HomeMy WebLinkAbout1190 MAGNOLIA AVE; ; AS070177; Permit5/30/25, 11:53 AM AS070177 Permit Data
City of Carlsbad
Sprinkler Permit
Job Address: 1190 MAGNOLIAAV
Permit Type: SPRINK
Parcel No: 2052109800
Lot #: 0
Permit No: AS070177
Status: ISSUED
Applied 7/5/2007
Approved: 7/6/2007
Reference No.: Issued: 7/6/2007
PC #: Inspector:
Project Title: SHAMSHOIAN RESIDENCE 3 RESIDENTIAL FIRE SPRINKLER
INSPECTIONS @ $62/EA
Applicant:
INNOVATIVE FIRE PROTECTION
405 VERNON WAY
ELCAJON
(619) 593-8200
Owner:
SHAMSHO IAN LUCIA E
1184 MAGNOLIA AVE
CARLSBAD CA
Fees ($) Add'l Fees ($) Total ($) Balance ($)
186 0 186 0
about:blank 1/1
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 1 DATE: 5/30/2007 C:\HASS78\C3671.SDF JOB TITLE: SHAMSHOIAN RESIDENCE II
- TWO HEAD CALC - MEZZANINE VAULT
WATER SUPPLY DATA
SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D NODE PRESS. PRESS. @ PRESS. @ DEMAND PRESS. TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI)
1 83.0 80.0 500.0 83.0 31.2 60.1
AGGREGATE FLOW ANALYSIS:
TOTAL FLOW AT SOURCE 31.2 GPM TOTAL HOSE STREAM ALLOWANCE AT SOURCE 0.0 GPM OTHER HOSE STREAM ALLOWANCES 5.0 GPM TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 26.2 GPM
NODE ANALYSIS DATA
NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE
(ET) (PSI) (GPM)
1 121.0 SOURCE 60.1 31.2 2 121.0 - - - - 50.3 - - - 2A 121.0 - - - - 46.3 - - - 3A 121.0 HOSE STREAM 43.7 5.0 DC 122.0 - - - - 42.0 - - - DA 122.0 - - - - 35.0 - - - 3 123.0 - - - 33.3 - - - 4 126.0 - - - - 30.3 - - - 5 131.0 - - - - 23.3 - - - 6 133.5 - - - 19.8 - - 7 142.5 - - - - 14.9 - - - 8 142.5 - - - - 13.1 - - - 9 142.5 - - - - 12.9 - - - 9A 148.0 - - - - 10.2 - - - 9B 149.0 K= 4.30 9.1 13.0 10 142.5 - - - - 13.1 - - - 10A 148.0 - - - - 10.3 - - - 108 149.0 K= 4.30 9.3 13.1 11
12
142.5
144.0
- - - -
- - - -
14.9
15.2
- -
- - - APPROVED ///67 1LL) 13 133.5 - - - - 20.0 - - -t APPROVED AS NOTED
ROVED SUBMIT NOT APP, RE
CECI(G IS CLY FOR COcF0RMAN!
THE ESO!J C0HEfl c THE
H9 COWPLiP TH THE
T' GVFi TiE CGTRACT
"EITS 'T0R IS RESPONSIBLE
SCIS fO BE C'jNFIBMED
LAftO Al THE JOB
/ S AND H1R COORDINATION O THE
kJ TRADES.
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2 DATE: 5/30/2007 C:\HASS78\C3671.SDF JOB TITLE: SHANSHOIAN RESIDENCE II - TO HEAD CALC - MEZZANINE VAULT
PIPE DATA
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM.
NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe: 1 31.2 0.995 PL 30.00 PF 9.9
1 121.0 SRCE 60.1 (N/A) 12.9 150 FTG TG PE 0.0
2 121.0 0.0 50.3 0.0 0.253 TL 39.00 PV
Pipe: 2 FIXED PRESSURE LOSS DEVICE
2 121.0 0.0 50.3 0.0 4.0 psi, 31.1 gpm
2A 121.0 0.0 46.3 0.0
Pipe: 3 31.1 1.360 PL 40.00 PF 2.5
2A 121.0 0.0 46.3 0.0 6.9 150 FTG 3L PE 0.0
3A 121.0 H.S. 43.7 5.0 0.055 TL 46.00 PV
Pipe: 4 26.1 1.025 PL 3.00 PF 1.3
3A 121.0 H.S. 43.7 5.0 10.2 150 FTG EL PE -0.4
DC 122.0 0.0 42.0 0.0 0.158 TL 8.00 PV
Pipe: 5 FIXED PRESSURE LOSS DEVICE
DC 122.0 0.0 42.0 0.0 7.0 psi, 26.1 gpm
DA 122.0 0.0 35.0 0.0
Pipe: 6 26.1 1.025 PL 3.00 PF 1.3
DA 122.0 0.0 35.0 0.0 10.2 150 FTG EL PE -0.4
3 123.0 0.0 33.3 0.0 0.158 TL 8.00 PV
Pipe: 7 26.1 1.049 PL 3.00 PF 1.7
3 123.0 0.0 33.3 0.0 9.7 120 FTG C PE -1.3
4 126.0 0.0 30.3 0.0 0.213 TL 8.00 PV
Pipe: 8 26.1 1.101 PL 27.00 PF 4.9
4 126.0 0.0 30.3 0.0 8.8 150 FTG E2T PE -2.2
5 131.0 0.0 23.3 0.0 0.112 TL 44.00 PV
Pipe: 9 15.5 1.101 PL 24.50 PF 2.3
5 131.0 0.0 23.3 0.0 5.2 150 FTG 2E3TR PE -1.1
6 133.5 0.0 19.8 0.0 0.043 TL 54.50 PV
Pipe: 10 15.5 1.101 PL 10.00 PF 1.0 6 133.5 0.0 19.8 0.0 5.2 150 FTG 2E PE -3.9 7 142.5 0.0 14.9 0.0 0.043 TL 24.00 PV
Pipe: 11 16.0 1.101 PL 26.50 PF 1.8
7 142.5 0.0 14.9 0.0 5.4 150 FTG 2T3R PE 0.0
8 142.5 0.0 13.1 0.0 0.045 TL 39.50 PV
Pipe: 12 13.0 1.101 PL 2.00 PF 0.2 8 142.5 0.0 13.1 0.0 4.4 150 FTG T PE 0.0 9 142.5 0.0 12.9 0.0 0.031 TL 7.00 PV
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3
DATE: 5/30/2007 C:\HASS78\C3671.SDF
JOB TITLE: SHAMSHOIAN RESIDENCE II - TWO HEAD CALC - MEZZANINE VAULT
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM.
NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe: 13 13.0 1.101 PL 5.50 PF 0.4
9 142.5 0.0 12.9 0.0 4.4 150 FTG E PE -2.4
9A 148.0 0.0 10.2 0.0 0.031 TL 12.50 PV
Pipe: 14 13.0 1.101 PL 4.00 PF 0.6
9A 148.0 0.0 10.2 0.0 4.4 150 FTG 2ER PH -0.4
9B 149.0 4.3 9.1 13.0 0.031 TL 19.00 PV
Pipe: 15 3.0 1.101 PL 20.00 PF 0.1
8 142.5 0.0 13.1 0.0 1.0 150 FTG 2H4R PE 0.0
10 142.5 0.0 13.1 0.0 0.002 TL 38.00 PV
Pipe: 16 13.1 1.101 PL 5.50 PE 0.3
10 142.5 0.0 13.1 0.0 4.4 150 FTG T PH -2.4
10A 148.0 0.0 10.3 0.0 0.031 TL 10.50 PV
Pipe: 17 13.1 1.101 PL 4.00 PF 0.6
10A 148.0 0.0 10.3 0.0 4.4 150 FTG 2ER PH -0.4
lOB 149.0 4.3 9.3 13.1 0.031 TL 19.00 PV
Pipe: 18 -10.1 1.101 PL 35.00 PF 1.9
10 142.5 0.0 13.1 0.0 3.4 150 FTG 8E6R PE 0.0
11 142.5 0.0 14.9 0.0 0.019 TL 97.00 PV
Pipe: 19 0.5 1.101 PL 17.00 PF 0.0
11 142.5 0.0 14.9 0.0 0.2 150 FTG 2T3R PE 0.0
7 142.5 0.0 14.9 0.0 0.000 TL 30.00 PV
Pipe: 20 -10.6 1.101 PL 16.00 PF 0.9
11 142.5 0.0 14.9 0.0 3.6 150 FTG 3ETR PH -0.6
12 144.0 . 0.0 15.2 0.0 0.021 TL 43.00 PV
Pipe: 21 -10.6 1.101 PL 10.50 PF 0.3
12 144.0 0.0 15.2 0.0 3.6 150 FTG T PH 4.5
13 133.5 0.0 20.0 0.0 0.021 TL 15.50 PV
Pipe: 22 -10.6 1.101 PL 52.50 PF 2.1
13 133.5 0.0 20.0 0.0 3.6 150 FTG 4E4TR PH 1.1
5 131.0 0.0 23.3 0.0 0.021 TL 101.50 PV
NOTES:
(1) Calculations were performed by the HASS 7.8 computer program
under license no. 16080621 granted by
1-IRS Systems, Inc.
4792 LaVista Road
Tucker, GA 30084
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4
DATE: 5/30/2007 C:\HA5578\C3671.SDF
JOB TITLE: SHAMSHOIAN RESIDENCE II - TWO HEAD CALC - MEZZANINE VAULT
The system has been calculated to provide an average
imbalance at each node of 0.010 gpm and a maximum
imbalance at any node of 0.188 gpm.
Total pressure at each node is used in balancing the system.
Maximum water velocity is 12.9 ft/sec at pipe 1.
PIPE FITTINGS TABLE
Pipe Table Name: FSS.PIP
PAGE: A MATERIAL: SCH40 HWC: 120
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C. B G A D
Ell Tee
1.049 2.00 5.00 2.00 5.00 6.00 1.00 1.00 1.00
PAGE: H MATERIAL: CPVC HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) H T R K C L B L
Ell Tee TEERUN COUPLG EL45
1.101 7.00 5.00 1.00 0.00 1.00 1.00 0.00 1.00
PAGE: I MATERIAL: CPPR-L HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) H T L C B G A D
Ell Tee
1.025 3.00 8.00 2.00 8.00 2.00 2.00 0.00 0.00
PAGE: J MATERIAL: S40PVC HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D
Ell Tee
1.360 5.00 9.00 2.00 11.00 6.00 2.00 0.00 0.00
PAGE: K MATERIAL: CPPR-K HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) H T L C B G A D
Eli Tee L
0.995 2.00 6.00 1.50 0.50 0.50 3.00 0.00 0.00
WATER SUPPLY ANALYSIS
100.0
1
G 80.0
A
U
G
E
P 60.0
R
E
S
S
40.0
ie
S
±
20 . 0
0.0
LO.L.LL. O..).'J%J ljo U. J.VL) £Juw; .)%JU.0 y piL
LEGEND
Available pressure
82.98 psi @ 31.2 gpm
Required pressure
2 60.13 psi 8 31.2 gpm
Source Supply Curve
System Demand Curve
—14.7
200 300 400 500 600 700 800 900 1000
FLOW (GPM)
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 6
DATE: 5/30/2007 C:\HASS78\C3671.sDF
JOB TITLE: SHANSHOIAN RESIDENCE II - TWO HEAD CALC - MEZZANINE VAULT
WATER SUPPLY CURVE
84+
0\\\\\\\\\\\\\\\\\
I * <-80.0 psi @ 500 gpm
I Flow Test Point
77+
70+
63+
x
P 56+
R
E
S I
S 49+
U
R I
E I
42+
( I
P I
S
I. 35+
28+
21+
14+ LEGEND
I H
I X = Required Water Supply
I 60.13 psi @ 31.2 gpm
7+
I 0 = Available Water Supply
I 82.98 psi @ 31.2 gpm
0++-+---+----+-----+------+--------+--------+---------+-----------+
200 300 400 500 600 700 800 900 1000
FLOW (GPM)
APPROVE, SUBMITTED
tXC!1DFERTMENT
MODEL 950
FEATURES
3/40 to 2N
C1 Double check valve assembly consisting of two
independently operated spring-loaded "Y" type
center guided check valves
O Complete with two full port resilient seated ball
valves for shut-off and four resilient seated ball
valve test cocks
Bronze body construction
C) Entire unit serviceable in-line
C1 Replacable seat option available
ij Available with BSP - threads (less shut-off valves)
Maximum operating pressure: 175 psi
0 Temperature range: 33°F to 140°F
O STANDARDS: A3SE (No. 1015), IAPMO®,
AWWA, GSA B64.5, USG/FCCC & HR
/
OPTIONS
/ Model 950XL Same as 950 except supplied with Noryl replaceable seats and silicone rubber check
discs. (temperature range 33°F to 1800F).
