, Suite R, El Cajon CA 92020. Date: 05-19-2012 File: C:\RESDEN43\12-102.RES JOB : MAGNOLIA LOT 2 16'FT FLAT
SOURCE I STATIC : 75.0 Psi RESIDUAL : 74.0 Psi FLOW : 31 Gpm
DESIGN SPRINKLER MANUF : TYCO MODEL : LF II SPRINKLER Q : .0 Gpm VALVE : .0 Psi I SPRINKLER P : .0 Psi METER : 4.0 Psi
NODE ELEVATION K- PRESSURE DISCHARGE NO. Feet FACTOR Psi Gpm
1 25.0 4.9 7.1 13.1
2 25.0 4.9 7.0 13.0
3 25.0 7.5 4 25.0 7.6
5 25.0 8.3 6 25.0 8.7
7 25.0 9.3
8 15.0 13.9
9 15.0 15.0
10 15.0 17.2
11 9.0 22.8 5.0 DOME 12 5.0 27.8
13 3.0 39.5
14 .0 SOURCE 50.8 31.0
SPRINKLERS FLOWING : 2
AREA PER SPRINKLER : 256 Sq Ft
TOTAL DESIGN AREA : 512 Sq Ft
Page .1
REQUIRED DENSITY : Gpth/Sq Ft COMPUTED DENSITY : .051 Gpm/Sq Ft
TOTAL SPRINKLER FLOW : 26.0 Gpm TOTAL DOMESTIC FLOW : 5 Gpm
TOTAL WATER REQUIRED : 31.0 Gpm
TOTAL SPRINKLER PRESS : 46.8 Psi WATER METER LOSS : 4.0 Psi VALVE FIXED LOSS : .0 Psi
Copyright (2002) SUPPLY PRESS AVAILABLE : 74.0 Psi by DEMAND PRESS REQUIRED : 50.8 Psi Hydronics Engineering PRESSURE CUSHION : 23.2 Psi 34119 Fremont Bi, Suite 609
Fremont, Ca., 94555
MAXIMUM VELOCITY : 12.8 F/S (510) 487-9160
HYDRONICS: RESIDENTIAL FIRE SPRINKLER HYDRAULICS 4.31
- SUBMITTAL. Page 2
ENGINEERS : SYMONS FIRE PROTECTION. (619) 588-6364.
ADDRESS :1050 Pioneer Way, Suite R, El Cajon CA 92020.
Date: 05-19-2012 File: C:\RESDEN43\12-102.RES
JOB : MAGNOLIA LOT 2 16'FT FLAT
PIPE BEG FLOW K-FACTOR LENGTH C-FACTOR PRESSURE NO. Gpm FITTING TYPE FTG FR- LOSS Psi END DIAMETER TOTAL (Psi/Ft)
1 q= 13.1 K=
-------------------------------------------------------------------------------
4.9 L= 4.0 Pt 7.1 Pt 7.1 1 Q= 13.1 F= 1B1L F= 12.0 C= 150 Pe .0 Pv -.1 Vel= 4.4 D= 1.101 TL= 16.0 .0309 Pf .5 Pn 7.0 4 Pt 7.6
2 q= 13.0 K= 4.9
--------------------------------------------------------------------------
L= 5.0 Pt 7.0 Pt 7.0 2 Q= 13.0 F= 1B1L F= 12.0 C= 150 Pe .0 Pv -.1 Vel= 4.4 D= 1.101 TL= 17.0 .0306 Pf .5 Pn 6.9 3 Pt 7.5
3 q= .0 K= .0
--------------------------------------------------------------------------
L= 5.0 Pt 7.5 Pt 7.5 3 Q= 4.1 F= 2B F= 10.0 C= 150 Pe .0 Pv .0 Vel= 1.4 D= 1.101 TL= 15.0 .0037 Pf .1 Pn 7.5 4 Pt 7.6
4 q= .0 K= .0
--------------------------------------------------------------------------
L= 3.0 Pt 7.6 Pt 7.6 4 Q= 17.2 F= 2B F= 10.0 C= 150 Pe .0 Pv -.2 Vel= 5.8 D= 1.101 TL= 13.0 .0514 Pf .7 Pn 7.4 5 Pt 8.3
3 q= .0 K= .0
--------------------------------------------------------------------------
L= 47.0 Pt 7.5 Pt 7.5 5 Q= 8.8 F= 5R1L3B F= 27.0 C= 150 Pe .0 Pv -.1 Vel= 3.0 D= 1.101 TL= 74.0 .015 Pf 1.1 Pn 7.5 6 Pt 8.7
6 q= .0 K= .0
--------------------------------------------------------------------------
L= 27.0 Pt 8.7 Pt 8.7 6 Q= 8.8 F= 1R3B F= 16.0 C= 150 Pe .0 Pv -.1 Vel= 3.0 D= 1.101 TL= 43.0 .015 Pf .6 Pn 8.6 7 Pt 9.3
5 q= .0 K= .0
--------------------------------------------------------------------------
L= 49.0 Pt 8.3 Pt 8.3 7 Q= 8.4 F= 5R1L3B F= 27.0 C= 150 Pe .0 Pv -.1 Vel= 2.8 D= 1.101 TL= 76.0 .0136 Pf 1.0 Pn 8.2 7 Pt 9.3
5 q= .0 K= .0.
--------------------------------------------------------------------------
L= 46.0 Pt 8.3 Pt 8.3 8 Q= 8.8 F= 3B4L F= 43.0 C= 150 Pe 4.3 Pv -.1 Vel= 3.0 D= 1.101 TL= 89.0 .0149 Pf 1.3 Pn 8.2 8 Pt 13.9
8 q= .0 K= .0
--------------------------------------------------------------------------
L= 46.0 Pt 13.9 Pt 13.9. 9 Q= 8.8 F= 6R3B1L F= 28.0 C= 150 Pe .0 Pv -.1 Vel= 3.0 D= 1.101 TL= 74.0 .0149 Pf 1.1 Pn 13.9 9 Pt 15.0
HYDRONICS: RESIDENTIAL FIRE SPRINKLER HYDRAULICS 4.31 - SUBMITTAL. Page 3
ENGINEERS : SYMONS FIRE PROTECTION. (619) 588-6364.
ADDRESS : 1050 Pioneer Way, Suite R, El Cajon CA 92020.
Date: 05-19-2012 File: C:\RESDEN43\12-102.RES
JOB : MAGNOLIA LOT 2 161 FT FLAT
PIPE BEG FLOW K-FACTOR LENGTH C-FACTOR PRESSURE
NO. Gpm FITTING TYPE FTG FR- LOSS Psi
END DIAMETER TOTAL (Psi/Ft)
7 q= .0 K= .0
-------------------------------------------------------------------------------
L= 15.0 Pt 9.3 Pt 9.3
10 Q= 17.2 F= 1B1L F= 12.0 C= 150 Pe 4.3 Pv -.2
Vel= 5.8 D= 1.101 TL= 27.0 .0516 Pf 1.4 Pn 9.1
9 Pt 15.0
9 q= .0 K= .0
--------------------------------------------------------------------------
L= 7.0 Pt 15.0 Pt 15.0
11 Q= 26.0 F= 1B1L F= 12.0 C= 150 Pe .0 Pv -.5
Vel= 8.8 D= 1.101 TL= 19.0 .1108 Pf 2.1 Pn 14.5
10 Pt 17.2
10 q= .0 K= .0
--------------------------------------------------------------------------
L= 6.0 Pt 17.2 Pt 17.2.
