HomeMy WebLinkAbout3144 EL CAMINO REAL; 103; AS060072; Permit-------·~··--------------
5/4/26, 1 :56 PM AS060072 Permit Data
City of Carlsbad
Sprinkler Permit
Job Address:
3144 EL CAMINO
REAL
Permit Type: SPRINK
Parcel No: 1670907300
Lot#: 0
Reference No.:
PC#:
Permit No: AS060072
Status: ISSUED
Applied 4/19/2006
Approved: 4/21/2006
Issued: 4/21/2006
Inspector:
Project Title: CARLSBAD MEDICAL OFFICE FIRE SPRINKLER PLAN CHECK &
INSPECTIONS
Applicant:
SHASTA FIRE PROTECTION
STE B
345 NO MARKET PL
ESCONDIDO CA
760-480-9210
about:blank
Fees($)
120
Add'I Fees ($)
0
Owner:
Total($)
120
Balance($)
0
1/1
)
)
LOBE®
FIRE SPRINKLER
CORPORATION
DESCRIPTION AND OPERATION
QUICK RESPONSE
AUTOMATIC SPRINKLERS
GL SERIES
UPRIGHT PENDENT
VERTICAL SIDEWALL
HORIZONTAL SIDEWALL
CONVENTIONAL (OLD STYLE)
The Globe Quick Response GL Series Sprinklers are a low
profile yet durable design which utilizes a 3mm frangible glass ampule
as the thermosensitive element. This provides sprinkler operation
approximately six times faster than ordinary sprinklers. While the
Quick Response Sprinkler provides an aesthetically pleasing appear
ance, it can be installed wherever standard spray sprinkl~rs are
specified when allowed by the applicable standards. It offers the
additional feature of greatly increased safety to life and is available
in various styles, orifices, temperature ratings and finishes to meet
many varying design requirements. Quick Response Sprinklers
should be used advisedly and under the direction of approving
authorities having jurisdiction.
The heart of Globe's GL Series sprinkler proven actuating
assembly is a hermetically sealed frangible glass ampule that contains
a precisely measured amount of fluid. When heat is absorbed, the
liquid within the bulb expands increasing the internal pressure. At
the prescribed temperature the internal pressure within the ampule
exceeds the strength of the glass causing the glass to shatter. This
results in water discharge which is distributed in an approved
pattern depending upon the deflector style used.
TECHNICAL DATA
See reverse side for Approvals and Specifications.
Temperature Ratings -I 35°F (57°C), I 55°F (68°C), I 75°F (79°C),
200°F (93°C), 286°F (141°C).
Water Working Pressure Rating -175 psi ( 12 Bars).
Factory tested hydrostatically to 500 psi (34 Bars).
Maximum low temperature glass bulb rating is -67°F (-55°C).
Frame -bronze Deflector -brass Screw -brass
Bulb seat -copper Spring -nickel alloy Seal -teflon
Bulb -glass with alcohol based solution, 3mm size.
-,. "'.' ,
Ai
QUICK RESPONSE
UPRIGHT CONVENTIONAL
QUICK RESPONSE
PENDENT VERTICAL
SIDEWALL
QUICK RESPONSE
HORIZONTAL SIDEWALL
SPRINKLER TEMPERATURE RATING/CLASSIFICATION and COLOR CODING
CLASSIFICATION AVAILABLE SPRINKLER
TEMPERATURES
ORDINARY 135"F/155°F 57"C/68°C
INTERMEDIATE 17S'F/200"F 79'C/93'C
HIGH 286'F 141'C
4077 AIRPARK DRIVE. STANDISH. MICHIGAN 48658
NOVEMBER 2000 A-6
BULB
COLOR
ORANGE/RED
YELLOW/GREEN
BLUE
N.F.P.A. MAXIMUM
CEILING TEMPERATURE
l~"F ·38°C ~-' ,. IS '•F ... s. 66°C
•. -,4, ' .. 22$'F • 107'C
517-846-4583 • FAX 517-846-9231
BULLETIN GL56 I 5
QUICK RESPONSE
AUTOMATIC SPRINKLERS
GLSERIES
UPRIGHT• PENDENT• VERTICAL SIDEWALL
HORIZONTAL SIDEWALL• CONVENTIONAL (OLD STYLE)
SPECIFICATIONS
NOMINAL "K" FACTOR THREAD SIZE •LENGTH FINISHES
2.8 (39 metric) 1/2" NPT 2 1/4" (5.7 cm) Fact0ry Bronze
4.2 (59 metric) 1/2" NPT 2 1/4" (5.7 cm) ""Satin Chrome
Bright Chrome
5.6 (80 metric) 1/2" NPT 2 1/4" (5.7 cm) White Polyester+
7.8 ( 111 metric) 1/2" NPT 2 I /4" (5.7 cm) Black Polyester+
8.1 ( I 16 metric) 3/4" NPT 2 7/16" (6.2 cm) ""Lead Coated
NOTE: METRIC CONVERSIONS ARE APPROXIMATE. • HORIZONTAL SIDEWALL IS 2 9/16" .
