HomeMy WebLinkAboutCUP 154D; Pacific Bell; Conditional Use Permit (CUP) (21)- City of Carlsbad
October 19, 2000
Allied Design Group
Andrew Atkinson
2359 Fourth Avenue
San Diego CA 92101
SUBJECT: CUP 154(D) - PACIFIC BELL
Dear Andrew:
Please find attached a list of items regarding the review of the Pacific Bell expansion
project. Please address the items and resubmit four sets of plans to the Planning
Department. I am
currently submitting additional plan sets to other departments for their review and hope to
have additional comments to you within a couple of weeks.
Some of the items we have discussed previously over the phone.
If you have any comments regarding the items below, please call me at (760) 602-4613 or
for Engineering comments, contact David Rick at (760) 602-2781. Attached is a set of
redlined plans to aid the engineer and architect with their revisions. Please return the
redlined plans with the next resubmittal package.
Sincerely,
Associate Planner
VL:cs
Attachments
C: David Rick
file
1635 Faraday Avenue Carlsbad, CA 92008-7314 (760) 602-4600 FAX (760) 602-8559 www.ci.carlsbad.ca.us
~~
CUP 154(D) - PACIFIC BELL
PLANNING
1. Please explain what will happen to the new temporary paved area after the
expansion is completed. This area should be replaced with landscaping as it is not
needed for parking.
2. Please draw in and label the 50-foot front yard setback line on the plans. The
proposed temporary paving will need to be removed from this area.
3. Please correct item number 16 which may conflict with item number 6 on the
General Notes, Sheet A1 .
4. Please identify item number 18 of the General Notes, sheet A1 .
5. Add new notes to identify the new driveway and entry gates. Please show any
proposed keypad entry feature.
6. Please correct note under "Average Daily Trip Generation" that the "public does - NOT have access to this facility."
7. Please explain the Recreational Space number of 1,340 sq ft under Resume, Sheet
Al.
8. Please add the square footage of the employee eating area on the title sheet. The
project currently provides 1,886 square feet. The requirement is for 2,368 square
feet of area but Planning will consider the 1,886 square feet provided as adequate
for the site. Also show the existing second floor outdoor patio space on the roof
plans and floor plans.
9. Please provide the projected number of employees at this location.
10. Please delete the first five parking spaces on the right side of the parking lot as you
enter the site. This area is preferred to be left as a landscaped area and will
preserve a large eucalyptus tree as well. The site generates approximately 40
parking spaces based on a warehouse use (1 space /lo00 sq ft). The remaining 52
parking spaces will be adequate to serve the site.
1 1, Please correct item three on the east elevation and item 10 on the west elevation of
Sheet A5.
12. Please verify on grading plan, Sheet C2, that the top of wall (TW) and FL are
correct at the southwestern corner of the property. (TW 216.0/FL206.25 and TW
21 5.O/FL205.81). Is the flow line of the proposed browditch or of the curb?
ENGINEERING
1. Adequate turn-around for trash trucks must be provided. Turn around can be
achieved by preserving the paved area north of the proposed trash receptacle. This
-.
2.
3.
space is currently being used as a parking space. Place a note stating "parking
space to be replaced with backup space for trash truck and marked with a no
parking sign".
The angle of intersection between the driveway and street cannot be more than ten
degrees from a right angle within the public right-of- way. This standard applies to
that portion of the driveway within the proposed 5-fOOt dedication for public right-
of-way as well. Provide curves to the driveway as it connects with that portion of
the driveway within the right-of-way. Also, add a "Do Not Enter" sign next to the
driveway for egress. In addition, the required minimum driveway width is 12 feet
for the egress and ingress portions. Please revise the site plan and grading plan
accordingly.
Please explain how the site is constrained such that the concrete brow ditch cannot
be replaced with a grass swale. Based on my field observation, the entire concrete
brow ditch could be replaced with a grass swale from the curb outlet to the existing
ditch. Although drain inlet filters can be an effective method of filtering pollutants,
vegetation requires less monitoring, maintenance and expense. Failure to maintain
and replace the inlet filter will render the filter useless. Furthermore, I don't
understand where the outlet would be placed for the proposed inlet in the brow
ditch. One alternative design to consider is as follows:
Replace the concrete brow ditch with a grass and gravel swale beginning
approximately 30 feet from the street curb (about where the inlet box is currently
proposed yet is no longer needed) to 100 feet or more southward. In addition,
adjust the grades to drain the parking lot to a proposed curb opening at the
northwest corner of the most northerly parking space instead of the location
currently proposed. Unlike the current proposal, this location will not be subject to
any water bypassing the curb opening. This opening would be followed by a grass
and gravel swale to connect with the modified drainage ditch.
4. You indicated that the on-site fire hydrant and water main is private. You may be
correct, but only because documents to record easements for the benefit of the City
were never processed under the previous Conditional Use Permit Amendment. The
intent, however, was to provide the City access to these water facilities via an
easement. Therefore, this project will be conditioned to require that the property
owner dedicate a water easement to the City prior to the issuance of building
permit or show proof that dedication has already been granted. In addition, a
construction change to DWG 348-9 will be required.
5. Provide an energy dissipater at the terminus of the brow ditch that collects slope
runoff at the rear of the lot. If the cobblestone rock is to remain as the dissipater,
then state so on the plans.