Model 950L Same as 950 except supplied less shut-off valves.
Model 950LXL Same as 950XL except supplied less shut-off valves.
Model 950S Same as 950 except supplied with "Y" strainer.
Model 950XLS Same as 950XL except supplied with"Y strainer.
Model 950U Same as 950 except supplied with union connections between ball valves and the
device.
Model 950US Same as 950U except supplied with "V strainer.
Model 950XLU Same as 950XL except supplied with union connections between ball valves and the
device.
Model 950XLUS Same as 950XLU except supplied with strainer.
22
a 20
C') CL
u 15
0 a.
.90 U) U) 0
ui 60
a:
Cl-)
30
a: a
0 0 40 80 120 160 200 240
FLOW RATE (U.S. GPM) FLOW RATE (L/S) 23
DIMENSIONS &WEIGHTS
DIMENSIONS (In.) WEIGHT (Ib8.)
MODEL A A B
LESS LESS WITH SIZE BALL DOUBLE UNION BALL BALL BALL VALVES BALL VALVES VALVES C D E F VALVES VALVES
3/4 11.12 12.50 7.00 3.10 2.77 2.87 1.22 4.80 6.47
1 12.37 13.75 7.00 3.10 2.77 2.87 1.22 4.80 7.75
1114 17.00 N/A 10.57 4.40 4.33 3.50 1.98 11.13 15.75
1112 17.62 19.12 10.57 4.40 4.33 3.50 1.98 11.55 18.30
2 18.25 20.00 10.57 4.40 4.33 3.50 1.98 1 11.92 23.05
FLOW CHARACTERISTICS
AMERICAN STANDARD METRIC STANDARD
0 10 20 30 40 50 60 0 1 2 3 4
FLOW RATE (U.S. GPM) FLOW RATE (IfS) a 20
'
Fl Res 49
Recessed Pendent/ F1
Fl Res 44
Recessed HSW/F2
Fl Res 40
Recessed HSW/F2
Fl Res 49
Pendent
Fl Res 44
HSW
Fl Res 40
HSW
RFC 43
Bulletin 035 Rev.0
tEl C
CD
0 (A) Cii
CD
C-)
11abl ,ee Residential Sprinklers
For Sloped Ceilings
Guidelines for Listed Residential Sprinkler
installations below Sloped Ceilings
Fl Res 49 Recessed Pendent/11711
Fl Res 44 HSW
Fl Res 44 Recessed HSW/F2
Fl Res 40 HSW
Fl Res 40 Recessed HSW/F2
Fl Res 49CCP
RFC 43 Flat Concealed
Listings & Approvals
Listed by Underwriters Laboratories Inc. and
UL Certified for Canada (cULus)
NYC MEA 258-93-E
UL Listing Category
Residential Automatic Sprinkler
UL Guide Number
VKKW
Patents: US Patent number 6,516,893
Model Fl Res 49
The Installation guidelines cover
I Residential Sprinkler Models:
Fl Res 49 Pendent
Product Description for Fl Res Sprinklers
Model Fl Res Pendent sprinklers are fast response
sprinklers combining excellent durability, high
sensitivity glass-bulb and low profile decorative
design. The Fl Res Horizontal Sidewall sprinklers
are equally attractive when above ceiling piping
cannot be used.
The 3mm glass-bulb pendent sprinklers, with a K
Factor of 4.9 for pendent and 4.4 for horizontal
sidewall, permit the efficient use of residential water
supplies for sprinkler coverage in residential fire
protection design.
The low flow Fl Res sprinklers are specially
engineered for fast thermal response to meet the
sensitive fire protection application needs of the
latest residential market standards (UL 1626
Standard *) Upon fire conditions, rising heat causes
a sprinkler's heat-sensitive glass-bulb to shatter,
releasing the waterway for water flow onto the
deflector, evenly distributing the discharged water to
control a fire.
Fl Res 49 CCP
Pendent
RFC 43
* Effective date July 12, 2002
The Reliable Automatic Sprinkler Co., lnc.d 525 North MacQuesten Parkway, Mount Vernon, New York 10552
Product DescriptionRFC 43
Model RFC43 Concealed Residential Sprinklers are
fast response residential fusible solder link automatic
sprinklers. Residential sprinklers differ from standard
sprinklers primarily in their response time and water
distribution patterns.
Model RFC43 sprinklers discharge water in a
hemispherical pattern below the sprinkler deflector.
Residential distribution patterns are higher and
generally contain a finer droplet size than standard
sprinkler patterns.
The combination of speed of operation and high
discharge pattern required for residential sprinklers
has demonstrated, in fire testing, an ability for
controlling residential fires, and thereby providing
significant evacuation time for occupants.
The RFC43 Sprinkler provides the best form of fire
protection by combining an attractive appearance and
½" (13mm) of cover adjustment for ease of installation.
The small diameter cover plate is easily and positively
attached and blends into the ceiling, concealing the
most dependable fire protection available, an
automatic sprinkler system.
The RFC43 is a UL Listed Residential Sprinkler to be
installed in the residential portions of any occupancy in
accordance with NFPA 13,13R, & 13D.
The RFC43 can reduce the need for precise cutting
of drop nipples. The threaded cover plate assembly
can be adjusted without tools to fit accurately against
the ceiling. The fire protection system need not be shut
down to adjust or remove the cover plate assembly.
