HomeMy WebLinkAboutCP 90-11; Shinn Condominium Conversion; Condo Permit (CP) (9)CITTOF CARLSBAD
INTER-OFFICE CORRESPONDENCE
TO: Karen Hirata
FROM: Ray Garrison. Building Technician
SUBJECT: 4537 Cove Drive
George Shinn. Cvdnev Shinn
OFFICE: Deputy City Attorney
DATE: January 29. 1991
MESSAGE:
Please find attached the Code Sections and explanation of the violations observed at the
above referenced property. Also included is a copy of the plans submitted for his
condominium permit, highlighted to show separation in Unit A. The highlighted area is
one unit, as converted by the owner. The Principal Building Inspector will permit the
cabinets to remain in the attic area.
Codes Violated:
1. C.M.C. 21.22.080 - More than two units is over density for this lot. The lot is 40
feet by 117 feet which equals 4,680 square feet.
4680
43560 = 0.107438 x 20 units = 2.14876 units, or two units are permitted on this
lot.
2. C.M.C. 18.04.015 - Conversion of attic to usable floor area without permits. A
portion of the usable floor area is being used as habital space. Reference U.B.C.
Section 409:
HABITABLE SPACE (ROOM) is a space in a structure for living, sleeping,
eating or cooking. Bathrooms, toilet compartments, closets, halls.storage
or utility space, and similar areas, are not considered habitable space.
Articles of habitation would then be things that would be found in rooms used for
human habitation.
3. C.M.C. 18.04.015 - Closing off stairway without permits. Reference U.B.C. 3301 (c).
Exit Obstruction. Obstructions shall not be placed in the required width of
an exit except projections permitted by this chapter.
Wall dividing second floor into two units at stairway. Reference U.B.C. 3303(a).
The second story shall be provided with not less than two exits when the
occupant load is ten or more. Occupants on floors above the second story
and in basements shall have access to not less than two separate exits
from the floor or basement.
Karen Hirata
January 29, 1991
Page Two
Exceptions:
3. When the third floor within an individual dwelling unit does not exceed
500 square feet, only one exit need be provided from that floor.
This requires two exits from floors above the second floor if the space above the
second floor is over 500 square feet.
4. C.M.C. 18.12.240 - Electrical conduit installed on exterior wall of building and in rain
gutter downspout.
5. C.M.C. 18.12.080 - Electrical work installed in attic space without permit or
inspections.
Signature:
c: Principal Building Inspector
Senior Building Inspector
Assistant Planning Director
21.22.060
distance between buildings used for human habi-
tation and accessory buildings shall be eight feet.
(Ord. 9189 § 1 (part): Ord. 9060 § 955)
21.22.070 Minimum lot area.
The minimum required area of a lot in the R-
W zone shall not be less than five thousand
square feet. (Ord. 9336 § 9, 1972: Ord. 9189 § 1
(part): Ord. 9060 § 956)
21.22.080 Maximum allowable density.
The maximum allowable density shall be
twenty units per acre. A density of up to thirty
dwelling units per acre may be established by the
planning commission or city council, whichever
is the final decisionmaking body for a project
requiring a discretionary permit or entitlement
under this code, or the planning commission for
all other projects if said body finds that the den-
sity is consistent with the general plan and the
provisions of this code.
Except when the city council is the final deci-
sionmaking body for a project, a decision of the
planning commission establishing density may
be appealed to the city council not later than ten
days after the decision or not later than the time
for appeal of the discretionary permit or entitle-
ment for the project, whichever is later. (Ord.
9606 § 1 (part), 1981: Ord. 9189 § 1 (part): Ord.
