HomeMy WebLinkAboutCDP 2017-0008; THERMO FISHER PARKING LOT; GEOTECHNICAL INVESTIGATION; 2017-01-12ctrjo I1-ooD 6960 Flanders Drive U Sari Diego California 92121 2974 U Telephone 858.558.60M- U Fox 858 558 6159 TABLE OF CONTENTS I PURPOSE AND SCOPE 1 2 SITE AND PROJECT DESCRIPTION 3 SOIL AND GEOLOGIC CONDITIONS 2 -3.1. Previously Placed Fill (Qpf) 2 3 2 Santiago Formation (Tsa) 2 I 4 'GROUNDWATER 2 I 5 GEOLOGIC HAZARDS 3 5.4 Faulting and Seismicity 3 5.2- Ground Rupture 4 5.3 Tsunamis and Seiches 5 I 5 4 Liquefaction 5 5 5 Landslides 5 I 6 CONCLUSIONS AND RECOMMENDATIONS 6 .6 General 1.1 6 .6.2. Excavation and Soil Charactenstics 6 1 .6.3'' Seismic Design Cntena - California Building Code 8 6 4 Grading 9 6.5 Retaining Walls 10 I 6.6 Lateral Loading 61, Preliminary Pavement Recommendations 12 13 6 8 Site Drainage and Moisture Protection 18 I LIMITATIONS AND UNIFORMITY OF CONDITIONS MAPS AND ILLUSTRATIONS I Figure 1, Vicinity Map Figure 2, Site Plan (Map Pocket) Figure 3, Wall/Column Footing Dimension Detail I Figure 4, Typical Retaining Wall Drain Detail APPENDIX I LABORATORY TESTING Table A-I, Summary of Laboratory Maximum Dry Density and Optimum Moisture Content Test Results Table A-IT, Summary of Laboratory Direct Shear Test Results I Table A-ill, Summary of Laboratory Expansion Index Test Results Table A-TV, Summary of Laboratory Water-Soluble Sulfate Test Results Table A-V, Summary of Laboratory Resistance Value (R-Value) Test Results I APPENDIX B STORM WATER INVESTIGATION REPORT 1 LIST OF REFERENCES I I 1 GEOTECHNICAL INVESTIGATION 1. PURPOSE AND SCOPE - This report presents the results of our geotechnical investigation for the proposed parking lot I improvements within the Thermo Fisher campus in Carlsbad, California. The purpose of this geotechnical investigation is to evaluate the surface and subsurfacç soil conditions and general site geology, and to identify geotechnical constraints that may impact development of the property I including faulting and seismic shaking based on the 2016 .CBC seismic design riteria. The scope of our study includes pràviding recommendations for pavement, remedial grading in the area of parking 1 expansion, retaining walls, and storm water management recommendations. I Our scope of services included the review of aerial photographs, readily available published and unpublished geologic literature and the previous geotechnical investigation for the site (see List of References), excavating surficial soil samples to a maximum depth of approximately 5 feet, I performing in-situ infiltration field testing, soil sampling, laboratory testing, engineering analyses, and preparation of this geotechnical report. We performed laboratory tests on selected soil samples obtained during the field investigation to evaluate physical and chemical properties for engineering analyses and to assist in providing geotechnical engineering recommendations for project improvement design. Details of the laboratory tests and a summary of the test results are presented in Appendix A. We used plans prepared by Michael Baker International as the base to prepare our Site Plan, Figure 2. Appendix B presents the results of our storm water management investigation and recommendations. I 2. SITE AND PROJECT DESCRIPTION The site is located at 5823 Newton Drive within the Thermo Fisher campus at the northern terminus I of the Newton Drive cul-de-sac in the City of Carlsbad, California (see Vicinity Map, Figure 1). The site is occupied by a two-story, concrete tilt-up office and warehouse building surrounded by asphalt 1 concrete (AC) parking stalls and driveways and a Portland cement concrete (PCC) loading dock area on the east side of the building The topography within the area of the proposed improvements is I relatively flat with an elevations ranging from approximately 260 to 270 feet above Mean Sea Level (MSL) A descending 11/2:1 (horizontal to vertical) slope with a maximum height of approximately ' 25 feet exists along the east perimeter of the site. We understand the proposed improvements will consist of constructing additional parking spaces ' around the building, two stairs supported by retaining walls on the eastern descending slope to provide access to the adjacent property parking area and a cart path at the northern portion of the site Project No. G2066-11-01 -1 January 12,20i7 connecting to the adjacent lot to the east. We also understand that storm water management BMP devices will be added to the project consisting of permeable pavement to improve water quality. The site description and proposed development are based on a site reconnaissance and discussions with you. If development plans differ from those described herein, Geocon Incorporated should be contacted for review of the plans and provide possible revisions to this report. 3. SOIL AND GEOLOGIC CONDITIONS Based on our review of the referenced previous geotechnical investigation performed at the site, and our current field investigation, we expect the site is underlain by previously placed fill overlying Santiago Formation. The geologic units are described herein in order of increasing age. 3.1 Previously Placed Fill (Qpf) We estimate the site is generally underlain by a maximum of approximately 5 feet of previously placed fill associated with grading of the site with thicker fill potentially present near at the entrance at Newton Drive and on the northern portion of the parking lot. The fill was likely generated from excavations within the underlying Santiago Formation at the site The fill soils encountered during our field investigation generally consist of sandy clays and silty or clayey sands. Based on the results of our laboratory testing, we expect the fill possesses a "very low" to "medium" expansion potential (expansion index of 90 or less). The upper portion of the previously placed fill will require remedial grading. 3.2 Santiago Formation (Tsa) We expect the Santiago Formation underlies the previously placed fill. The Santiago Formation at the site generally consists of olive gray, silty sandstones and sandy siltstones with occasional clay seams. Based on the results of our laboratory testing, we expect the Santiago Formation possesses a "very low" to "medium" expansion potential (expansion index of 90 or less). The Santiago Formation is suitable for support of the proposed improvements. 4. GROUNDWATER Groundwater was not encountered during the previous field investigation performed by GeoSoils in 1997 and we expect it to be at least 100 below existing finish grades. We do not expect groundwater to have a significant influence on construction operations or the performance of the improvements. It is not uncommon for seepage conditions to develop where none previously existed. Seepage is dependent on seasonal precipitation, irrigation and land use, among other factors, and varies as a result. Proper surface drainage will be critical to future performance of the project. Project No. G2066-11-01 - 2 - January 12, 2017 1 5. GEOLOGIC HAZARDS I 5.1 Faulting and Seismicity A review of the referenced geologic materials and our knowledge of the general area indicate that the site is not underlain by active, potentially active, or inactive faults. An active fault is defined by the I California Geological Survey (CGS) as a fault showing evidence for activity within the .last 11,000 years. The site is not located within a State of California Earthquake Fault Zone. According to the computer program EZ-FRISK (Version 7.65), 10 known active faults are located within a search radius of 50 miles from the property. We used the 2008 USGS fault database that provides several models and combinations of fault data to evaluate the fault information. Based on this database, the nearest known active fault is the Newport-Inglewood and Rose Canyon Fault system, located approximately 6 miles west of the site and is the dominant source of potential ground motion. Earthquakes that might occur on the Newport-Inglewood and Rose Canyon Faults or other faults within the southern California and northern Baja California area are potential generators of significant ground motion at the site. The estimated deterministic maximum earthquake magnitude and peak ground acceleration for the Newport-Inglewood Fault are 7.5 and 0.34g, respectively. Table 5.1.1 lists the estimated maximum earthquake magnitude and peak ground acceleration for the most dominant faults in relationship to the site location. We calculated peak ground acceleration (PGA) using Boore-Atkinson (2008) NGA USGS2008, Campbell-Bozorgnia (2008) NGA USGS 2008, and Chiou-Youngs (2007) NGA USGS2008 acceleration-attenuation relationships. TABLE 5.1.1 DETERMINISTIC SPECTRA SITE PARAMETERS Fault Name Distance from Site (miles) Maximum Earthquake Magnitude (Mw) Peak Ground Acceleration Boore- Atkinson 2008 (g) Campbell- Bozorgnia 2008 (g) Chiou- Youngs 2007 (g) Newport-Inglewood 6 7.5 0.29 0.27 0.34 Rose Canyon 6 6.9 0.24 0.25 0.28 Elsinore 21 7.9 0.18 0.13 0.17 Coronado Bank 22 7.4 0.15 0.11 0.12 Palos Verdes Connected 22 7.7 0.16 0.12 0.15 Palos Verdes 38 7.3 0.09 0.07 0.07 San Joaquin Hills 38 7.1 0.08 0.08 0.07 Earthquake Valley 41 6.8 0.07 0.05 0.04 San Jacinto 47 7.9 0.10 0.07 0.09 Chino 49 6.8 0.05 0.04 0.03. 1 Project No. G2066-11-01 -3- January 12, 2017 We used the computer program EZ-FRISK to perform a probabilistic seismic hazard analysis. The computer program EZ-FRISK operates under the assumption that the occurrence rate of earthquakes on each mappable Quaternary fault is proportional to the faults slip rate. The program accounts for fault rupture length as a function of earthquake magnitude, and site acceleration estimates are made using the earthquake magnitude and distance from the site to the rupture zone. The program also accounts for uncertainty in each of following: (1) earthquake magnitude, (2) rupture length for a given magnitude, (3) location of the rupture zone, (4) maximum possible magnitude of a given earthquake, and (5) acceleration at the site from a given earthquake along each fault. By calculating the expected accelerations from considered earthquake sources, the program calculates the total average annual expected number of occurrences of site acceleration greater than a specified value. We utilized acceleration-attenuation relationships suggested by Boore-Atkinson (2008) NGA USGS 2008, Campbell-Bozorgnia (2008) NGA USGS 2008, and Chiou-Youngs (2007) NGA USGS2008 in the analysis. Table 5.1.2 presents the site-specific probabilistic seismic hazard parameters including acceleration-attenuation relationships and the probability of exceedence. TABLE 5.1.2 PROBABILISTIC SEISMIC HAZARD PARAMETERS Probability of Exceedence Peak Ground Acceleration Boore-Atkinson, 2008 (g) Campbell-Bozorgnia, 2008 (g) Chiou-Youngs, 2007 (g) 2% in a 50 Year Period 0.42 0.42 0.47 5% in a 50 Year Period 0.31 0.30 0.33 10% in a 50 Year Period 0.24 0.23 0.24 While listing peak accelerations is useful for comparison of potential effects of fault activity in a region, other considerations are important in seismic design, including the frequency and duration of motion and the soil conditions underlying the site. Seismic design of the structure should be evaluated in accordance with the California Building Code (CBC) guidelines currently adopted by the City of Carlsbad. 