HomeMy WebLinkAbout4222; Palomar Airport Road Widening; Palomar Airport Road; 1986-12-01GEOTECHNICAL AND PAVEMENT ANALYSIS
PALOMAR AIRPORT ROAD WIDENING
CARLSBAD, CALIFORNIA
FOR
WILDAN ASSOCIATES
6363 GREENWICH DRIVE, SUITE 250
SAN DIEGO, CALIFORNIA 92122
JOB NO. 4222 DECEMBER 1, 1986
Testing Engineers — San Diego
Mailing Address:
Post Office Box 80985
San Diego, CA 92138
3467 Kurtz Street
San Diego, CA 92110
(619) 225-9641
December 1, 1986
Job No. 4222-1
Wildan Associates
6363 Greenwich Drive, Suite 250
San Diego, California 92122
Attention:Mr. Mike Sabvini
Subject:Geotechnical and Pavement Analysis
Palomar Airport Road Widening
Carlsbad, California
Gentlemen:
The results of our geotechnical and pavement analysis are
presented in this report. The accompanying report presents
conclusions and recommendations pertaining to the site, as well
as the results of our field reconnaissance and laboratory
results.
Palomar Airport Road Widening
Carlsbad, California
December 1, 1986
Job No. 4222-1
We have appreciated the opportunity to be of service to you on
this interesting project and look forward to a continued
association on this and future projects. If you have any
questions, please do not hesitate to contact our office.
Vincent J. Patula
Project Geologist
VJP/SMP/DM/eh
Addressee (4)
Respectfully submitted,
TESTING-KNGINEERS-SAN DIEGO
Materials Engineer
Stephen M. Poole, RCE 40219
Geotechnical Department Manager
TABLE OF CONTENTS
Page
INTRODUCTION 1
PROJECT DESCRIPTION 1
PROJECT SCOPE 2
FIELD EXPLORATION 2
GEOLOGIC HAZARDS 3
SLUMPING 3
LABORATORY TESTING 5
CLASSIFICATION 5
MOISTURE/CONTENT 5
U.B.C. SWELL TEST 7
"R" VALUE 8
CONCLUSIONS AND RECOMMENDATIONS 9
RECOMMENDED GRADING SPECIFICATIONS 10
GENERAL DESCRIPTION 10
PREPARING AREAS TO BE FILLED 11
MATERIALS 13
PLACING, SPREADING, AND COMPACTING FILL MATERIALS ... 15
INSPECTION 16
SLOPES 17
PAVEMENT SECTION 17
LIMITATIONS AND UNIFORMITY OF CONDITIONS 21
ENCLOSURES;
Sample Location Map Figure 1
Unified Soil Classification Plate 1
City of Carlsbad Design Table Plate 2
INTRODUCTION
PROJECT DESCRIPTION
A major portion of the site is located between McClellan Drive
and El Camino Real on the north and south sides of Palomar
Airport Road see Figures 1,2, and 3. The road widening extends
from 550 feet west of McClellan Drive to 100 feet east of El
Camino Real.
It is our understanding that the road widening is to be
developed by additional grading and remedial slope stability
measures. It is to be widened to its ultimate prime-arterial
standards.
To assist in the preparation of this report we were provided
with a copy of the proposed improvements by Wilden and
Associates.
N\n~13"IDDlA!
3
I_k
A
•o
O
> CO
33 >
? m
0 r-
H 0
30 >o i
> 0
0 Z
m 3;
5 ^z
CO
oz
-I'sl
S- 1?s c>G- m
O
Z
31
1
L-_
O O
CO>
2TJr-rn
r
OO>
H
Z
O
a: w
"£o£
TImm
H
"A \V\\\\\\V:A\\'\V,«
\\W\Yl\
Z3
CO
r-0
2
>
3)
>
5
o
2"^
3D
O
>
O
mX
%
Oz
(0>
2 .•o
r~
O
>
H
0
Z
2>
U
CO
m
g§
8g
m
o Q
C, z
"n Hi
z
**
Wildan Associates . Page No. 2
Paloraar Airport Road December 1, 1986
Job No. 4222
PROJECT SCOPE
This investigation consisted of surface reconnaissance, limited
subsurface hand augering, obtaining representative disturbed
samples, limited laboratory testing, analysis of field and
laboratory, and preparing this report. Specifically the intent
of this study is to:
o recommend three structural pavement sections
o give recommendations for cut and/or fill slopes
required to extend the roadway shoulder
o identify soils present and their properties
o provide limits of the report which would result in
recommendations over the project limits
FIELD EXPLORATION
Subsurface conditions were explored by hand augering to depths
ranging from 1 to 5 feet in order to obtain bag samples for
laboratory analysis and soil profile description. Sample
locations are shown on Figures 1 through 3.
