Loading...
HomeMy WebLinkAboutCT 01-01; CALAVERA HILLS VILLAGE; COMPACTION REPORT OF GEOTECHNICAL OBSERVATION AND TESTING SERVICES; 2005-03-15Geotechnical Geologic. Environmental 5741 Palmer Way • Carlsbad, California 92008 • (760) 438-3155 • FAX (760) 931-0915 March 15, 2005 W.O. 3459.L2-D/E-SC Calavera Hills II, LLC 2727 Hoover Avenue National City,, California 91,950 Attention: Mr. Don Mitchell Subject: Compaction Report of Geotechnical Observation and Testing Services, Offsite Improvements, Calavera Hills II, Village L2, Carlsbad Tract 01-01, City of Carlsbad, San Diego County, California Dear Mr. Mitchell This report presents a summary of the geotechnical engineering observation and testing services provided byGeoSoils, Inc. (GSI) during the observation and testing of water, joint trench and sewer trench backfill operations, subgrade/base for street pavements, curb/gutter and sidewalk, and asphaltic concrete for the subject site. This report covers only the geotechnical services provided by GSI from June 2004 through August 2004. TRENCH BACKFILL (PHASE D) Backfill operations were observed by GSI personnel on a part-time basis as solely requested and directed by the contractor/client. Select native onsite soils and import soils were used as backfill for the utility trenches and placed in general accordance with standards of practice and GSI (2002). The required compaction was achieved, by mechanical means. The minimum compaction required was 90 percent of the laboratory standard (ASTM D-1557). Our tests indicate that compaction to at least 90 percent of the laboratory standard (ASTM D-1557) has been achieved in the areas where testing was requested. Test results are presented in the Table 1 (Field Density Test Results), located at the rear of the text. SUBGRADE. AGGREGATE BASE, AND ASPHALTIC CONCRETE TESTING (PHASE E) Testing of curb/gutter and street subgrade and base, and sidewalk subgrade was also only performed on a part-time basis, as solely requested and directed by the contractor/client. Ourtests indicate that the compaction of the subgrade and aggregate base materials meet or exceed the minimum requirement of 95 percent relative compaction of the laboratory standard (ASTM D-1 557). Testing of asphaltic concrete pavement was also performed. Test results indicate that the asphalt appears to have been compacted to a minimum relative compaction of at least 95 percent of the Hveem maximum density (Cal Test 304). Test results are presented in the attached Table 1 (Field Density Test Results), located in the rear of the text. Representative samples of asphalt material were obtained during paving operations, and tested in order to verify that the asphalt meets, or exceeds, the minimum specifications per Section 203-6.4 of the "Green Book" (2003 edition) with respect to gradation and extraction testing (ASTM D-2172). Testing indicates that the asphalt meets, and/or exceeds, the minimum requirements in accordance with Section 203-6.4. Recommendations for pavement design and construction were provided in our pavement design report (GSl, 2003a). FIELD TESTING Field density tests were performed using the nuclear densometer ASTM D-2922 and ASTM D-3017. The test results are presented in the attached Table 1. Field density tests were taken at periodic intervals and random locations to check the compactive efforts provided by the contractor. Where test results indicated a less than the required minimum compaction, the contractor was notified and the area was reworked until the required minimum relative compaction was achieved for