5.2 Ground Rupture Ground surface rupture occurs when movement along a fault is sufficient to cause a gap or rupture where the upper edge of the fault zone intersects the earth surface. The potential for ground rupture is considered to be negligible due to the absence of active faults at the subject site. Project No. G2066-11-01 -4- January 12, 2017 5.3 Tsunamis and Seiches A tsunami is a series of long-period waves generated in the ocean by a sudden displacement of large volumes of water. The site is located approximately 2'/2 miles from the Pacific Ocean at elevations ranging from approximately, 260 to 270 feet MSL Therefore, the risk of a tsunami impacting the site is considered negligible due to the large distance from the ocean and relatively high elevation Seiches are standing wave oscillations of an enclosed water body after the original driving force has dissipated Dnving forces are typically caused by seismic ground shaking The site is not located near a body of water, therefore, the risk of a seiche impacting the site is considered negligible 54 Liquefaction Liquefaction typically occurs when a site is located in a zone with seismic activity, on-site soils are cohesionless or silt/clay with low plasticity, groundwater is encountered, and soil relative densities are less than about 70 percent If the four previous criteria are met, a seismic event could result in a rapid pore-water pressure increase from the earthquake-generated ground accelerations Seismically induced settlement may occur whether the potential for liquefaction exists or not Due to the lack of a near surface groundwater table and the dense nature of the existing compacted fill and the Santiago Formation, the potential for liquefaction and seismically induced settlement occurring at the site is considered negligible. : 5.5 Landslides — We have reviewed the Geologic Map of the Oceanside 30' x,60' Quadrangle prepared by Kennedy I and Tan, 2007 which indicates a mapped landslide northwest of the parking lot on the descending slope to the northwest of the site However, the pnor, geotechnical investigation did not encounter the landslide within the parking lot area Based on review of the geologic maps and examination of aerial I photographs, it is our opinion that landsliding will not impact the proposed parking lot improvements I I I 1 I I Project No. 62066-:11 -0 i _'5 7 January 12, 2017 6. CONCLUSIONS AND RECOMMENDATIONS 6.1 General 6.1.1 From a geotechnical engineering standpoint, it is our opinion the site is suitable for development provided the recommendations presented herein are implemented in design and construction of the project. 6.1.2 We estimate the site is underlain by up to approximately 5 feet of fill overlying the Santiago Formation. The upper portion of the fill will require remedial grading in the area of the planned improvements. The underlying Santiago Formation is considered suitable for support of additional fill and/or structural loads from the proposed improvements. 6.1.3 Excavation of the existing compacted fill and the underlying Santiago Formation (if encountered) should generally be possible with medium to heavy effort using conventional, heavy-duty equipment during remedial grading and trenching operations. We expect some cemented zones within the Santiago Formation could be encountered during trenching operations requiring very heavy effort. 6.1.4 We do not expect groundwater to adversely impact the proposed project. However, wet conditions and seepage could affect proposed construction if grading and trenching operations occur during or shortly after a rain event and water is allowed to temporarily pond on the site. 6.1.5 The proposed retaining wall structures can be supported on conventional shallow footings founded in properly compacted fill or Santiago Formation as recommended herein. We should be contacted if additional foundation recommendations are required. 6.2 Excavation and Soil Characteristics 6.2.1 The soil encountered in the field investigation is considered to be "expansive" (expansion index [El] greater than 20) as defined by 2016 California Building Code (CBC) Section 1803.5.3. Table 6.2.1 presents soil classifications based on the expansion index. We expect a majority of the soil encountered possess a "very low" to "medium" expansion potential (expansion index of 90 or less). Project No. G2066-fl-01 -6- January 12, 2017 I.. , TABLE 6;2.1 EXPANSION CLASSIFICATION BASED ON EXPANSION INDEX' Expansion Index (El) ASTM D 4829 Expansion Classification 2016 CBC Expansion Classification 0-20 Very Low Non-Epansive Low Expansive Very. High 51-90 Medium '91-l30 .High Greater Than 130 I 6.2.21 1 We performed laboratory tests on samples of the site materials to evaluate the percentage I of water-soluble sulfate content Results from the laboratory, water-soluble sulfate content tests are presented in Appendix B and indicate that the 'on-site materials at the location I tested possesses "S Y' to "S2" sulfate exposure classes tO, concrete structures as defined by 2016 CBC Section 1904 and ACT 318-14 Chapter 19. Table 6.2.2 presents a summary of concrete requirements set forth by 2016 CBC Section 1904 'and ACT 318. The concrete I improvements at the site should be designed for S2" sulfate exposure class according to Table 6.2.2: The ' presence of water-soluble sulfates' is not a visually discernible I characteristic; therefore, other soil samples from the site could yield different concentrations Additionally, over time landscaping activities (i.e., addition of fertilizers and other soil nutrients) may affect the concentration. - TABLE 6.2.2 : I REQUIREMENTS FOR CONCRETE EXPOSED TO. SULFATE-CONTAINING SOLUTIONS Wàtèr-Soluble Cement,*. Maximum Minimum Exposure Class . - Percent ' Sulfate (SO4) ' .Type(ASTM C -" ' ' Water to , . Cement Ratio Compressive :. by Weight ' : 150) by Weight ,. Strength (psi) SO ' SO4<0.10 No Type Restriction NA . 2,500 Si' . , ' 0.10SO4<0.20 ' ' Ii , , ' 0.50 •' 4,000 S2 ' 0.20S02.00 '.' V ,. .0.45 SO4?2.00' ' '+PozOIa'n or Slag, '- ,' 0:45 . 4,500 6.2.3' Geocon Incorporated does not practice in the field of corrosion engineering. Therefore, further evaluation by a corrosion ehgineer may be necessary if improvements that, could be susceptible to corrosion are plannd. . I Project No: G2066- 1-01 -7- . ,: ''. January 12, 2017 , ' 6.3 Seismic Design Criteria - California Building Code 6.3.1 We used the computer program US. Seismic Design Maps, provided by the USGS to evaluate the seismic design criteria. Table 6.3.1 summarizes site-specific design criteria I obtained from the 2016 California Building Code (CBC; Based on the 2015 International Building Code [IBC] and ASCE 7-10), Chapter 16 Structural Design, Section 1613 Earthquake Loads. The short spectral response uses a period of 0.2 second. The structures and improvements should be designed using a Site Class C. We evaluated the Site Class based on the discussion in Section 1613.3.2 of the 2016 CBC and Table 20.3-1 of ASCE 7- 10. The values presented in Table 6.3.1 are for the risk-targeted maximum considered earthquake (MCER). I TABLE 6.3.1 2016 CBC SEISMIC DESIGN PARAMETERS Parameter Value 2016 CBC Reference Soil Site Class C Section 1613.3.2 NICER Ground Motion Spectral Response 1.074g Figure 1613.3.1(1) Acceleration - Class B_(short),_Ss NICER Ground Motion Spectral Response 0.414g Figure 1613.3.1(2) Acceleration - Class B_(1_sec),_Si Site Coefficient, FA 1.000 Table 1613.3.3(1) Site Coefficient, Fv 1.386 Table 1613.3.3(2) Site Class Modified NICER 1.074g Section 1613.3.3 Spectral Response Acceleration (short), SMS (Eqn 16-37) Site Class Modified NICER 0.574g Section 16 13.3.3 Spectral Response Acceleration (1 sec), SMI (Eqn 16-38) 5% Damped Design 0.716g Section 1613.3.4 Spectral Response Acceleration (short), SDS (Eqn 16-39) 5% Damped Design 0.383g Section 1613.3.4 Spectral Response Acceleration (1 sec), SDi (Eqn 16-40) 6.3.2 Table 6.3.2 presents additional seismic design parameters for projects located in Seismic Design Categories of D through F in accordance with ASCE 7-10 for the mapped I maximum considered geometric mean (MCEG). Project No. G2066-11-01 -8- January 12, 2017 TABLE 6.3.2 2016 CBC SITE ACCELERATION DESIGN PARAMETERS Parameter Value ASCE 7-10 Reference Mapped MCE0 Peak Ground Acceleration, PGA 0.4159 Figure 22-7 Site Coefficient, FPGA 1.000 Table 11.8-1 Site Class Modified MCEG Peak Ground Acceleration, PGAM 0.415g Section 11.8.3 (Eqn 11.8-1) 6.3.3. Conformance to the criteria in' Tables 6.3.1 and 6.3.2 for seismic design does not constitute any kind of guarantee or assurance, that significant structural damage or ground failure will not occur if a large earthquake occurs. The primary goal of seismic design is to protect life, not to avoid all damage, since such design may be economically prohibitive. 1 6.4 Grading 6.4.1 Grading should be performed in accordance with the recommendations presented herein I. and the City of Carlsbad Grading Ordinance. Earthwork should be observed, and compacted fill tested by representatives of Geocon Incorporated. 6.4.2 Prior to commencing grading, a preconstruction conference should be held at the site with the owner or developer, city inspector, grading contractor, civil engineer, and geotechnical engineer in attendance. Special soil handling requirements can be discussed at that time. 6.4.3 Site preparation should begin with the removal of landscaping vegetation, irrigation pipes, and debris. The depth of removal should be such that material to be used as fill is generally free of organic matter. Material generated during stripping operations should be exported from the site. 6.4.4 In general, the upper I to 2 feet of the existing ground surface within the areas of improvements will require processing, moisture conditioning as necessary, and recompaction prior to placing fill or surface improvements. 6.4.5 Some areas of overly wet and saturated soil should be expected in existing landscape irrigation areas. The saturated soil would require additional effort prior to placement of compacted fill or additional improvements. Stabilization of the soil would include scarifying and air-drying, removing and replacement with drier soil, use of stabilization fabric (e.g. Tensar TX7 or other approved fabric), or chemical treating (i.e. cement or lime treatment). . I Project No. G2066-11-01 -9- January 12, 2017 6.4.6 The contractor should be careful during the remedial grading operations to avoid a "pumping" condition at the base of the removals. Where recompaction of the excavated bottom will result in a "pumping" condition, the bottom of the excavation should be tracked with low ground pressure earthmoving equipment prior to placing fill. If needed to improve the stability of the excavation bottoms, reinforcing fabric or 2- to 3-inch crushed rock can be placed prior to placement of compacted fill. 6.4.7 Excavated soil generally free of deleterious debris and vegetation can be placed as fill and compacted in layers to the design finish grade elevations. The onsite soils can be re-used as compacted fills. Oversize rock material greater than 6 inches should not be placed within the upper 3 feet of proposed finish grades. Fill and backfill materials should be compacted to a dry density of at least 90 percent of the laboratory maximum dry density near to slightly above optimum moisture content as determined by ASTM D1557. 6.4.8 Import fill (if necessary) should consist of granular materials with a "very low" to "low" expansion potential (El of 50 or less), free of deleterious material or rock larger than 1 foot, and should be compacted as recommended herein. Geocôn Incorporated should be notified of the import soil source and should perform laboratory testing of import soil prior to its arrival at the site to evaluate its suitability as fill material. 6.4.9 Disturbed slopes should be re-landscaped with drought-tolerant vegetation having variable root depths and requiring minimal landscape irrigation. In addition, all slopes should be drained and properly maintained to reduce erosion. 6.5 Retaining Walls 6.5.1 Retaining walls not restrained at the top and having a level backfill surface should be designed for an active soil pressure equivalent to the pressure exerted by a fluid density of 40 pounds per cubic foot (pcf). Where the backfill will be inclined at 2:1 (horizontal to vertical), we recommend an active soil pressure of 55 pcf. Soil with an expansion index (El) of greater than 90 should not be used as backfill material behind retaining walls. 