12 Q= 26.0 F= 1C4R1S1L
21.0 C= 150 Pe 2.6 Pv -.5
Vel= 8.8 D= 1.101 TL= 27.0 .1108 Pf 3.0 Pn 16.6
11 Pt 22.8
11 q= 5.0 DOME
--------------------------------------------------------------------------
L= 5.0 Pt 22.8 Pt 22.8
13 Q= 31.0 F= 1G1B2L F= 10.0 C= 150 Pe 1.7 Pv -1.0
Vel= 12.1 D= 1.025 TL= 15.0 .2173 Pf 3.3 Pn 21.8
12 Pt 27.8
12 q= .0 K= .0
--------------------------------------------------------------------------
L= 210.0 Pt 27.8 Pt 27.8
14 Q= 31.0 F= 11C F= 11.0 C= 150 Pe .9 Pv -.3 Vel= 6.5 D= 1.394 TL= 221.0 .0486 Pf 10.7 Pn 27.5
13 Pt 39.5
13 q= .0 K= .0
--------------------------------------------------------------------------
1= 20.0 Pt 39.5 Pt 39.5
15 Q= 31.0 F= 2C F= 4.0 C=150 Pe 1.3 Pv-1.1
Vel= 12.8 D= .995 TL= 24.0 .2511 Pf 6.0 Pn 38.4
14
-------------------------------------------------------------------------- Pt 46.8
Meter = 4.0
Q= 31.0 <<<
--------------------------------------------------------------------------
-------------------------------------------------------------------------- SOURCE >>> Pt 50.8
E=>45-Elb L=>90-Elb B=>TeeBch R=>TeeRun C=>CouPlg S=>SwgChk G=>GatVlv
HYDRONICS: RESIDENTIAL FIRE SPRINKLER HYDRAULICS 4.2 - SUBMITTAL
ENGINEERS : SYF'JONS FIRE PROTECTION. (619) 588-6364.
ADDRESS : 1050 Pioneer Way, Suite R, El Cajon CA 92020.
DATE : 05-19-2012 FILE : C:\RESDEN43\12-102.RES
JOB : MAGNOLIA LOT 2 16'FT FLAT
PSI FIRE SPRINKLER HYDRAULIC GRAPH
100
90 ----
80
-e
70
60
40
50
30
20
10
10 15 20 25
° Supply Curve
Static : 75.0
Resid : 74.0
Flow :31.0
30 35 40 45 50
FLOW - Gpm
Demand Curve
Avi Pr : 74.0 @ 31
Req Pr : 50.8 @ 31
Pr Cush: 23.2
Copyright: Hydronics Engineering, 2002.
34119 Fremont El, Suite 609,
Fremont, CA. 94555.
(510) 487-9160.
tUCO Fire Suppression
& Building Products
Technical Services 800-381-9312 1+1-401-781-8220
www.tyco-fire.com
0
rapid esponse
HOME FARE SPRINKLER SYSTEM
,!flIMi Residential Sprinklers
The TYCO RAPID RESPONSE Series
LFII Residential Flat-Plate Concealed
Pendent Sprinklers (1Y2524) are decora-
tive, fast response, fusible solder sprin-
klers designed for use in residential oc-
cupancies such as homes, apartments,
dormitories, and hotels.
The Cover Plate/Retainer Assembly con-
ceals the sprinkler operating compo-
nents above the ceiling. The flat profile
of the Cover Plate provides the optimum
aesthetically appealing sprinkler design.
Additionally, the concealed design of the
Series LFII Residential Flat-Plate Con-
cealed Pendent Sprinklers provides 1/2
inch (12,8 mm) vertical adjustment. This'
adjustment provides a measure of flex-
ibility when cutting fixed sprinkler drops.
The Series LFII Residential Fiat-Plate
Concealed Pendent Sprinklers are in-
tended for use in the following systems:
wet and dry pipe residential sprin-
kler systems for one- and two-fam-
ily dwellings and mobile homes per
NFPA 13D
wet and dry pipe residential sprin-
kler systems for residential occu-
pancies up to and including four sto-
ries in height per NFPA 13R
wet and dry pipe sprinkler systems
for the residential portions of any
occupancy per NFPA 13.
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its components
and cause the sprinkler to fall to
operate in a fire situation or cause it
to operate prematurely.
Historically, residential sprinklers, based
on their Listing, have been limited to
wet pipe sprinkler systems to assure
speed of water delivery for a given pre-
scribed design area (number of design
sprinklers).
The Listing for the Series LFII Residen-
tial Flat-Plate Concealed Pendent Sprin-
kler now offers the laboratory approved
option of designing dry pipe residential
sprinkler systems.
For dry systems, as described in U.S.
Patent 7,712,543, through extensive
testing it has been determined that the
number of design sprinklers (hydrau-
lic design area) for the Series LFII Resi-
dential Flat-Plate Concealed Sprinklers
(1Y2524) need not be increased over the
number of design sprinklers (hydrau-
lic design area) specified for wet pipe
sprinkler systems, as is customary for
density/area sprinkler systems designed
per NFPA 13,13D, or 13R.
Consequently, the Series LFII Residen-
tial Flat-Plate Concealed Sprinklers
(TY2524) offer the features of non-wa-
ter filled pipe in addition to not having to
increase the number of design sprinklers
(hydraulic design area) for systems de-
signed to NFPA 13,13D, or 13R. Non-
water filled pipe will permit options for
areas sensitive to freezing.
The Series LFII Residential Fiat-Plate
Concealed Pendent Sprinkler has a 4.9
(70,6) K-factor that provides the required
residential flow rates at reduced pres-
sures, enabling smaller pipe sizes and
water supply requirements.
This sprinkler has been designed with
heat sensitivity and water distribution
characteristics proven to help in the con-
trol of residential fires and to improve
the chance for occupants to escape or
be evacuated.
The Series LFII Residential Flat-Plate
Concealed Pendent Sprinklers are
shipped with a Disposable Protective
Cap. The Protective Cap protects the
sprinkler during ceiling installation or
finish. After ceiling installation is com-
plete, the Protective Cap is removed
and the Cover Plate/Retainer Assem-
bly is installed. Removing the Protec-
tive Cap is required for proper sprinkler
performance.
The Series LFl/ Residential Rat-Plate
Concealed Pendent Sprinklers (7Y2524)
described herein must be installed and
maintained in compliance with this doc-
ument and with the applicable standards
of the National Fire Protection Associa-
tion, in addition to the standards of any
authorities having jurisdiction. Failure
to do so may impair the performance
of these devices.
Owners are responsible for maintaining
their fire protection system and devices
in proper operating condition. The in-
stalling contractor or sprinkler manu-
facturer should be contacted with any
questions.
