Loading...
HomeMy WebLinkAboutCT 93-09; Ocean Bluff; Tentative Map (CT) (22)City of Carlsb. J 93142 Fire Department Bureau of Prevention Plan Review: Requirements Category: Fire Conditions Date of Report: Friday. October 13,1995 Reviewed by: Contact Name Anne Hysong Address Las Palmas r City, State CBD CA 92009 Blda. Deot. No. Job Name Ocean Bluff Job Address Black Rail/Poinsettia Plannina No. CT93-9 *%&- - N»x\L Ste. or Blda. No. E3 Approved - The item you have submitted for review has been approved. The approval is based on plans; information and/or specifications provided in your submittal; therefore any changes to these items after this date, including field modifica- tions, must be reviewed by this office to insure continued conformance with applicable codes. Please review carefully all comments attached, as failure to comply with instructions in this report can result in suspension of permit to construct or install improvements. D Disapproved - Please see the attached report of deficiencies. Please make corrections to plans or specifications necessary to indicate compliance with applicable codes and standards. Submit corrected plans and/or specifications to this office for review. For Fire Department Use Only Review 1 st 2nd 3rd CFD Job# 93142 File* Other Agency ID 2560 Orion Way Carlsbad, California 92008 (619) 931-2121 City of CarlsbaW 93142 Fire Department • Bureau of Prevention General Comments: Date of Report: Friday, October 13,1995 Contact Name Anne Hysong Address Las Paimas City, State CBD CA 92009 Bldg. Dept. No. Planning No. CT93-9 Job Name Ocean Bluff Job Address Black Rail/Poinsettia Ste. or Bldg. No. Copy of landscape plan is forwarded with request to delete plantings that are highlighted if they are within the 60' fire buffer zone. These species are identified as moderate hazard in the landscape manual. 2560 Orion Way • Carlsbad, California 92008 • (619) 931-2121 Requirements Category: je Conditions ", 93142* Deficiency Item: Pending 08 Fire lanes Prior to building occupany, private roads and driveways which serve as required access for / emergency service vehicles shall be posted as fire lanes in accordance with the requirements of J section 17.04.020 of the Carlsbad Municipal Code. Deficiency Item: Pending 09 Brush clearance Native vegetation which presents a fire hazard to structures shall be modified or removed in accordance with the specifications contained in the City of Carlsbad Landscape Guidelines Manual. Applicant shall submit a Fire Suppression plan to the Fire Department for approval. Proposed new condition Prior to issuance of the building permit, the applicant shall obtain fire department approval of a wildland fuel management plan. The plan shall clearly indicate methods proposed to mitigate and manage fire risk associated with native vegetation growing within 60 feet of structures. The plan shall reflect the standards presented in the fire suppression element of the City of Carlsbad Landscape Guidelines Manual. mare below Prior to occupancy of buildings, all wildland fuel mitigation activities must be complete, and the condition of all vegetation within 60 feet of structures found to be in conformance with an approved wildland fuel management plan. Deficiency Item: Pending 10 Fire protection systems- sprinklers, alarms, standpipes Plans and/or specifications for fire alarm systems, fire hydrants, automatic fire sprinkler systems and other fire protection systems shall be submitted to the Fire Department for approval prior to construction. Proposed language All buildings having an aggregate floor area in excess of 10,000 square feet must be protected by ;<^ I automatic fire sprinkler systems. Plans and specifications must be approved by the fire department, ^ and a permit obtained prior to installation. Proposed multifamily residential buildings must be protected by fire alarm systems. Plans and specifications must be approved, and a permit obtained prior to installation. Deficiency Item: Pending 12 Emergency response maps , The applicant shall provide a street map which conforms to the following requirements: A 400 scale / photo-reduction mylar, depicting proposed improvements and at least two existing intersections or streets. The map shall also clearly depict street centerlines, hydrant locations and street names. Deficiency Item: Pending 13 Monument sign A monument sign shall be installed at the entrance to the driveway or private street indicating the ^ J addresses of the buildings on site. Page3 10/13/95 •Requirements Category: 'e Conditions ^^> 93142 Deficiency Item: Pending 01 Bu ilding Permits Prior to the issuance of building permits, complete building plans shall be approved by the Fire Department. / Proposed language: Prior to issuance of building permits, the Fire Department shall evaluate building plans for conformance with applicable fire and life safety requirements of the state and local Fire Codes. Deficiency Item: Pending 02 Hydrants Additional on-site public water mains and fire hydrants are required. Proposed change for Industrial and multi family: Provide additional public fire hydrants at intervals of 300 feet along public streets and private driveways. Hydrants should be located at street intersections when possible, but should be positioned no closer than 100 feet from terminus of a street or driveway. Proposed change for single family residences: Provide additional public fire hydrants at intervals of 500 feet along public streets and/or private driveways. Hydrants should be located at street intersections when possible, but should be positioned no closer than 100 feet from terminus of a street or driveway. Deficiency Item: Pending 03 Site Plan/Hydrants Applicant shall submit a site plan to the Fire Department for approval, which depicts location of required, proposed and existing public water mains and fire hydrants. The plan should include off-site fire hydrants within 200 feet of the project. Deficiency Item: Pending 04 Site plan/access / Applicant shall submit a site plan depicting emergency access routes, driveways and traffic v nrn ilatinn fnr Firo nenartmont annrnvalcirculation for Fire Department approval. Deficiency Item: Pending 05 Access during construction An all weather, unobstructed access road suitable for emergency service vehicles shall be provided / and maintained during construction. When in the opinion of the Fire Chief, the access road has / become unserviceable due to inclement weather or other reasons, he may, in the interest of public safety, require that construction operations cease until the condition is corrected. Deficiency Item: Pending 06 Combustible construction materials on site All required water mains, fire hydrants and appurtenances shall be operational before combustible building materials are located on the construction site. Deficiency Item: Pending 07 Security gate systems /' Prior to final inspection, all security gate systems controlling vehicular access shall be equipped with a "Knox", key-operated emergency entry device. Applicant shall contact the Fire Prevention Bureau for specifications and approvals prior to installation. Page 2 10/13/95