each respective area. Testing was provided solely on a part-time basis, as requested. Visual classification of the soil in the field was the basis for determining the maximum density value to use for a given density test. LABORATORY TESTING The laboratory maximum dry density and optimum moisture content for each of the major soil types was determined according to test method ASTM D-1 557. Corrected values for Calavera Hills II, LLC w.o 3459. L2. DIE-SC Calavera Hills II, Village L-2 March 15, 2005 File: e:\wp9\3400\3459.L2..de.cro Page 2 GeoSoils, Inc. the percentage of rock in a given sample were used in the determination of relative compaction. The following table presents the results: MAXIMUM DRY DENSITY:".`-,OPTIMUM MOISTURE SOIL TYPE (pcf) CONTENT (%) : C - Brown, Silty SAND 126.0 11.0 F - Brown, Sandy GRAVEL 126.5 10.0 (processed material) I - Dark Brown, Silty GRAVEL 134.0 8.5 (processed material) Aggregate Base 1 146.0 . 7.5 Aggregate Base 2 135.0 8.5. REGULATORY COMPLIANCE Placement of compacted backfllls, under the purview of this report, have been completed using the observation and selective testing services provided by representatives of GSl. Backfill operations were performed in general compliance with the requirements of the City. Our findings were made in conformance with generally accepted professional engineering practices, and no further warranty is implied or made. GSI assumes no responsibility or liability for work, testing, or recommendations performed or provided by others. This report is subject to review by the controlling authorities for this project. Calavera Hills II, LLC W.O. 3459.L2.D/E-SC Calavera Hills II, Village L-2 March 15, 2005 File: e:\wp9\3400\3459.L2..de.cro Page 3 GeoSoils, Inc. David Civil E We appreciate this opportunity to be of service. If you have any questions pertaining to this report, please contact us at (760) 438-3155. Respectfully submitted tIAL C\ GeoSoils, Inc. No. 1934 g Certified Engineering p Geologist Robert G. Crisman PC CM Engineering Geologist, CEG 1934 RGC/DWS/JPF/jk Attachments: Table 1 - Field Density Test Results Appendix - References Distribution: (4) Addressee Calavera Hills II, LLC W.O. 3459.L2.DIE-SC Calavera Hills II, Village L-2 March 15, 2005 File: e:\wp9\3400\3459.La.de.cro Page 4 GeoSoils, Inc. S.' S., r"' Ilage L-2 420.0 8.9. 123.3 92.0 ND - Ilage L-2 419.0 8.8 124.6 93.0 ND - Ilage L-2 418.0 8.9 126.0 94.0 ND Ilage L-2 413.0 8.1 '123.3 92.0 ND' Rage L-2 409.0 8.2 ' ' 124.6 93.0 ND Ilage L-2 422.0 8.0 122.0 91.0', ND Ilage L-2 420.0 8.2 123.3 92.0 ND 'I Ilage L-2 415.0 ' ' 8.1 . 123.3 92.0. ND , I Ilage L-2 408.0 8.3 122.0 91.0 ND .. 'I'. Ilage L-2 409.0 8.2 124.6 93.0 ND I 71190111 Ilage L-2 422.0 9.8 115.0 90.9 ND F Ilage L-2 414.0 10.3 115.1 91.0 ND . 'F iiage'L-2 410.0 .10.2 114.2 " 90.3 ND F ilage L-2 418.0 9.7 . 114.6 90.6 'ND F, Ilage L-2 409.0 10.7 116.9 92.4 ND' F ilage L-2 411.0 12.4 116.8 92.3 ND F iiage L-2 414.0 12.2 - 16.5 92.1 ND :'F' iiageL-2 416.0 12.6 116.1. 91.8 ND ' F iiage L-2 421.0 12.7 116.0. 91.7 ND _. .,F" iiageL-2 424.0 12.8 ' 116.5 92.1 -ND .F ilageL-2 414.0 12.4 116.3 91.9 ' ND. . F lage L-9 SG .10.2 121.2 95.8 ND F' iageL-2 SG 10.8' 121.7 , 96.2 ND 'F lage L-2 SG 9.9 120.6 95.3 ND' F [age L-2 SG .10.8 ' '121.3 95.9 . ND F' lage L-2 SG 11.1 123.1 97.3 ND.. F lage L-2 SG 10.9 120.3 95.1 ND 'F lage L-2 SG 10.0, 123.4 96.4 'ND ' F EIR J4t ft- 03 lage _-2 SG 10.8 121.0 95.6 ND , 'F [age L-2 SG 10.6 ' 121.4 96.0 ND ' F lage L-2 SG 110 1212 958 ND F lage L-2 SG ', 10.9 121.0 95.6 ' ND F lage L-2 SG ' ' 10.8 ' 121.2 95.8 ND , F [age L-2 øSG 12.2 123.4 '97.9 ,ND, ' lage L-2 SG , 11.9 ' 123.7' '98.2 ND C lage L-2 SG 12.8 122.1 96.9 ND C lage L-2 BG ' 7.2 143.8 98.5 ND Base1 lage L-2 BG 6.8 142.6 . 