6.5.2 Retaining walls shall be designed to ensure stability against overturning sliding, excessive foundation pressure and water uplift. Where a keyway is extended below the wall base with the intent to engage passive pressure and enhance sliding stability, it is not necessary to consider active pressure on the keyway. 6.5.3 In general, wall foundations having a minimum depth and width of 1 foot may be designed for an allowable soil bearing pressure of 2,000 psf. The allowable soil bearing pressure Project No. G2066-I1-01 -10- January 12, 2017 may be increased by an additional 300 psf for each additional foot of depth and width, to a maximum allowable bearing capacity of 3,000 psf. The proximity of the foundation to the top of a slope steeper than 3:1 could impact the allowable soil bearing pressure. Therefore, retaining wall foundations should be deepened such that the bottom outside edge of the footing is at least 7 feet horizontally from the face of the slope. Figure 3 presents a wall/column footing detail. 6.5.4 Unrestrained walls are those that are allowed to rotate more than 0.001H (where H equals the height of the retaining portion of the wall) at the top of the wall. Where walls are restrained from movement at the top (at-rest condition), an additional uniform pressure of 7H psf should be added to the active soil pressure for walls 8 feet or less. For retaining walls subject to vehicular loads within a horizontal distance equal to two-thirds the wall height, a surcharge equivalent to 2 feet of fill soil should be added. 6.5.5 Drainage openings through the base of the wall (weep holes) should not be used where the seepage could be a nuisance Or otherwise adversely affect the property adjacent to the base of the wall. The recommendations herein assume a properly compacted granular (El of 90 or less) free-draining backfill material with no hydrostatic forces or imposed surcharge load. Figure 4 presents a typical retaining wall drainage detail. If conditions different than those described are expected, or if specific drainage details are desired, Geocon Incorporated should be contacted for additional recommendations. I 6.5.6 The structural engineer should determine the Seismic Design Category for the project in accordance with Section 1613.3.5 of the 2016 CBC or Section 11.6 of ASCE 7-10. For I structures assigned to Seismic Design Category of D, E, or F, retaining walls that support more than 6 feet of backfill should be designed with seismic lateral pressure in accordance I with Section 1803.5.12 of the 2016 CBC. The seismic load is dependent on the retained height where H is the height of the wall, in feet, and the calculated loads result in pounds per square foot (psf) exerted at the base of the wall and zero at the top of the wall. A I seismic load of 17H should be used for design. We used the peak ground acceleration adjusted for Site Class, effects, PGAM, of 0.415g calculated from ASCE 7-10 Section 11. 8.3 and applied a pseudo-static coefficient of 0.3. 6.5.7 The retaining walls may be designed using either the active and restrained (at-rest) loading I condition or the active and seismic loading condition as suggested by the structural engineer. Typically, it appears the design of the restrained condition for retaining wall I .loading may be adequate for the seismic design of the retaining walls. However, the active earth pressure combined with the seismic design load should be reviewed and also considered in the design of the retaining walls. Project No. G2066-11-01 -11- January 12,2O17 6.5.8 The recommendations presented herein are generally applicable to the design of rigid concrete or masonry retaining walls having a maximum height of 8 feet. In the event that walls higher than 8 feet or other types of walls (such as mechanically stabilized earth [MSE] walls, soil nail walls, or soldier pile walls) are planned, Geocon Incorporated should be consulted for additional recommendations. 6.5.9 Unrestrained walls will move laterally when backfilled and loading is applied. The amount of lateral deflection is dependent on the wall height, the type of soil used for backfill, and loads acting on the wall. The retaining walls and improvements above the retaining walls should be designed to incorporate an appropriate amount of lateral deflection as determined by the structural engineer. 6.5.10. Soil contemplated for use as retaining wall backfill, including import materials, should-be identified in the field prior to backfill. At that time, Geocon Incorporated should obtain samples for laboratory testing to evaluate its suitability. Modified lateral earth pressures may be necessary if the backfill soil does not meet the required expansion index or shear strength. City or regional standard wall designs, if used, are based on a specific active lateral earth pressure and/or soil friction angle. In this regard, on-site soil to be used as backfill may or may not meet the values for standard wall designs. Geocon Incorporated should be consulted to assess the suitability of the on-site soil for use as wall backfill if standard wall designs will be used. 6.6 Lateral Loading 6.6.1 To resist lateral loads, a passive pressure exerted by an equivalent fluid density of 300 pounds per cubic foot (pcf) should be used for the design of footings or shear keys. The allowable passive pressure assumes a horizontal surface extending at least 5 feet, or three times the surface generating the passive pressure, whichever is greater. The upper 12 inches of material in areas not protected by floor slabs or pavement should not be included in design for passive resistance. 6.6.2 If friction is to be used to resist lateral loads, an allowable coefficient of friction between soil and concrete of 0.35 should be used for design. The friction coefficient may be reduced depending on the vapor barrier or waterproofing material used for construction in accordance with the manufaëturer's recommendations. 6.6.3 The passive and frictional resistant loads can be combined for design purposes. The lateral passive pressures may be increased by one-third when considering transient loads due to wind or seismic forces. Project No. G2066-11-01 - 12 - January 12, 2017 1 6.7 Preliminary Pavement Recommendations 6.7.1 We calculated the flexible pavement sections in general conformance with the Caltrans Method of Flexible Pavement Design (Highway Design Manual, Section 608.4) using an estimated Traffic Index (TI)of 5.0, 5.5, 6.0, and 7.0 for parking stalls, driveways, medium truck traffic areas, and heavy truck traffic areas, respectively. The project civil engineer and owner should review the pavement designations to determine appropriate locations for pavement thickness. The final pavement sections for the parking lots additions should be based on the R-Value of the subgrade soil encountered at final subgrade elevation. We assumed an R-Value of 5 and 78 for the subgrade soil and base materials, respectively, for the purposes of this preliminary analysis. Table 6.7.1 presents the preliminary flexible pavement sections. TABLE 6.7.1 PRELIMINARY FLEXIBLE PAVEMENT SECTION Assumed Assumed Asphalt Class 2 Location Traffic Subgrade Concrete Aggregate Index R-Value (inches) Base (inches) Parking stalls for automobiles 5.0 5 3 10 _light and -duty vehicles Driveways for automobiles 5 5 3 12 and -duty _light _vehicles Medium truck traffic areas 6.0 5 3.5 13 Driveways for heavy truck traffic 7.0 5 4 16 6.7.2 Prior to placing base materials, the upper 12 inches of the subgrade soil should be scarified, moisture conditioned as necessary, and recompacted to a dry density of at least 95 percent of the laboratory maximum dry density near to slightly above optimum moisture content as determined by ASTM D 1557. Similarly, the base material should be compacted to a dry density of at least 95 percent of the laboratory maximum dry density near to slightly above optimum moisture content. Asphalt concrete should be compacted to a density of at least 95 percent of the laboratory Hveem density in accordance with ASTM D 2726. 6.7.3 Base materials should conform to Section 26-1.028 of the Standard Specifications for The State of California Department of Transportation (Caltrans) with a 3/4-inch maximum size aggregate. The asphalt concrete should conform to Section 203-6 of the Standard Specifications for Public Works Construction (Greenbook). Project No. G2066-1 1 -01 -13- January 12, 2017 6.7.4 The base thickness can be reduced if a reinforcement geogrid is used during the installation I of the pavement. Geocon should be contact for additional recommendations, if required. 6.7.5 A rigid Portland Cement concrete (PCC) pavement section should be placed in driveway entrance aprons, trash bin loading/storage areas and loading dock areas. The concrete pad for trash truck areas should be large enough such that the truck wheels will be positioned on the concrete during loading. We calculated the rigid pavement section in general conformance with the procedure recommended by the American Concrete Institute report ACI 330R-08 Guide for Design and Construction of Concrete Parking Lots using the parameters presented in Table 6.7.2. TABLE 6.7.2 RIGID PAVEMENT DESIGN PARAMETERS Design Parameter Design Value Modulus of subgrade reaction, k 50 pci Modulus of rupture for concrete, MR 500 psi Traffic Category, TC A and C Average daily truck traffic, ADTF 10 and 100 6.7.6 Based on the criteria presented herein, the PCC pavement sections should have a minimum thickness as presented in Table 6.7.3. TABLE 6.7.3 RIGID PAVEMENT RECOMMENDATIONS Location Portland Cement Concrete (inches) Automobile Parking Areas (TC=A) 6.0 Heavy Truck and Fire Lane Areas (TC=C) 7.5 6.7.7 The PCC pavement should be placed over subgrade soil that is compacted to a dry density of at least 95 percent of the laboratory maximum dry density near to slightly above optimum moisture content. This pavement section is based on a minimum concrete compressive strength of approximately 3,000 psi (pounds per square inch). 6.7.8 A thickened edge or integral curb should be constructed on the outside of concrete slabs subjected to wheel loads. The thickened edge should be 1.2 times the slab thickness or a minimum thickness of 2 inches, whichever results in a thicker edge, and taper back to the Project No. G2066-ll-01 -14- January 12, 2017 recommended slab thickness 4 feet behind the face of the slab (e.g., a 7.5-inch-thick slab would have a 9.5-inch-thick edge). Reinforcing steel will not be necessary within the concrete for geotechnical purposes with the possible exception of dowels' at construction joints as discussed herein. 6.7.9 To control the location and spread of concrete shrinkage cracks, crack-control joints (weakened plane joints) should be included in the design of the concrete pavement slab. Crack-control joints should not exceed 30 times the slab thickness with a maximum spacing of 5 feet for the 6- and 7.5-inch-thick slabs and should be sealed with an appropriate sealant to prevent the migration of water through the control joint to the subgrade materials. The depth of the crack-control joints should be determined by the referenced ACT report. The depth of the crack-control joints should be at least 1/4 of the slab thickness when using a conventional saw, or at least 1 inch when using early-entry saws on slabs 9 inches or less in thickness,'as determined by the referenced ACT report discussed in the pavement section herein. Cuts at least ¼ inch wide are required for sealed joints, and a % inch wide cut is commonly recommended. A narrow joint width of 1/10 to 1/8-inch wide is common for unsealed joints. 