Technical Data (Fl Res Sprinklers):
Thermal Sensor: Nominal 3mm glass-bulb
• Sprinkler Frame: Brass Casting
Sprinkler Pressure Rating: 175 psi
Factory Hydrostatically Tested to 500 psi
Thread Size : ½' NPT (R½)
K Factor : 4.9 (Actual) - Fl Res 49 Pendent Sprinkler
4.4 (Actual) - Fl Res 44 HSW Sprinkler
4.0 (Actual) - Fl Res 40 HSW Sprinkler
• Density : Minimum .05 gpm/ft2
Technical Data (RFC 43):
Thermal Sensor: 165°F Fusible Link
• Sprinkler Frame: Brass Machined
Sprinkler Pressure Rating: 175 psi
Factory Hydrostatically Tested to 500 psi
Thread Size : ½' NPT (R½)
K Factor : 4.3 (Actual)
Density : Minimum .05 gpm/ft2
Application
Model Fl Res and RFC 43 Sprinklers are used for
Residential Fire Protection according to UL 1626 Standard*. Be sure that orifice size, temperature rating,
deflector style, cover plate and sprinkler type are in
accordance with the latest published standards of The
National Fire Protection Association or the approving
Authority Having Jurisdiction.
* Effective date July 12, 2002
2.
METHOD OF CALCULATING THE CONVERSION
OF 'RISE—OVER—RUN' TO DEGREES OF AN ANGLE.
(rise)
= TAN-' (0/b)
2. slope distance: c = 7 7b*
Example: a = 4
b = 12
.4A = TAN-' (alb)
= TAN-' = (0.333)
= 18.43'
035_ROR-A
slope distance: a = '4_+12k
C '160
C = 12.65
1
3.
Model Fl Res 49 Pendent & Fl Res 49 Recessed Pendent/F1 & Fl Res 49 CCP Pendent &
RFC 43 Pendent Flat Concealed Sprinklers installed below Sloped Ceilings.
Fl Res 49
Pendent
Fl Res 49
Recessed Pendent / F2 Fl Res 49 COP
Pendent
RFC 43 RFC 43
4.
L/2
JI'IJIL'J'
B
LISTED AREA OF COVERAGE
CORRESPONDS TO CEILING SLOPE -
L = THE MAXIMUM LISTED SPRINKLER
SPACING, LENGTH (8'-0" MINIMUM).
L/2 = ONE HALF THE MAXIMUM LISTED
SPRINKLER SPACING (0'-4 MINIMUM).
W = THE MAXIMUM LISTED SPRINKLER
SPACING, WIDTH.
A = 3'-0 MAXIMUM.
B = RANGE: 2/12 (9.4') < B :9 8/12 (33.7').
C = 8'-0" MINIMUM.
Sprinkler spacing below single sloped ceilings with a maximum slope of 8/2 (33.70) pitch.
II
L
L1D AREA OF CO~ CORRESPOAOS 10 cE(MG SU
L = THE MAXIMUM LISTED SPRINKLER
SPACING. LENGTH (8'-0 MINIMUM).
1/2 = ONE HALF THE MAXIMUM LISTED
SPRINKLER SPACING (0'-4 MINIMUM).
W = THE MAXIMUM LISTED SPRINKLER
SPACING. WIDTH.
A = 34 0* MAXIMUM.
B = RANGE: 2/12(9A')'cB8/12(33.T).
C = 8'—O" MINIMUM.
Sprinkler spacing below multiple sloped ceilings with a maximum slope of 8/2 (33.70) pitch.
I Model Fl Res 49 Pendent & Fl Res 49 Recessed Pendent/F2 installed below Sloped Ceiling.
Technical Data
Thread
Sire
Max. Pressure
psi (bar)
Max.
Ambient Temp.
I OF
I Actual
K Factor
I Sj,rhi
Length Escutcheon i
I Sprinkler
I Identification
(°C) (metric) I I Number (SIN) I
½"NPT(R½) 175 (12) 100(38) 4.9(69,94) 2.25" I
(Y"
F2
Adjustment) R3516
Table 1 - Application
Max. Sprinkler Spacing Along Slope
(W)Wldthx(L)Length it (m)
Max. Slope of ¶42(33.7°) Pitch Max. Slope of ¶42(18.4°) Pitch
Sprinkler Temp. Rating °F (°C)
155(68)
Sprinkler Temp. Rating °F (°C)
155 (68) & 175 (79
Mm. Flow Per Sprinkler Head
gpm (Lpm)
Pressure
psi (bar)
Mm. Flow Per Sprinkler Head
gpm (Lpm)
Pressure
psi (bar)
12 x 12 (3,6 x 3,6) 19(71,9) 15.1 (1,04) 13(49) 7.0(0,48)
14x 14(4,3x4,3) 19(71,9) 15.1 (1,04) 13(49) 7.0(0,48)
16 x 16 (4,9 x 4,9) 19(71,9) 15.1 (1,04) 13(49) 7.0(0,48)
18 x 18 (5,5 x 5,5) 20(75,7) 16.7(1,15) 17(64,3) 12.0(0,83)
20 x 20 (6,1 x 6, 1) 25(94,5) 26(1,78) 20(75,7) 16.7(1,15)
Model Fl Res 49 CCP Pendent installed below Sloped Ceiling.
Technical Data
Sprinkler Temp. CCP Assy. I Temp.
I Max I I Max.
I Ambient
Actual
I K
I
I Sprinkler
I I
Sprinkler Thread Size Rat1n
°F (°C Rating I Pressure I Temp. Factor I length Identification
°F (°C) psi (bar) I °m (°C) (metric) I Number (SIN)
y2"NPT(Ry2) 155(68) 135 (57) I 175 (12) I 100 (38) I 4.9(69,94) I 2.25" I R3516 I
Table 2- Application
Max. Sprinkler Spacing Along Slope
(W) Width x ( L) Length ft (m)
Max. Slope of 8A2 (33.7°) Pitch
Min. Flow Per Sprinkler Head Pressure
gpm (Lpm) psi (bar)
Max. Slope of ,42 (18.4° Pitch
Mm. Flow Per Sprinkler Head Pressure
gpm (Lpm) psi (bar)
12 x 12(3,6 x 3,6) 20(75,7) 16.7(1,15) 13(49) 7.0(0,48)
14 x 14(4,3 x 4,3) 20(75,7) 16.7(1,15) 13(49) 7.0 (0,48)
16 x 16(4,9 x 4,9) 20(75,7) 16.7(1,15) 14(53)
18x 18(5,5x5,5) 21(79,4) 18.4(1,27)
20x20(6,1 x6,1) 21(79,4) 18.4 (1.27)
Model RFC 43 Pendent Flat Concealed installed below Sloped Ceiling.
