HomeMy WebLinkAbout; Poinsettia Park Soccer Field Geotechnical Recs; Poinsettia Park Soccer Field Geotechnical Recommendations; 2002-05-17GEOTECHNICAL
ENGINEERING
RECOMMENDATIONS
POINSETTIA PARK
SOCCER FIELD
Hidden Valley Road
Carlsbad, California
Prepared for:
Mr. Duane Soileau
City of Carlsbad - Inspection Division
1635 Faraday Avenue
Carlsbad, Caliornia
Prepared by:
Testing Engineers - San Diego, Inc.
7895 Convoy Court, Suit 18
San Diego, CaUfornia 92111
ProjectNo. 2002-0315
May 17, 2002
Testing Engineers- San Diego, Inc. Established 1946
City of Carlsbad May 16, 2002
Inspection Division Project No. 2002-0315
Attn: Mr. Duane Soileau Telephone; 760-602-2780
1635 Faraday Avenue Fax:760-438-4178
Carlsbad, CA 92008
Subject: Geotecimical Engineering Recommendation
Project: Poinsettia Park Soccer Field
Hidden Valley Road
Carlsbad, CA
Reference: "Precise Grading Plan for Poinsettia Community Park", City of Carlsbad,
Engineering Department.
Dear Mr. Soileau:
This letter presents geotechnical engineering recommendations prepared by Testing Engineers-San
Diego, Inc. for the soccer field subgrade preparation. Review of the information provided, which
includes the referenced graduig plan, indicates that the field is to be covered with artificial turf. We
understand that the new artificial turf needs be placed over a uniform, moisture conditioned and
compacted subgrade.
Site Description
The subject soccer field is located at the northwest comer of the Poinsettia Community Park, which
in turn is located west of Hidden Valley Road and Plum Tree Road intersection in Carlsbad,
Califomia. A Vicinity Map is presented on Plate 1. The field encompasses a previously graded lot,
approximately 320 by 400 feet. The lot gently slopes towards the west; it is bordered by a cut slope
to the east and by a fill slope to the west and southwest.
Subsurface Exploration
In order to obtain information regarding the existing soils conditions, in-place density tests were
performed in five locations within the soccer field as indicated on the Site Plan, Plate 2. The density
tests were performed on the subgrade soil, after the existing natural grass and the heavy-root zone
were removed. In addition, hand-auger borings were performed at the same five locations as the
density tests to a maximum depth of 2.5 feet.
Generally, two different soil conditions were found. Bay Point Formation sandstone was
encountered at the SCI and SC5 locations, to the total depth of the boring. The orange/reddish
brown sandstone was moist to wet, dense to very dense, and weakly cemented.
Testing Engineers - San Diego, Inc., 7895 Convoy Court, SuitelS San Diego, CA. 92111 [858] 7 1 5-5800 Fax [858] 715-5810
Undocumented Fill was encountered at the SC2 through SC4 locations, to the total depth of the
boring. The fill encountered consisted of a moist to wet, medium dense to dense, silty sand with a
trace of clay. It appears that the soil used as fill was derived from the cut areas, during the original
grading. Appendix A contains logs of the subsurface exploration.
The in-place density tests were performed in accordance with ASTM D1556 test method. Two of the
density tests were in the cut area of the field, and the other three on the fill portion of it. The
densities varied from 109.3 to 123.4 pounds per cubic foot and the in-place moisture varied from 8.3
to 12.0 percent. The following table describes the density test results, including the location and
relative compaction.
Density Test
Location
SCI SC2 SC3 SC4 SC5
Type of Soil Formation Fill Fill Fill Formation
Wet Density
(pcf)
126.6 119.5 130.7 123.7 138.2
Dry Density
(pcf)
116.9 109.3 120.2 113.0 123.4
Moisture
Content (%)
8.3 9.3 8.7 9.4 12.0
Maximum
Density (pcf)
130.0 128.0 128.0 128.0 130.0
Optimum
Moisture (%)
9.0 9.0 9.0 9.0 9.0
Percent
Compaction (%)
90 85 94 88 95
Laboratory Testing
Laboratory maximum density tests (ASTM D1557) were performed on two samples, one represents
the fomiational sandstone and the other represents the fill material. The formational sandstone has a
maximum density and optimum moisture content of 130.0 pcf and 9.0 percent, respectively. The fill
material has a maximum density and optimum moisture content of 128.0 pcf and 9.0 percent,
respectively. The test results are contained in Appendix B.