Model/Sprinkler
Identification
Number (SIN)
TY2524
Page 1 of 6 AUGUST 2011 TFP443
TFP443
Page 2of6
WET PIPE SYSTEM
Minimum Flow and Residual Pressure
Horizontal Ceiling (°''°l Sloped CeilingldM Sloped Ceiling(.d.e)
Maximum
Coverage Maximum
Area Spacing (Maximum 2-inch rise (Greater than 2-inch rise (Greater than 4-inch rise Ft Ft Ft. for 12-inch run) up to maximum 4-inch up to maximum 8-inch (m x m) (m) rise for 12-inch run) rise for 12-inch run)
160°F (71°C) 160°F (71°C) 160°F (71°C) Sprinkler Sprinkler Sprinkler 12 x 12 12 13 GPM (49,2 LPM) 17 GPM (64,3 LPM) 17 GPM (64,3 LPM) (3,7 x 3,7) (3,7) 7.0 psi (0,48 bar) 12.0 psi (0,83 bar) 12.0 psi (0,83 bar) 14 x 14 14 13 GPM (49,2 LPM) 17 GPM (64,3 LPM) 17 GPM (64,3 LPM) (4,3 x 4,3) (4,3) 7.0 psi (0,48 bar) 12.0 psi (0,83 bar) 12.0 psi (0,83 bar) 16 x 16 16 13 GPM (49,2 LPM) 17 GPM (64,3 LPM) 17 GPM (64,3 LPM) (4,9 x 4,9) (4,9) 7.0 psi (0,48 bar) 12.0 psi (0,83 bar) 12.0 psi (0,83 bar) 18 x 18 18 17 GPM (64,3 LPM) 22 GPM (83,3 LPM) 22 GPM (83,3 LPM) (5,5 x 5,5) (5,5) 12.0 psi (0,83 bar) 20.2 psi (1,39 bar) 20.2 psi (1,39 bar) 20 x 20 20 20 GPM (75,7 LPM) 24 GPM (90,8 LPM) 24 GPM (90,8 LPM) (6,1 x 6,1) (6,1) 16.7 psi (1,15 bar) 24.0 psi (1,65 bar) 24.0 psi (1,65 bar) For coverage area dimensions less than or between those indicated, use the minimum r
e
q
u
i
r
e
d
f
l
o
w
f
o
r
t
h
e
n
e
x
t
h
i
g
h
e
s
t
c
o
v
e
r
a
g
e
a
r
e
a
f
o
r
w
h
i
c
h
Hydraulic Design section under the Design Criteria are stated.
The Minimum Flow requirement is based on minimum flow in GPM (LPM) from each sprin
k
l
e
r
.
T
h
e
a
s
s
o
c
i
a
t
e
d
r
e
s
i
d
u
a
l
p
r
e
s
s
u
r
e
s
a
r
e
c
a
l
c
u
l
a
t
e
d
u
s
i
n
g
the nominal K-factor. Refer to "Hydraulic Design" in the Design Criteria section for details. For NFPA 130 2010 applications, Horizontal Ceiling criteria shall be used for certain sloped
c
e
i
l
i
n
g
c
o
n
f
i
g
u
r
a
t
i
o
n
s
u
p
t
o
8
:
1
2
p
i
t
c
h
.
Refer to TIA 1028R for allowed sloped ceiling limitations when using horizontal ceiling criteria For NFPA 13R applications, Horizontal Ceiling criteria may be used for sloped ce
i
l
i
n
g
c
o
n
f
i
g
u
r
a
t
i
o
n
s
u
p
t
o
8
:
1
2
p
i
t
c
h
w
h
e
n
a
c
c
e
p
t
a
b
l
e
t
o
the Local Authority Having Jurisdiction.
For NFPA 13 residential applications, the greater of 0.1 GPM/Ft.' over the design area or the flow in accordance with the cri
t
e
r
i
a
i
n
Table A must be used.
TABLE A SERIES LFII RESIDENTIAL FLAT-PLATE CONCEALED PENDENT SPRIN
K
L
E
R
(
T
Y
2
5
2
4
)
NFPA 13,13D AND 13R HYDRAULIC DESIGN CRITERIA
- WET PIPE SYSTEMS -
DRY PIPE SYSTEM (b)
Maximum Minimum Flow and Residual Pressure
Coverage Area l) Maximum Spacing
Horizontal Ceiling Minimum Flow and Residual Pressure let Ft. x Ft. Ft.(Maximum 2-Inch Rise for 12-Inch Run) (m x m)
160°F (71°C) Sprinkler
12x12 12 15 GPM (56,8 LPM) (3,7 x 3,7) (3,7) 9.4 psi (0,65 bar)
14x14 14 15 GPM (56,8 LPM) (4,3 x 4,3) (4,3) 9.4 psi (0,65 bar)
16x16 16 16 GPM (60,6 LPM) (4,9x4,9) (4,9) 10,7 psi (0,74 bar)
18x18 18 17 GPM (64,3 LPM) (5,5 x 5,5) (5,5) 12.0 psi (0,83 bar)
20 x 20 20 21 GPM (79,5 LPM) (6,1 x 6,1) (6,1) 18,4 psi (1,27 bar)
For coverage area dimensions less than or between those indicated, use the minimum required flow for the next highest coverage area for which Hydraulic Design section under the Design Criteria are stated.
The Minimum Flow requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures are calculated using the nominal K-factor. Refer to "Hydraulic Design" in the Design Criter
i
a
s
e
c
t
i
o
n
f
o
r
d
e
t
a
i
l
s
.
For NFPA 13D 2010 applications, Horizontal Ceiling criteria shall be used for certain s
l
o
p
e
d
c
e
i
l
i
n
g
c
o
n
f
i
g
u
r
a
t
i
o
n
s
u
p
t
o
8
:
1
2
p
i
t
c
h
.
Refer to TIA 1028R for allowed sloped ceiling limitations when using horizontal c
e
i
l
i
n
g
c
r
i
t
e
r
i
a
.
TABLE B SERIES LFII RESIDENTIAL FLAT-PLATE CONCEALED PENDENT SPRI
N
K
L
E
R
(
T
Y
2
5
2
4
)
NFPA 13D AND NFPA 13R HYDRAULIC DESIGN CRITERIA
- DRY PIPE SYSTEMS -
TFP443
Page 3 of 6
BODY
SEALING (1/2"NPT)
ASSEMBLY
CAP
SPRINKLER
WRENCHING
AREA SADDLE
-
SUPPORT COMPRESSION CUP WITH SCREW ROLL FORMED
THREADS
LEVER
GUIDE
PIN
SOLDER LINK / ELEMENT GUIDE PIN
HOUSING
/ DEFLECTOR / DEFLECTOR -"
----s-I (OPERATED
------------ POSITION)
SPRINKLER/SUPPORT CUP
ASSEMBLY
THREAD INTO
RETAINER SUPPORT CUP
THREAD UNTIL MOUNTING
PLES SURFACE IS Q rFLUSH WITH
CEILING
H
L EJECTION
RING
SOWER COVER PLATE/RETAINER COVER TAB ASSEMBLY PLATE
FIGURE 1 FLAT-PLATE CONCEALED PENDENT SPRINKLER (TY2524)
- ASSEMBLY -
WRENCH
RECESS
PUSH WRENCH
IN TO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURE 2
W-TYPE 18
- SPRINKLER WRENCH -
2-1/2" DIA.
SPRINKLER- (63,5 mm)
SUPPORT CUP /2"(12,7 mm) FACE OF
ASSEMBLY
112 THREADED SPRINKLER
/ OPERATED
NPT ADJUSTMENT FITtING
SPRINKLER
_____
COVER
PLATE (47,6 mm
RETAINER 1/8 GAP ±3,2 mm)
__ (3,2mm)
7/8 (22,2 mm) COVER- SPRINKLER- MOUNTING
1-1/8" (28,6 mm)
RETAINER SUPPORT CUP
3/16" SURFACE
________
ASSEMBLY ASSEMBLY (4,8 mm) //>/ \ 3-3/16" DIA.
DISPOSABLE DEFLECTOR IN
(81,0 mm)
TIP PROTECTIVE CAP OPERATED POSITION FIGURE 3 PROTECTIVE CAP AND ACTIVATED DEFLECTOR
- INSTALLATION DIMENSIONS
-
TFP443
Page 4 of 6
Approvals
UL and C-UL Listed
NSF-61 Certified
The Series LFII Residential Fiat-Plate
Concealed Pendent Sprinklers are only
listed with the Series LFII Concealed
Cover Plates having a factory-applied
finish.