Technical Data
Thread
Size
Sprinkler
Rating
I Coverplate
I Temp. Rating
°(°C)
I Max.
I Pressure
psi (bar)
I Max.
I Ambient Temp.
I °F(°C)
I Actual
J K Factor
(metric)
Max.
lAdlUstmentl
I Sprinkler I
Identification I
Number (SIN)
Y2" NPT (R½) I 165(74) 135(57) 175(12) 100(38) I 4.3 (61,4) I Y. RA0612
Table 3- Application
Max. Sprinkler Spacing Along Slope
(W) Width x ( L) Length ft (m)
Max. Slope of 6A2 (33.7°' Pitch
Mm. Flow Per Sprinkler Head Pressure
gpm (Lpm) psi (bar)
Max. Slope of ¶42(18.4°' Pitch
Mm. Flow Per Sprinkler Head Pressure
gpm (Lpm) psi (bar)
12 x 12 (3,6 x 3,6) 18(68) 17.5 (1,21) 13(49) 9.1(0,63)
14 x 14 (4,3 x 4,3) 18(68) 17.5 (1,21) 13(49) 9.1(0,63)
16x 16(4,9x4,9) 18(68) 17.5(1,21) 13(49) 9.1(0,63)
18 x 18(5,5 x 5,5) 21(79) 23.8 (1,654)
20x20(6,1 x6,1) 21(79) 23.8(1,64)
1 7.
Fl Res 44
Recessed HSW/F2 Horizontal Sidewall Sprinkler
(with discharge directed across the slope)
Fl Res44
Installation Guidelines
For systems designed in accordance with NFPA 13,
13D and 13R, where specific UL Listed flows are not
required, consult with the local Authority Having
Jurisdiction regarding the number of design sprinklers
for sloped ceilings having a pitch greater than Y12(9.40).
Installation of UL Listed residential sprinklers under
sloped ceilings shall be limited to a type of unobstructed
construction consisting of smooth ceiliflgs, as defined b
NFPA 13, having a maximum pitch of 4/12(18.4°) or 8/1
(33.7°).
Spacing of residential sprinklers under sloped ceilings is
measured along the slope when determining the
distance off of walls and between sprinklers.
Measure listed areas of coverage along the sloped ceiling. The actual floor coverage area wifi be less than
the listed area.
For coverage areas less than the listed coverage area
shown in Tables 1 through 5, use the minimum flow
requirement for the next largest listed coverage area.
Minimum spacing between pendent type sprinklers is 8
ft. (2.4 m). Minimum distance from a pendent type
sprinkler and an adjacent wall is 4' (102 mm).
Residential sprinklers located closest to the peak of the
ceiling shall have the deflectors located not more than
3 ft (11 m) vertically down from the peak. Align deflectors
parallel with the ceiling slope 1' to 4" (25mm to
102mm) below the sloped ceiling.
Hydraulic Requirements:
For NFPA 13D Systems, the number of design
sprinklers shall include all sprinklers within a
compartment up to a maximum of two sprinklers
(where specific UL Listed flows are required) that
requires the greatest hydraulic demand.
For NFPA 13R Systems, the number of design
sprinklers shall include all sprinklers within a
compartment up to a maximum of four (4) sprinklers
(where specific UL Listed flows are required), that
requires the greatest hydraulic demand.
For NFPA 13 systems, the design area shall be the
area that includes the four (4J hydraulically most
demanding sprinklers. The minimum required
discharge from each of the four hydraulically
demanding sprinklers shall be the greater of the
following:
In accordance with the minimum flow rates
indicated by the individual listings (that already
will provide a minimum density ofO. 1 gprrVft2); or
A calculated value based on delivering a
minimum of 0.1 gprrVft2 over the design area.
Because of the varied nature of residential construction
features, there will be some compartment designs which
cannot be fully sprinklered in accordance with NFPA 13,
13D, or 13R. In these instances, consult the Authority
Having Jurisdiction (AHJ) for guidance and approval.
This includes sloped ceilings having a pitch greater than
8/12 (33.7°).
Model Fl Res 44 & 40 HSW and Fl Res 44 & 40 Recessed HSW/F2
installed below the slope ceiling.
Fir
LISTED AREA OF COVERAGE
CORRESPONDS TO CEILING SLOPE
TOP OF DEFLECTOR MUST BE LOCATED
4 TO 12' BELOW SLOPED CEILING.
THE TOP OF THE DEFLECTOR OUST BE
PARALLEL WITH THE PLANE OF THE CEILING. L
DISCHARGE IS ACROSS THE SLOPE. ELEVATION
L = THE MAXIMUM USTED SPRINKLER
SPACING, LENGTH.
W = THE MAXIMUM LISTED SPRINKLER
SPACING, WIDTH.
W/2 = ONE—HALF THE MAXIMUM LISTED SPRINKLER
SPACING, WIDTH (0'-4" MINIMUM).
A = 3'-0" MAXIMUM.
B = RANGE: 2/12 (9.4') < B ic 8/12 (33.7').
C = 8'-0" MINIMUM.
HSW sprinkler spacing below single sloped ceilings with a maximum slope of 8/2 (33.7°) pitch.
w
/2 W/2
41/2
Lls7rD AREA OF COHERACE
CORRESPONDS 70 CEILiNG SLOPE
F. TOP OF DEFLECTOR *AiSr BE LOCATED 4 70 I2 BELOW SLOPED CEILING. ELEVATiON THE TOP OF THE OtflEC10R KIST BE
R4RAUEL $lflI THE PLANE OP Flit CEILING.
D6C?i4RCE IS .4L Flit SLOPE. -.
L = THE MAXIMUM LISTED SPRINKLER
SPACING. LENGTH.
