Thank you for applying for Land Use Permits in the City of Carlsbad. The Planning
Department has reviewed your Planned Industrial Permit, application no. PIP 97-03, as to
its completeness for processing.
The application is incomplete, as submitted. Attached are two lists. The first list is
information which must be submitted to complete your application. This list of items must
be submitted directly to your staff planner by appointment. All list items must be
submitted simultaneously and a copy of this list must be included with your
submittals. No processing of your application can occur until the application is determined
to be complete. The second list is issues of concern to staff. When all required materials
are submitted the City has 30 days to make a determination of completeness. If the
application is determined to be complete, processing for a decision on the application will be
initiated. In addition, please note that you have six months from the date the application
was initially filed, April 9, 1997, to either resubmit the application or submit the required
information. Failure to resubmit the application or to submit the materials necessary to
determine your application complete shall be deemed to constitute withdrawal of the
application. If an application is withdrawn or deemed withdrawn, a new application must be
submitted.
Please contact your staff planner, Mike Grim, at (760)438-1161 , extension 4499, if you have
any questions or wish to set up a meeting to discuss the application.
MJH:MG:kr
c: Gary Wayne Clyde Wtkcham
Bobbie Hoder File Copy
Chris DeCerbo Planning Aide
2075 Las Palmas Dr. - Carlsbad, CA 92009-1576 - (61 9) 438-1161 * FAX (619) 438-0894 @
LIST OF ITEMS NEEDED
TOCOMPLETE THE APPLICATION
NO. PIP 97-03 - REAL PROPERTY SERVICES
1. Please provide the following information on the site plan, typically in tabular form:
a. Project name and application type and number.
b. Name, address and telephone number of applicant.
c. General Plan designation of the site, that being P-l (Planned Industrial)
d. Number of parking spaces required. This is based on the proportion of
proposed uses, please ‘see issues comment number 3 below.
e. Square footage of required employee eating area based on square footage of
the building (300 square feet of eating area per 5,000 square feet of building
floor area).
f. Average Daily Traffic generated by the project broken down by separate
uses.
g. Grading quantities, including cut, fill and export volumes, must be shown.
2. Please provide floor plans with square footage of each proposed use. The amount
of parking required for the project will be determined by the maximum allotment of
each proposed use. This includes the second story, which appears to possess no
access points or stairways and yet is described as smaller than the first floor.
3. Please dimension the distance between the building and each property line, at the
minimum distance.
4. Please provide a detail of the proposed employee eating area showing all proposed
tables, benches, landscaping and other improvements.
5. Please show all project fencing, including location, height and materials. None is
shown on the site plan, grading plan or landscaping plan.
6. The BTH of the proposed palms trees is not specified on the preliminary landscape
plan, please specify.
7. The roof plan uses the same reference number (e.g. #3) for different roof top
features, please clarify. No roof top equipment is shown. Please note that all roof
top equipment must be approved through the Planned Industrial Permit process. If
any is planned, it must be shown on the exhibits. All roof top appurtenances must be
adequately screened from public views.
ISSUES OF CONCERN
Planning:
1.
2.
3.
4.
5.
6.
The Carlsbad Airport Centre Specific Plan requires a 30 foot setback along special
landscaped streets, which includes Camino Vida Roble. The site plan shows parking
in this area which is not allowed. Please redesign to remove parking from this
setback.
The City’s Landscape Manual requires trees in parking areas at a ratio of one tree
for every four parking stalls. The submitted landscape plan shows only 20 trees
whereas the parking lot contains 137 spaces. It should also be noted that the
maximum number of parking spaces in one row without planting islands (with trees)
is ten (IO). Please revise the parking lot landscaping to meet these requirements.
The total proportion of all uses must be known in order to calculate parking
requirements. In lieu of establishing the proportion of uses, the entire building shall
be assumed to be office uses and the parking will be required at a ratio of one space
per 250 square feet of gross floor area. The proportion of uses will be included in a
deed restriction to be placed on the property prior to issuance of any building
permits.
A condition of the project will be conformance with the operational standards of the
P-M zone (Section 21.34.090 of the Zoning Ordinance) and the Carlsbad Airport
Centre (SP 181 (A)). It is advised that you review these operational restrictions.
The proposed employee eating area is at the same grade and very close to the
adjacent property’s parking and loading area. Please enhance the landscaping
along the western property line to offer more screening for the employee eating area.
Staff has no issues with the proposed architectural elevations.
Engineering:
1. The EngineedArchitect should redesign the loading dock to allow for semi-truck
access. The City uses the CalTrans semi-truck turn templates (407-D). Please
consider both the entrance and exit maneuvers.
2. The driveway access is too steep for trucks and the type of use proposed. The City
can support up to a 12 percent grade, but this is still a bit steep for semi-trucks.
3. The proposed grade across the parking lot is five (5) percent. Please note that the
maximum grade allowed on parking lots is five (5) percent.
4. The EngineedArchitect should include a cross section (B-B) top show slope setback
and access to maintain drainage structures between the proposed building and the
three (3) foot retaining wall (north side of building).
.
5. The proposed drainage outlet is located uphill from the driveway to this project. This
will produce a constant tracking of nuisance water and a possible hazard at the
entrance. Most projects try to locate the outlets downstream from entrances. Also,
there needs to be an additional inlet to catch the drainage out the driveway.
6. The following condition requiring conformance with the National Pollutant Discharge
Elimination System protocol will be placed upon any approval for this project. The
Engineer and Architect should be aware of this requirement as well.
“The developer. shall comply with the City’s requirements of the National Pollutant
Discharge Elimination System (NPDES) permit. The developer shall provide best
management practices as referenced in the “California Storm Water Best
Management Practices Handbook“ to reduce surface pollutants to an acceptable
level prior to discharge to sensitive areas. Plans for such improvements shall be
approved by the City Engineer. Said plans shall include but not be limited to
notifying prospective owners and tenants of the following:
A. All owners and tenants shall coordinate efforts to establish or work with
established disposal programs to remove and properly dispose of toxic and
hazardous waster products.
B. Toxic chemicals or hydrocarbon compounds such as gasoline, motor oil,
antifreeze, solvents, paints, paint thinners, wood preservatives, and other
such fluids shall not be discharged into any street, public or private, or into
storm drain or storm water conveyance systems. Use and disposal of
pesticides, fungicides, herbicides, insecticides, fertilizers and other such
chemical treatments shall meet Federal, State, County and City requirements
as prescribed in their respective containers.
C. Best Management Practices shall be used to eliminate or reduce surface
pollutants when planning any changes to the landscaping and surface
improvements.”
7. The structural section for the access aisles must be designed with a traffic index of
5.0 in accordance with City Standards due to truck access through the parking area
and/or aisles with an ADT greater than 500. The structural pavement design of the
aisle ways shall be submitted together with required R-value soil test information and
approved by the City as part of the building site plan review.