9060 § 957)
21.22.090 Lot width.
Every lot shall have a width of not less than
forty feet at the rear line of the required front
yard. (Ord. 9189 § 1 (part): Ord. 9060 § 958)
21.22.100 Lot coverage.
All buildings, including accessory buildings
and structures, shall not cover more than sev-
enty-five percent of the area of the lot. (Ord. 9189
§ 1 (part): Ord. 9060 § 959)
21.22.120 Waterway access.
Not less than seventy percent in number of the
R-W zoned lots in any subdivision in an R-W
zone shall have direct access to a navigable water-
way. For each twenty lots or portion thereof with-
out direct access to a navigable waterway, there
shall be provided a boat launching facility within
the subdivision on an R-W zoned lot which does
have direct access to a navigable waterway. The
area of such lot not utilized for the boat launch-
ing facility shall be improved for parking and
shall conform to the requirements of Sections
21.44.180 and 21.44.200. "Direct access" for the
purpose of this section shall mean that at least
twenty feet or one-half, whichever is the longer,
of a side or rear lot line shall border upon such
navigable waterway. "Navigable waterway" for
the purpose of this section means an ocean inlet
or lagoon, or other arm of the sea, actually usable
for boating; and any channel actually usable for
boating and docking facilities connecting with an
ocean inlet or lagoon or other arm of the sea.
(Ord. 9189 § 1 (part): Ord. 9060 § 961)
603/605 (Carlsbad 8-88)
18.04.010
Chapter 18.04
BUILDING CODE
Sections:
18.04.010 Adopted.
18.04.015 Section 301 (a) amended—
Permits required.
18.04.020 Section 303(a) amended—
Building permit issuance.
18.04.030 Section 303(d) amended—
Expiration.
18.04.035 Section 304(d) amended—
Expiration of plan review.
18.04.040 Factory built housing.
18.04.160 Section I807(a) amended—
Special provisions.
18.04.170 Section 1808 added—Special
provisions for buildings
between 35 and 55 feet in
height.
18.04.180 Special provisions for buildings
between 35 and 55 feet in
height—Type I-F.R.
18.04.190 Special provisions for buildings
between 35 and 55 feet in
height—Type III.
18.04.210 Special provisions for buildings
between 35 and 55 feet in
height—Type IV.
18.04.220 Section 2312(d)2—Earthquake
regulations.
18.04.230 Section 3201 amended—
General.
18.04.235 Spark arrester.
18.04.260 Section 3802(a) amended—
Automatic fire extinguishing
systems.
18.04.270 Section 3802(h) amended—
Group R Division 1 and 3
Occupancies.
18.04310 Violations.
18.04.320 Building numbering.
18.04J30 Street name signs.
18.04J40 Findings.
18.04.010 Adopted.
The Uniform Building Code, excluding Chap-
ters 53 and 70 of the Appendix, 1988 Edition,
hereinafter referred to as "the code," and the
Uniform Building Code Standards, 1988 Edi-
tion, published by the International Conference
of Building Officials, referred to as "standards,"
two copies of which are on file in the office of the
city clerk for public record and inspection, are
adopted by reference as the city building code for
regulating the erection, construction, enlarge-
ment, alteration, repair, moving, removal, dem-
olition, conversion, occupancy, equipment, use,
height, area, and maintenance of all buildings or
structures in the city, except for changes, addi-
tions, deletions and amendments in this chapter,
which shall supersede the provisions of said code.
(Ord. NS-105 § 1 (part), 1990)
18.04.015 Section 301 (a) amended—Permits
required.
Section 301(a) of the Uniform Building Code
is amended to read:
Except as specified in Subsection (b) of this
section, no building or structure regulated by
this code shall be erected, constructed,
enlarged, altered, repaired, moved, improved,
removed, converted or demolished unless a
separate permit for each building or structure
has first been obtained from the building offi-
cial.
(b) Exempted Work. A building permit
shall not be required for the following:
1. One-story detached accessory buildings
used as tool and storage sheds, patio cover
structures, playhouses, treehouses and similar
uses, provided the projected roof area does not
exceed 120 square feet.
2. Playground, gymnastic and similar
equipment and structures used for recreation
and athletic activities.
3. Fences not over 6 feet high.
4. Oil derricks.
399 I Carlsbad 6-90
18.12.030
inspections, reinspections made and other offi-
cial work performed in accordance with the
provisions of this code. The director of building
and planning may delegate any of his powers or
duties to any of his assistants. (Ord. 8098 § 2
(pan), 1982; Ord. 8061 (part), 1972: prior code §
9.1 (part))
18.12.040 Director of building and
planning — Authority.