Wildan Associates Page No. 3
Paloraar Airport Road December 1, 1986
Job No. 4222
GEOLOGIC HAZARDS
SLUMPING
In their present condition there is a potential for further
surface slumping of the fill slopes adjacent to the proposed
roadway widening and the slopes underlying the road bed. It is
possible that this soil movement could cause minor road damage.
The two major slope areas presented in Figure 1, Section B, and
Figure 2, Section D, have undergone episodes of surficial
slumping and soil creep.
In Section D on the western side of the slope there is a visible
slumping episode of approximately 72 feet long at the scarp.
This section has a slope of 1.3 to 1 (horizontal to vertical)
and is sparsely vegetated.
Wildan Associates Page No. 4
Palomar Airport Road December 1, 1986
Job No. 4222
Further evidence that soil creep is occuring, is the presence of
curved tree trunks. Although no present tension cracks were
observed along the top of the slope, with further erosion the
slump scarp, may with time, undermine the roadway and sidewalk.
The slopes in Section B exhibit heavy rilling, 6 inches to 2
feet in depth, and several slumping episodes below and above
the backset bench area were observed. One set of tension cracks
measured was approximately 2 inches in width and 12 feet in
length. In several different areas bulging of the toe of the
slope was observed. The slumping events occured in areas that
were sparsely landscaped and had slopes of 1.3 and 1.5 to 1
(horizontal to vertical). Other areas that are less than 2 to 1
and vegetated, exhibited rilling but no slumping events.
Wildan Associates Page No. 5
Palomar Airport Road December 1, 1986
Job No. 4222
LABORATORY TESTING
CLASSIFICATION
Soils were visually classified according to the Unified Soil
Classification System as presented on Plate 1. Percent material
passing the No. 200 sieve was used as an aid in soil
classification with the results and soil description presented
on Table 1.
MOISTURE/CONTENT
For selected disturbed soil samples, field moisture contents
were obtained by hand augering. The field moisture content was
determined as a percentage of the dry weight. Results of these
tests are shown on Table 1.
Wildan Associates
Palomar Airport Road
Page No. 6
December 1, 1986
Job No. 4222
TABLE 1
Sample
No.
1
2
Depth ,
Feet
0-3
0-1
Moisture
Content,
Percent
25.3
9.9
Percent
Passing
No. 200
--
Description
dark brown sandy clay
light brown silty fim
3
4
5
6
7
8
0-5
0-1
0-2
0-1
22.1
surface 6.6
surface 7.4
12.8
15.8
9.9
48
65
sand
medium brown clayey
fine sand
gray brown silty fine
sand, some iron
staining
medium brown clayey
sand
brown-yellow silty
fine sand
brown fine sandy clay
brown silty sand,
slightly clayey
Wildan Associates Page No. 7
Palomar Airport Road December 1, 1986
Job No. 4222
U.B.C. SWELL TEST
The expansion potential of selected samples was evaluated using
a swell test (U.B.C. Test Standard No. 29-2). A sample of soil
was molded to a saturation content of approximately 50 percent.
A surcharge load of 144 pounds per square foot was applied to
the sample, which was then inundated. The expansion index
(E.I.) was recorded relative to the increase in the thickness of
the soil sample to the original one inch sample. The sample was
allowed to swell for at least 24 hours.