Maximum Working Pressure
175 psi (12,1 bar)
Discharge Coefficient
K=4.9 GPM/psi112 (70,6 LPM/bar1"2)
Temperature Rating
Sprinkler: 160°F (71°C)
Cover Plate: 139°F (59°C)
Vertical Adjustment
1/2 inch (12,7 mm)
Finishes
Refer to the Ordering Procedure
section.
Physical Characteristics
Cover Plate/Retainer Assembly:
Cover Plate .............Copper
Ejection Spring . . . . Stainless Steel Retainer ................Brass
Sprinkler/Support Cup Assembly:
Body ...................Brass
Cap ...................Bronze
Saddle ..................Brass
Sealing Assembly .......Beryllium
Nickel w/ Teflon' Soldered Link Halves ......Nickel
Lever ..................Bronze
Compression Screw .......Brass
Deflector ...............Bronze
Guide Pin Housing........Bronze
Guide Pins .............Bronze
Support Cup ..............Steel
When exposed to heat from a fire, the
Cover Plate, which is normally soldered
to the Retainer at three points, falls away
to expose the Sprinkler/Support Cup As-
sembly. At this point, the Deflector, sup-
ported by the Guide Pins, drops down
to its operated position.
The Solder Link Element of the Sprinkler/
Support Cup Assembly is comprised of
two link halves that are soldered togeth-
er with a thin layer of solder. When the
rated temperature is reached, the sol-
der melts and the two link halves sepa-
rate, allowing the sprinkler to activate
and flow water.
1 Registered trademark of DuPont
Design
Criteria
The TYCO RAPID RESPONSE Series
LFII Residential Flat-Plate Concealed
Pendent Sprinklers (TY2524) are UL
and C-UL Listed for installation in ac-
cordance with the following criteria.
When conditions exist that are outside
the scope of the provided criteria, re-
fer to the Residential Sprinkler Design
Guide TFP490 for the manufacturer's
recommendations that maybe accept-
able to the Authority Having Jurisdiction.
The Series LFII Residential Flat-Plate
Concealed Pendent Sprinklers must
not be used in applications where the
air pressure above the ceiling is greater
than that below. Down drafts through
the Support Cup can delay sprinkler op-
eration in a fire situation.
System Type
Per the UL Listing, wet pipe and dry pipe
systems may be utilized. Per the C-UL
Listing, only wet pipe systems may be
utilized.
For dry systems not using CPVC,
corrosion-resistant or internally gal-
vanized pipe shall be utilized with
the sprinklers described in this data
sheet
For dry systems, pendent sprinklers
shall be installed on return bends,
where the sprinklers, return bends,
and branch line piping (that is, po-
tential areas for trapped water) are in
areas at or above 40'F (4'C)
Refer to technical data sheet TFP485
about the use of Residential Sprinklers
in residential dry pipe systems.
NOTICE
When corrosion-resistant or internally
galvanized pipe and fittings with a po-
table water supply are utilized, return
bends need not be installed. However,
any portion of the piping that has the
potential to trap water must be main-
tained at or above 40°F (4°C) unless pro-
vision to drain such areas is provided
and maintained dry.
Water Delivery
When using the Series LFII Residential
Flat-Plate Concealed Pendent Sprinklers
(TY2524) in dry pipe sprinkler systems,
the requirements for 'Dry System Water
Delivery" per Section 8.3.4.3 of the 2010
edition of NFPA 13D apply. For a resi-
dential hazard, in no case shall the time
of water delivery exceed 15 seconds for
the most remote operating sprinkler.
Hydraulic Design
(NFPA 13D and 13R)
The minimum required sprinkler flow rate
for systems 'designed to NFPA 13D or
NFPA 13R are given in Tables A and B
as a function of temperature rating and
the maximum allowable coverage areas.
The sprinkler flow rate is the minimum
required discharge from each of the total
number of 'design sprinklers" as speci-
fied in NFPA 13D or NFPA 13R.
W&T!CE.
The number of "design sprinklers' spec-
ified in NFPA 130 and 13R for wet pipe
systems is to be applied when design-
ing dry pipe systems. There is no need•
to increase the design area, as is the.
case for density/area systems, in ac-
cordance with U.S. Patent 7,712,543.
Refer to technical data sheet TFP485
for details.
Hydraulic Design
(NFPA 13)
For systems designed to NFPA 13, the.
number of design sprinklers is to be
the four most hydraulically demanding
sprinklers. The minimum required dis-
charge from each of the four sprinklers
is to be the greater of the following:
The flow rates given in Tables A and B
for NFPA 13D and 13R as a function of
temperature rating and the maximum
allowable coverage area.
A minimum discharge of 0.1 GPM/
sq. ft. over the "design area" com-
prised of the four most hydraulically
demanding sprinklers for the actual
coverage areas being protected by
the four sprinklers.
111
The number of "design sprinklers"
specified in NFPA 13 for wet pipe sys-
tems is to be applied when designing
dry pipe systems. There is no need to increase the design area, as is the case
for density/area systems, in accordance
with U.S. Patent 7,712,543. Refer to
technical data sheet TFP485 for details.
Obstruction to Water
Distribution.
Sprinklers are to be located in accor-
dance with the obstruction rules of
NFPA 13D, 13R, and 13 as applicable
for residential sprinklers as well as with
the obstruction criteria described within
the TYCO technical data sheet TFP490.
Operational Sensitivity
Install sprinklers relative to the ceiling
mounting surface as shown in Figure 3.
TFP443
Page 5 of 6
Sprinkler Spacing
The minimum spacing between sprin-
klers is 8 feet (2,4 m).
The maximum spacing between sprin-
klers cannot exceed the length of the
coverage area (Table A) being hydrau-
lically calculated; for example, a maxi-
mum of 12 feet for a 12 ft. x 12 ft. cov-
erage area or 20 feet for a 20 ft. x 20 ft.
coverage area.
The TYCO RAPID RESPONSE Series
LFlI Residential Flat-Plate Concealed
Pendent Sprinklers must be installed
in accordance with the following
instructions.
Damage to the Solder Link Element dur-
ing installation can be avoided by han-
dling the sprinkler by the Support Cup
only; that is, do not apply pressure to the
Solder Link Element (Figure 1).
Obtain a leak-tight 1/2 inch NPT sprinkler joint by applying a minimum-to -maxi-
mum torque of 7 to 14 ft.-lbs. (9,5 to 19,0
Nm). Higher levels of torque can distort
the sprinkler inlet with consequent leak-
age or impairment of the sprinkler.
Do not attempt to compensate for in-
sufficient adjustment in the Cover Plate!
Retainer Assembly by under- or over-
tightening the sprinkler. Re-adjust the
position of the sprinkler fitting to suit.
Install pendent sprinklers in the
pendent position, with the center-
line of the sprinkler perpendicular
to the mounting surface.
Remove the Protective Cap.
With pipe-thread sealant applied
to the pipe threads, and using the
W-Type 18 Wrench shown in Figure
2, install and tighten the Sprinkler!
Support Cup Assembly into the fit-
ting. The W-Type 18 Wrench ac-
cepts a 1/2 inch ratchet drive.
Replace the Protective Cap by
pushing it upwards until it bottoms
out against the Support Cup. The
Protective Cap helps prevent dam-
age to the Deflector and Guide
Pins during ceiling installation and/
or during application of the finish
coating of the ceiling.
As long as the protective Cap re-
mains in place, the system is con-
sidered "Out Of Service".