The director of building and planning shall
have the right during reasonable hours or at any
time when extreme danger exists to enter any
building in the discharge of his official duties or
for the purpose of making an inspection,
reinspection, or test of the installation of elec-
trical wiring, devices, appliances, and equipment
contained therein. The director of building and
planning shall have the authority to cut or dis-
connect any wire in cases of emergencies where
necessary to safety or life of property or where
such wire may interfere with the work of the fire
department. The director of building and plan-
ning is authorized to disconnect or order discon-
tinuance of electrical service to any electrical
wiring, device, appliance, or equipment found to
be dangerous to life or property because they are
defective or defectively installed. (Ord. 8089 § 2
(part), 1982; Ord. 8061 (part), 1972: prior code §
18.12.050 Interpretation.
The language used in this code and in the
National Electrical Code, which is herein
adopted by reference, is intended to convey the
common and accepted meaning familiar to the
electrical industry. The director of building and
planning is authorized to determine the intent
and meaning of any provisions of this code. Such
determination shall be made in writing and a
record kept which record shall be open to the
public. (Ord. 8098 § 2 (part), 1982; Ord. 8061
(part), 1972: prior code § 9.1(B))
418-1
18.12.060 Responsibility.
This code shall not be construed to relieve
from or lessen the responsibility of any party
owning, operating, controlling, or installing any
electrical wiring, electrical device, or electrical
materials for damage to person or property
caused by any defect therein, nor shall the city or
any officer or employee thereof enforcing this
code be held as assuming any such liability by
reason of the inspections authorized therein, or
certificate of inspection issued in accordance
with the provisions of this code. (Ord. 8061
(part), 1972: prior code § 9.1(Q)
18.12.070 Prohibitions.
It is unlawful for any person either as owner,
architect, contractor, artisan or otherwise to do
or knowingly to cause or permit to be done any
electric wiring in such manner that the same shall
not conform to all of the provisions of this code.
(Ord. 8061 (part), 1972: prior code § 9.2)
18.12.080 Permits—Required.
(a) No electric wiring, devices, appliances or
equipment shall be installed within or on any
building, structure or premises nor shall any
alteration without first securing a permit therefor
from the building and planning director except
as stated in Section 18.12.090.
(b) Permits shall be obtained before or at the
time work is started, except in cases where emer-
gency or urgent necessity can be shown to exist
provided a permit is obtained within twenty-four
hours, exclusive of Saturdays, Sundays, and holi-
days.
(c) A separate permit shall be required for
each building or structure which stands alone.
(d) Permits for privately-owned conduits or
other materials in public places and in and across
streets and alleys may be issued only after
approval has been granted for the installation by
the city engineer. All work shall be done in
accordance with law and special regulations
applicable thereto.
(Carlsbad 1-8
18.12.230
duplex is not considered a multiple-occupancy
in this instance." (Ord. 8104 § 2 (part), 1985:
Ord. 8069 § 3 (part), 1976: Ord. 8061 (part),
1972: prior code §9.26)
II. Modifications*
•Prior history: Prior code §§ 9.20 and 9.26. Ords. 8061. 8069, 8078
and 8098.
18.12.240 Article 225-10 amended—Outside
branch circuits and feeders.
Section 225-10 of the National Electrical Code
is amended by the addition of the following:
The installation of outside wiring on roof
surfaces shall not be allowed. The installation
of outside wiring on surface of building shall
have approval of the administrative authority.
(Ord. 8104 §2 (part), 1985)
18.12.241 Article 230-79—Rating of
disconnect.
Article 230-79 of the National Electrical Code
is amended to read:
The service disconnecting means shall have
a rating not less than one hundred amperes or
with approval of the administrative authority
a rating not less than the load to be carried,
determined in accordance with Article 220. In
no case shall the rating be lower than specified
in (a), (b), (c) or (d) below.
(Ord. NS-27 § 3 (part), 1988)
18.12.245 Article 250-8l(c)—Concrete
encased electrode amended.
Article 250-8 l(c) of the National Electrical
Code is amended to read:
The primary grounding method shall be
that which is referred to as the "Ufer Ground"
consisting of 20 feet or more of Copper Con-
ductor #4 (minimum) or larger sized from
N.E.C. Table 250-904, "Grounding Electrode
Conductor for AC Systems." The copper con-
ductor shall be placed three inches up from the
bottom and a three-inch clearance from the
sides of the concrete footing and supported by
a Reinforcing Bar #4 or larger completely
encased in concrete. When below ground, the
copper electrical conductor shall be encased in
concrete (or in rigid nonmetallic conduit from
six inches inside the concrete roofing) to the
service equipment.