Conclusions and Recommendations
Based on the test results, the observations of the hand-auger borings and TESD's experience with
similar soil conditions, it is concluded that the existing condition of the soil within the, soccer field
is stable. However, the upper one foot of soil has a variable density and moisture content. Therefore,
the observed soil conditions indicate that the proposed soccer field turf subgrade will likely consist
of varying supporting conditions.
TESD recommends that the upper 8 inches of subgrade be scarified, uniformly moisture conditioned
and recompacted to 90 percent relative compaction in accordance with ASTM D1557 test method.
The scarification should be performed so that it produces a uniform lift with the required density and
moisture content. This will create a more uniform supporting condition for the new artificial turf.
TESD. Inc. * Poinsettia Park - Soccer Field* 2002-0315 * May . 2002
2 of 3
Limits of Investigation
Our investigation was performed using the skill and degree of care ordinarily exercised, under similar
circumstances, by reputable geotechnical engineers and geologists practicing in this or sunilar
localities. No other warranty, expressed or implied, is made as to the conclusions and professional
advice included in this report. This report is prepared for the sole use of our client and may not be
assigned to others without the written consent of the client and Testmg Engineers-San Diego.
The samples taken and used for testiag, and the observations made, are believed representative of site
conditions; however, soil and geologic conditions can vary significantly between borings and surface
exposures. As in most major projects, conditions revealed by constmction excavations may vary with
preliminary findings. If this occurs, a representative of Testing Engineers-San Diego must evaluate
the changed conditions and designs adjusted as required or altemate designs recommended.
This report is issued with the understanding that it is the responsibility of the owner, or of his
representative, to ensure that the information and recommendations contained herein are brought to
the attention of the project architect and engineer. The necessary steps should be taken to see that the
contractor and subcontractors carry out such recommendations in the field.
The findings of this report are valid as of this present date. However, changes in the conditions of a
property can occur with the passage of time, whether they are due to natural processes or the works of
man on this or adjacent properties. In addition, changes in applicable or appropriate standards may
occur from legislation or the broadening of knowledge. Accordingly, the findmgs of this report may
be invalidated wholly or partially by changes outside of our control. Therefore, this report is subject
to review and should be updated after a period of three years.
Additional Services
The review of plans and specifications, field observations and testing under TESD's direction is an
integral part of the recommendations made in this report. If Testing Engineers-San Diego is not
retained for these services, the client agrees to assume our responsibility for any potential claims that
may arise during constmction. Observation and testing are additional services, which are provided by
TESD, and should be budgeted withm the cost of development.
Testing Engineers-San Diego, Inc. appreciates the opportunity to provide this geotechnical
engineering service for your project. Please contact this office if you have any questions_CQii£OTiing
the content of this letter.
RespectfiiUy submitted.
Testing Engineers - San Diego, Inc.
Carlos E. Afcero
Staff Engineer
Enck Aldrich, RCE 578
Geotechnical Engineer
TESD. Inc. * Poinsettia Park - Soccer Field* 2002-0315 * May . 2002
3 of 3
PLATES
• u •%-
-JTSO ft: 1 apo tJl=.A '.^.ij t-opyiigilit E>el_oim« Yaamoum, ME O^io^e, Scale: ^ : 1:2^00 oetail;
Testing Engineers - San Diego, Inc.
7895 Convoy Court, Suite 18
San Diego, CA 92111
Tel: (858) 715-5800 Fax: (858) 715-5810
Vicinity IVIAP - Plate 1
Polnsetia Park -Soccer Field
Carlsbad, California
2002-0315 IVlay, 2002
I
APPENDIX A
FIELD EXPLORATION LOGS
GENERAL NOTES
SAMPLE IDENTIFICATION
The Unified Soil Classification System is used to identify the soil unless otherwise noted.
SOIL PROPERTY SYMBOLS
N: Standard "N" penetration: Blows per foot of a 140 pound hammer falling 30 inches on a
2-inch O.D. split-spoon.
Qu: Unconfmed compressive strength, tsf.
Qp: Penetrometer value, unconfmed compressive strength, tsf.
Mc: Water content, %.