After the ceiling has been complet-
ed with the 2-1/2 inch (63 mm) di-
ameter hole and in preparation for
installing the Cover Plate/Retain-
er Assembly, remove and discard
the Protective Cap, and verify that
the Deflector moves up and down
freely.
If the Sprinkler has been damaged
and the Deflector does not move up
and down freely, replace the entire
Sprinkler assembly. Do not attempt to
modify or repair a damaged sprinkler.
Screw on the Cover Plate/Retainer
Assembly until its flange contacts
the ceiling.
Do not continue to screw on the
Cover Plate/Retainer Assembly such
that it lifts a ceiling panel out of its
normal position.
If the Cover Plate/Retainer Assembly
cannot be engaged with the Mounting
Cup or the Cover Plate/RetainerAs-
sembly cannot be engaged sufficiently
to contact the ceiling, the Sprinkler
Fitting must be repositioned.
Care and
F1J7 •4i Jg L'
The TYCO RAPID RESPONSE Series
LFll Residential Flat-Plate Concealed
Pendent Sprinkler (TY2524) must be
maintained and serviced in accordance
with the following instructions.
Before closing a fire protection system
main control valve for maintenance work
on the fire protection system that it con-
trols, obtain permission to shut down the
affected fire protection system from the
proper authorities and notify all person-
nel who may be affected by this action.
When properly installed, there is a nomi-
nal 1/8 inch (3,2 mm) air gap between
the lip of the Cover Plate and the ceil-
ing, as shown in Figure 3. This air gap
is necessary for proper operation of the
sprinkler by allowing heat flow from a
fire to pass below and above the Cover
Plate to help assure appropriate release
of the Cover Plate in a fire situation. If the
ceiling needs repainting after sprinkler
installation, exercise care to ensure that
the new paint does NOT seal off any of
the air gap. Failure to do so may impair
sprinkler operation.
Absence of a Cover Plate can delay the
sprinkler operation in afire situation.
Do not pull the Cover Plate relative to the
Retainer. Separation may result.
Exercise care to avoid damage to sprin-
klers before, during, and after installa-
tion. Never paint, plate, coat, or other-
wise alter automatic sprinklers after they
leave the factory.
Never repaint factory-painted Cover
Plates. When necessary, replace cover
plates with factory-painted units. Non-
factory applied paint can adversely de-
lay or prevent sprinkler operation in the
event of a fire and is not permitted by
NFPA.
Replace sprinklers that:
were damaged by dropping, striking,
wrench twisting, wrench slippage, or
the like.
were modified or over-heated.
are leaking or exhibiting visible signs
of corrosion.
Responsibility lies with owners for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards of
the National Fire Protection Association
(for example, NFPA 25), in addition to
the standards of any other authorities
having jurisdiction. Contact the install-
ing contractor or sprinkler manufacturer
regarding any questions.
Automatic sprinkler systems are rec-
ommended to be inspected, tested,
and maintained by a qualified Inspec-
tion Service in accordance with local
requirements and/or national codes.
TFP443
Page 6 of 6
Limited
Products manufactured by Tyco Fire
Suppression & Building Products
(TFSBP) are warranted solely to the orig-
inal Buyer for ten (10) years against de-
fects in material and workmanship when
paid for and properly installed and main-
tained under normal use and service.
This warranty will expire ten (10) years
from date of shipment by TFSBP. No
warranty is given for products or com-
ponents manufactured by companies
not affiliated by ownership with TFSBP
or for products and components which
have been subject to misuse, improper
installation, corrosion, or which have not
been installed, maintained, modified or
repaired in accordance with applicable
Standards of the National Fire Protection
Association, and/or the standards of any
other Authorities Having Jurisdiction.
Materials found by TFSBP to be defec-
tive shall be either repaired or replaced,
at TFSBP's sole option. TFSBP neither
assumes, nor authorizes any person to
assume for it, any other obligation in
connection with the sale of products or
parts of products. TFSBP shall not be
responsible for sprinkler system design
errors or inaccurate or incomplete in-
formation supplied by Buyer or Buyer's
representatives.
In no event shall TFSBP be liable, in con-
tract, tort, strict liability or under any oth-
er legal theory, for incidental, indirect,
special or consequential damages, in-
cluding but not limited to labor charg-
es, regardless of whether TFSBP was
informed about the possibility of such
damages, and in no event shall TFSBP's
liability exceed an amount equal to the
sales price.
-
The foregoing warranty is made in lieu
of any and all other warranties, express
or implied, including warranties of mer-
chantability and fitness for a particular
purpose.
This limited warranty sets forth the ex-
clusive remedy for claims based on fail-
ure of or defect in products, materials or
components, whether the claim is made
in contract, tort, strict liability or any oth-
er legal theory.
This warranty will apply to the full extent
permitted by law. The invalidity, in whole
or part, of any portion of this warranty
will not affect the remainder.
Ordering
Contact your local distributor for avail-
ability. When placing an order, indicate
the full product description and Part
Number (P/N).
Sprinkler/Support Cup Assembly
Specify Series LFll Residential Flat-Plate
Concealed Pendent Sprinkler (TY2524),
K=4.9 (70,6), without Cover Plate/Retain-
erAssembly, P/N 51-114-1-160.
Cover Plate/Retainer Assembly
Specify Cover Plate/Retainer Assem-
bly with finish (below) for the Series LFll
Residential Flat-Plate Concealed Pen-
dent Sprinkler (TY2524), K=4.9 (70,6),
P/N (below):
Off White ................P/N 56-201-0-1
3
5
Pure White'
(RAL9010) ..............P/N 56-201-3-13
5
Signal White'
(RAL9003) ..............P/N 56-201-4-135
Standard White (Grey White)
(RAL9002) ..............PIN 56-201-5-135
Custom ...................P/N 56-201-X-135
Eastern Hemisphere sales only
Previously known as Bright White
Note: All Custom Cover Plates are painted us-ing Sherwin Williams Interior Latex Paint.
C
o
n
t
a
c
t
TYCO Customer Service with any questions related
to custom orders.
Optional Cover Plate/Retainer
Assembly for Horizontal (Flat)
Ceilinu Aonlications Only
Specify Cover Plate/Retainer Assem-
bly with finish (below) for the Series LFll
Residential Flat-Plate Concealed Pen-
dent Sprinkler (TY2524), K=4.9 (70,6),
P/N (below):
Ott White .................P/N 56-122-0-135
Pure White'
(RAL90I0) ................P/N 56-122-3-135
Signal White'
(RAL9003) ................P/N 56-122-4-13
5
Custom ...................P/N 56-122-X-135
* Eastern Hemisphere sales only
Previously known as Bright While
Note: All Custom Cover Plates are painted us-ing Sherwin Williams Interior Latex Paint.
C
o
n
t
a
c
t
TYCO Customer Service with any questions related to custom orders.
Sprinkler Wrench
Specify W-Type 18 Sprinkler Wrench,
P/N 56-000-1-265.
Copyright 02010, 2011 Tyco Fire Suppressi
o
n
&
B
u
i
l
d
i
n
g
P
r
o
d
u
c
t
s
.
A
l
l
r
i
g
h
t
s
r
e
s
e
r
v
e
d
.
September 30, 2011 Sprinkler 41a
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.
c
o
m
DESCRIPTION
Viking Microfast® and MicrofastHP® Quick Response Pendent Sprinklers are small,
thermosensitive, glass-bulb spray sprinklers available in several different finishes and
temperature ratings and K-Factorsto meetdesign requirements. The special Polyester
and Teflon® coatings can be used in decorative applications where colors are de-
sired. In addition, these coatings have been investigated for installation in corrosive
atmospheres and are cULus listed as corrosion resistant as indicated in theApproval
Chart. (Note: FM Global has no approval classification for Teflon® and Polyester
coatings as corrosion resistant.)