The copper electrode conductor shall be
continuous and unbroken to its termination at
the service connection.
For single-family residential use only (up to
and including 200 amp service), the concrete
encased electrode (rebar) may be used subject
to the following requirements:
1. The Rebar #4 ('/:") or larger to which the
grounding electrode conductor is connected
must be a minimum of 20 feet long, unbroken.
2. The total developed length of rebar
placed three inches up from the bottom of the
foundation must be no less than 20 feet.
Where splices are necessary to obtain the
required 20 feet of rebar, they must be made so
that the two bars overlap by no less than 15
inches and are secured by at least two steel tie
wires. The splice shall occur at the opposite
end from the extended location.
3. The rebar may only extend out of the
slab in a dry location.
4. The rebar must extend out of the slab at
least six inches and not more than 18 inches
and the point of connection of the grounding
electrode connector must be accessible.
Aluminum or copper-clad aluminum elec-
trode conductor shall not be used in concrete,
outside or in any other corrosive environ-
ment.
(Ord. NS-27 § 2 (part), 1988)
423 (Carlsbad 1-89)
407-409 UNIFORM BUILDING CODE
FLAMMABLE LIQUID. See Fire Code.
FLOOR AREA is the area included within the surrounding exterior walls of a
building or portion thereof, exclusive of vent shafts and courts. The floor area of a
building, or portion thereof, not provided with surrounding exterior walls shall be
the usable area under the horizontal projection of the roof or floor above.
FOAM PLASTIC INSULATION is a plastic which is intentionally expanded
by the use of a foaming agent to produce a reduced density plastic containing
voids consisting of hollow spheres or interconnected cells distributed throughout
the plastic for thermal insulating purposes and which has a density less than 20
pounds per cubic foot.
FOOTING is that portion of the foundation of a structure which spreads and
transmits loads directly to the soil or the piles.
FRONT OF LOT is the front boundary line of a lot bordering on the street and,
in the case of a corner lot, may be either frontage.
Sec. 408. GARAGE is a building or portion thereof in which a motor vehicle
containing flammable or combustible liquids or gas in its tank is stored, repaired
or kept.
GARAGE, PRIVATE, is a building or a portion of a building, not more than
1000 square feet in area, in which only motor vehicles used by the tenants of the
building or buildings on the premises are stored or kept. (See Section 1101.)
GARAGE, PUBLIC, is any garage other than a private garage.
GRADE (Adjacent Ground Elevation) is the lowest point of elevation of the
finished surface of the ground, paving or sidewalk within the area between the
building and the property line or, when the property line is more than 5 feet from
the building, between the building and a line 5 feet from the building.
GRADE (Lumber) is the classification of lumber in regard to strength and
utility.
GUARDRAIL is a system of building components located near the open sides
of elevated walking surfaces for the purpose of minimizing the possibility of an
accidental fall from the walking surface to the lower level.
GUEST is any person hiring or occupying a room for living or sleeping
purposes.
GUEST ROOM is any room or rooms used or intended to be used by a guest for
sleeping purposes. Every 100 square feet of superficial floor area in a dormitory
shall be considered to be a guest room.
H
~. Sec. 409. HABITABLE SPACE (ROOM) is space in a structure for living,
sleeping, eating or cooking. Bathrooms, toilet compartments, closets, halls,
storage or utility space, and similar areas, are not considered habitable space.
24
3301 UNIFORM BUILDING CODE
Chapter 33
EXITS
General
Sec. 3301. (a) Genera]. Every building or portion thereof shall be provided
with exits as required by this chapter.
(b) Definitions. For the purpose of this chapter, certain terms are defined as
follows:
BALCONY, EXTERIOR EXIT, is a landing or porch projecting from the
wall of a building, and which serves as a required exit. The long side shall be at
least 50 percent open, and the open area above the guardrail shall be so distributed
as to prevent the accumulation of smoke or toxic gases.