6.7.10 To provide load transfer between adjacent pavement slab sections, a butt-type construction joint should be constructed. The butt-type joint should be thickened by at least 20 percent at the edge and taper back at least 4 feet from the face of the slab. As an alternative to the butt-type construction joint, dowelling can be used between construction joints for pavements of 7 inches or thicker. As discussed in the referenced ACT guide, dowels should consist of smooth, 1-inch-diameter reinforcing steel 14 inches long embedded a minimum of 6 inches into the slab on either side of the construction joint. Dowels should be located at the midpoint of the slab, spaced at 12 inches on center and lubricated to allow joint movement while still transferring loads. In addition, tie bars should be installed at the as recommended in Section 3.8.3 of the referenced ACT guide. The structural engineer should provide other alternative recommendations for load transfer. 6.7.11 Concrete curb/gutter should be placed on soil subgrade compacted to a dry density of at least 90 percent of' the laboratory maximum dry density near to slightly above optimum moisture content. Cross-gutters should be placed on subgrade soil compacted to a dry density of at least 95 percent of the laboratory maximum dry density near t6. slightly above optimum moisture content. Base materials should not be placed below the curb/gutter, cross-gutters, or sidewalk so water is not able to migrate from the adjacent parkways to the pavement sections. Where flatwork is located directly adjacent to the curb/gutter, the concrete flatwork should be structurally connected to the curbs to help reduce the potential for offsets between the curbs and the flatwork. Project No. G2066-11-01 -15- January 12, 2017 6.7.12 We understand permeable payers will be used on the property. We calculated the permeable paver section general conformance with the Caltrans Method of Flexible Pavement Design (Highway Design Manual, Section 608.4) using an estimated Traffic Index (TI) of 5.0, 5.5, 6.0, and 7.0 for parking stalls, driveways, medium truck traffic areas, and heavy truck traffic areas, respectively. The project civil engineer and owner should review the pavement designations to determine appropriate locations for pavement thickness. Based on the Interlocking Concrete Pavement Institute (ICPI), the payers should possess a minimum thickness of 31/8 inches overlying 1 to 1 Y2 inch of sand. In addition, the payers should be installed in a pattern acceptable for vehicular traffic. The payers used for storm water management should be underlain by Class 2 permeable base or aggregate in accordance with ASTM C 33 based on the civil engineer/manufacturer's recommendations. Table 6.7.4 presents the preliminary flexible pavement sections. The payers can be underlain by PCC with thicknesses shown in Table 6.7.3 in pavement areas not be used for storm water management. TABLE 6.7.4 PAVER SECTION RECOMMENDATIONS Equivalent Option 1 Option 2 Traffic Assumed Paver Asphalt Estimated Location Index Subgrade Sand BaseConcrete ASTM C 33 (TI) R-Value Thickness Thickness Materials Aggregate (inches) (inches) (inches) Parking stalls for 2" #8 I automobiles 5.0 5 3'/8 1 10 4" #57 / and light-duty 7" #2 vehicles Driveways for 2" #8 / automobiles 5.5 5 3¼ 1 12 4"#57/ and light-duty 9" #2 vehicles Medium truck 6.0 5 31/8 2"#8 1 1 14 4" #57/ traffic areas 11"#2 Driveways for 2" #8 / heavy truck 7.0 5 31/81 1 18 4"#57/ traffic I I I I 1 1 16"#2 6.7.13 The Class 2 permeable base/aggregate section can be thickened to increase the water capacity as required by the project civil engineer. Prior to placing base/aggregate materials, the subgrade soil should be scarified, moisture conditioned as necessary, and recompacted to a dry density of at least 95 percent of the laboratory maximum dry density near to Project No. 62066-11-01 -16- January 12, 2017 slightly above optimum moisture content as determined by ASTM D 1557. The depth of compaction should be at least 12 inches. Similarly, the base materials should be compacted to a dry density of at least 95 percent of the laboratory maximum dry density near to slightly above optimum moisture content. 6.7.14 The subgrade of the water quality payers should be graded to allow water to flow to a subdrain. The subdrain should be placed at the bottom of the base/aggregate section below the payers and run the distance of the paver area to reduce the potential for water to build up within the paving section. The drain should be connected to an approved drainage device. Continuous impermeable liners should be installed along the sides of the water quality paver section to prevent water migration along the edge adjacent to the landscape area. The owner should consider placing a liner at the bottom of the pavement section to help prevent subgrade soil saturation: The liners should consist of a high density polyethylene (HDPE) with a minimum thickness of 15 mil or equivalent. The liner should be sealed at the connections in accordance with manufacturer recommendations and should be properly waterproofed at the drain connection. The drain should consist of a 3-inch diameter perforated Schedule 40, PVC pipe and placed at the bottom of the base materials. The paver section for relatively small area should be completely lined, a drain installed, and the drain properly outlet to an approved drainage control device. 6.7.15 The payers should be installed and maintained in accordance with the manufacturer's recommendations. The future owners should be made aware and responsible for the maintenance program. In addition, payers tend to shift vertically and horizontally during the life of the pavement and should be expected. The payers normally require a concrete border to prevent lateral movement from traffic. The concrete border surrounding the payers should be embedded at least 6 inches into the subgrade to reduce the potential for water migration to the adjacent landscape areas and pavement areas. The payers should be placed tightly adjacent to each other and the spacing between the paver units should be filled with appropriate filler. A polymer sand (Poly-Sand) can be used on decorative, non- storm water quality paver area to help prevent water infiltration. 6.7.16 The performance of pavement is highly dependent on providing positive surface drainage away from the edge of the pavement. Ponding of water on or adjacent to the pavement and subgrade will likely result in pavement distress and subgrade failure. Drainage from landscaped areas should be directed to controlled drainage structures. Landscape areas adjacent to the edge of asphalt pavements are not recommended due to the potential for surface or irrigation water to infiltrate the underlying permeable aggregate base and cause distress. Where such a condition cannot be avoided, consideration should be given to incorporating measures that will significantly reduce the potential for subsurface water Project No. G2066-11-01 - 17 - January 12, 2017 migration into the aggregate base. If planter islands are planned, the perimeter curb should extend at least 6 inches below the level of the base materials. 6.8 Site Drainage and Moisture Protection 6.8.1 Adequate site drainage is critical to reduce the potential ,for differential soil movement, erosion and subsurface seepage. Under no circumstances should water be allowed to pond adjacent to footings. The site should be graded and maintained such that surface drainage is directed away from structures in accordance with 2016 CBC 1804.4 or other applicable standards. In addition, surface drainage should be directed away from the top of slopes into swales or other controlled drainage devices. Roof and pavement drainage should be directed into conduits that carry runoff away from the proposed structure. 6.8.2 Underground utilities should be leak free. Utility and irrigation lines should be checked periodically for leaks, and detected leaks should be repaired promptly. Detrimental soil movement could occur if water is allowed to infiltrate the soil for prolonged periods of time. 6.83 Landscaping planters adjacent to paved areas are not recommended due to the potential for surface or irrigation water to infiltrate the pavement's subgrade and base course. Area drains to collect excess irrigation water and transmit it to drainage structures or impervious above-grade planter boxes can be used. In addition, where landscaping is planned adjacent to the pavement, construction of a cutoff wall along the edge of the pavement that extends at least 6 inches below the bottom of the base material should be considered. Project No. G2066-11-01 - 18 - January 12, 2017 LIMITATIONS AND UNIFORMITY OF CONDITIONS The firm that performed the geotechnical investigation for the project should be retained to provide testing and observation services during construction to provide continuity of geotechnical interpretation and to check that the recommendations presented for geotechnical aspects of site development are incorporated during site grading, construction of improvements, and excavation of foundations. If another geotechnical firm is selected to perform the testing and observation services during construction operations, that firm should prepare a letter indicating their intent to assume the responsibilities of project geotechnical engineer of record. A copy of the letter should be provided to the regulatory agency for their records. In addition, that firm should provide revised recommendations concerning the geotechnical aspects of the proposed development, or a written acknowledgement of their concurrence with the recommendations presented in our report. They should also perform additional analyses deemed necessary to assume the role Of Geotechnical Engineer of Record. The recommendations of this report pertain only to the site investigated and are based upon the assumption that the soil conditions do not deviate from those disclosed in the investigation. If any variations or undesirable conditions are encountered during construction, or if the proposed construction will differ from that anticipated herein, Geocon Incorporated should be notified so that supplemental recommendations can be given. The evaluation or identification of the potential presence of hazardous or corrosive materials was not part of the scope of services provided by Geocon Incorporated. This report is issued with the understanding that it is the responsibility of the owner or his representative to ensure that the information and recommendations contained herein are brought to the attention of the architect and engineer for the project and incorporated into the plans, and the necessary steps are taken to see that the contractor and subcontractors carry out such recommendations in the field. The findings of this report are valid as of the present date. However, changes in the conditions of a property can occur with the passage of time, whether they are due to natural processes or the works of man on this or adjacent properties. In addition, changes in applicable or appropriate standards may occur, whether they result from legislation or the broadening of knowledge. Accordingly, the findings of this report may be invalidated wholly or partially by changes outside our control. Therefore, this report is subject to review and should not be relied upon after a period of three years. Project No. G2066-11-01 January 12, 2017 THE GEOGRAPHICAL INFORMATION MADE AVAILABLE FOR DISPLAY WAS PROVIDED BY GOOGLE EARTH, SUBJECT TO A LICENSING AGREEMENT. THE INFORMATION IS FOR ILLUSTRATIVE PURPOSES Ofll. Y; IT IS NOT INTENDED FOR CLIENT'S USE OR RELIANCE AND SHALL NOT BE REPROOLICED BY CLIENT. CLIENT SHALL INDEMNIFY, DEFEND AND HOLD HARMLESS GEOCON FROM AN'f LIABILITY INCURRED AS A RESULT OF SUCH USE OR RELIANCE BY CLIENT. VICINITY MAP GE OCON INCORPORATED GEOTECHNICAL • ENVIRONMENTAL• MATERIALS 6960 FLANDERS DRIVE • SAN DIEGO, CALIFORNIA 92121 • 297 A PHONE 858 558-6900 • FAX 858 558-6159 t N NO SCALE THERMO FISHER 5823 NEWTON DRIVE CARLSBAD I CALIFORNIA RM I AML I I DSK/GTYPD DATE 01 • 12 • 2017 I PROJECT NO. G2066 • 11 • 01 I FIG. 1 I I I , I EXISTING BUILDING 0 GRAPHIC SCAL~ • 75 25 __ 100' , 200' 15_0 --- " 50 (on 3 4) SCALE 1 = GEOCON LEGEND OF SOIL SAMPLE LOCATION APPROX RATION TEST LOCATION OF INFILT APPROX. SITE PLAN THERMO FISHER WTON DRIVE 5823 NE CALIFORNIA ON ~ PROJECTNO. G2066-1 1 •01 2 GEO(;•'"" ·=-• , , I N C O R p ~L • ENVIRONMEr:~IA 92121·2974 SHEET 1 0 ETS\G206S-11-01 Slte ~n.ctwg TECHNI NDEGO CA "''""" GEO l»OERSDSJVE ·SA S5B-6l59 ""'"'6-"-01 JTh•= 6960 F S51l-6900. FAX 858 "'°'~''""'"c PHONE 858 \1N LADRIU.Or-101 RI• CARLSBAD, DATE 01-12 -2017 SCALE 1" : 50' FIGURE Ph,nelt01/13f.l0117: OOAM I Ely.Al. CONCRETE SLAB ............ :.'. a I PAD GRADE SAND AND VAPOR RETARDER IN o ACCORDANCE WITH ACI 00 44 ..... .\ k \...::.. "':.. LI. .40."...... I FOOTING* WIDTH 4 . :4 4- ri 4 4- A 'SAND AND VA RETARDERIN PORJ 4 A ACCORDANCE WITH ACI .4 f : LL A 13 FOOTING WIDTH *SEE REPORT FOR FOUNDATION WIDTH AND DEPTH RECOMMENDATION NO SCALE I WALL / COLUMN FOOTING DIMENSION DETAIL I GEOTECHNICAL •rENVIRONMENTAL. MATERIALS 6960 FLANDERS DRIVE -SAN DIEGO, CALIFORNIA 92121- 2974 PHONE 858 558-6900 - FAX 858 558-6159 RM / AML DSK/GTYPD Pbtted:0111312017 7:04AM ByALVNLADRLLOI THERMO FISHER 5823 NEWTON DRIVE CARLSBAD, CALIFORNIA DATE 01-12-2017 PROJECT NO. G2066- 11-01 1 FIG. 3 I Fib LQCafOn:YPROJECTS\G2068-I 1Ol (The,mo Fher)\DETAILS\Wo3Cot.,n,n Footno Onenso Doto0tCOLFOOT2t.do CONCRETE BROWDITCH GROUND SURFACE PROPOSED 7 RETAINING WALL PROPERLY COMPACTED / : BACKFILL TEMPORARY BACKCUT WATER PROOFING - / PER OSHA f PER ARCHITECT - 213 • IMIRAFI14ON FILTER FABRIC I - I (OR EQUIVALENT) I OPEN GRADED 1" MAX. AGGREGATE GROUND SURFACE - FOOTING 4 D. PERFORATED SCHEDULE L-1 40 PVC PIPE EXTENDED TO APPROVED OUTLET 12 CONCRETE BROWDITCH RETAINING WALL - 2/3 H GROUND SURFACE WATER PROOFING .-PER ARCHITECT DRAINAGE PANEL — (MIRADRAIN 6000 OR EQUIVALENT) 12H 3/4 CRUSHED ROCK (1 CU.FTJFT.) j— FILTER FABRIC ENVELOPE MIRAFI 140N OR EQUIVALENT - 4 DIA. SCHEDULE 40 PERFORATED PVC PIPE OR TOTAL DRAIN EXTENDED TO APPROVED OUTLET CONCRETE BROWDITCH RETAINING WALL 2/3 H GROUND SURFACE WATER PROOFING PER ARCHITECT DRAINAGE PANEL (MIRADRAIN 6000 OR EQUIVALENT) 4 DIA. SCHEDULE 40 PERFORATED PVC PIPE OR TOTAL DRAIN EXTENDED TO APPROVED OUTLET PROPOSED FOOTING PROPOSED NOTE: DRAIN SHOULD BE UNIFORMLY SLOPED TO GRAVITY OUTLET OR TO A SUMP WHERE WATER CAN BE REMOVED BY PUMPING NO SCALE I TYPICAL RETAINING WALL. DRAIN DETAIL I QrE QCON . (4 INCO , RPORATED GEOTECHNICALu ENVIRONMENTAL. MATERIALS 6960 FLANDERS DRIVE - SAN DIEGO, CALIFORNIA 92121- 2974 PHONE 858 5586900 - FAX 858 558-6159 RM I AML DSKIGTYPD THERMO FISHER 5823 NEWTON DRIVE CARLSBAD, CALIFORNIA I DATE 01 - 12- 2017 PROJECT NO. G2066 - 11 -01 1 FIG. 4 Pbfted:0111312017 7:04AM I By.ALV04 LADRLLOM I Fide Loctn:Y:R0JECTS\G2066-11.0I (Thermo Fho,DETALS\TypcaI Retaig WOIDm.aOO DetiIRW0D7AI.dwO APPENDIX A LABORATORY TESTING We performed laboratory tests on samples collected during our investigation in accordance with the current, generally accepted test methods of the American Society for Testing and Materials (ASTM) or other suggested procedures. We tested selected samples for their maximum dry density and optimum moisture content, direct shear strength, expansion, water-soluble sulfate content and R-value characteristics. Tables A-Lthrough A-V present the results of our laboratory tests. TABLE A-I SUMMARY OF LABORATORY MAXIMUM DRY DENSITY AND OPTIMUM MOISTURE CONTENT TEST RESULTS ASTM D 1557 Maximum Optimum Sample No. Depth (feet) Description (Geologic Unit) Dry Density Moisture Content (pci) (% dry wt.) S-2 0-3 Light grayish brown, Silty, fine to medium SAND 123.1 11.2 S-4 0-3 Brown, Clayey fine to medium SAND 123.6 .11.1 TABLE A-Il SUMMARY OF LABORATORY DIRECT SHEAR TEST RESULTS ASTM D 3080 Sample No. Depth (feet) Geologic Unit Dry Density (pci) Moisture Content (%) Unit Peak [Ultimate'] Cohesion Angle of Peak [Ultimate'] Shear Resistance Initial Final (psi) (degrees) S-42 0-5 Qpf/Tsa 111.8 10.1 18.9 1 375 [275] 1 28 [28] 'Ultimate indicates the end-of-tests at a deflection of about 0.2 inch. 'Sample remolded to 90 percent of the maximum dry density. TABLE A-Ill SUMMARY OF LABORATORY EXPANSION INDEX TEST RESULTS ASTM D 4829 Moisture Content (%) Dry Density . Expansion 2016 CBC ASTM Soil I I Sample No. (pci) Index Expansion Expansion Before Test After Test Classification Classification 5-5 11.7 26.8 103.5 83 Expansive Medium Project No. G2066-1 1 -01 -A-I - January 12, 2017 Sample No Depth (feet) Geolog ic Unit Water-Soluble Sulfate Exposure Sulfate (%) Class S-11-03 Qpf 0.100 Si S5 03 Qpf, 0379 S2 TABLE AN, SUMMARY OF LABORATORY AESISTANCE VALUE (R-VALUE) TEST RESULTS ASTM D 2844 Sample No Depth (feet) Description (Geologic Unit) R-Value S-i 013 Olive gray, Sandy CLAY <5 S-3. 0 3 Light brown Sandy CLAY <5 APPENDIX B STORM WATER MANAGEMENT INVESTIGATION We understand storm water management devices will be used in accordance with the 2016 City of Carlsbad BMP Design Manual. If not properly constructed, there is a potential for distress to improvements and properties located hydrologically down gradient or adjacent to these devices. Factors such as the amount of water to be detained, its residence time, and soil permeability have an important effect on seepage transmission and the potential adverse impacts that may occur if the storm water management features are not properly designed and constructed. We have not performed a hydrogeological study at the site. If infiltration of storm water runoff occurs, downstream properties may be subjected to seeps, springs, slope instability, raised groundwater, movement of foundations and slabs, or other undesirable impacts as a result of water infiltration. Hydrologic Soil Group The United States Department of Agriculture (USDA), Natural Resources Conservation Services, possesses general information regarding the existing soil conditions for areas within the United States. The USDA website also provides the Hydrologic Soil Group. Table B-I presents the descriptions of the hydrologic soil groups. If a soil is assigned to a dual hydrologic group (AID, B/D, or C/D), the first letter is for drained areas and the second is for undrained areas In addition, the USDA website also provides an estimated saturated hydraulic conductivity for the existing soil. TABLE B-I HYDROLOGIC SOIL GROUP DEFINITIONS. Soil Group Soil Group Definition Soils having a high infiltration rate (low runoff potential) when thoroughly wet. These A consist mainly of deep, well drained to excessively drained sands or gravelly sands. These soils have a high rate of water transmission. Soils having a moderate infiltration rate when thoroughly wet These consist chiefly of B moderately deep or deep, moderately well drained or well drained soils that have moderately fine texture to moderately coarse texture. These soils have a moderate rate of water transmission. Soils having a slow infiltration kate when thoroughly wet. These consist chiefly of soils C having a layer that impedes the downward movement of water or soils of moderately fine texture or fine texture These soils have a slow rate of water transmission Soils having a very slow infiltration rate (high runoff potential) when thoroughly wet. These D consist chiefly of clays that have a high shrink-swell potential, soils that have a high water table, soils that have a claypan or clay layer at or near the surface, and soils that are' shallow over nearly impervious material. These soils have a very 'slow rate of water transmission. Project No. G2066-ll-Ol ' -B-1 - 'January 12, 2017 The property is underlain by man-made previously placed fill and should be classified as Soil Group D. Table B-Il presents the information from the USDA website for the subject property. TABLE B-Il USDA WEB SOIL SURVEY - HYDROLOGIC SOIL GROUP Map Unit Approximate Hydrologic kSAT of Most Map Unit Name Symbol Percentage Soil Group Limiting Layer of Property (Inches! Hour) Cieneba coarse sandy loam, CIE2 35 D 0.00 -0.06 15 to 30 percent slopes, eroded Cienaba-Fallbrook rocky sandy loams, CnG2 65 D 0.00 -0.06 30 to 65 percent slopes, eroded In-Situ Testing The infiltration rate, percolation rates and saturated hydraulic conductivity are different and have different meanings. Percolation rates tend to overestimate infiltration rates and saturated hydraulic conductivities by a factor of 10 or more. Table B-Ill describes the differences in the definitions. TABLE B-Ill SOIL PERMEABILITY DEFINITIONS Term Definition The observation of the flow of water through a material into the ground Infiltration Rate downward into a given soil structure under long term conditions. This is . a function of layering of soil, density, pore space, discontinuities and initial moisture content. The observation of the flow of water through a material into the ground Percolation Rate downward and laterally into a given soil structure under long term i conditions. This s a function of layering of soil, density, pore space, discontinuities and initial moisture content. The volume of water that will move in a porous medium under a Saturated Hydraulic hydraulic gradient through a unit area. This is a function of density, Conductivity (ksAT, Permeability) structure, stratification, fines content and discontinuities. It is also a function of the properties of the liquid as well as of the porous medium. The degree of soil compaction or in-situ density has a significant impact on soil permeability and infiltration. Based on our experience and other studies we performed, an increase in compaction results in a decrease in soil permeability. We performed 8 Aardvark Permeameter tests at locations shown on the attached Site Plan, Figure 2. The test borings were 5 inches in diameter. The results of the tests provide parameters regarding the saturated hydraulic conductivity and infiltration characteristics of on-site soil and geologic units. Project No. G2066-11-01 - B-2 - January 12, 2017 Table B-IV presents the results of the estimated field saturated hydraulic conductivity and estimated infiltration rates obtained from the Aardvark Permeameter tests. The field sheets are also attached herein. We used a factor of safety applied to the test results on the worksheet values. The designer of storm water devices should apply an appropriate factor of safety. Soil infiltration rates from in-situ tests can vary significantly from one location to another due to the heterogeneous characteristics inherent to most soil. Based on a discussion in the County of Riverside Design Handbook for Low Impact Development Best Management Practices, the infiltration rate should be considered equal to the saturated hydraulic conductivity rate. - TABLE B-IV FIELD PERMEAMETER INFILTRATION TEST RESULTS Test No. Geologic Unit Test Depth (feet, below grade) Field-Saturated Hydraulic Conductivity, ksat (inch/hour) P-1 Fill 4.9 0.021 P-2 Santiago Formation 3.0 0.059 P-3 Fill .. 4.0 0.030 P-4 Santiago Formation 1.7 1.018 P-5 Santiago Formation 3.5 0.215 P-6 Santiago Formation 4.0 0.006 P-7 Santiago Formation 5.0 0.003 P-8 Santiago Formation 3.8 . 