HomeMy WebLinkAboutCDP 16-18; Rancho Paradiso; Grading Plan Review; 2017-06-05Geotechnical Exploration, Inc.
SOIL AND FOUNDATION ENGINEERING e GROUNDWATER e ENGINEERING GEOLOGY
05 June 2017
Mr. Gary Barberio
4270 Clearview Drive
Carlsbad, CA 92008
Job No. 15-10764
Subject: Grading Piao Review
Barberio Residence
252 Normandy Lane
Carlsbad, california
Dear Mr. Barberio:
As requested, we have reviewed the grading plans (4 sheets) for the subject property, undated, and
prepared by Mr. Robert Sukup of The Sea Bright Company. The grading plans have been reviewed
from a geotechnical engineering viewpoint to verify their adequate compliance with our
recommendations presented in the "Report of Preliminary Geotechnical Investigation ... " for the subject
site, dated May 19, 2015.
After suggested corrections were made, it Is our opinion that the grading plans are in adequate
conformance with the recommendations presented in our geotechnical investigation report dated May
19, 2015. Any soil compaction and grading at the site shall be as required by the City of Carlsbad and
in accordance with our report. If you have any questions regarding this letter, please contact our
office. Reference to our Job No.15-10764 will help expedite a response to your inquiry.
Respectfully submitted,
GEOTECHNICAL EXPLORATION, INC. ~
EtZ~ ~ 00
C)
(',.J
~ c:-l
Jaime A. Cerros, P.E. .-of u CT) R.C.E. 34422/G.E.2007 w ~ l.J... Senior Geotechnical Engineer ~
Cc: The Sea Bright Company
MAA Architects
7420 TRADE STREET• SAN DIEGO, CA. 92121 • (858) 549-7222 • FAX: (858) 549-1604 e EMAIL: geotech@gel-sd.com
f-z w (!) ~ /
0.. = 0 C
__J I Jj
!..!J : J
.> ,,.
liJ --0 )
C L z UJ
:5
Geotechnical Exploration, Inc.
son. AND FOUNDATION er«;JHEERJNG • GROUNDWATER • ENGI1EEIUHG GEOLOGY
09 June 2016
Mr. Gary Barberio
4270 Cle'arvlew Drive
carlsbad,CA ·92008
Subject: ere11m1narv Grading Plan Review
Barberio Residence
228 Normandy Lane
Carlsbad, Callfomla
Dear Mr. Barberio:
Job No. 15-10764
As requested, we have reviewed an undated prellmlnary grading plan for the
subject property prepared by Mr. ~obert Sukup of The Sea Bright Company. The
plan was reviewed from a geotechnlcal engineering viewpoint to verify adequate
compllence with our recommendations as presented In our \\Report of Preliminary
Geotechnlcal Investigation" for the site, dated May 19, 2015.
' After review and discussions with Mr. Sukup, It Is our opinion that the plan
adequately conforms to the recommendations presented In our report dated May
19, 2015. We understand that a final grading plan Is In progress. We should also
review the · final plan, when completed, to verify compliance with our
recommendations. Any soil compactJon and grading should be as required by the
City of Carlsbad and In accordance with our report.
If you have any questfons regarding this letter, please contact our office. Reference
to our Job No. 15-10764 wlll help expedite a response to your Inquiry.
Respectfully submitted,
GEOT CHNICAL EXPLORATION, INC.
Jaime A. Cerros, P.E.
R.C.E. 34422/G.E. 200
Senior Geotechnical Engineer
cc: The Sea Bright Company
7-i20 TRADE STREETIII ~_DIEGO, CA. 92121 • (858) 549-7222 e FAX: {858) 519-1604 • EMAIL: geotechOgekd.co
Geotechnical Exploration, Inc.
SOIL NfJ ~ EfGNEEROO • GlOllfONATER • eGNEBUHG GEOLOGY
19 May-2015
Mr. Gary.Barberio
4270 Cearvlew Dr1ve
cartsbad, CA 92008
Job No. 15-10764
Subject: BIP9d Qf PnllmJoncv Gegbldlnlcal lnwstlqBtloo
Barberio Residence
228 Normandy Lane
carlsbad, catlfomla
Dear Mr. Barberio:
In accordance with your request, a representative of Geotechnlcal Explonltlon,
:tnc. has visited the subject site and performed an evaluation of the soll conditions
In the area of the proposed new structure. It Is our understanding that the site Is
being developed to receive a new three-story slngle-famlly residence with an
attached two-car garage and associated Improvements. The new structure wlll
utilize continuous and Isolated footings with conaete slab-on-grade. As part of our
lnvestlgatlonr we observed and evaluated the shallow soil conditions at two
locations within the proposed new bulldlng area.