W = THE MAXIMUM LISTED SPRINKLER
SPACING. WIDTH (0'-4 MINIMUM).
W/2 = ONE—HALF THE MAXIMUM LISTED SPRINKLER
SPACING. WIDTH (0'-4 MINIMUM).
A 3-0 MAXIMUM.
B = RANGE: 2/12 (9.4') B a 8/12 (33.7).
C = 81-0" MINIMUM.
HSW Sprinkler spacing below multiple sloped ceilings with a maximum slope of 8/2 (33.70) pitch.
9. /
rable 5 - Application
Discharge Directed
Down the Slope
4" to 6" Deflector to Ceiling
Discharge Directed
Down the Slope
6" to 12"
Deflector to Ceiling
Discharge Directed Across the Slope
4" to 6" Deflector to Ceiling
Max. Sprinkler Spacing Along Slope
(W) Width x ( L) Length ft (m)
Min. Flow
gpm (Lpm)
Pressure
psi (bar)
'Mln. Flow
gpm (Lpm)
Pressure
psi (bar)
1Mln. Flow
gpm (Lpm)
Pressure
psi (bar)
12 x 12(3,6 x 3,6) 13 (49,0) 10.6(0,73) 13(49,0) 10.6(0,73) 17(64,3) 18.1 (1,24)
14 x 14 (4,3 x 4,3) 16 (605) 16 (1,10) 17(64,3) 18.1 (1,10) 17(69,3) 18.1 (1,24)
16x 16(4,9x4,9) 17 (64,3) 18.1 (1,24) 20(75,7) 25 (1,72) 17(64,3) 18.1 (1,24)
16 x 18 (4,9 x 5,5) 20°(75,7) 25° (172)
16 x 20 (4,9 x 6, 1) 23 (87,0) 33.1(2,28)
*Min flow and pressure on 175°F
temperature rating only is 21 gpm
(79,5 Lpm) and 27.6_ psi bar) _(1,9 ________________________ ___
Escutcheons Recessed with F2 Recessed with F2 Standard or raised mount only
Temperature Rating OF (°C) 155(68),175 (79) 155(68), 175(79) 155(68)
(1) Minimum Flow Per Sprinkler gpm (Lpm)
Installation Guidelines
For systems designed in accordance with NFPA 13,
130 and 13R, where specific UL Listed flows are not
required, consult with the local Authority Having
Jurisdiction regarding the number of design sprinklers
for sloped ceilings having pitch greater than 2/2 (9.411 ).
Installation of UL Listed residential sprinklers under
sloped ceilings shall be limited to a type of
unobstructed construction consisting of flat, smooth
ceilings, as defined by NFPA 13, having a maximum
pitch of 4/12 (18.40) or 8112 (33.70).
Where listed, install horizontal sidewall sprinklers along
the wall below the sloped ceiling when discharge is
directed across the slope, and install at the peak below
the sloped ceiling when discharge is directed down the
slope. Always align the sprinkler deflector parallel with
the direction of the sloped ceiling.
Residential HSW sprinklers located closed to the peak
of the ceiling shall have the deflectors located not more
than 3 ft. (11 m) vertically down from the peak.
Spacing of residential HSW sprinklers under sloped ceilings is measured along the slope when determining the distance off of walls and between sprinklers.
Measure listed areas of coverage along the sloped
ceiling. The actual floor coverage area will be less than
the listed area.
For coverage areas less than the listed coverage area
shown in Tables 1 through 5, use the minimum flow
requirement for next largest listed coverage area.
Minimum spacing between horizontal sidewall
sprinklers is 8 ft. (2.4 m). Minimum distance from a
horizontal sidewall sprinkler and an adjacent wall is 4"
(102 mm).
Where installation of Fl Res 40 horizontal sidewall
sprinklers provide discharge across a slope having a
maximum pitch of 8/12, F2 escutcheons may be used
for surface mounting only.
Hydraulic Requirements:
For NFPA 130 Systems, the number of design
sprinklers shall include all sprinklers within a
compartment up to a maximum of two sprinklers
(where speciic UL Listed flows are required) that
requires the greatest hydraulic demand.
Exception: For Fl Res 40 horizontal sidewall
sprinklers, where discharge is directed across a
slope having a maximum pitch of 8/12 and the
compartment that requires the greatest hydraulic
demand is large enough where three (3) or more
sprinklers are required for adequate coverage, the
minimum number of design sprinklers within that
compartment shall be three (3), where specific UL
Listed flows are required.
For NFPA 13R Systems, the number of design
sprinklers shall include all sprinklers within a
compartment, up to a maximum of four (4)
sprinklers (where specific UL Listed flows are
required), that requires the greatest hydraulic
demand.
For NFPA 13 systems, the design area shall be the
area that includes the four (4) hydraulically most
demanding sprinklers. The minimum required
discharge from each of the four hydraulically
demanding sprinklers shall be the greater of the
following:
In accordance with the minimum flow rates
indicated by the individual listings (that already
will provide a minimum density of 0.1 gprrVft2); or
A calculated value based on delivering a
minimum of 0.1 gprrv1t2 over the design area.
Because of the varied nature of residential construction
features, there will be some compartment designs
which cannot be fully sprinklered in accordance with
NFPA 13, 130, or 13R. In these instances, consult the
Authority Having Jurisdiction (AHJ) for guidance and
approval. This includes sloped ceilings having a pitch
greater than 8/12(33.7).
11.
Model Fl Res 44 HSW & Fl Res 44 HSW Recessed HSW/F2 with a maximum slope of %2(18.4°) pitch.
Technical Data r Thread Sprinkler Max.