Results were as follows:
Test Pit Depth, Material Expansion
Location Feet Type E.I. Potential
1.5 brown slightly 59 Medium
sandy clay
Wildan Associates
Palomar Airport Road
Page No. 8
December 1, 1986
Job No. 4222
"R" - VALUE
Representative samples of near surface native soils were tested
to evaluate pavement design criteria. These samples were taken
from native subgrade below base materials at corehole locations
indicated on Figures 1 and 3. Testing was done using the "R" -
value test, California Standard 301. The results were as
follows:
Test
Location
10
Depth
Feet
1.0
1.2
Material
Type
clayey silty
fine sand
silty fine
sand with
trace clay
"R" - Value
24
21
Wildan Associates Page No. 9
Paloraar Airport Road December 1, 1986
Job No. 4222
CONCLUSIONS AND RECOMMENDATIONS
Based on our field investigation, laboratory analysis, and
engineering analysis, we offer the following conclusions and
recommendations:
1. Site materials consist of silty fine sands and sandy clays.
These materials are adequate for the proposed roadway
widening.
2. Remedial slope repair, landscaping and maintenance is
recommended.
3. Additional exploration is recommended to determine depth to
bedrock, soil stratigraphy, and their engineering
properties. For the proposed widening of the roadway by
filling, the engineering properties of the underlying soils
must be determined in order to evaluate removal depths and
other construction recommendations.
4. A review by a geotechnical engineer of the revised grading
plans, to determine the drainage system necessary to
accommodate runoff and aid in the slope stabilization is
recommended.
wildan Associates Page No. 10
Palomar Airport Road December 1, 1986
Job No. 4222
RECOMMENDED GRADING SPECIFICATIONS
1. GENERAL DESCRIPTION
1.1 These specifications have been prepared for general
grading and site development of the project. Testing
Engineers-San Diego, herein after, described as the
Soil Engineer, should be consulted prior to any site
work connected with site development to ensure
compliance with these specifications. These
specifications shall be used in conjunction with the
soil report of which they are a part.
1.2 This item shall include all site work consisting of all
clearing and grubbing, preparation of land to be
filled, filling of the land, spreading, compaction,
density testing of the fill, and all subsidiary work
necessary to complete the grading of the filled areas
to conform with the lines, grades, and slopes as shown
and specified on the accepted plans.
Wildan Associates . Page No. 11
Palomar Airport Road December 1, 1986
Job No. 4222
1.3 The Soil Engineer shall be the Owner's representative
to inspect the construction of fills. Excavation and
placing of fill shall be under the direct inspection of
the Soil Engineer. In the event that any unusual
conditions, not covered by these specifications are
encountered during grading operations, the Soil
Engineer shall be immediately notified.
2. PREPARING AREAS TO BE FILLED
2.1 All existing unnecessary materials such as timber,
logs, trees, brush, abandoned buildings, debris and
other rubbish shall be removed or disposed of so as the
area will be left neat and with finished appearance.
2.2 All loose soil and organic matter shall be removed from
the surface upon which the fill is to be placed. The
surface shall then be plowed or scarified to the
recommended depth, and until the surface is free from
ruts, hummocks or other uneven features which would
tend to prevent uniform compaction by the equipment to
be used.
Wildan Associates Page No. 12
Palomar Airport Road December 1, 1986
Job No. 4222
2.3 The area, after being cleared should be disced or
bladed until it is uniform and free from large clods.
Proper moisture content must be maintained. The
moisture content should be at least within two percent
of optimum moisture by adding water or aerating and
compacted to a relative compaction of not less than 90
percent of the maximum dry density as determined by
ASTM Test Procedure No. D-1557.
2.4 Buried tanks, if encountered, should be removed and the
resulting depressions properly backfilled and
compacted. The soil surrounding the buried tanks
should be tested for hazardous materials and disposed
of properly.
Wildan Associates Page No. 13
Palomar Airport Road December 1, 1986
Job No. 4222
3. MATERIALS
3.1 Materials for compacted fill shall consist of any
material imported or excavated from the cut areas that,
in the opinion of the Soil Engineer, is suitable for
use in constructing fills. The materials used should
be free of organic matter and other deleterious
substances. It shall contain no rocks or hard lumps
greater than 6-inches in size.
3.2 No materials of a perishable, spongy or improper nature
shall be used in filling.
3.3 Any potentially expansive soil encountered shall be
used as fill only below 3 feet of the design finished
grades. The upper 3 feet of fill shall be comprised of
non-expansive sandy fill material. Any expansive soil
encountered at the finished subgrade elevations in cut
Wildan Associates Page No. 14
Palomar Airport Road December 1, 1986
Job No. 4222
areas shall be undercut and replaced with compacted
non-expansive sandy fill material. The depths and
lateral extent of any required expansive soil removal
shall be determined by the Soil Engineer at the time of
construction.