0.057 STORM WATER MANAGEMENT CONCLUSIONS The Site Plan, Figure 2, depicts the existing property and the locations of the field excavations and the in-situ infiltration test locations. Soil Types Previously Compacted Fill - Previously compacted fill exists on and adjacent to the subject property to depths of up to about 5 feet on the site and likely thicker near the entrance at Newton Drive. The previously placed fill is comprised of silty to clayey sands and sandy clays. The compacted fill supports existing parking lot, utilities and the existing building structure and was not designed to incorporate infiltration. Hazards that occur in the saturation of fill soil include a potential for hydroconsolidation, long term fill settlement, lateral movement associated with saturated fill relaxation. These hazards are not easily evaluated without performing significant testing, modeling and evaluation with specific computer software. Full and partial infiltration within the fill should not be considered based on the measured rates and because the fill supports existing improvements and infrastructure. Project No. G2066-11-01 - B-3 - January 12, 2017 Santiago Formation - We expect Santiago Formation materials will be located below the existing fill soils. The formational materials typically consist of hard to very dense sandstones and siltstones that are locally slightly cemented. Full infiltration into the Santiago Formation is considered infeasible due to the very dense and hard nature of the unit and the cementation of the sandstones and siltstones and the observed infiltration rates. Proposed Compacted Fill - Some new compacted fills will be placed on the property during site improvements. The compacted fill will be comprised of on-site materials. In addition, the fill will be compacted to a dry density of at least 90 percent of the laboratory maximum dry density. In our experience, compacted fill does not possess infiltration rates appropriate with infiltration. Compacted fill will possess swelling (expansion) potential and will support planned improvements. Therefore, full and partial infiltration should be considered infeasible. Infiltration Rates We performed 8 Aardvark Permeameter tests at depths ranging from approximately 1.7 to 5 feet within previously placed fill and Santiago Formation. The test results indicate the approximate infiltration rates range from less than 0.01 to 1.018 inches per hour (0.002 to 0.51 inches per hour with an applied factor of safety of 2). Full infiltration should be considered infeasible because a reliable rate of greater than 0.5 inches/hour is not present on the property. Groundwater Elevations We expect groundwater is greater than 100 feet below the existing grade. Therefore, infiltration associated with groundwater elevations would be considered feasible. New or Existing Utilities Utilities are present on the existing property boundaries and within the existing Newton Drive. Full or partial infiltration should not be allowed as utilities are conducive to migrating infiltration water and potentially causing off site damage to improvements. Mitigation measures to prevent water from infiltrating the utilities consist of setbacks, installing cutoff walls around the utilities and installing subdrains and/or installing liners. Existing and Planned Structures Existing structures exist to the east and south of the site. Water should not be allowed to infiltrate in areas where it could affect the existing and neighboring properties and existing and adjacent structures, improvements and roadways. Infiltration should be considered infeasible due to the lateral migration characteristics of the soil. Mitigation for existing structures consists of not allowing water infiltration within a 1:1 plane from existing foundations and extending the infiltration areas at least Project No. G2066- 1-01 - B-4 - January 12, 2017 I . 10 feet below the existing foundations and into formational materials. However, this is considered unreasonable due to the relatively large excavation depths that would be required. I Slopes and Other Geologic Hazards .I Descending graded 2:1 (horizontal to vertical) slopes exist along the,east of the site with heights of up to about 25 feet. In addition, an existing natural slope exists to the north and a vacant lot to the west. Water that, infiltrates the soil will affect the existing slopes to the north, east and west of the site. I Water migration and the resulting seepage forces can negatively affect the stability of slopes and cause daylight seepage, erosion and surficial slope instability. Due to the potential for lateral water migration within the, existing soil, full or partial infiltration should be considered infeasible. Storm Water Management Devices Liners and subdrains should be incorporated into the design and construction of the planned storm water devices. The liners should be impermeable (e.g. High-density polyethylene, HDPE, with a thickness of about 30 mil or equivalent Polyvinyl Chloride, PVC) to prevent water migration. The subdrains should be perforated within the liner area, installed at the base and above the liner, be at least 3 inches in diameter and consist of Schedule 40 PVC pipe. The subdrains outside of the liner should consist of solid pipe. The penetration of the liners at the subdrains should be properly waterproofed. The subdrains should be connected to a proper outlet. The' devices should also be installed in accordance with the manufacturer's recommendations. Storm Water Standard Worksheets The SWS requests the geotechnical engineer complete the Categorization of Infiltration Feasibility I Condition (Worksheet C.4-1 or 1-8) worksheet information to help evaluate the potential for infiltration on the property. The attached Worksheet C.4-1 presents the completed information for the u submittal process The regional storm Water standards also have a worksheet (Worksheet D.5-1 or Form 1-9) that helps the project civil engineer estimate the factor of safety based on several factors. Table B-V describes the suitability assessment input parameters related to the geotechnical engineering aspects for the factor of safety determination. ' . .. Project No. G2066-11-0 . - B-5- January 12, 2017 TABLE B-V SUITABILITY ASSESSMENT RELATED CONSIDERATIONS FOR INFILTRATION FACILITY SAFETY FACTORS Consideration High Medium Low Concern - 3 Points Concern - 2 Points Concern - 1 Point Use of soil survey maps or Use of well permeameter or simple texture analysis to borehole methods with Direct measurement with estimate short-term accompanying continuous boring log, localized (i.e. small- infiltration rates. Use of Direct measurement of scale) infiltration testing Assessment Methods well permeameter or infiltration area with methods at relatively high borehole methods without localized infiltration resolution or use of accompanying continuous measurement methods extensive test pit boring log. Relatively (e.g., Infiltrometer). infiltration measurement sparse testing with direct Moderate spatial methods. infiltration methods resolution Predominant Soil Silty and clayey soils Loamy soils Granular to slightly Texture with significant fines loamy soils Highly variable soils Soil boring/test pits Soil boring/test pits Site Soil Variability indicated from site assessment or unknown indicate moderately indicate relatively variability homogenous soils homogenous soils Depth to Groundwater! <5 feet below 5-15 feet below >15 feet below Impervious Layer facility bottom facility bottom facility bottom Based on our geotechnical investigation and the previous table, Table B-VT presents the estimated factor values for the evaluation of the factor of safety. This table only presents the suitability assessment safety factor (Part A) of the worksheet. The project civil engineer should evaluate the safety factor for design (Part B) and use the combined safety factor for the design infiltration rate. TABLE B-VI FACTOR OF SAFETY WORKSHEET DESIGN VALUES - PART A1 Suitability Assessment Factor Category Assigned (w) Factor Value (v) Product Weight (p = w x v) Assessment Methods 0.25 2 0.50 Predominant Soil Texture 0.25 3 0.75 Site Soil Variability 0.25 2 0.50 Depth to Groundwater! Impervious Layer 0.25 1 0.25 Suitability Assessment Safety Factor, SA = p 2.00 The project civil engineer should complete Worksheet D.5-1 or Form 1-9 using the data on this table. Additional information is required to evaluate the design factor of safety. Project No. G2066-11-01 - B-6 - January 12, 2017 Part 1'- Full Infiltration FeaibiIity Screening Criteria , .7 - . -' . '. 'Wou1d mfiltrattn of the full design volume be feasible from a physical perspective without any undesirable oneuences that1caniot b easoably mrngted .. f; •.- . - - -- 1 .Criterja .--1 Y ' Screening Question -- . AYes .T_v; No ________• - .- --.--,eJ. • •.. '..--- -..m. .. ..-.. . Is the estimated reliable infiltration rate below proposed facility locations greater than 0.5 inches per hour? The response 1 to this Screening Question shall be based on a comprehensive . - X evaluation of the factors presented in Appendix C.2 and Appendix D. ) Provide basis: I We performed 8 Aardvark Permearneter tests at the site within the Santiago Formation and previously existing fill. The following presents the results of our field infiltration tests: P-i at 4.9 feet in fill: 0.021 inches/hour (0.011 inches per hour with FOS=2) P-2 at 3.0 feet in Santiago Formation 0.059 inches/hour (0.030 inches/hour with FOS=2) P-3at 4.0 feet in fill: 0.030 inches/hour (0.015 inches/hour with F0S2) P.4 at 1.7 feet in Santiago Formation: 1.018 inches/hour (0.51 inches per hour with F052) P-S at 3.5 feet in Santiago Formation: 0.215 inches/hour (0.108 inôhes/hour with FOS=2) P-6 at 4.0 feet in Santiago Formation: 0.006 inches/hour (0.003 inches/hour vith FOS=2) P-7 at 5.0 feet in Santiago Formation: 0.003 inches/hour (0.002 inches per hour with FOS=2) P-8 at 3.8 feet in Santiago Formation: 0.057 inches/hour (0.029 inches/hour with FOS=2) In addition, based on the USGS Soil Survey; the site consists of units that possess a Hydrologic Soil Group D classification with an estimated k 1 of 0.00 to 0.06 inches per hour. The measured rates are less than 0.5 inches per hour and full infiltration is not considered feasible. Summarize flndinjs of studies; provide reference to studies, calculations, maps, data sources, etc. Provide narrative discussion of study/data source applicability. ' . • - Can infiltration greater than 0.5 inches per hour be allowed without increasing risk of geotehnical hazards (slope stability, 2 groundwater mounding, utilities, or other factors) that cannot be mitigated to an acceptable level? TheT response to this Screening Question shall be based on a comprehensive evaluation of - the factors presented in Appendix C.2. Provide basis: . . . -. . We expect previously placed fill and Santiago Formation underlies the permeable pavement areas. These materials mainly possess lateral infiltration characteristics. Lateral water migration would cause instabilityto adjacent slopes; right of ways, and the utilities and fill underlying the right of ways. Water that exist the slope faces would cause daylight seepage, local slope instability and migration of soil: Water would migrate into the compacted fill associated with the right of way and could cause settlement and distress to roadway pavements. Therefore, full and partial infiltration should be considered infeasible. Summarize findings of studies; provide reference to studies, calculations, maps, data sources, etc. Provide narrative discussion of study/data source applicability. - W6&sheet ii ; . 