I
I Max. I I
Actual I Sprinkler I Sprinkler I I I Size Temp Rating . Pressure Ambient Temp. K Factor Length Escutcheon Identification OF (°C) psi (bar) OF (°C) (metric) Number (SIN) I I
½" NPT(R½) 155(68)175 (79) 175(12) 100(38) 4.4(62,8) 2.45" ('/2"
F2
adjustment)I R3531
Table 4 - Application
Discharge Directed
Across the Slope
4" to 6"
Deflector to Ceiling
Discharge Directed
Across the Slope
6" to 12"
Deflector to Ceiling
Max. Sprinkler Spacing Along Slope
(W) Width x ( L) Length ft (m)
Mm. Flow
gpm (Lpm)
Pressure
psi (bar)
Mm. Flow
gpm (Lpm)
Pressure
psi (bar)
12 x 12 (3,6 x 3,6) 16 (60,5) 13.3(0,92) 17(64,3) 15(1,04)
14x 14(4,3x4,3) 16 (60,5) 13.3 (0,92) 17(64,3) 15(1,04)
16 x 16 (4,9 x 4,9) 16 (60,5) 13.3(0, 2) 17(64,3) 15(104)
16 x 18(4,9 x 5,5) 18 (68,1) 16.8 (1,16) 20 (75,6) 20.7(1,43)
16x20(4,9x6,1) 23 (68,1) 27.4(1,89) 23(68,1) 27.4(1,89)
Model Fl Res 40 HSW and Fl Res 40 HSW Recessed HSW/F2 with a maximum slope of %2 (33.7°) pitch.
Fl Res 40 H Hes40
HSW Recessed HSW/F2
Technical Data
Thread Max. I Max. Actual I K I Sprinkler I Sprinkler
Size Pressure Ambient Temp. Factor I Length Identification
psi (bar) OF (°C) (metric) Number (SIN)
½NPT(R½) 175(12) 100(38) I 4.0(57,09) 2.45" I R3538
10.
Bulletin 136 Rev.L
R'elmable
Model Fl FR
Model Fl FR Recessed
Quick Response
Sprinklers
Model Fl FR Sprinkler Types
Standard Upright
Standard Pendent
Conventional
Vertical Sidewall
Horizontal Sidewall
- HSW 1 Deflector
Model Fl FR Recessed Sprinkler Types
Recessed Pendent
Recessed Horizontal Sidewall
- HSW 1 Deflector
Listings & Approvals
Listed by Underwriters Laboratories, Inc. (UL)
Listed by Underwriters Laboratories of Canada (ULC)
Certified by FM Approvals
Loss Prevention Council (LPC, UK)
NYC BS&A No. 587-75-SA
Meets MIL-S-901C and MIL-STD 167-1
Verband der Schadenversicherer (VdS, Germany)
NYC MEA 258-93-E
I UL Listing Category
Sprinklers, Automatic & Open
Quick Response Sprinkler
I UL Guide Number
VNIV
Product Description
Reliable Models F1FR and F1FR Recessed Sprinklers are
quick response sprinklers which combine the durability of a
standard sprinkler with the attractive km profile of a decorative
sprinkler.
The Models Fl FR and El ER Recessed automatic sprinklers
utilize a 3.0 mm frangible glass bulb. These sprinklers have
demonstrated response times in laboratory tests which are live
to ten times faster than standard response sprinklers. This
quick response enables the Model F1FR and F1 FR Recessed
sprinklers to apply water to a fire much faster than standard
sprinklers of the same temperature rating.
The glass bulb consists of an accurately controlled amount
of special fluid hermetically sealed inside a precisely manufac-
tured glass capsule. This glass bulb is specially constructed to
provide fast thermal response. The balance of parts are made
of brass, copper and beryllium nickel.
At normal temperatures, the glass bulb contains the fluid
in both the liquid and vapor phases. The vapor phase can
be seen as a small bubble. As heat is applied, the liquid ex-
pands, forcing the bubble smaller and smaller as the liquid
pressure increases. Continued heating forces the liquid to
push out against the bulb, causing the glass to shatter,
opening the waterway and allowing the deflector to distrib-
ute the discharging water.
The temperature rating of the sprinkler is identified by the
color of the glass bulb.
Upright Pendent
Vertical Sidewall Conventional
/
Horizontal Sidewall
HSW 1 Deflector Recessed Pendent
Application
Quick response sprinklers are used in fixed fire protec-
tion systems: Wet, Dry, Deluge or Preaction. Care must be
exercised that the orifice size, temperature rating, deflector
style and sprinkler type are in accordance with the latest
published standards of the National Fire Protection Asso-
ciation or the approving Authority Having Jurisdiction.
Quick response sprinklers are intended for installation as
specified in NFPA 13. Quick response sprinklers and stan-
dard response sprinklers should not be intermixed.
The Reliable Automatic Spunkier Co., Inc. 525 North MacQuesten Parkway, Mount Vernon, New York 10552
Upright Pendent Upright
Model Fl FR Quick Response Upright, Pendent & Conventional Sprinklers
Installation Wrench: Model D Sprinkler Wrench
Installation Data:
Sprinkler Type
Standard-Upright (SSLJ) and Pendent (SSP)
Deflectors Marked to Indicate
K Factor _ Sprinkler Approval
Organization
Sprinkler Identification
Number (SIN)
us metric ssu ssp
X" (15mm) Standard Orifice with ," NPT (AX) Thread 5.6 Q 2.2" (56mm) 1,2,34,5.6,7 83625 83615
%(2nm) Large Orifice with "NPT(R3A)Thread 8.0 115 2.3"(58rrm) 1,2,3,4,7.8 R3622 83612
/6 (l7mm) Small Orifice withX"NPT(R,Y2)Thread 4.2 1 60 2.54(65mm) 1,2.8 83623 R3613
" (lom) Small Orifice withX"NPT(R/2)Thread 2.8 40 2.54(65nTfl) 1,2,8 83621 83611
lOmm Orifice XLHwithR%"Thread 4.2 60 56.1mm 4,6,7 83624 - 83614
Conventional-Install in Upright or Pendent Position
4.2
5.6
8.0
60
80
115
56.1mm
56.1mm
58.4mm
-
4,6,7
4.7
83674
83675
R3672
10mm Orifice XLH with R)Thread
15mm Standard Orifice with ," NPT (RX) Thread
20mm Large Orifice with 3R'NPT(R°A)Thread
Conventional
Model Fl FR Quick Response Recessed Pendent Sprinkler
Installation Wrench: Model RC1 Sprinkler Wrench
Installation Data:
Nominal
Orifice
Thread -
Size
K Factor Sprinkler
Height
ApprovaiW
Organizations
Sprinkler Identification
Number (SIN) US Metric
/" (15mm) /" NPT(RY) 5.6 80 22"(56rnm) 1,2,3,4,5,7,8 R3615
y/32"(20nin) "NPT(R3%) 8.0 115 2.3" (58mm) 1,2,3 R3612
/6 (11 mm) )ç'NPT(81/2) 4.2 60 254" (65mm) 1,2,8 83613
%' (10mm) /"NPT(8Y2) 2.8 40 254(65mm) 1,2,8 83611
l0n-xn RY, 4.2 60 56.1mm 4.7 83614
Refer to escutcheon data table for approvals and dimensions.