LL: Liquid limit, %.
PI: Plasticity index, %.
DD: Natural dry density, PCF.
V : Apparent groundwater level at time noted after completion.
DRILLING AND SAMPLING SYMBOLS
CAL: Modified Califomia Sampler - 2 5/8" I.D., 3.0" O.D., except where noted.
SS: Split-Spoon - 1 3/8" I.D., 2" O.D., except where noted.
ST: Shelby Tube - 3" O.D., except where noted.
AU: Auger Sample.
DB: Diamond Bit.
CB: Carbide Bit.
WS: Washed Sample.
RELATIVE DENSITY AND CONSISTENCY CLASSIHCATION
TERM (NON-COHESIVE SOILS) STANDARD PENETRATION RESISTANCE (SPT)
Very Loose 0 to 4
Loose 4 to 10
Medium Dense 11 to 30
Dense 31 to 50
Very Dense Over 50
TERM (COHESIVE SOILS) SPT QU - (TSF)
Very Soft 0 to 2 0 -0.25
Soft 2 to 4 0.25-0.50
, Medium Stiff 4 to 8 0.50- 1.00
Stiff 8 to 16 1.00-2.00
Very Stiff 16 to 32 2.00 - 4.00
Hard Over 32 4.00+
PARTICLE SIZE
Boulders 12 in. 4- Coarse Sand 5mm-0.6mm Silt 0.074 mm-0.005mm
Cobbles 12 in -3.in Medium Sand 0.6mm-0.2mm Clay < 0.005mm
Gravel 3 in -5mm Fine Sand 0.2mm-0.074mm
Testing Engineers - San Diego, Inc.
7895 Convoy Court, Suite 18
San Diego, CA 920111
Tel (858) 715-5800 Fax (858) 715-5810
LOG OF HAND-AUGER BORING
PROJECT NAME: Poinsettia Park-Soccer Field PROJECTNO: ^00^-0315
DATE OBSERVED:
LOGGED BY;
5/3/02
CEA GROUND ELEVATION:
METHOD OF EXCAVATION: Hand Auger
N/A LOCATION: See Map
DEPTH
(INCHES CLASS N
UNO
SAMPLE
BULK
SAMPLE
MOIST.
CONT.
(%)
DD
BORING NO.: SC-1
DESCRIPTION SOIL TEST
Grass turf, heavy-root zone 2-inch thick
-
SM 8.3 116.9 Sandstone (Bay Point Formation)
Orange/reddish brown, moist, dense to very dense, weakly
cemented
M.O. = 130.0 pcf
O.M.= 9.0%
10 —
20 —
Terminated at 2 feet 2 inches
30 — No Groundwater was encountered
LOGGED BY: CEA GROUND ELEVATION: N/A LOCATION: See Map
BORING NO.: SC-2
Grass turf, heavy-root zone 2-inch thick
SM 9.3 109.3 Silty SAND with trace clay (Undocumented Fill) M.D.= 128.0 pcf
Orange/brown, moist, dense, mottled with brown/olive gray clay
trace of granite gravel (3/4-inch)
O.M.=9.0%
10 —
• 20 —
Terminated at 2 feet 2 inches
30 — No groundwater encountered
-
Test Pit Logs
, Testing Engineers - San Diego, Inc.
7895 Convoy Court, Suite 18
San Diego, CA 920111
Tel (858) 715-5800 Fax (858) 715-5810
LOG OF HAND-AUGER BORING
PROJECT NAME: Poinsettia Park-Soccer Field PROJECTNO: 2002-U315
DATE OBSERVED: 5/3/02 METHOD OF EXCAVATION: Hsnd Auger
LOGGED BY: CEA GROUND ELEVATION: ' N/A LOCATION: See Map
DEPTH UND BULK MOIST. BORING NO.: SC-3
(INCHES CLASS N SAMPLE SAMPLE CONT.