1-4 j " Screemng Quesuon Yes ; No Can infiltration greater than 0.5 inches per hour be allowed without increasing risk of groundwater contamination (shallow water table, storm water pollutants or other factors) that cannot x be mitigated to an acceptable level? The response to this Screening Question shall be based on a comprehensive evaluation of the factors presented in Appendix C.3. . Provide basis: - - - We expect groundwater is at least 100 feet from the'existing elevations. Summarize findings of studies; provide reference to studies, calculations, maps, data sources, etc. Provide narrative discussion of study/data source applicability. * Can infiltration greater than 0.5 inches per hour be allowed without causing potential water balance issues such as change of seasonality of ephemeral streams or increased discharge of contaminated groundwater to surface waters? The response to this Screening Question shall be based on a comprehensive evaluation of the factors presented in Appendix C.3. - Provide basis: - - - We do not expect infiltration will cause water balance issues such as seasbnality of ephemeral streams or increased discharge of contaminated groundwater to surface waters. - Summarize findings of studies; provide reference to studies, calculations, maps, data sources, etc. Provide narrative discussion of study/data source applicability. - If all answers to rows I - 4 are "Yes"a full infiltration design is potentially feasible. Part 1 - The feasibility screening category is Full Infiltration No Full Result* . If any answer from row 1-4 is "No", infiltration may be possible to some extentbut Infiltration would not generally be feasible or desirable to achieve a "full infiltration" design. Proceed to Part 2 *To be completed using gathered site information and best professional judgment considering the definition of MEP in the MS4 Permit. Additional testing and/or studies may be7 required by the City to substantiate findings. Part 2P lInfilt idivs' NoIñfiltraiid'nFeasibility ScéningCrit a.Tr df'er ir anyap ciabltiniit b hyi.115r feasibi vth'oist an rative . '1 _'n .i' consequences that cannot be reasonably mitigated ' .. ..i - 4 " 4 Criteria ..., Question r t Yes 4Screening -p,..; • . No ,. Do soil and geologic conditions allow for infiltration in any appreciable rate or volume? The response to this Screening X - 5 Question shall be based on a comprehensive evaluation of the factors presented in Appendix C.2 and Appendix D. Provide basis: We performed 8 Aardvark Permeameter tests at the site within the Santiago Formation and previously existing fill. The following presents the results of our field infiltration tests: P-i at 4.9 feet in fill: 0.021 inches/hour (0.0 11 inches per hour with FOS=2) P-2 at 3.0 feet in Santiago Formation: 0.059 inches/hour (0.030 inches/hour with FOS=2) P-3 at 4.0 feet in fill: 0.030 inches/hour (0.015 inches/hour with FOS=2) P-4 at 1.7 feet in Santiago Formation: 1.018 inches/hour (0.51 inches per hour with FOS=2) P-5 at 3.5 feet in Santiago Formation: 0.215 inches/hour (0.108 inches/hour with FOS=2) P-6 at 4.0 feet in Santiago Formation: 0.006 inches/hour (0.003 inches/hour with FOS=2) P-7 at 5.0 feet in Santiago Formation: 0.003 inches/hour (0.002 inches per hour with F0S2) P-8 at 3.8 feet in Santiago Formation: 0.057 inches/hour (0.029 inches/hour with FOS=2) Summarize findings of studies; provide reference to studied, caléulatións, maps, data sources, etc. Provide narrative discussion of study/data source applicability and why it was not feasible to mitigate low infiltration rates., Can Infiltration in any appreciable quantity be allowed without increasing risk of geotechnical hazards (slope 6 stability, groundwater mounding, utilities, or other factors) that cannot be mitigated to an acceptable level? The response to this Screening Question shall be based on a comprehensive evaluation of the factors presented in Appendix C.2. . - Provide basis: We expect previously placed fill and Santiago Formation will underlie the proposed permeable pavement'areas. These materials mainly, possess lateral infiltration characteristics. Lateral water migration would cause instability to adjacent slopes, right of ways, and the utilities and fill underlying the right of ways. .Water that exist the slope faces would cause daylight seepage, local slope instability and migration of soiL Water would migrate into the compacted fill associated with the right of way and could cause settlement and distress to roadway pavémeins. Therefore, full and partial infiltration should be considered infeasible. Summarize findings of studies provide reference to studies calculations maps data sources etc Provide narrative discussion of study/data source applicability and why it was not feasible to mitigate low infiltration rates. I Criteria 'j" creenmgQuestion4 . - Yes ,A - ' No Can Infiltration in any appreciable quantity be allowed without posing significant risk for groundwater related concerns (shallow water table, storm water pollutants or other factors)? The response to this Screening Question shall be based on a comprehensive evaluation of the factors presented in Appendix C.3. Provide basis: - We expect groundwater is at least 100 feet from the existing elevations. Summarize findings of studies; provide reference to studies, calculations, maps, data sources, etc. Provide narrative discussion of study/data source applicability and why it was not feasible to mitigate low infiltration rates. Can infiltration be allowed without violating downstream - - 8 water rights? The response to this Screening Question shall be based on a comprehensive evaluation of the factors presented in Appendix C.3. Provide basis: - - We did not provide a study regarding water rights. However, these rights are not typical in the San Diego County area. Summarize findings of studies; provide reference to studies, calculations, maps, data sources, etc. Pro'ride 'narrative discussion of study/data source applicability and why it was not feasible to mitigate low infiltration rates. If all answers from row 1-4 are yes then partial infiltration design is potentially feasible. The feasibility screening categcfry is Partial Infiltration. Part 2 es t* Result* . No Infiltration i If any answer from row 5-8 s no; in filtration nfiltration of any volume is considered to be - infeasible within the drainage area. The feasibility screening category is No Infiltration. *To be completed using gathered site informationand best professional judgment considering the definition of MEP in the MS4 Permit. Additional testing and/or studies may be required by the City to substantiate findings. GEOCON Aardvark Permeameter Data Analysis -. Project Name: rTijsh7,'.. Date: Fi11/29/20161 Project Number: I " iG2066-11-01-.j By:.. Borehole Location: U4 ,. . P-f Ref. EL (feet, MSL): 1T 2640'ri - Bottom EL (feet, MSL): 259.1 Borehole Diameter (inches): ..4.00 Borehole Depth, H (inhes): 5900 -' Wetted Area, A (in2):I Distance Between Reservoir & Top of Borehole (inches): ;.t- . 27.50.'%..'-' Depth to Water Table, s (feet): .100 Height APM Raised from Bottom (inches): Distance Between Resevoir and APM, 0 (inches): Head Height Calculated, h (inches): Head Height Recorded, In (inches): Distance Between Constant Head and Water Table, I (inches) 6,27. 775 8.00 ... .. 1149 Reading Time (mm) Time Elapsed (mm) Reservoir Water Weight (g) Resevoir Water Weight (Ibs) a Interval Water Consumption (Ibs) Total Water - Consumption (Ibs) *Water Consumption Rate (in 3/ min) 1 200 --i19.200 - n ' .6.00, 4.00 '.. 19.155 r! . 0.045;- . 0.045 0.312 - - C 10.0011, 400 i' ..19130 ... 0.025 0.070 0.173 4 51400 1 400 v-'- " 19110 0.020 0.090 0.139 - - 18.00V 400 ...-.. ' 19.090 0.020 0.110 0.139 _6_ . 22.00'..: . 4.00 ... . -.19.075 :. 0.015 0.125 0.104 - - ._..'- 26.00, ,'• - 4.00 ...'SL .- 19.060' '0.015 0.140 . ... 0.104 -. . 30.00 4.00 . 19.045:' 0.015 . . 0.155 - 0.104 - .. . 34.O0'-' 4.00 . . ' "19.030 ' .0.015 . 0.170 - 0.104 10 ,.- 12 17 k 13 3 14 15 - . •"; - . ; '-.._ - 16 ' . -- 17 18 19 .... _1,_• - ,tl L. .20 21 23 1 .-:, •i --' . . - - . ., ____________ 24 25 . .. - 26 L.-. .. 27 -, 28 Steady Flow Raté,Q (in 3/min): 0.104 1.00 C 0 I 0.75 0.50 I ::: 0.00 0 10 •20 Time (mm) Field-Saturated Hydraulic Conductivity (Infiltration Rate) Case l:L/h.>3 K= .3.55E-04 30 " .40 0.021 ]in/hr 10 20 30 40 50 60 Time (mm) GEOCON Aardvark Permeameter Data Analysis Project Date: 1/29/2016 Project Number: - G206641-01 ,- .j By: ;': IR '1 Borehole Location: r'-T' Ref. EL (feet, MSL): rToT Bottom EL (feet, MSL): 270.0 Borehole Diameter (inches): 4.00 Borehole Depth, H (inches): :____36.00 Wetted Area, A (in 2):I 71.53 I Distance Between Reservoir & Top of Borehole (inches): '- . 30.00 Depth to Water Table, s (feet): ioo Height APM Raised from Bottom (inches): . ioo Distance Between Resevoir and APM, D (inches): Head Height Calculated, h (inches): Head Height Recorded, h (inches):' Distance Between Constant Head and Water Table, 1 (inches): 4.81 4.69 6.00 1169 Reading Time (mm) Time Elapsed (mm) Reservoir Water Weight (g) Resevoir Water Weight (lbs) Interval Water Consumption (lbs) Total Water Consumption (lbs) *Water Consumption Rate (in 3/M in) 1 0.00 ' . J962. 2 5.00. 5.00 3 3' 7950 . .' .• 3'.. 0.026 0.026 0.147 3 . 10.00 -1 5.00 ". .1 7932 ..:"' 0.040 0.066 0.220 4 15.00 5.00 37914. . .. 0.040 0.106 0.220 5 '20.00 5.00 *' 7890 .3 . I . 0.053 0.159 0.293 6 25.00 5.00 7878 " . 0.026 0.185 0.147 7 30.00 5.00 . - 7860-'3.. 0.040 0.225 0.220 8 3 35.00 . 5.00 . 7842 S ...: - i 0.040 0.265 0.220 9 .. 40.00. 5.00 .37826 .. 0.035 0.300 0.196 10 45.00 ... 5.00 .. 78141 . I. . 0.026 0.326 0.147 11 50.00. . 5.00 .-. ,..-.7802 . ' 0.026 0.353 0.147 12 ' I .. . - ,• 13 14 16 17 ..' - _______ .1_•_, _________ __________ __________ __________ 18 19 .- . . . .- ________________ ___________________ ___________________ 20 . 21 . .. -' - :-' 22 23 24 -,.' .- 1. ' . ,-' 1 I' _________________ _________________ __________________ 25 26 27 28 ... Steady Flow Rate, Q (in 3/rnin): 0.147 Field-Saturated Hydraulic Conductivity (Infiltration Rate) Case 1: L/h >3 Ks t = 9.84E-04 Jin/min 0.059 uin/hr 1.0 C o 0.8 .1-• 0. • 0. 0.2 '5. - is 0.0 0 10 20 30 40 50 Time (mm) GE.IO.,O1 Aardvark Permeameter Data Analysis Project Name: 1. , Thishe7r'T I Project Number: 1, G2066-11-01 ;; By:) I Borehole Location:[ 'p3•7, Ref. EL (feet, MSL):[77263.0 r Bottom EL (feet, MSL): 259.0 Borehole Diameter (inches): 400 . Borehole Depth, H (inches): V 48.00 Wetted Area, A (in2):I. 84.52 I Distance Between Reservoir & Top of Borehole (inches): '. 29.00 .' Depth to Water Table, s (feet): - 100 Height APM Raised from Bottom (inches): "2.00 - Distance Between Resevoir and APM, D (inches): Head Height Calculated, h (inches): Head Height Recorded, h (inches): Distance Between Constant Head and Water Table, L(inches): - 5.65 5.73 i-' 6.00" . 1158 Reading - . Time (mm) Time Elapsed (mm) Reservoir Water . Weight (g) Resevoir Water - Weight (Ibs) . Interval Water Consumption (Ibs) Total Water Consumption (Ibs) *Water Consumption Rate (in 1mm) 1 .-0.00 4478-.. L . ' 2 '500 t' 500 '- 4460 0.040 0.040 0.220 3. ....- io.00: 5.00 . '-4448 1 ... 0.026 0.066 0.147 4 . .15.00' . 5.00 4434 i.'. 0.031 0.097 0.171 5 '..20.00-. 5.00 4426 ?' , - . 0.018 0.115 0.098 6 -' 25.00 , 5.00 '4420'A''.'-.. 0.013 0.128 0.073, 7 3000" 5.00 .. .4410 ..' - 0.022 0.150 . 0.122 8 5.00 44MEe,,.'-e 0.018 0.168 0.098 9 40.00 . 5.00 ' 439.4 'i 'F : 0.018 0.185 0.098 10 ' __________ • ______________ ., . - ii . .- ' . '. . -. -- ,----, - .• . - - 12 13 14 _________ -'_''.'.. ..•.. ,,' _____________ _____________ 15. 16 .7 . _________ 1.7. • 17 18 19 - 47,77 22 ______ ______ ''' • _______ 23 24 -:. 25 . :7 14, 26 -. 27 . . . 28 Steady Flow Rate, Q (in3/min): 0.098 Field-Saturated Hydraulic Conductivity (Infiltration Rite) .Case l:L/h>3' K5 = 5.05E-04i in/min . 0.030 .uin/hr - 10 20 30 40 Time (mm) C~ - 1) GE.00ON Aardvark Permeameter Data Analysis - Project Name: Date: fi1/29/2016T Project Number:., G2066-1101 - By: - 'KH Borehole Location: Ref. Ref. EL (feet, MSL):j -7269.0 T.} Bottom EL (feet, MSL): 267.3 Borehole Diameter (inches): 40O • Borehole Depth, H (inches): 20.50: Wetted Area, A (in2):I 108.40 1 Distance Between Reservoir & Top of Borehole (inches): ç --28.50 ' . I Depth to Water Table, s (feet): ioo Height APM Raised from Bottom (inches): .4.00 Distance Between Resevoir and APM, D (inches): Head Height Calculated, h (inches): Head Height Recorded, h (inches)... Distance Between Constant Head and Water Table, 1 (inches): 3.15 7.63 - 7.50 - 1187 Reading Time (mm) Time Elapsed (mm) Reservoir Water Weight (g) Resevoir Water Weight (Ibs) Interval Water Consumpt.ion (Ibs) Total Water Consumption (Ibs) *Water Consumption Rate (in 1mm) - 2.00 - -. -. 20.125- _2 - 6.00 . 