3.4 The contractor shall notify the Soil Engineer in
advance of his intention to import soil from any source
outside the project areas, and shall permit the Soil
Engineer to sample as necessary for the purpose of
making tests to establish the qualities of these
materials.
3.5 During operations, soil types other than those analyzed
in the report of the soil investigation may be
encountered by the Contractor. The Soil Engineer shall
be consulted to determine the suitability of these
soils.
Wildan Associates Page No. 15
Palomar Airport Road December 1, 1986
Job No. 4222
4. PLACING, SPREADING, AND COMPACTING FILL MATERIALS
4.1 Fill materials should be placed in layers, which, when
compacted, would permit adequate bonding and
compaction. Each layer shall be spread evenly and
shall be thoroughly mixed during the spreading to
provide uniformity of material in each layer.
4.2 After each layer has been placed, mixed and spread
evenly, it should be thoroughly compacted to a relative
compaction of not less than 90 percent of the maximum
dry density as determined by ASTM Test Method D-1557,
unless otherwise specified.
4.3 Compaction shall be continuous over the entire area and
the equipment shall make sufficient trips to ensure
that the desired density has been obtained throughout
the entire fill.
Wildan Associates Page No. 16
Palomar Airport Road December 1, 1986
Job No. 4222
5. INSPECTION
5.1 Observations and compaction tests shall be made by the
Soil Engineer during the filling and compaction
operations.
5.2 The standard test used to define maximum densities of
the soil will be the ASTM Test Method D-1557.
Compaction of the fill shall be expressed as the
percent of the field density to the maximum density.
When the compaction of the fill is below the specified
value, the particular layer or portion shall be
recompacted. The number and kind of tests shall be
determined by the Soil Engineer.
5.3 During construction, the contractor shall properly
grade all excavated surfaces to provide positive
drainage and prevent the ponding of water. He shall
control surface water to avoid damage to adjoining
properties or to finished work on the site.
o o
Wildan Associates Page No. 17
Palomar Airport Road December 1, 1986
Job No. 4222
SLOPES
All fill or cut slopes shall be at no greater than 2 to 1
(horizontal to vertical) slope. Landscaping and brow ditches
are recommended to reduce surface erosion and failure. All
future slopes must be benched and keyed into existing slopes.
The slope in section "D" should have a stabilization fill place
adjacent to the area of slumping.
Further examination would be necessary to determine drain
placement.
PAVEMENT SECTION
"R"-Value samples were taken from two locations along Palomar
Airport Road representing changes in soil type or color. The
existing structural section was measured for analyses at each
location and the measurements are presented in Table 2.
o o
Wildan Associates Page No. 18
Palomar Airport Road December 1, 1986
Job No. 4222
Pavement structural section recommendations were developed using
a basement soil "R"-value of 21. Table 3 shows computation for
developing three alternate structural sections.
The City of Carlsbad, design table, Plate 2 was used to
determine traffic index (T.I.) and minimum asphaltic concrete
thickness. The design assumes the use of Class II processed
aggregate base course. Disintegrated granite (D.G.) (minimum
"R"-value of 50) would only be used as select import for a
subbase course. Recommended for the asphaltic pavement section
is a 4 inch single lift of type B, 3/4 inch medium a.c. base
course and 2 inch surface course of type "B", 1/2 inch medium
a.c., both with AR-4000 asphalt.
o o
Wildan Associates Page No. 19
Palomar Airport Road December 1, 1986
Job No. 4222
TABLE NO. 2
BASEMENT SOIL SAMPLES LOCATIONS
AND EXISTING SECTION MEASUREMENTS
Sample No. 1: 720 feet east of Yarrow Drive, east bound lane, 15
feet north of curb line.
A.C. - 3 1/2 inches, 1 lift of 1/2 inch medium A.C.
Aggregate base - 71/2 inches, disintegrated granite.
Subgrade - Tan clayey silty fine sand.
Sample No. 2: 475 feet west of El Camino Real, east bound lane,
added grade and pave for right turn lane, 15 feet north of curb
line.