CONTINENTAL SEATING is the configuration of fixed seating where the
number of seats per row exceeds 14 and required exits from the seating area are
side exits.
EXIT is a continuous and unobstructed means of egress to a public way and
shall include intervening aisles, doors, doorways, corridors, exterior exit balco-
nies, ramps, stairways, smokeproof enclosures, horizontal exits, exit passage-
ways, exit courts and yards.
EXIT COURT is a yard or court providing access to a public way for one or
more required exits.
EXIT PASSAGEWAY is an enclosed exit connecting a required exit or exit
court with a public way.
HORIZONTAL EXIT is an exit from one building into another building on
approximately the same level, or through or around a wall constructed as required
for a two-hour occupancy separation and which completely divides a floor into
two or more separate areas so as to establish an area of refuge affording safety
from fire or smoke coming from the area from which escape is made.
PANIC HARDWARE is a door- latching assembly incorporating an unlatching
device, the activating portion of which extends across at least one half the width of
the door leaf on which it is installed.
PRIVATE STAIRWAY is a stairway serving one tenant only.
PUBLIC WAY is any street, alley or similar parcel of land essentially unob-
structed from the ground to the sky which is deeded, dedicated or otherwise
permanently appropriated to the public for public use and having a clear width of
not less than 10 feet.
\ SPIRAL STAIRWAY is a stairway having a closed circular form in its plan
\ view with uniform section shaped treads attached to and radiating about a mini-
mum diameter supporting column. The effective tread is delineated by the nosing
radius line, the exterior arc (center line of railing) and the overlap radius line
(nosing radius line of tread above). Effective tread dimensions are taken along a
line perpendicular to the center line of the tread.
(c) Exit Obstruction. Obstructions shall not be placed in the required width of
an exit except projections permitted by this chapter.
634
3302-3303 UNIFORM BUILDING CODE:
' •
The maximum occupant load for an assembly use shall not exceed the occupant
load as determined in accordance with Section 3302 (a).
EXCEPTION: The occupant load for an assembly building or portion thereof
maybe increased, when approved by the building official, if all the requirements of
this code are met for such increased number of persons. The building official may
i require an approved aisle, seating or fixed equipment diagram to substantiate such an
increase, and may require that such diagram be posted.
(c) Posting of Room Capacity. Any room having an occupant load of 50 or
--«i more where fixed seats are not installed, and which is used for classroom,
,m3 assembly or similar purpose, shall have the capacity of the room posted in a
} conspicuous place on an approved sign near the main exit from the room. Such
signs shall be maintained legible by the owner or his authorized agent and shall
indicate the number of occupants permitted for each room use.
(d) Revised Occupant Load. After a building is occupied, any change in use or
increase in occupant load shall comply with this chapter. See Section 502.
Exits Required
Sec. 3303. (a) Number of Exits. Every building or usable portion thereof shall
have at least one exit, not less than two exits where required by Table No. 33-A and
additional exits as required by this subsection.
For purposes of this section, basements and occupied roofs shall be provided
with exits as required for stories.
EXCEPTIONS: Occupied roofs on Group R, Division 3 Occupancies may have
s one exit if such occupied areas are less than 500 square feet and are located no higher
""--.. than immediately above the second story.
Floors complying with the provisions for mezzanines as specified in Section
1716 shall be provided with exits as specified therein.
The second story shall be provided with not less than two exits when the
occupant load is ten or more. Occupants on floors above the second story and in
• basements shall have access to not less than two separate exits from the floor or
X ' basement.
\ ; EXCEPTIONS: 1. Two or more dwelling units on the second story or in a
basement may have access to only one common exit when the total occupant load
served by that exit does not exceed ten.
^ 2. Except as provided in Table No. 33-A. only one exit need be provided from the
\ ' second floor or a basement within an individual dwelling unit. Refer to Section 1204
\ * tor emergency escape or rescue requirements from sleeping rooms.
3. When the third floor within an individual dwelling unit docs not exceed 500
\ ^ square feet, only one exit need be provided from that floor.
4. Floors and basements used exclusively for service of the building may have
one exit. For the purposes of this exception, storage rooms, laundry rooms, mainte-
Sj nance offices and similar uses shall not be considered as providing service to the
,; building.