2.
Vertical Sidewall
Model Fl FR Quick Response Vertical Sidewall Sprinkler
Installation Wrench: Model D Sprinkler Wrench
Installation Position: Upright or Pendent
Approval Type: Light Hazard Occupancy
Installation Data:
Nominal Orifice Thread Size
K Factor Sprinkler Height Approval
Organizations
Sprinkler Identification
Number (SIN) US Metric
½" 1/2" NPT (RI/2) 5.6 80 2.2" (56mm) 1, 2.3.6.8
15mm ½" NPT (R½) 5.6 80 2.2" (56mm) 4(1)
R3685
(1) LPC Approval is for Pendent position only.
Orientation Deflector to Ceiling
Dimension (Mm. - Max.)
Upright J 4"- 12" (102mm - 305mm)
Pendent I 6"- 12" (152mm - 305mm)
Model Fl FR Quick Response Horizontal Sidewall Sprinkler
Deflector: HSW 1
Installation Wrench: Model D Sprinkler Wrench
Installation Data:
K Factor
I Approval Organizations I and Type of Approval
I Sprinkler I Identification
Nominal
Orifice
Thread
Size US
I I Metric I Sprinkler I Length Light
Hazard
I Ordinary I Hazard
Number
I (SIN)
X"(lsmm) X"NPT(RV2) 5.6 80 2.63" (67mm) 1,2,3,5,8 1,2,5.8 R3635
NOTE: UL and ULC Listing permits use with Fl or F2 recessed escutcheon.
Horizontal Sidewall
3.
Installation
Quick response sprinklers are intended for installation
as specified in NFPA 13. Quick response sprinklers and
standard response sprinklers should not be intermixed.
The Model Fl FR Recessed Quick Response Sprinklers
are to be installed as shown. The Model Fl or F2 Escutch-
eons illustrated are the only recessed escutcheons to be
used with the Model El ER Sprinklers. The use of any other
recessed escutcheon will void all approvals and negate all
warranties.
When installing Model Fl FR Sprinklers, use the Model D
Sprinkler Wrench. When installing Model Fl FR Recessed
Sidewall Sprinklers, use the Model GFR1 Sprinkler
Wrench. Use the Model RC1 Wrench for installing F1FR
Recessed Pendent Sprinklers. Any other type of wrench
may damage these sprinklers.
Temperature Ratings
Classification
Sprinkler Max. Ambient
Temp.
Bulb
Color C_
Ordinary 57 135 10(rF(38°c) Orange
Ordinary 68 155 100-F(38"C) Red
Intermediate 79 175 150-F (66-C) Yellow
Intermediate 93 20) 150-F (66-C) Green
High1t1 1 141 286 1 225-F(107-C) I Blue
t) Not available for recessed sprinklers.
Escutcheon Data
Escutcheon "A" Face of Fitting
Model
'A"Adiustaient
Wad Dimension
Fl 1.2.4 (19mm) (19mm) (5mm-24rrrr)
F2 1.2.3.4.5.7.8 /2" 1"
(13mm) (25mm) (5rwn- 17nyn)
/6" F' 1,2 Fully Recessed (11mm) Push-on/
Thread-off 1,2 Fully Retracted V
(24mm)
Maintenance
The Models F1FR and F1FR Recessed Sprinklers
should be inspected quarterly and the sprinkler system
maintained in accordance with NFPA 25. Do not clean
sprinklers with soap and water, ammonia or any other
cleaning fluids. Remove dust by using a soft brush or gen-
tle vacuuming. Remove any sprinkler which has been
painted (other than factory applied) or damaged in any
way. A stock of spare sprinklers should be maintained to
allow quick replacement of damaged or operated sprin-
klers. Prior to installation, sprinklers should be maintained
in the original cartons and packaging until used to mini-
mize the potential for damage to sprinklers that would
cause improper operation or non-operation.
Sprinkler Types
Standard Upright
Standard Pendent
Conventional
Sidewall (Vertical, Horizontal HSW1)
Recessed Pendent
Recessed Horizontal Sidewall HSWl
Finishes ""2'
Standard Finishes
Sprinkler Escutcheon
Bronze Brass
Chrome Plated Chrome Plated (31
White Polyester Coated White Painted (31
Special Application Finishes
Sprinkler Escutcheon
Bright Brass Bright Brass
Black Plated Black Plated
Black Paint Black Paint
Off White Ott White
Satin Chrome Satin Chrome
Other finishes and colors are available on special order.
Consult the factory for details.
FM Approvals is limited to bronze and brass, chrome or black
plated finishes only.
FP Push-on/Thread-off escutcheon
Ordering Information
Specify:
Sprinkler Model
Sprinkler Type
Orifice Size
Deflector Type
Temperature Rating
Sprinkler Finish
Escutcheon Type
Escutcheon Finish (where applicable)
Note: When Model F1FR Recessed sprinklers are
ordered, the sprinklers and escutcheons are packaged
separately.
The equipment presented in this bulletin is to be installed in accordance with the latest pertinent Standards of the National Fire Protection Association. Factory Mutual Research
Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 80 years. and are installed and serviced by the most highly qualified and reputa-
ble sprinkler contractors located throughout the United States. Canada and foreign countries.
Manufactured by
Reliabld ~11
The Reliable Automatic Sprinkler Co., Inc.
(800)431-1588 Sales Offices
(800)848-6051 Sales Fax
(914)668-3470 Corporate Offices
www.retiablesprinklec.com Internet Address
® Recycled Paper
Revision lines indicate updated or new data
EG. Printed in U.S.A. 3,03 P1149999970027