.. FINISHES AVAILABLE ON SPECIAL ORDER.
+ AVAILABLE AS UL ANO C-UL LISTED CORROSION
RESISTANT WHEN SPECIFIED ON ORDER. APPROVALS
K IJS'F ISS'F 175'F 200°F 286'F CANADIAN ♦ N. Y.C. • D.O.B. STYLE MODEL FACTOR 57'C 68"C 79'C 93°C 141'C U.L. U.L F.M. MEA 101-92-E
GL2815 28 X X X X X X X --X
GL4215 4.2 X X X X X X X --X
UPRIGHT GLS615 5.6 X X X X X X X X X
GLBI IS 7.8' X X X X X X X --X
GL8118 8.1 X X X X X X X --X
GL2801 28 X X X X X X X --X
GL4201 4.2 X X X X X X X --X
PENDENT GLS601 5.6 X X X X X X X X X
GLBI0I 7.8" X X X X X X X --X
GL8106 8.1 X X X X X X X --X
VERTICAL t GLS632 5.6 X X X X X X X ----
SIDEWALL GLBIJJ 8.1 X X X X X X X -----
HORIZONTAL GL2826 28 X X X X X X X ... X
SIDEWALL§ GL4226 4.2 X X X X X X X ... X
GLS626 5.6 X X X X X X X X X
CONVENTIONAL GLS624 5.6 X X X X X -... ... ...
(OLD STILE) GL8125 8.1 X X X X X --... ---...
I HORIZONTAL SIDEWALL UL AND C-UL LISTED FOR DEFLECTOR ◄" TO 12" BELOW THE CEILING, FM APPROVED ◄" TO 6".
t VERTICAL SIDEWALL SPRINKLER UL AND C-UL LISTED FOR LIGHT HAZARD ONLY.
PENDENT VERTICAL SIDEWALL UL ANO C-Ul LISTED FOR 6' MIN. SPACING
UPRIGHT VERTICAL SIDEWALL UL ANO C-UL LISTED FOR 9' MIN. SPACING
~11r NPT.
ORDERING INFORMATION ♦ FM APPROVED FOR IJS"FAND ISS'F ONLY.
SPECIFY
Quantity Model Number Style
Orifice Thread Sizes Temperature
Finishes desired
Quantity -Wrenches -P/N 325390 (1/2"),
P/N 312366 (L.O.)
LOBE®
FIRE SPRINKLER
CORPORATION
NOVEMBER 2000
GLOB~ PRODUCT WARRANTY
Globe agrees to repair or replace any of its own manufac
tured products found to be defective in material or workman
ship for a period of one year from date of shipment.
For specific details of our warranty please refer to Price
list Terms and Conditions of Sale (Our Price List).
4077 AIRPARK DRIVE. STANDISH, MICHIGAN 48658
S 17-846-4583
1-800-248-0278
PRINTEDU.5.A
FAX 517-846-9231
www.globesprinkler.com
BULLETIN GLS6 IS