5. Storage rooms, laundry rooms and maintenance offices not exceeding 300
square feet in floor area may be provided with only one exit.
For special requirements see the following sections: Group A, Sections 3317
636
JANUARY 25, 1991
TO: BUILDING DEPARTMENT
PETE DREIBELBIS
TONY MATA
RAY GARRISON
FROM: City Attorney
4537 COVE DRIVE/CONDOMINIUM CONVERSION
Attached is a letter I received from George Shinn. He delivered it
in person and asked to speak to me about the problem. I told him
our policy is to seek voluntary compliance whenever possible, but
he must comply with the building code and city ordinances.
I also told him that it appeared to me that he was trying to use
technicalities to convert two units into four or five and he was
not being honest about it.
The City Attorney wants me to answer his letter in detail,
explaining exactly what code sections he has violated. Please list
all of the items which are in violation, and attach highlighted
code sections describing the violation. Also, please make a list
of the items he has added which are not in the approved plans.
The City Attorney wants the planning department to investigate this
situation as a violation of our zoning ordinances. Please
coordinate our legal position with the planning department. I will
send them a memo requesting their assistance.
KAREN J. HIRATA
Deputy City Attorney
afd
-£,,„.. ,i,,, , ^ C,TY QF CARLS3AD_
ENGINEERING DEPARTS -T
Inter-Office Corresoondence
TO: Parks Dept. / . CRMWD
Planning Dept. /X" LCWD
Util.Maint. Dept. Olivenhain WD
Fire Dept. SMCWD
jUBJECi : Request for comments relative to Minor Subdivision No.
Applicant:'
Enclosed is a copy of the Tentative Parcel Map of the subject Minor Subdivision with
ittachmenis for your information as follows:
Dlease review this proposed development and submit your comments to the City Engineer,
<Utn:'/ /Std-* A^L^c+Jgi . Failure to respond to this request
oy />•- 7--&-f o * will be interpreted to mean that the proposal has your endorsement
as submitted and no fees, deposits, or specific conditions wilt-be required..
,x;C^---
Thank you for your cooperation. ' V
T5J>
City Engineer
REPLY:
/LfrTcr »J xr0«*!«Hr
$>ll*<Jxa;'*G
o •*
18.04.015
5. Movable cases, counters and partitions
not over 5 feet 9 inches high.
6. Retaining walls which are not over 4 feet
in height measured from the bottom of the
footing to the top of the wall, unless support-
ing a surcharge or impounding Gass I, II or
III-A liquids.
7. Water tanks supported directly upon
grade if the capacity does not exceed 5,000
gallons and the ratio of height to diameter or
width does not exceed two to one.
8. Platforms, walks and driveways not
more than 30 inches above grade and not over
any basement or story below.
9. Painting, papering and similar finish
work.
10. Temporary motion picture, television
and theater stage sets and scenery.
11. Window awnings supported by an exte-
rior wall of Group R, Division 3, and Group M
Occupancies when projecting not more than
54 inches.
12. Prefabricated swimming pools
accessory to a Group R, Division 3 Occupancy
in which the pool walls are entirely above the
adjacent grade and if. the capacity does not
exceed 5,000 gallons.
13. Patio Cover structures up to 300 square
feet of projected roof area located at least 6 feet
from any other building on the same property.
14. Antennas supported on the roof.
15. Electrolier standards, flag poles and
antennas not over 35 feet in height above
finish grade when fully extended.
16. Repairs which involve only the replace-
ment of component parts or existing work
with similar materials only for the purpose of
maintenance and which do not aggregate over
$1,000.00 in valuation and do not affect any
electrical or mechanical installations. Repairs
exempt from permit requirements shall not
include any addition, change or modification
in construction, exit facilities or permanent
fixtures or equipment. Specifically exempt
from permit requirements regardless of value:
(Carlsbad 6-90) 400
a. Painting and decorating.
b. Installation of floor covering.
c. Cabinetwork.
d. Outside paving.
Unless otherwise exempted, separate
plumbing, electrical and mechanical permits
will be required for the above exempted items.