A.C. - 6 inches, 1 lift of 1/2 inch medium A.C.
Aggregate base - 13 inches, Class II aggregate base
material.
Subgrade - Light brown silty fine sand with trace clay.
o
Wildan Associates . Page No. 20
Palomar Airport Road December 1, 1986
Job No. 4222
TABLE NO. 3
RECOMMENDED SECTION DESIGN ALTERNATIVES
Basement Soil R-Value 21
Traffic Index (Prime Arterial) 9.0
Minimum a.c. Thickness, ft. (inch) 0.5' (6")
Minimum cover required (GE) ft. (inch) 2.29 (27.5")
Note: Materials referenced to Cal Trans Standard Specifications
for aggregate subbase, aggregate base, and asphaltic concrete.
Alternative 1:
Actual
Thickness
Feet Inch
0.50 6
1.26 15
1.75 21
Alternative
0.50 6
0.50 6
0.84 10
1.83 22
Alternative
0.50 6
0.83 10
0.48 6
1.83 22
Course
Asphaltic Concrete
Class II Agg. Base
2:
Asphaltic Concrete
Class II Agg. Base
Class II Agg. Subbase
3:
Asphaltic Concrete
Class II Agg. Base
Class II Agg. Subbase
(Gf)
1.80
1.10
1.80
1.10
1.00
1.80
1.10
1.00
Gravel
Equivalent (GE)
Feet
0.90
1.39
2.29
0.90
0.55
0.84
2.29
0.90
0.91
0.48
2.29
o o
Wildan Associates Page No. 21
Palomar Airport Road December 1, 1986
Job No. 4222
LIMITATIONS AND UNIFORMITY OF CONDITIONS
The recommendations presented in this report are contingent upon
our review of final plans and specifications.
It is recommended that Testing Engineers-San Diego, be retained
to provide continuous soil engineering services during the
earthwork operations. This is to observe compliance with the
design concepts, specifications or recommendations and to allow
design changes in the event that subsurface conditions differ
from those anticipated prior to start of construction.
The recommendations and opinions expressed in this report
reflect our best estimate of the project requirements based on
an evaluation of the subsurface soil conditions encountered at
the subsurface exploration locations and the assumption that the
soil conditions do not deviate appreciably from those
encountered.
o o
Wildan Associates Page No. 22
Palomar Airport Road December \, 1986
Job No. 4222
It should be recognized that the performance of the foundations
and/or cut and fill slopes may be influenced by undisclosed or
unforeseen variations in the soil conditions that may occur in
the intermediate and unexplored areas. Any unusual conditions
not covered in this report that may be encountered during site
development should be brought to the attention of the soil
engineer so that he may make modifications if necessary.
This office should be advised of any changes in the project
scope or proposed site grading so that it may be determined if
the recommendations contained herein are appropriate. This
should be verified in writing or modified by a written addendum.
The findings of this report are valid as of this date. Changes
in the condition of a property can, however, occur with the
passage of time, whether they be due to natural processes or the
work of man on this or adjacent properties. In addition,
changes in the State-of-the-Art and/or Government Codes may
occur. Due to such changes, the findings of this report may be
invalidated wholly or in part by changes beyond our control.
o o
Wildan Associates Page No. 23
Palomar Airport Road December 1, 1986
Job No. 4222
Therefore, this report should not be relied upon after a period
of two years without a review by us verifying the suitability,
the conclusions, and recommendations.
In the performance of our professional services, we comply with
that level of care and skill ordinarily exercised by members of
our profession currently practicing under similar conditions and
in the same locality. The client recognizes that subsurface
conditions may vary from those encountered at the locations
where our borings, surveys, and explorations are made, and that
our data, interpretations and recommendations are based solely
on the information obtained by us. We will be responsible for
those data, interpretations and recommendations, but shall not
be responsible for the interpretations by others of the
information developed. Our services consist of professional
consultation and observation only, and no warranty of any kind
whatsoever, expressed or implied, is made or intended in
connection with the work performed or to be performed by us, or
by our proposal for consulting or other services, or by our
furnishing of oral or written reports or findings.