LISTINGS AND APPROVALS
cULus Listed: Category VNIV
FM Approved: Classes 2001, 2002, 2015, and 2017
kIFt' A .1. t'.I,-...,,J..... kI,...,,,I.,.,.. 7 'A ......J IAIA Ot (' '.I,..I,,....,-. .1 I I'. t4JpIuvru. aiei UI i'luI I IL?I U)t dl JU IVILP\ VUUI I U ABS Certified: Certificate 04HS407984C-PDA
VdS Approved: Certificates G4040095, G4040097, G4060056, G4060057, G4880045, G4930038, and G4980021
LPC Approved: Ref. Nos. 096e/03 and 096e/04
CE Certified: Standard EN 12259-1, EC-certificates of conformity 0786-CPD-40130, 0786-CPD-40170 and 0786-
C
P
D
-
4
0
2
7
9
,
0832-CPD-2001, and 0832-CPD-2003
MED Certified: Standard EN 12259-1, EC-certificate of conformity 0832-MED-1003 and 0832-MED-1008
NOTE: Other International approval certificates are available upon request.
Refer to Approval Chart 1 and Design Criteria on page 41d for cULus Listing requirements and refer to Approval Cha
r
t
2
a
n
d
D
e
s
i
g
n
Criteria on page 41f for FM Approval requirements that must be followed.
TECHNICAL DATA
Specifications:
Available since 1987.
Minimum Operating Pressure: 7 psi (0.5 bar)*
Maximum Working Pressure: Sprinklers 12282 and 12290 are rated for Viking Technical Data may be found on use with water working pressures ranging from the minimum 7 psi (0.5 The Viking Corporation's Web site at bar) up to 250 psi (17 bar) for high-pressure systems. High-pressure http:I1www.vikinggroupinc.com. (HP) sprinklers can be identified by locating "250" stamped on the The Web site may include a more recent deflector. All other Part Nos. not mentioned above are rated to a maxi- edition of this Technical Data Page. mum 175 psi (12 bar) wwp.
Factory tested hydrostatically to 500 psi (34.5 bar)
Thread size: Refer to the Approval Charts
Nominal K-Factor: Refer to the Approval Charts
Glass-bulb fluid temperature rated to -65 °F (-55 °C)
Overall Length: Refer to the Approval Charts .cULus Listing, FM Approval, and NFPA 13 installs require a minimum of 7 psi (0.5 bar). The minimum operating pressure f
o
r
L
P
C
B
a
n
d
C
E
Approvals ONLY is 5 psi (0.35 bar).
Material Standards:
Frame Casting: Brass UNS-C84400 or QM Brass for Sprinklers 06662B and 12282. Brass UNS-C84400 for all other sprinkl
e
r
s
.
Deflector: Phosphor Bronze UNS-051000 or Copper UNS-C19500 for Sprinklers 06662B, 06666B, and 06765B. Copper
U
N
S
-
C 19500 for Sprinkler 12282. Phosphor Bronze UNS-051000, Copper UNS-C19500 or Brass UNS-C26000 for Sprinkler
0
6
7
2
0
B
.
Brass UNS-C26000 for all other Sprinklers.
Bushing (for Sprinklers 06718B, 06720B, and 12290): Brass UNS-C36000
Bulb: Glass, nominal 3 mm diameter
Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with Teflon Tape
Screw: Brass UNS-C36000
Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400
For Teflon® Coated Srrinklers: Belleville Spring-Exposed, Screw-Nickel Plated, Pip Cap-Teflon® Coated
For Polyester Coated Sprinklers: Belleville Spring-Exposed
081296 Form No. F Replaces page 41a-f, dated July 28, 2011. (Wrench _
, 16036W/B replaces Wrench 12144W/B.)
Sprinkler 4Th
September 30, 2011
-. 1.0 :.:..EC.HNiCALDATA. QUICK
RESPONSE PENDENT
MICAST@ AND
$ I NIN
& k The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-81
8
-
1
6
8
0
E
m
a
i
l
:
t
e
c
h
s
v
c
s
@
v
i
k
i
n
g
c
o
r
p
.
c
o
m
Ordering Information: (Also refer to the current Viking price list.) Order Microfast® and MicrofastHP® Quick Response Pendent Sprinklers by first adding the app
r
o
p
r
i
a
t
e
s
u
f
f
i
x
f
o
r
t
h
e
s
p
r
i
n
k
l
e
r
f
i
n
i
s
h
and then the appropriate suffix for the temperature rating to the sprinkler base
p
a
r
t
n
u
m
b
e
r
.
Finish Suffix: Brass = A, Chrome-Enloy® = F, White Polyester = M-NV, Black Polyester = M-IB, and Black Teflon® = N Temperature Suffix (°F/°C): 135°I57° = A, 155°/68° = B, 175°/79° = D, 200°/93° = E, and 286"/141° = G For example, sprinkler VK302 with a 1/2" thread, Brass finish and a 15
5
¶
1
6
8
"
C
t
e
m
p
e
r
a
t
u
r
e
r
a
t
i
n
g
= Part No. 06662BAB Available Finishes And Temperature Ratings:
Refer to Table 1.
Accessories: (Also refer to the "Sprinkler Accessories" section of the Viking data book.)
Sprinkler Wrenches:
Standard Wrench: Part No. 10896W/B (available since 2000). Wrench for Recessed Pendent Sprinklers: Part No. 16036W/B* (available since 2011) Optional Protective Sprinkler Cap Remover/Escutcheon Installer Tool** Part No. 15915 (available since 2010.) *A %" ratchet is required (not available from 'liking).
**Allows use from the floor by attaching a length of 1" diameter CPVC tubing to the tool. Ide
a
l
f
o
r
s
p
r
i
n
k
l
e
r
c
a
b
i
n
e
t
s
.
R
e
f
e
r
t
o
B
u
l
l
e
t
i
n
F
0
5
1
8
0
8
.
Sprinkler Cabinets:
Six-head capacity: Part No. 01724A (available since 197 1)
Twelve-head capacity: Part No. 01725A (available since 1971)
INSTALLATION
Refer to appropriate NFPA Installation Standards.
OPERATION
During fire conditions, the heat-sensitive liquid in the glass bulb expands, causi
n
g
t
h
e
g
l
a
s
s
t
o
s
h
a
t
t
e
r
,
r
e
l
e
a
s
i
n
g
t
h
e
p
i
p
c
a
p
a
n
d
sealing spring assembly. Water flowing through the sprinkler orifice strikes the
s
p
r
i
n
k
l
e
r
d
e
f
l
e
c
t
o
r
,
f
o
r
m
i
n
g
a
u
n
i
f
o
r
m
s
p
r
a
y
p
a
t
t
e
r
n
to extinguish or control the fire.
INSPECTIONS, TESTS AND MAINTENANCE
Refer to NFPA 25 for Inspection, Testing and Maintenance requirements.
AVAILABILITY
The Viking Microfast® and MicrofastHP® Quick Response Pendent
Sprinklers are available through a network of domestic and
international distributors. See The Viking Corporation web site for
the closest distributor or contact The Viking Corporation.
GUARANTEE
For details of warranty, refer to Viking's current list price schedule
or contact Viking directly.