Exemption from the permit requirements
of this code shall not be deemed to grant
authorization for any work to be done in any
manner in violation of the provisions of this
code or any other laws or ordinances of this
jurisdiction.
(Ord. NS-105 § 1 (part), 1990)
18.04.020 Section 303(a) amended—Building
permit issuance.
Section 303(a) of the Uniform Building Code
is amended to read:
The application, plans, and specifications
filed by an applicant for a permit shall be
checked by the Building Official. Such plans
may be reviewed by other departments of the
City to check compliance with the laws and
ordinances under their jurisdiction. If the
Building Official is satisfied that the work
described in an application for permit and the
plans filed therewith conform to the require-
ments of this code and other pertinent laws
and ordinances and that the fee specified in
this chapter has been paid, he shall issue a
permit therefor to the applicant. In the case of
new building, all fees required for connection
to public water systems and to sewer systems
provided by entities other than the City must
be paid or a bond posted before a permit is
issued.
When the Building Official issues a permit,
he shall endorse in writing or stamp on both
sets of plans and specifications, "Approved."
Such approved plans and specifications shall
not be changed, modified, or altered without
18.12.080
(e) Permits shall only be issued to contractors
licensed by the state of California to engage in the
business or act in the capacity of a contractor,
relating to electrical inspection installation, and
to persons holding a valid master electrician cer-
tificate of competency for work performed only
on the property of his employer, or the owner.
(Ord. 1266 § I (part), 1983; Ord. 8061 (part),
1972: prior code §9.3)
18.12.090 Permits—Exceptions.
(a) No permit shall be required for minor
repair work such as repairing flush or snap
switches, replacing fuses, repairing lamp sockets
and receptacles when such work is done in
accordance with the provisions of this code.
(b) No permit shall be required for the
replacement of lamps or the connection of porta-
ble appliances to suitable receptacles which have
been permanently installed.
(c) No permit shall be required for the
installation, alteration or repair of wiring,
devices, appliances or equipment for the opera-
tion of signals or the transmission of intelligence
(not including the control of lighting or
appliance circuits) where such wiring, devices,
appliances or equipment operate a voltage not
exceeding twenty-five volts between conductors
and do not include generating or transforming
equipment capable of supplying more than one
hundred watts of energy.
(d) No permit shall be required for the
installation, alteration or repair of electric wir-
ing, devices, appliances and equipment installed
by or for a public service corporation in the oper-
ation of signals or the transmission of intel-
ligence.
(e) No permit shall be required for the
installation of temporary wiring for testing elec-
trical apparatus or equipment. (Ord. 8061 (part),
1972: prior code § 9.4)
18.12.100 Permits—Expiration.
(a) If the work authorized by a permit is not
commenced within one hundred eighty days
after issuance or if the work authorized by a
permit is suspended or abandoned at any time
after the work is commenced for a period of one
hundred eighty days, the permit shall become
void.
(b) Permits shall expire one year after the date
of issuance unless the permit is issued for a longer
period of time.
(c) Permits for a period longer than one year
must be requested at the time of application for
the original permit. Said permits will be issued
for a period of time determined by the building
and planning director to be reasonably necessary
to complete the work for which a permit is
requested.
(d) An expired permit may be renewed upon
payment of a fee to cover the unfinished work
according to the fee schedule. (Ord. 1266 § 1
(part), 1983; Ord. 8098 § 3, 1982; Ord. 8061
(part), 1972: prior code § 9.5)
18.12.110 Installations—Incompleted.
Should any person to whom a permit has been
issued quit an installation, for any reason, he
shall notify the building and planning director
within forty-eight hours and request an inspec-
tion of work installed. No person shall resume
work on an uncompleted installation until such
installation shall have been approved by the
building and planning director and necessary
permit obtained. (Ord. 1266 § 1 (part), 1983; Ord.
8061 (part), 1972: prior code § 9.6)
18.12.120 Permit—Scope.
The permit when issued shall be for such
installation as is described in the application and
no deviation shall be made from the installation
so described without the written approval of the
building and planning director. (Ord. 1266 § 1
(part), 1983; Ord. 8061 (part), 1972: prior code §
9.7)
18.12.130 Permit—Application.
Application for permit, describing the work to
be done, shall be made in writing to the director
419