4.00 -. . . 19.335-: . 0.790 0.790 5.474 3 - - 10.00... 4.00 .-.. . .18.550 • 0.785 1.575 5.440 4 - ... 14.00 - 4.00 .- 17.790 . 0.760 2.335 5.267 5 - 19.00 - 5.00 16.870 0.920 3.255 5.100 6 - 22.00 . 3.00 - 16.335 0.535 3.790 4.943 7 - ..25.00 - '- 3.00 I •S. 5. .45.795 . 0.540 4.330 4.989 _8 - .27.00 . - 2.00 ... .. 15.435 0.360 4.690 4.989 9 29.00; . 2.00 1 .. 15.085 - 0.350 5.040 4.851 10 . 30.00. -t 1.00 . . .. 14.905- . 0.180 5.220 4.989 11 -'p31.00 1.00 14.735 . . 0.170 5.390 4.712 12 . .32.00 1.00 . • - - - 14.555"- 0.180 5.570 4.989 13 -. 33.00., 1.00 .. 1. -' .14.365 0.190 5.760 5.267 14 . .' .34.00 1.00 .. 77 - 14:205 '. 0.160 5.920 4.435 15 '235.00.: 1.00 . '14.030 . 0.175 6.095 4.851 16 36.00 . 1.00 .-' -. - 13.855 .. 0.175 6.270 4.851 17 . 37.00Th 1.00 .- - . . - - 13.680 . 0.175 6.445 4.851 18 19 20 21 -.- -: .-. . . '.-,-, S - • 22 .; ; 23 _,.. --.- .::- __________________ S 24 WA.... 25 - -: ___________ . !..- -I• -, - 26 27 28 ______ -..•--.'--, - Steady Flow Rate, Q (in3/min): 4.851 Field-Saturated Hydraulic Conductivity (Infiltration Rate) Case 1: LJh >3 K,.t = 1.70E-02 uin/min 1.018 tin/hr :GEOCON Aardvark Permeameter Data Analysis . Project Name: 'Thirmb Date:fjTj7öiZ1 -. Project Number:I By: AR 1 Borehole Location: P-5.>', ' Ref. EL (feet, MSL): .".. 271.O .Bottom EL (feet, MSL): 267.5 Borehole Diameter (inches): -' 4.00!., Borehole Depth, H (inches):I. '42.00'. Wetted Area, A (in 2):1 109.36 I Distance Between Reservoir & Top of Borehole (inches):I -'--.36.00.--- Depth to Water Table, s (feet): [_': 100 - Height APM Raised from Bottom (inchs):I -z 4.00 Distance Between Resevoir and APM, 0 (inches): Head Height Calculated, h (inches): Head Height Recorded, h(inches): Distance Between Constant Head and Water Table, 1 (inches): 5.06 7.70 850' 1166 Reading Time (mm) Time Elapsed (mm) Reservoir Water 't . Weigh (g) - Resevoir Water Weight (Ibs) . . Interval Water Consumption (lbs) Total Water ' Consumption (Ibs) - *Water Consumption Rate (in 3/M in) 1 -. ''O.00'' T.6394'.. -,: '. ___________ ___________ 2 - .5.00. :. 5.00 .-... ..'.6zo8: -. '....., 0.410 .0.410 2.273 3 - 10.00... 5.00 . ..6076 ''i '''•.- 0.291 0.701 1.613 4. ''.15.00 5.00 ..5962:-- .. ..- 0.251 . . 0.952 . 1.393 5 - 20.00 5.00 0.225 1.177 1 247 .6 t21;00"ct 1.00 5840 0.044. .. 1.221' . i1.222 7 -. , 22.00 N..t . 1.00 . ___5822,z - ..' ' 0.040 1.261 1.100 8 - , 23.00' P 1.00 .- ' 5802.- Z. :.-- 0.044 1.305 1.222 9 2400 100 - ,5782 0.044 1.349 1.222 10 .25.00.-:H 1.00 .. L5764 - . 0.040 .1.389 1.100 11 26.00. 1.00 , .5744 .'H'- ._'1-., '0.044 ' 1.433 1.222 12 ,;..27.00 1.00 -..--i5724 ,.' '--'t- . 0.044 . 1477 1.222 13 'i28O0' f . 1.00 -.-, '.5708:., . . 0.035 . . 1.512 0.978 14 2900 100 '... 5690 ' s..- . 0.040 1.552 1.100 15 A0.00- 1.00 '.-.5672 .' -" . 0.040 1.592 1.100 16 .-'..32.06 2.00 .'-,. 0.075 ' 1.667 - 1.039 17 - . 34.00. 2.00 .-5602 . • .. . - 0.079 1.746 . " 1.100 18 ' -36.0V 2.00 . 5568'A'-' "i. .'.' 0.075 1.821 . 1.039 19 - '40.00-'- 4.00 . - 5500:-'- 0.150'- 1.971 1.039 20 . . 42.O6 . 2.00 5468' . 0.071 ' 2.041..- 0.978 21 -44.00-.. 2.00 -,5434:.,'."- :'y - '0.075 ' 2.116 . .1.039 22 :b. 23 ''..Ti'' - . -.-' ,1..J'•, i'': . -' - 24 25 ' frf ' _________ . . -• ____________ 26 27 28 - . Steady Flow' Rate, Q (in 3/min): 1.039 10.0 8. CL EE 6.0 - 2' .4., o 2. I. - - 0.0 0 10 . 20 1 30 Time (mm) Field-Saturated Hydraulic Conductivity (Infiltration Rate) Case 1: L/h >3 = - 3.58E-03 In/mm 40 50 0.215 uin/hr C .2 0.4 E 0.3 —S In In CC o. 0.2 0.1 0.0 0 10 20 30 40 50 Time (mm) - GEOCON Aardvark Permeameter Data Analysis Project Name [thj'rmo Fish.777 'r Date:111/29/2016 J Project Number: • ..G2066-11-01 By:; Borehole Ref. EL (feet, MSL):f 265.0....1 Bottom EL (feet, MSL) 261.0 Borehole Diameter (inches): .4.00.:' .' Borehole Depth, H (inches): .. Y48.00 Wetted Area, A (in 2): 78.30 I Distance Between Reservoir & Top of Borehole (inches): 30.00 Depth to Water Table, s (feet): v 100 Height APM Raised from Bottom (inches): 1,.50- Distance Between Resevoir and APM, D (inches): Head Height Calculated, h (inches): Head Height Recorded, h (inches): Distance Between Constant Head and Water Table, 1 (inches): 5.77 5.23 .. 5.00 1157 Reading Time (mm) Time Elapsed (mm) Reservoir Water Weight (g) Resevoir Water Weight (Ibs) Interval Water Consumption (Ibs) Total Water Consumption (Ibs) *Water Consumption Rate (in 1mm) 1 .0.00 . s-8434 2 .5.00 . 5.00 -. . 8416..' .. , .- :. 0.040 0.040 0.220 3 .10.00.i 5.00 ........8414 .JL :'. 0.004 0.044 0.024 4 15.00. 5.00 8414 . . , 0.000 0.044 0.000 S ..20.00 5.00 .8414' 0.000 0.044 0.000 6 '25.00 5.00 8412 0.004 0.049 0.024 7 kAo.00 15.00 - 8408.. 0.009 0.057 0.016 _9_ 10 12 :.- .'' .. -•- .. 13 14 - - --... -. . 15 ..•..,-.. .-., 16 ... .. •' .. _____________ -. .. .-, - ___________________ 17 18 '--' -'_... - .- .- .- • * - 19 ..- ____________ .. •.. .., _________________ __________________ __________________ 20 7 21 22 23 . .'.z.:;:-- : T , .-' 24 25 26 l';." xl . - 27 28 ..- ,. Steady Flow Rate, 0 (in 3/min): 0.016 Field-Saturated Hydraulic Conductivity (Infiltration Rate) Case 1: L/h >3 = in/min 0.006 In/hr 30 10.0 C .9 ._. 8.0 0. E 6.0 4.0 'S.. CC o ' 2.0 0.0 0 10 • 20 Aardvark Permeameter Data Analysis Project Date: U11/29/2616s.zl Project Number: G2066-1101 4 By: Borehole Location:f" Ref.'EL (feet, MSL):r.268.0. Bottom EL (feet, MSL): 263.0 - . Borehole Diameter (inches): . " 4.00 v.-. _____________________ Borehole Depth, H (inches): .60.00- Wetted Area, A (1n2):I 110.09 Distance Between Reservoir & Top of Borehole (inches) 29.50 Depth to Water Table, s (feet): 777750 Height APM Raised from Bottom (inches): 4.00 Distance Between Resevoir and APM, D (inches): Head Height Calculated, h (inches): Head Height Recorded, h (inches): Distance Between Constant Head and Water Table, 1 (inches): 6.52 7.76 77 7.50 1148 • ,Reading Time (mm) Time Elapsed (mm) Reservoir Water Weight (g) - - Resevoir Water Weight (Ibs) . -. Interval Water Consumption (Ibs) Total Water . Consumption (Ibs) *Water Consumption Rate (in 1mm) 20.29.5 •. ______________ ______________ ______________ - 2.00 ' 0.025 ' 0.025 0.346 3 .-7•0Q 2.00 T, - 20.260. 0.010 D.035 0.139 4 1100 400 .. 20185 0.075 0.110 0.520 - - 21.O0 10.00 '. .' 20:180 0.005 0.115 0.014 - __•j 10. - 4 - - 12 - .t 13 . 14 -. .". .. •• .' 't - .j .15 _________ -- j-Ji•,, _4__• , . 16 - t 17 ;- ____________ ___________ ______________ ..:-,- •:.. . - 18 - 19 20 _________ ------_.- - •- - -. 21 22 23 - . --- 24 -':' 25 ._-•.t ______ _________ - -.. 26 ~ _______ -: _________ ___________ ___________ ___________ 28 .:• .•. Steady Flow Rate, 0 (in 3/min): 0.014 Time (mm) Field-Saturated Hydraulic Conductivity (Infiltration Rate) _______ Case 1: L/h ->3 = 4.73E-05 un/mm 0.003 un/hr 5.0 - C 4.0 E- E 3.0 I,, CC 2.0 1.0 0.0 0 10 20 30 40 Time (mm) (4) GEOCON Aardvark Permeameter Data Analysis Project Name:f Thermo Fisher T Date:1 ,;.11/T2j Project Number: G206641-01' .1 By: KH. Borehole iocation:f 78. Ref. EL (feet, MSL):F TTh.o T1 Bottom EL (feet, MSL): 265.3 Borehole Diameter (inches): - 4.00 -- Borehole Depth, H (inches): 45.00 Wetted Area, A (in 2):I 109.40 1 Distance Between Reservoir & Top of Borehole (inches): - 28.00 Depth to Water Table, s (feet): .100 Height APM Raised from Bottom (inches): 4.00 Distance Between Resevoir and APM, D (inches): Head Height Calculated, h (inches): Head Height Recorded, h (inches): Distance Between Constant Head and Water Table, L (inches): 5.15 7.71 -. 9.00 1163 Reading Time (mm) Time Elapsed (mm) Reservoir Water Weight (g) Resevoir Water Weight (Ibs) Interval Water Consumption (Ibs) Total Water Consumption (Ibs) *Water Consumption Rate (in 3/min) 1 2.00 - - 20.590 2 .' 4.00 2.00 - :' 20.485' ' 0.105 0.105 1.455 3 .6.00 2.00 . . . 20.415: . 0.070 0.175 0.970 4 . ' 10.00 4.00 20.305 . 0.110 0.285 0.762 S - - ' 14.00 4.00 . - - 20.280: 0.025 0.310 0.173 6 18.00-. 4.00 . 20.280 . 0.000 0.310 0.000 7 . .:22.00 4.00 - 20.280: 0.000 0.310 0.000 8 '26.00- 4.00 .:. -; .., -..... 20.240 - 0.040 0.350 0.277 9 . .30.00 4.00 . ' - 20.200 0.040 0.390 0.277 10 :32.00 . 2.00 . ___. !.-20.180 0.020 0.410 0.277 12 13 14 15 16 17 18 19 20 21 : _•.-: ____________ --,;.- ,.,r.. __ 22 23 24 25 26 27 .-..1.____. ' _.. _. -.-•'.c 28 Steady Flow Rate, 0 (in'/min): 0.277 Field-Saturated Hydraulic Conductivity _(infiltration Rate ) Case 1: L/h >3 = -o un/mn 0.057uin/hr LIST OF REFERENCES 2016 California Building Code, California Code of Regulations, Title 24, Part 2, based on the 2015 International Building Code, prepared by California Building Standards Commission, dated July, 2016. A CI 318-11, Building Code Requirements for Structural Concrete and Commentary, prepared by the American Concrete Institute, dated August, 2011. A CI 330-08, Guide for the Design and Construction of Concrete Parking Lots, prepared by the American Concrete Institute, dated June, 2008. 4., Anderson, J. G., T. K. Rockwell, and D. C. Agnew, Past and Possible Future Earthquakes of Significance to the San Diego Region: Earthquake Spectra, 1989, v. 5, no. 2, p. 299-333. ASCE 7-10, Minimum Design Loads for Buildings and Other Structures, Second Printing, April 6, 2011. Boore, D. M., and G. M Atkinson, Ground Motion Prediction Equations for the Average Horizontal Component of PGA, PVG, and 5%-Ramped PSA at Spectral Periods between 0.01s and 10.0s, Earthquake Spectra, Vol. 24, Issue I, February 2008. California Emergency Management Agency (CEMA), Tsunami Inundation Map For Emergency Planning, Point Loma Quadrangle, dated June 1, 2009. California Geological Survey, Seismic Shaking Hazards in California, Based on the USGS/CGS Probabilistic Seismic Hazards Assessment (PSHA) Model, 2002 (revised April 2003). 10% probability of being exceeded in 50 years. http://redirect.conservation.ca.gov/cgs/rghmlpshamap/pshamain.html Campbell, K. W., and Y. Bozorgnia, NGA Ground Motion Model for the Geometric Mean Horizontal Component of PGA, PGV, PGD and 5% Damped Linear Elastic Response Spectra for Periods Ranging from 0.01 to 10 s, Preprint of version submitted for publication in the NGA Special Volume of Earthquake Spectra, Volume. 24, Issue 1, pages 139-171, February 2008. Chiou, Brian S. J., and Robert R. Young's, A NGA Model for the Average Horizontal Component of Peak Ground Motion and Response Spectra, preprint- for article to be pub1ished in NGA Special Edition of Earthquake Spectra, Spring 2008. I II.. Geosoils Incorporated, Preliminary Geotechnical Feasibility Evaluation Portion of 14-acre Parcel on Newton Drive, Carlsbad, San Diego County, California, dated April 15, 1997 (W.O. 2212-A-SC). I 12. Jennings, C. W., and Bryant, W. A., 2010, Fault Activity Map of California, California Geologic Survey, Geologic Data Map No. 6. I 13. Kennedy, M. P., and S. S. Tan, 2002, Geologic Map of the Oceanside 30'x60' Quadrangle, California, USGS Regional Map Series Map No. 2, Scale 1:100,000. I S. Project No. G2066-11-01 January 12, 2017 I 'LIST OF REFERENCES (Concluded) . . I 14. Legg, M. R., J. C. Borrero, and C. E. Synolakis (2002), Evaluation of Tsunami Risk to Southern California Coastal Cities, 2002 NEHRP Professional Fellowship Report, dated January. 1 15: Lindvall; 'S. C., T. K. Rockwell, and C. E. Lindvall, The Seismic. Hazard of San Diego Revised: New Evidence for Magnitude. 6+ Holocene Earthquakes on the Rose Canyon Fault Zone: Proceedings of the Fourth U.S. National Conference on Earthquake Engineering, 1990, I 11 .. . . 16. Risk Engineering, EZ-FRISK, Version 7.65, 2015. 1 17. Unpublished reports, stereo aerial photographs, and maps on file with Geocon Incorporated. I 18. United States Geologic Siiri'ey, US. Seismic Design Maps; . 19. URS, 2004, San Diego County Multi-Jurisdictional Hazard Mitigation Plan, San Diego I County, California, dated March 15, (TJRS Project No. 27653042.00500). 1 ' 1 H . i .. I : I. . . ,. . . .. . ,. . I .. 1 . . . Project No. G2066-11-01 . . . . . January 12, 2017