Wrench
Protective
Sprinkler
Flats
Cap
10896 :=(D
Figure 1: Standard Sprinkler Wrench 10896W/B
September 30, 2011
Sprinkler 4 1 c
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-168
0
E
m
a
i
l
:
t
e
c
h
s
v
c
s
@
v
i
k
i
n
g
c
o
r
p
.
c
o
m
R.; ATINGS ANDPIMSHES
7Sjp,,n6k1e,
,
Temperature Sprinkler Nominal Maximum i Arni ient
Bulb Color sirm.atmon omperafure Rating C- ong Temperature
Odinary 135 °F(57 0C) 100 'F (38 'C) Orange Ordinary 155 'F (68 'C) 100 °F (38 'C) Red Intermediate 175 'F (79 'C) 150 'F (65 'C) Yellow Intermediate 200 'F (93 'C) 150 'F (65 'C) Green High 286 'F (141 'C) 225 'F (107 'C) Blue Sprinkler Finishes: Brass, Chrome-Enloy®, White Polyester, Black Polyester, and Black Teflon® Corrosion-Resistant Coatings3: White Polyester, Black Polyester, and Black Teflon®
Footnotes
1 The sprinkler temperature rating is stamped on the deflector.
2 Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other req
u
i
r
e
m
e
n
t
s
o
f
t
h
e
A
u
t
h
o
r
i
t
y
H
a
v
i
n
g
J
u
r
i
s
d
i
c
t
i
o
n
.
Refer to specific installation standards.
corrosion-resistant coatings have passed the standard corrosion test required by the approving agencies indicate
d
i
n
t
h
e
A
p
p
r
o
v
a
l
C
h
a
r
t
s
.
T
h
e
s
e
tests cannot and do not represent all possible corrosive environments. Pnor to installation, verify through the e
n
d
-
u
s
e
r
t
h
a
t
t
h
e
c
o
a
t
i
n
g
s
a
r
e
c
o
m
p
a
t
-
ible with or suitable for the proposed environment. For automatic sprinklers, the coatings indicated are applied to t
h
e
e
x
p
o
s
e
d
e
x
t
e
r
i
o
r
s
u
r
f
a
c
e
s
o
n
l
y
.
Note that the spring is exposed on sprinklers with Polyester and Teflon® coatings.
Sprinkler Wrench
/ 16036\.//P.*® for
L
I installing recessed
sprinklers pendent Carefully slide the
________ i wrench sideways *AA 1/2' ratchet is required
(not avcli(oble From Viking). around the protective ii I cap, ensuring engage-
ment with the sprinkler
wrench flats,
Figure 2: Wrench 16036W/B for Recessed Pendent Sprinklers
Sprinkler 41d
September 30, 2011
.: . MICROFASTO
MicrofastHP11 QUICK TECHNICAL DATA
RESPONSE PENDENT
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI
49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax:
269-818-1680 Email: techsvcs@vikingcorp.com
Approval Chart I (UL) KEY Microfast and MicrofastHP Quick Response Pendent Sprinklers
Maximum 175 PSI (12 burl MP
Nominal Overall [ Listings and Approvals'
Sprinkler Thread Size I Base SIN K-Factor Length (Refer also to Design Criteria on page 41e.)
I
Part No.' NPT BSP U.S. metric2 Inches I mm] cULus4 NYC5 VdS LPCB I Standard Orifice
06662B ] VK302 1/2' 115 mm] 5.6 80.6 2-1/4" 58 ]_AiX, B1Y J AiX, B1Y A2 J A2X, B2Y C2X, E2Y'1 C2X, E2Y14
Large Orifice
0666613 1 VK352 13/41 20mm 8.O] 115.2 ]_2-3/8" 160] AiX, B1 [ AiX, B1Y A21 A2X C211 1 - 06765B '/1(352 [1/2"1 15mm 8.0 115.2 j_2-3/8"_j60jA1X, B1Y [AiX, B1Y A21
-- A,12 -
Small Orifice'
0671813 VK329 1/2' 15 mm 2.8 40.3 2-3/16" 56 AiX, B1Y AiX, WY 06720B9 VK331 1/2" 15 mm 4.2 57 2-1/4" 58 AIX, B1Y AiX, B1Y
06932B VK331 -- 10 mm 4.2 57 2-3/8" 60 G313
- Maximum 250 PSI (17 bar) WWP
Standard Orifice
Sprinkler Thread Size Nominal Overall Listings and Approvals' Base SIN K-Factor Length (Refer also to Design Criteria on page 41e.) Part No' NPT[ BSP U.S. [metr1c2 Inches mm. cLiLus4 NYC'- VdS LPCB
12282 VK317 1/2" 15 mm5.6 [ 80.6 2-1/4" 1 58 AiX, BiY AIX --
--_t - - Maximum 250 PSI (17 bar) VW
Small Orifice'
1229010 IvK342 I 1/2" 15 mmI 2.8 J 40.3 1 2-3/16" 1 56 ] Al X, BI J AiX
- -- -- Approved Temperature Ratings
A - 135 "F (57 "C) 155°F (68 "C) 175°F (79 "C), 200 "F (93 "C),
Approved Finishes Approved Escutcheons and 286 "F (141 °C)
- Brass, Chrome-Enloy', White - Standard surface-mounted escutcheon or "F "C), "F °C), °F °C), "F B - 135 (57 155 (68 175 (79 and 200 (93 "C) . Polyester67, Black Polyester67 the Viking Microfast Model F-i Adjustable C - 155 °F (68 °C), 175 "F (79 "C), 200 "F (93 °C), and 286 "F
' and Black Teflon ESCtthO (141 °C) 2 - Brass, Chrome-EnJoy'0, white Y - Standard surface-mounted escutcheon or 0 - 135 °F (57 °C). 155 "F (68 "C), 175 "F (79 "C), and 286 °F Polyester', and Black Polyester6 the Viking Microfast® Model F-i Adjustable (141 "C)
3 - Brass and Chrome-Enloy'0 Escutcheon or recessed with the Viking E - 155 °F (68 "C), 175°F (79 "C), and 200°F (93 "C)
MicromatiC'0 Model E-i or E-2 Recessed F - 155 °F (68 °C), 175 "F (79 "C), and 286 "F (141 °C)
Escutcheon G - 155 °F (68 "C)
Footnotes 1 Base part number is shown. For complete part number, refer to Viking's current price
s
c
h
e
d
u
l
e
.
2 Metric K-factor measurement shown is when pressure is measured in Bar. When p
r
e
s
s
u
r
e
i
s
m
e
a
s
u
r
e
d
i
n
k
P
a
,
d
i
v
i
d
e
t
h
e
m
e
t
r
i
c
K
-
f
a
c
t
o
r
s
h
o
w
n
b
y
1
0
.
0
.
This table shows the listings and approvals available at the time of printing. Check
w
i
t
h
t
h
e
m
a
n
u
f
a
c
t
u
r
e
r
f
o
r
a
n
y
a
d
d
i
t
i
o
n
a
l
a
p
p
r
o
v
a
l
s
.
Listed by Underwriters Laboratories Inc. for use in the U.S. and Canada. 5 Accepted for use, City of New York Board of Standards and Appeals, Calendar N
u
m
b
e
r
2
1
9
-
7
6
-
S
A
.
6 cULus Listed as corrosion resistant.
Other colors are available on request with the same Listings and Approvals as the stand
a
r
d
c
o
l
o
r
s
.
8 Listings and Approvals limited to Light Hazard Occupancies where allowed by
t
h
e
i
n
s
t
a
l
l
a
t
i
o
n
s
t
a
n
d
a
r
d
s
b
e
i
n
g
a
p
p
l
i
e
d
,
w
i
t
h
h
y
d
r
a
u
l
i
c
a
l
l
y
c
a
l
c
u
l
a
t
e
d
wet systems only. Exception: 4.2K sprinklers may be installed on hydraulically calc
u
l
a
t
e
d
d
r
y
p
i
p
e
s
y
s
t
e
m
s
w
h
e
r
e
p
i
p
i
n
g
i
s
c
o
r
r
o
s
i
o
n
r
e
s
i
s
t
a
n
t
o
r
internally galvanized.
