Loading...
HomeMy WebLinkAboutPIP 00-01; MV Technical; Planned Industrial Permit (PIP) (5)City of Carlsbad ENGINEEmG DEVELOPMENT SERVICES MEMORANDUM March 1, 2001 TO: Mike Grim, Planning FROM: Jeremy Riddle, SUBJECT: SECOND REVIEW OF MV TECHNICAL, PIP 00-01 The Engineering Department has completed a review of the above subject. We have reviewed the application for completeness and have determined that the application and plans submitted for the project are complete. However, prior to a final determination by Engineering staff, the following issues must be resolved: 1. 2. 3. 4. 5. 6. 7. On the site plans, revise waterline connection near the easterly driveway so that it is centered in the proposed driveway and connects to the existing public main in the street as described in the first review comments. The existing 8-inch stub was not installed in the same location as the driveway proposed by this project. The re-submitted plans now depict a proposed public main installed in the parkway in the “dry utility” area under drainage structures. Please note this alignment will not be permitted. On the site plan, include the quantity of remedial earthwork. This information has been added to the preliminary grading plans, but is also required on the project data area on the site plan. On the site plan, add a note regarding storm water quality stating that all inlets collecting water from in paved areas of the parking lot will be fitted with fossil filters or approved alternative. Clarify how storm run-off will be intercepted and conveyed from the 30-foot high rear slopes. Add a note to the site plan that indicates the minimum sight distance required per Caltrans Standards (30 mph x 11 = 330 feet). This will help clarify the distances you have added to the site plan meet the minimum requirements. On the site plan, add the cross-section of the retaining wall along the easterly property line. Although a notation was added for the cross-section, I am unable to find it in the exhibits. On the site plan clarify the turning radius is for a 60-foot radius vehicle per 407- D. " I- , MV Technical March 1,2001 Page 2 of 2 8. On the site plan remove the proposed easement line within city right-of-way as shown on the returned plans. 9. A redlined check print is enclosed for the applicants use in making the requested revisions. This check print must be returned with the plan revisions to facilitate continued staff review. If you have any questions, please either see or call me at (760) 602-2737. Attachment c: Skip Hammann, Senior Civil Engineer File