In addition, we reviewed the conceptual architectural plans by Ayala Archttecture,
dated July 30, 2014, in accordance wJth the requirements of the City of Carlsbad.
We should review tne foundation plans when avallable.
The field work, conducted on May 8, 2015, consisted of excavating two hand-
excavated test pits In the locatfon of the proposed new structure. The excavations
revealed that the building site Is underlain by approximately 12 Inches of medium
dense, silty sand flll/topsoll over medium dense to dense, silty -sand formatlonal
7420 TRADE STREETe SAN DIEGO, CA. 92121 e (85B) 549-7222 G OOC: (858) 549-1604 o EMAIL: ~
_)
Barberio Property
Carlsbad, Callfomla
Job No. 15-10764
Pege2
materials. The on-Site soils are considered to have 8 low expansion potential with
an Expansion Index of less thlln 50.
Based upon our observation, probing of the on-site soils, It Is our opinion that the
new foundations for the additions can be founded directly Into the existing mrtural
ground materials. The surface flll/topsolls In the proposed bl4!dlng pad area should
be removed and/or property compacted as part of site preparatlon under any new
slab areas. The new flll should be compacted to at least 90 percent of Maximum
Dry Density. The Maximum Dry Density of the soll has been determined per ASfM
D1557-12.
1. It Is our opinion thm: the existing medium dense to dense formatlonal
materials will provide adequate bearing strength for the proposed new
structure foundations. New footings placed In the existing medium dense to
dense natural soils or properly compacted fill solls can be designed for an
allowable soll bear1ng capacity of 2,500 pounds per square foot (psf). We do
recommend that the proposed footings and slabs be supported by
formatlonal soils and/or properly compacted fill, and contain at least a
nominal amount of reinforcing steel to reduce the separation of cracks should
they occur. The allowable soll bearing capacity may be Increased one-third
for structural design lndudlng seismic or wind loads.
2. The proposed footings should have a minimum depth of 18 inches and a
width of at least 15 Inches, founded In the dense formatlonal material or
properly compacted fills, A minimum of steel for continuous footings should
Include at least two No. 4 bars continuous, with two bars 3 Inches from the
bottom or the footing.
\"--,,
'-/
Barberio Property
Carlsbad, Calffomla
Job No. 15-10764
Page 3.
3. Site-specific seismic design a1terln to calculate the base shear needed for the
design of the residential addition ere presented In the following table. The
design criteria was obtained from the Callfomla Building Code (CBC) 2013
edition, and Is based on the distance to the dosest active fault and soil
profile dassfffcatlon.
4. The proposed addition should be designed In accordance with Section 1613 of
the 2013 CBC, which Incorporates by reference the ASCE 7-10 for seismic
design and the followlng parameters should be utlllzed. We have determined
the mapped spectral acceleration values for the site based on a latitude of
33.1644 degrees and longltude of 117.3545 degrees, utilizing a program
titled •'Design Maps and Tools," provided by the USGS, which provides a
solutfon for ASCE 7-10 (Section 1613 of the 2013 CBC) utillzJng digitized flies
for the Spectral Acceleration mnps.
In addition, we have assigned a Site Classification of D. The response
parameters for design are presented in the following table. Toe design
spectrum acceleration vs. Period T Is attached.
S F F
0.448 1.033 1.552
s. The liquefaction of saturated sands during earthquakes can be a major cause
of damage to buildings. Liquefaction Is the process by which soils are
transformed Into a viscous fluid that wlll flow es a liquid when unconfined. It
<>CaJrs prtmalily In loose, saturated sands and sifts when they are sufficiently
\
Barberio Property
cartsbad, Callfomla
Job No. 15-10764
Page4
shaken by an earthquake. Soft saturated clays can also deform during
earthquakes and contribute to slgnlffcent settlement.
On this site, the risk of llquefactlon of foundation materials due to seismic
shaking Is considered to be remote due to the relatively shallow, medium
dense fill solls, dense nature of the natural-ground material and the lack of a
shallow static groundwater surface under the site. No soll liquefaction or soll
strength loss Is anticipated to occur due to a seismic event.