The sprinkler orifice is bushed.
'°Accepted for use, City of New York Department of Buildings, MEA Number 89-92-E, Vol
.
1
6
.
11 ((Certified, Standard EN 12259-1, EC-certificates of conformity 0832-CPD-20
0
1
a
n
d
0
8
3
2
-
C
P
D
-
2
0
0
3
.
Certified, Standard EN 12259-1, EC-certificate of conformity 0786-CPD-40279. Certified, Standard EN 12259-1 EC-certificate of conformity 0786-CPD-40130 and
0
7
8
6
-
C
P
D
-
4
0
1
7
0
.
11 MED Certified, Standard EN 12259-1, EC-certificates of conformity 0832-MED-1003 an
d
0
8
3
2
-
M
E
D
-
1
0
0
8
.
September 30, 2011
Sprinkler 41e
MICROFASTO AND
NICALDAU Microfastl-IPO QUICK
RESPONSE PENDENT -
SPRINKLERS
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: tech
s
v
c
s
v
i
k
i
n
g
c
o
r
p
.
c
o
m
DESIGN CRITERIA - UL
.-
ctJLus Listing Requirements:
Microfast® and MicrofastHP® Quick Response Pendent Sprinklers are cULus Listed as indicated in the Approval Chart fo
r
i
n
s
t
a
l
l
a
t
i
o
n
i
n
a
c
c
o
r
d
a
n
c
e
w
i
t
h
the latest edition of NFPA 13 for standard spray sprinklers.
Designed for use in Light and Ordinary Hazard occupancies (exception: small orifice sprinklers are limited to Li
g
h
t
H
a
z
a
r
d
w
h
e
r
e
a
l
l
o
w
e
d
b
y
the installation standards being applied, with hydraulically calculated wet systems only).
The sprinkler installation rules contained in NFPA 13 for standard spray pendent sprinklers must be followed.
IMPORTANT: Always refer to Bulletin Form No. F_09 1699
- Care and Handling of Sprinklers. Also refer to page QRI-3 for general care, installation, and maintenance information. Viking sprinklers are to be ins
t
a
l
l
e
d
i
n
a
c
c
o
r
-
dance with the latest edition of Viking technical data, the appropriate standards of NFPA,
L
P
C
B
,
A
P
S
A
D
,
V
d
S
or other similar organizations, and also with the provisions of governmental codes, ordinances,
a
n
d
s
t
a
n
d
a
r
d
s
,
whenever applicable.
Ceiling Opening Size
2-5/16' (58.7 mm) minimum
2-1/8' 2-1/2' (63,5 mm) maximum
1/2'
(15 mm)
NPT
1-3/4' T
1-5/8'
(41 mm)
2-1/4'
(58 rim) (44.5 mm)
I
2'
(50.8 mm)
Maximum
1-1/2' (38,1 mm)
Minimum
Pendent Sprinkler
066622 (VK302)
Installed with a
standard 1/8' surface-
mounted escutcheon. Installed with a Microfast
Model F-i Adjustable Escutcheon
Figure 3: Sprinkler VK302 Dimensions with a Standard Escutcheon and the Model F-i Adjustable Escutcheo
n
2-1/8' I Ceiling Opening Size 2-1/8'
(54 mm) 2-5/16' (58,7 mm) minimum (54 mm)
2-1/2' (63.5 mm) maximum
1 11
1-3/4' 1-1/8" (28,6 mm)
(44,5 mm) Minimum
Maximum
Installed with a Micr-omatic
Model E-1 Recessed Escutcheon
2' ~Lj
1-1/8' (28.6 mm)
(50.8 mm) Minimum
Maximum __________
Installed with a thread on
Model E-2 Recessed Escutcheon
Figure 4: Sprinkler VK302 Dimensions with the Model E-1 and E-2 Recessed Escutcheons
Sprinkler 41f September 30, 2011
MICROFASTO AND "AIN Microfastl-IPO QUICK
RESPONSE PENDENT -
SPRINKLERS
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcsvikingcorp.com
Approval Chart 2 (FM) 1tL KEY Microfast Quick Response Penderit Sprinklers I IXatse3fl1f MaximLim 175 PSI (12 bar) WWP
Sprinkler Thread Size Nominal K-Factor Overall Length FM Approvals3 SIN Base Part No.' NPT BSP U.S. metric2 I Inches mm (Refer also to Design Criteria below.)
Standard Orifice
066628 [ VK302 1/2" 115 mm 5.6 80.6 2-1/4" 58 J A2X, 62Y
Large Orifice
06666B VK352 3/4" 20 mm 8.0 115.2 2-3/8" 60 AiX, B1Y
06765B VK352 1/2" 15 mm 8.0 115.2 2-3/8" 60 AiX, B1Y
Small Orifice'
06718B6 VK329 1/2" 115 mm 2.8 I 40.3 I 2-3/16" j 56 AiX
Approved Escutcheons
Approved Temperature Ratings Approved Finishes X - Standard surface-mounted escutcheon or the Viking
A- 135 °F (57 °C), 155°F (68 °C), 175°F (79 °C), 1 - Brass and Chrome-Enloy5 Microfast6 Model F-i Adjustable Escutcheon
200 °F (93 °C), and 286 °F (141 °C) Chrome-EnIoy5 WhitePolyester5 2-Brass,,, Y - Standard surface-mounted escutcheon or the
8-135°F (57 °C), 155°F (68 °C), 175°F (79 °C), and Black Polyester5 Viking Microfast Model F-i Adjustable Escutcheon °F °C) and 200 (93 or recessed with the Viking Micromatic5 Model E-1
or E-2 Recessed Escutcheon
Footnotes
1 Base part number is shown. For complete part number, refer to Viking's current price schedule.
2 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
This table shows the listings and approvals available at the time of printing. Check with the manufacturer for any additional approvals.
FM Approved as quick response control mode standard spray Non-storage sprinklers. For specific application and installation requirements, reference
the latest applicable FM Loss Prevention Data Sheets (including Data Sheet 2-0).
Other colors are available on request with the same Listings and Approvals as the standard colors.
6 The sprinkler orifice is bushed.
bESGN_CRITERlA - FM
1
FM Anoroval Requirements:
The sprinklers indicated in Approval Chart 2 are FM Approved as quick response Non-storage standard spray pendent sprinklers as indicated in the
FM Approval Guidet. For specific application and installation requirements, reference the latest applicable FM Loss Prevention Data Sheets (including
Data Sheets 2-0 and 8-9). FM Global Loss Prevention Data Sheets contain guidelines relating to, but not limited to: minimum water supply requirements,
hydraulic design, ceiling slope and obstructions, minimum and maximum allowable spacing, and deflector distance below the ceiling.
NOTE: The FM installation guidelines may differ from cULus and/or NFPA criteria.
tSprinklers VK302 and VK352 are also FM Approved as quick response Rack Storage standard spray pendent sprinklers. Refer to technical data
page 131a-e for Intermediate Level In-Rack Sprinklers.
IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page
QRI-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in ac-
cordance with the latest edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB,
APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and
standards, whenever applicable.
Form No. F_081296 Replaces page 41a-f, dated July 28, 2011. (Wrench
16036W/B replaces Wrench 12144W/B.)