(%)
DD DESCRIPTION SOIL TEST
Grass turf, heavy-root zone 2-inch thick
SM 8.7 120.2 Silty SAND with trace clay (Undocumented Fill)
Orange/brown,damp to moist, dense, mottled with brown/olive
gray clay, trace of granite gravel (3/4-inch)
10 —
20 —
30 — Terminated at 2 feet 4 inches
_ No Groundwater was encountered
LOGGED BY: CEA GROUND ELEVATION: N/A LOCATION: See Map
BORING NO.: SC-4
Grass turf, heavy-root zone 2-inch thick
SM 9.4 113.0 Silty SAND with trace clay (Undocumented Fill)
Orange/brown, moist, dense, mottled with brown/olive gray clay
trace of granite gravel (3/4-inch)
10 —
23 —
Terminated at 2 feet
No groundwater encountered
30 —
--
Test Pit Logs
Testing Engineers - San Diego, Inc.
7895 Convoy Court, Suite 18
San Diego, CA 920111
Tel (858) 715-5800 Fax (858) 715-5810
LOG OF HAND-AUGER BORING
PROJECT NAME: Poinsettia Park- Soccer Field PROJECTNO: 2U02-U;J1&
DATE OBSERVED: 5/3/02 METHOD OF EXCAVATION: Hand Augep
LOGGED BY: CEA GROUND ELEVATION: N/A LOCATION: ' Sse Map
DEPTH UND BULK MOIST. BORING NO.: SC-5
(INCHES CLASS N SAMPLE SAMPLE CONT.
(%)
DO DESCRIPTION SOIL TEST
Turf, heavy-root zone 2-inch thick
SM 12.0 123.4 Sandstone (Bay Point Formation)
Orange/reddish brown, moist to wet, dense to very dense
10 —
20 —
Terminated at 2 feet 2 inches
30 —
No Groundwater was encountered
LOGGED BY: CEA GROUND ELEVATION: N/A LOCATION: See Map
BORING NO.:
10 —
20 —
;
30 — I
I Test Pit Logs
APPENDIX B
LABORATORY TEST RESULTS
COMPACTION TEST REPORT
Curve No.: 1
ProjectNo.: 02-0315
Project: Poinsettia Park Soccer Field - Geo T&I
Location: FILL MATERIAL
Elev./Depth: 24"-32"
Remarks: TESD NO. 4515
Date: 5/3/02
MATERIAL DESCRIPTION
Description: BROWN CLAYEY SAND
Classifications - USCS:
Nat. Moist. =
Liquid Limit =
% > No.4 = %
AASHTO:
Sp.G. =
Plasticity Index =
% < No.200 =
140
130
120
Q. I lU
>^
'</) c <u
TD
a 100
90
80
70
TEST RESULTS
Maximum di7 density = 128 pcf
Optimum moisture = 9 %
Test specification:
k ASTM D 1557-91 Procedure A Modified -A
Test specification:
k ASTM D 1557-91 Procedure A Modified -A
100% SATURATION CURVES
FOR SPEC. GRAV. EQUAL TO:
100% SATURATION CURVES
FOR SPEC. GRAV. EQUAL TO:
2.8
2.7
2.6
2.8
2.7
2.6
2.8
2.7
2.6
2.8
2.7
2.6
1 ' I
i i
i i 1
i
10 15 20 25
Water content, %
30
-TESTING ENGINEERS-
35
Plate
40
COMPACTION TEST REPORT
Curve No.: 2
ProjectNo.: 02-0315
Project: Poinsettia Park Soccer Field - Geo T&I
Location: FORMATION SANDSTONE
Elev./Depth: 24"-26"
Remarks: TESD NO. 4516
MATERIAL DESCRIPTION
Description: DARK ORANGE-LIGHT BROWN CLAYEY SAND
Date: 5/3/02
Classifications
Nat. Moist. =
Liquid Limit =
%>No.4= %
USCS: AASHTO:
Sp.G. =
Plasticity Index =
% < No.200 =
TEST RESULTS
Maximum dry density = 130 pcf
Optimum moisture = 9 %
140
130
120
CL
C CD •D
Q 100
90
80
70
\ Test specification:
v,^ ASTM D 1557-91 Procedure A Modified
Test specification:
v,^ ASTM D 1557-91 Procedure A Modified
— — — —
J
/
/
100% SATURATION CURVES 100% SATURATION CURVES
hUK bKbC. UKAV. bUUAL 1 U!
2.8
2.7
2.6
2.8
2.7
2.6
2.8
2.7
2.6 -
2.8
2.7
2.6
s
-—
— — -—
— —
— —_
1
i
10 15 20 25
Water content,. %
-TESTING ENGINEERS
30 35
Plate
40