6. Any new conaete slabs on-grade ( on properly compacted fill or dense
fonnatlonal solls) should be a minimum of 4 Inches actual thickness and be
reinforced with at least No. 3 steel bars on 18-lnch centers, In both
directions, placed at mid-height In the slab. The Interior slab should be
underfaln by a 15-mil vapor barrier (15-mll StegoWrap) placed directly on
properly compacted subgrade. The sand base may be waived.
We recommend that lsolatlon joints and sawcuts be Incorporated to at least
one-fourth the thickness of the slab In any slab designs. The joints and ruts,
ff properly placed, should reduce the potential for and help control floor slab
aacklng. In no case, however, should control joints be spaced farther than
20 feet apart, or the width of the slab. Control joints should be placed within
12 hours after concrete placement as soon as concrete sets and no raveling
of aggregate ocaJrs. Slabs spanning any existing loose solls and supported
by perimeter deepened foundations should be d~ned as structural slabs.
7. Although no retaining walls are planned, the active earth pressure (to be
utilized In the design of cantilever, non-restrained walls) should be based on
an Equfvalent Fluld Weight of 38 pounds per ruble foot (for level backflll only)
'
Barberio Property
carlsbad, California
Job No. 15-10764.
Page 5
If on-site soils are used. Addltlonal loads applied within the potential failure
block should be added to the active soll earth pressure by multlpfylng the
vertical surcharge load by a 0.31 lateral earth pressure coefficient.
For restrained wall conditions, we recommend an equivalent fluid weight of
59 pcf. Surdtarge loads on restrained walls may be converted to lateral
pressures by muttlplyfng by a factor of 0.47. Should seismic soll Increment
be required, the unrestrained walls with level bl!!lckflll should be designed for
a b1angular pressure of 15 pcf, In addition to the regular static loading, with
zero pressure at the top and the maximum pressure at the bottom of the
wall.
8. The pass~e earth pressure of the encountered fill soils (to be used for design
of shallow found8tfons and footings to resist the lateral forces) should be
based on en Equfvalent Fluid Weight of 250 pcf. This passive earth pressure
should only be considered valid for design ff the ground adjacent to the
foundation structure Is essentially level for a distance of at least three times
the total depth of the foundation and Is proJ)4;!rly compacted or dense natural
sol!. An allowable Coeffldent of Friction of 0.35 times the dead load may be
used between the bearing soils and concrete foundations, walls or floor slabs.
9. Adequate measures should be taken to properly finish-grade the site after
the new additions and other Improvements are In place. Drainage waters
from this site and adjacent properties are to be directed away from perimeter
foundations, floor slabs, and footings, onto the natural drainage direction for
\
this area or Into properly designed and approved drainage fadlltles. Proper
subsurface and surfzice drainage will help minimize the potential for waters to
seek the level of the bearing soils under the foundations, footings, and floor
---,
)
\\.. --/
Barberio Property
Carlsbad, Callfomla
Job No. 15-10764
Page6
slabs. Fallure to observe this recommendation couk:I result in undermining,
differential settlement of the building foundation or other Improvements on
the site, or moisture-related problems.
It Is not within the scope of our services to provide quality control oversight
for surface or subsurface drainage construction or retain Ing wall sealing and
base of wall draf n ·construction. It Is the responsibility of the contractor
and/or their retained construction fnspectlon service provider to provide
proper sumice and subsurface drainage.
10. Due to the possible bulld-up of groundwater ( derived primarily from rainfall
and Irrigation), excess moisture Is e common problem In below-grade
stnJctures or behind retaining walls that may be planned. These problems
are generally In the form of water seepage through walls, mineral staining,
mlldew growth and high humidity. In order to minimize the potential for
moisture-related problems to develop, proper cross ventilation and water-
proofing must be provided for below-ground areas, In crawl spaces, and the
backfill side of all structure retaining walls must be adequately waterproofed
snd drained.
Proper subdrafns end free-draining backwall material (such as gravel or
geocomposlte drains sudt as Mlradraln 6000 or equivalent) should be
!~lied behind all retaining walls on the subject project In addition to wall
waterproofing. Geotet:hnlt:III Exploretlon, Inc. wlll assume no llablllty for
damage to structures that Is attributable to poor drainage.
Barberio Property·
Car1sbad, callfomla
Job No. 15-10764
Page 7
11. Planter areas and planter boxes should be sloped to drain away from the
foundations, footings, and floor slabs. Planter boxes should be constructed
with a dosed bottom and a subsurface drain, Installed In gravel, with the
direction of subsurface and surface flow away from the foundations, footings,
and floor slebs, to an adequate dralnege facility. The finish grade around the
addition should drain away from the perimeter walls to help reduce or
prevent water aca.imulatlon.