o o
Wildan Associates Page No. 24
Palomar Airport Road December 1, 1986
Job No. 4222
It is the responsibility of the owners, or their representatives
to ensure that the information and recommendations contained
herein are brought to the attention of the engineer and
architect for the project and incorporated into the project's
plans and specifications. It is further their responsibility to
take the necessary measures to ensure that the contractor and
his subcontractors carry out such recommendations during
construction.
o
Testing Engineers-San Diego
UNIFIED SOIL CLASSIFICATION
PLASTICITY CHART
60
50
40
r30
20
10
CL
V
CH
•>°/
ML ond OL
OH ond MH
0 TO 20 30 40 50 60. 70 80 90 100
Liquid Limit
"t>N'3>
o>.1v>
0o
CM
oin z
d c
0 =in £
O O>u o«
Z 0
2.=? i« 5§ io ».
<J 0
**>
of
£
0>
o2
GROUP
SYMBOL
GW
GP
GM
GC
SW
SP
SM
SC
TYPICAL NAMES
Well-groded gravels,
gravel-sand mixtures,
little or no fines
Poorly graded gravels,
gravel -sand mixtures,
little or no fines
Silty. gravels, gravel-
sand-silt mixtures
Clayey gravels, gravel
sand-clay mixtures
Well-graded sands,
gravelly sands, little
or no fines
Poorly graded sands,
gravelly sands, little
or no fines
Silty sands, sand-silt
mixture
Clayey sands, sand-
clay mixtures
V>a>
u>
OOCM
0
c0w £
_J w
0 »"> -5a Ejjj </>
Z a,
^ "~o: oo '«-1 £
UJ 02 e
"- -o
"5f
1
a>
o
GROUP
SYMBOL
ML
CL
QL
MH
CH
OH
Pt
TYPICAL NAMES
Inorganic silts and very
fine sands, rock flour
silty or clayey fine
sands, or clayey silts
with slight plasticity
Inorganic clays of low to
medium plasticity,
gravelly clays, sandy
clays, silty clays, lean
clays
Organic silts and organic
silty clays of low
plasticity
Inorganic silts, micaceous
or diatomaceous fine
sandy or silty soils,
elastic silts
Inorganic clays of high
plasticity, fat clays
Organic clays of medium
to high plasticity,
organic silts
Peat ond other highly
organic soils
NOTE: 1)Group symbol presented in SYMBOL column on BORING LOG.
2) The A line is an empirical relationship established by A. Casagrande.
PLATE
CITY OrCARLSBAD DESIGN TABLE o
MINIMUM SIR
I.I.
*ade
-Value
,
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
44
46
48
50
52
54
4.0
ALLEY
AC
3
3
3
UG
6
5
4
4.5
CUL-DE-
SAC
AC
3
3
3
UG
8
7
6
UCTURAL SECTION IK ii.'CHES Tl = 1.35 (EUL)
b.O
LOCAL
STREET
AC
3
3
3
3
3 ,
UG
10
9
8
7
6
670
COLLECTOR
AC
4
4
4
4
4
4
4
4
DB
13
12
11
10
9
8
7
6
7.0
LIGHT
INDUSTRIAL
AC
4
4
4
4
4
4
4
4
4
4
AB
15
14
13
12
11
10
9
8
7
6
. 8.0
SECONDARY
ARTERIAL
AC
4
4
4
4
4
4
4
4
4
4
4
4
4
AB
18
17
16
15
14
13
12
11
10
9
8
7
6
8.5
MAJOR
ARTERIAL
AC
5
5
5
5
5
5
5
5
5
5
5
5
5
Ab
18
17
16
15
14
13
12
11
10
9
8
7
6
3.0
PRIME '
ARTERIAL
AC
6
6
6
6
6
6
6
6
6
6
6
6
6
AB
18
17
16
15
14
13
12
11
10
9
8
7
6
NOTES;
1. A.C.Asphalt Concrete
2. D.G. = Disintegrated Granite, R = 73 min., S.E. = 30 min.
conforming to Section 400-2.3 of Green Book.
3. A.B. = Crushed Aggregate Base, R = 80 min., tS.E. = 50 min.
conforming to Section 200-2.2 of Green Book.
4. The bottom figures listed are the minimum permitted.
«.
•^
APPROVED DATE £/ry afrrtt&rt0>
y City Engineer Date
PLATE 2