Leighton and Associates, Inc.
A LEIGHTON GROUP COMPANY
April 30, 2004
Project No. 971009-017
To: Lennar Communities
1525 Faraday Avenue, Suite 300
Carlsbad, California 92008
Attention: Ms. Kristine Zortman
Subject: Results of Laboratory Tests on Import Class 2 Aggregate Base Samples Placed on
April 22, 2004 for the Bressi Ranch Backbone Streets, a Portion of Town Garden
Road, Bressi Ranch, Carlsbad, California
References: Caltrans, 1992, Standard Specifications, July 1992
Carlsbad, City of, 1996, Standards for Design and Construction of Public Works
Improvements in the City of Carlsbad, California, Project No. 05332-12-01, dated
April 20, 1993, revised December 10, 1996
In accordance with the requirements of the City of Carlsbad, we have performed laboratory tests on
representative samples of the import Class 2 Aggregate Base (AB) material placed on April 22,
2004 as part of the pavement section for a portion of Town Garden Road within Bressi Ranch
located in Carlsbad, California. Four representative samples of the Class 2 AB were sampled and
transported to our laboratory. Laboratory tests performed on the representative samples included
sand equivalent (in accordance with ASTM Test Method D2419) and sieve analysis (in
accordance with ASTM Test Method C136). The results of the laboratory tests are presented on
Tables 1 through 3.
Based on the City of Carlsbad requirements and the Caltrans specifications (Section 26-1.02A) as
indicated on the tables, the representative Class 2 aggregate base samples generally met the city
requirements. However, the samples on Town Garden Road at Station No. 19+50 and 17+00
were slightly out of specification (i.e. all three were 1-percent over the maximum value) with
respect to the percent passing the No. 4 sieve for the sample at Station No. 19+50 and the No. 30
and No. 200 sieves for the sample at Station No. 17+00.
3934 Murphy Canyon Road, Suite B205 • San Diego, CA 92123-4425
858.292.8030 • Fax 858.292.0771 • www.leightongeo.com
971009-017
Table 1
Laboratory Test Results of Import Class 2 Aggregate Base Material
Town Garden Road Station No. 24+75
Sieve Analysis (in accordance with ASTM Test Method C136)
Operating Range Required
Sieve Size Percentage Passing* Sample Result In Conformance?
1 inch 100 100 Yes
3/4 inch 90-100 96 Yes
No. 4 35-60 44 Yes
No 30 10-30 20 Yes
No. 200 2-9 7 Yes
Sand Equivalent (in accordance with ASTM Test Method D2419)
Required Minimum* Sample Result In Conformance?
25 51 Yes
*per Caltrans Standard Specifications Section 26 and City of Carlsbad Standard Special
Provisions for Construction.
Table 2
Laboratory Test Results of Import Class 2 Aggregate Base Material
Town Garden Road Station No. 19+50
Sieve Analysis (in accordance with ASTM Test Method C136)
Operating Range Required
Sieve Size Percentage Passing* Sample Result In Conformance?
1 inch 100 100 Yes
3/4 inch 90-100 97 Yes
No.4 35-60 61 No
No. 30 10-30 30 Yes
No. 200 2-9 9 Yes
Sand Equivalent (in accordance with ASTM Test Method D2419)
Required Minimum* Sample Result In Conformance?
25 46 Yes
*per Caltrans Standard Specifications Section 26 and City of Carlsbad Standard Special Provisions
for Construction.
-2-
Leighton
971009-017
Table 3
Laboratory Test Results of Import Class 2 Aggregate Base Material
Town Garden Road Station No. 5+50
Sieve Analysis (in accordance with ASTM Test Method C136)
Operating Range Required
Sieve Size Percentage Passing* Sample Result In Conformance?
1 inch 100 100 Yes
3/4 inch 90-100 94 Yes
No. 4 3 5-60 40 Yes
No. 30 10-30 19 Yes
No. 200 2-9 7 1 Yes
Sand Equivalent (in accordance with ASTM Test Method D2419)
Required Minimum* Sample Result In Conformance?
25 49 Yes
*per Caltrans Standard Specifications Section 26 and City of Carlsbad Standard Special
Provisions for Construction.
Table 4
Laboratory Test Results of Import Class 2 Aggregate Base Material
Town Garden Road Station No. 17+00
Sieve Analysis (in accordance with ASTM Test Method C136)
Operating Range Required
Sieve Size Percentage Passing* Sample Result In Conformance?
1 inch 100 100 Yes
% inch 90-100 98 Yes
No. 4 3 5-60 60 Yes
N o.30 10-30 31 No
No. 200 2-9 10 No
Sand Equivalent (in accordance with ASTM Test Method D2419)
Required Minimum* Sample Result In Conformance?
25 33 Yes
*per Caltrans Standard Specifications Section 26 and City of Carlsbad Standard Special Provisions
for Construction.
-3-
Leighton
971009-017
If you have any questions regarding our letter, please contact this office. We appreciate this
opportunity to be of service.
Respectfully submitted,
LEIGHTON AND ASSOCIATES, INC.
40 Randall
Ck'r---
Randall K. Wagner, CEG
Senior Associate
Distribution: (2) Addressee
Lennar Communities, Attention: Mr. Jim Urbina
City of Carlsbad, Public Works Department, Attention: Mr. Casey Arndt
(1) J. T. Kruer, Attention: Mr. Chuck Knight
-4-