Exterior slabs or rigid Improvements should also be built on property
compectecl solls and be provided with concrete shrinkage reinforcement and
adequately spaced joints.
Geotechnkal Explaratlon, Znc. recommends that we be asked to verify the
actual soil conditions revealed In footing excavations prior to ro·rm and steel
reinforcement placement.
Should you have any questions regarding this matter, please contact our office.
Reference to our Job No. 15-10784 wf II help to expedite a response to your
Inquiries.
Respectfully submitted,
Gl!OTECHNICAL EXPLORAnON, INC.
~
Senior Project Geologist
Jaime A. Cerros, P.E.
R.C.E. 34422/G.E. 2007
Senior Geotedlnlcal Englneet
'" -VICINITY MAP
l ~\< , ~I_4'J.y~
~ Bros GuJde San Diego Counfy pg 1 T~ \_
Barberio Property
228 Normandy Lane
Carlsbad, CA.
Figure No. I
Job No. 15-10764
'>.. ___ '
\
SURVEY PLAT
SHOWIN6 THE Rel.LT5o OF A Fl!LO
~VEY OF LOT 37. M.Y 1762. 6f<NNLLE rNU:. ~. GA.
Ot\TE OF Sl.«WY. '1~
I..EGEN)
o SET 31',• lltON rt!'!: W/TAb ~ LS t0.67
SCALE: 1" = 20'
32
REFERENCE: TIIJB Plot Pllln -plffltfl9d ml' 111 ..,_ Sl»M:Y l'f..AT bf EltllrBr ,__, ~ m
dlatl 7/fllfU MtllloaJ OIHll8 aid MWIL b 9
patblr9d by8EI.
I ( appro>elmafe )
• I i : I • I • I
31
LEGEND
~ Approximate Locaflon HIL1 of Exploratory Handpit
i I I I I I I I 1 I I I I I
36 : JCI
' ~~~! i;: GORfERI :..t l l I
30
PLOT PLAN
8ametb Propelty
228 Normandy Lane
Cadsbed, C4.
Rg,nNo. {I
Job No. 16-10784
ffi t=:='rnc. ~ Alllr21116
~) ~·----~·---------------------------------------------------------------
,.. EQIJFt.lBl1' DIMENl!QI I TYPE! a= EXCAVATICW DATE LOOOED
...
HandToofa 2' X 2' X 3' Hllndpll 6-8-11
SURFACE 8.EYATICW GROtN>WA1ERf SEEPAGE DEPTH I.COOB)&V
:t 71' Mean lea Lnel Not Encountered JKH
FELD~ l AND ~
H
i! ts I I a.ASSIRCATION !I H ii H !I 11 I I i DEBCRFT10NN6' RBMK8 I Ii --~Mcaa,Cln)
8IL lY SAND, 1lll8-to meaur, -.•--.., "1U1 tsM -some room. Medium denle. Dry. Light brown. -~8 FILU -TOPSOIL (CW)
-
1 811-lY BAND, m.10 ...... ~-Pt4edlum SM
d£l188 to denae. Damp. Red-brown. -. OLD PARAUC DEPOSITS (Qop~ --23% paeslng #200 sleYe. 8.0 134.!5
-
2--
-
-
--
3-U. M
-Bot1om@3'
-
-
4-
I -
I -
I -
i .
~ PERCHED WATER TABLE JOBNNrE
Barberio
t8J BULK BAG SAMPLE 8ITE 1..0CATD
[) IN-Pl.A.CE SAMPLE 221 Nannendy Lana, Carllbad, CA
• MODIFIED CALFORNIA SAMPLE
JOBIUIBER REYEWED Fl'f LDRIJAC LOGNo.
[!] NUCLEAR FIELD DENSITY TEST 15-10784 &;I HP-1 FWRENUMBER
ml STANDARD PE~TION TEST Ila
-...
EQJIPMENT DIIENBION I TYPE OF EXCAVATION DATE I..OCD:D
HandToola 2' X 2' X 3' Hudplt 6-8-16
IIIJU'ACE 8.EVAlJON ~SEEPAOEDEPTH LOOOEDBY
:t 76' Mean 8N Lnel Nol EnccNml8red JKH
FB.D DESCRIPT10N l Atl) ~ ~I @ ~x I Cl.ASSIFICA TION n n 11 i~ !I 11 I i i Ii Ii i DEBCRFT10H NfJ RSMRl(8
((aalllz9, ~ ....... Coler)
~ mLTTMNU, to,-~--......,wnn 8M
some roots. ,_.um denN. Dry. Ught brown. -
PIW -TOPSOL (Qaf)
-
1-~ -BL lY SAIi), Ina-to m -~-...... SM
dense to denee. Damp. RecM>rown. -
OLD PARAUC Dl!POSIT8 (Qapz,.J -\
-'
2-
-
-
-
3-
-Bottom@3' ---
-.
4-.
i -
t -
I -
i
;•
I ~ PERCHED WAlER TABLE JCEPW&:
BarbtHlo ii=,-'7
181 BULK BAG SAMPLE ll1TE LOCA1DI
I m IN-PLACE SAMPLE 228 Normandy l..me, Cllrlebad, CA
~ • MODIRED CALIFORNIA SAMPLE .KlB IIAIBER ~BY LDRIJAC LOONo.
'
[!] , NUCLEAR FIELD DENSITY 'TEST 1~10714 -· --HP-2 FIGlR: NIJr4BER ~~ Im.
I I. fil STANDARD PENETRATION TEST 11b .J
/ I
\ /
I
'
i
i
j
!
i ;
135 a\ ,
'I\ ,
• 1 \
" \
130 \
J \ \ • \
\ l
\ '
126 \
\ \
\ Scuce of Mmertal HP-1 aur
\ l 8IL TY SAND (811), Bfd:brOWD
\ ' Description of Malarial
1--\ l
\. Tast:Method ASTII D16S7 llethod A ' \ ' ' \
11& ' ' ' ' \ TEST RESULTS ~ ' 1
' \. Maxfinun Dry Denaffy 134.S PCF
110 I\ \ ' Optimum Water Content _M. % ' \.
1 I\
\ " \. i 108
\. ' Expalefon Index (El) --
' " r\. l
l 1
\ ' \ Ii.
' \
100 " \ .. Curves of 100% Seturetlon
i\ '' \ for Specific Gravity Equal to: i\
I\ ' 2.80
~ i\ ' \ \. \. 2.70
\. \ ..
\. " 2.60
' \ '
90 ' \. ' ' ...
\ i\ ' \ 1,
' " " 86 I'\ I\.
----. -------~ ' -" I\.. ' ...
"'-' , .... ', ...
80 I\. " ... "'\ ....
I'\.. "'\ -...
I'\.. ' ' I',. 'f
76 !'\I
0 1) 16 20 ~ j D ~ 5 .c ) 46
WATER CONTENT,%
~GNndl~
MOISTURE-DENSrrY RELATIONSHIP
1rap1ordon, Inc. Figure Number: IV
Job Name: Barberio Property
Sle Location: 228 Normandy Lene, Certabed. c.A
Job Number: 15-10784
· IIUSGS Design Maps Summary Report
U1er-Spedfled Input
Report Tltle 228 Normandy Lane, carlsbad
Mon May 18, 2015 18:17:49 UTC
Bulldlng Code Reference Document ASCE 7-10 Standard
(which utilizes USGS hazard data available in 2008)
Site CoordlnatN 33.1644°N, 117.3545°W
Site Soll Classification Site Class D -"Stiff Soll"
Risk Cat.gory I/II/III
j ' 2ml ------... , 5IHIII
USGS-Provlcled Output
s. = 1.168 g
S1 = 0.448 g
s,,.s = 1.206 g
s,,11 = o.696 g
S09 = 0.804 g
S01 = 0.464 g
Vista
0
...... EDI
For Information on how the SS and Sl values above have been calculated from probablllstlc (risk-targeted) and
deterministic ground motions In the direction of maximum horizontal response, please return to the appllcatlon and
select the "2009 NEHRP" building code reference document.
'I -rl
MCE11 Response Spectrum
1.4:il
1.30
1.17
1,04
0.'1
0.78
0.'5
0.52
O.:il9
O.:lS
o.u
0.00 1'---t---t---t--t----t--.,..._~...._-+-~f---1
0.00 0.20 o.,o O.CO O.IIO 1.00 1.20 1.,0 l.CC 1.80 2.00
P.-lod, T (••c)
'I -I
0.,0
Design Response Spectrum
0.81
o.n
o.n
0.54
0.'5
0.3'
0.:27
0.18
0.0,
0.00 +--+--~-+--+---+--+---+-'"""""f---+---1
0.00 0.:20 o.,o O.CO O.IIO 1.00 1.:20 1.,40 l.SO 1.80 2.00
Period, T (NC)
For PGA,.., Tv Cu, and CR1 values, please view the detailed report.
/