97.7 ,ND Base1 lage L-2 BG 7.0 143.4 98.2 ,ND . Base1 lage L-2 BG 6.3 .139.0 95.2' ND , Base1 lage L-2 BG 6.6 . 142.1 97.3 ND Basel [age L-2 BG; '6.2.' 143.2 98.1 ND , Basel "S 20 SM 6/18/03 Front of Lot5 V 21. SM 6/18/03 Front of Lot 6 . V 22 SM .6/18/03 Front of Lot V 23 SM 6/19/03 Front of Pad 9 ', V 24 SM 6/19/03 Front of Pad 11 Vi 25 SL 6/19/03 . Lot V 26 SL 6/19/03 Lot V 27 SL ' 6/20/03 ..' ' Lot 8'- V 28 SL 6/20/03 Lot 11 V 29 SL 6/20/03 Lot 12 Vi '1 WM 6/25/03 Granite Ct 5+05 V 2 WM 6/25/03 Granite Ct 3+50 V 3 WL 6/25/03 ' Lat Lot 10 V 4 WL 6/25/03 . Lat Lot 7 5 WM .7/2/03 Granite Ct +90 Vii JiNMI 1 JT 8/7/03 . Granite Ct 2+00 2 JT 8/7/03 Granite Ct 3+20 3 JT 8/7103 Granite Ct 4+70 V 4 JT 8/7/03 Granite Ct 5+40 . V 5 JT 8/7/03 Granite Ct 6+65 V 6 JT 8/7/03 Granite Ct 6+30 , Vii áW RAD'SE '1 CSG 8/11/03 Granite Ct 2+00 (North) VU 2 CSG 8/11/03 Granite Ct 3+50 (North) VU 3 CSG 8/11/03 Granite Ct 5+00 (North) VU 4 CSG 8/11/03 Granite Ct End of Cul de Sac VU 5 CSG 8/11/03 Granite Ct 4+50 (South) VU 6 CSG 8/11/03 Granite Ct 2+50 (South) VU 7' CSG 8/11/03 Granite Ct 1+30 (South) VU .1 SG 8/25/03 Granite Ct 1+50 VU 2'.' SG ' 8/25/03 Granite Ct 3+10 VU 3 SG 8/25/03 Granite Ct 4+50 ' Vii 4 SG 8/25/03 'End of Cul-De-Sac Vii 5 SG 8/25/03 End of Cul-De-Sac '. VU 44 SG 12/31/03 Cay Dr' VU 45 SG 12/31/03 ' Cay Dr. Vii 55 SG 1/12/04' Cay Dr Entrance B 8/12/03 'Granite Ct 1+25 (North) '-2 B 8/12/03 Granite Ct 2+50 (North) 3' B. '8/12/03 Granite Ct 4+00 (North)' '4 . B, 8/12/03 Granite Ct 5+50 (North) 5 B 8/12/03 Granite Ct 5+50 (South) 6 B 8/12/03 , Granite Ct 4+60 (South) Si • "r Calavera Hills II, LLC WO. 3459 L2 D/E SC Calavera Hills II Village L-2 • March 2005 File C \excei\tabies\3400\3459 L2 de cro GeoSoils, Inc. Page 1 Table 1 FIELD DENSITY TEST RESULTS TEST NO. UTILITVJ TYPE DATE TEST LOCATION TRACT NO. ELEV OR MOISTURE CONTENT DRY DENSITY REL COMP TEST METHOD SOIL TYPE 7 B 8/12/03 Granite Ct 3+00 (South) Village L-2 BG 6.9 139.3 95.4 ND Base 1 8 B 8/12/03 Granite Ct 2+00 (South) Village L-2 BG 6.9 138.8 95.1 ND Base 1 9 B 8/27/03 Granite Ct 1+50 Village L-2 BG 7.8 140.5 96.2 ND Base 1 10 B 8/27/03 Granite Ct 2+50 Village L-2 BG 7.4 140.7 96.4 ND Base 1 11 B 8/27/03 Granite Ct 4+00 Village L-2 BG 7.5 140.2 96.0 ND Base 1 12 B 8/27/03 Granite Ct 5+20 Village L-2 BG 7.3 140.0 95.8 ND Base 1 13 B 8/27/03 Granite Ct 5+20 (South) Village L-2 BG 7.6 140.3 96.1 ND Base 1 61 B 12/31/03 Cay Dr Entrance Village L-2 BG 8.1 129.1 95.6 ND Base 2 62 B 12/31/03 Cay Dr Entrance Village L-2 BG 7.9 129.9 96.2 ND Base 2 70 B 1/21/04 Cay Dr Entrance Village L-2 BG 8.9 129.0 95.5 ND Base 2 71 B 1/21/04 Cay Dr Entrance Village L-2 BG 4.0 130.5 96.6 ND Base 2 SJDAK1 V7. .. 1 SW 8/22/03 Lot 10 North Side Village L-2 SG 11.2 121.7 96.2 ND F 2 SW 8/22/03 Lot North Side Village L-2 SG 11.5 122.2 96.6 ND F 3 SW 8/22/03 Lot North Side Village L-2 SG 11.3 121.8 96.3 ND F SW 8/22/03 Lot 3 End Cul de Sac Village L-2 SG 11.7 121.2 95.8 ND F 5 SW 8/22/03 South Side 4+68 Village L-2 SG 11.9 121.0 95.6 ND F 6 SW 8/22/03 South Side 3+70 Village L-2 SG 11.7 121.7 96.2 ND F 7 SW 8/22/03 South Side 2+30 Village L-2 SG 11.8 121.2 95.8 ND F 1 AC 8/29/03 Granite Ct 1+35 Village L-2 1st Lift . 4.9 140.8 96.3 ND AC 2 AC 8/29/03 Granite Ct 2+80 Village L-2 1st Lift 7.2 139.5 95.4 ND AC 3 AC 8/29/03 Granite Ct 2+90 Village L-2 1st Lift 6.3 139.0 95.1 ND AC 4 AC 8/29/03 Granite Ct 3+60 Village L-2 1st Lift 4.2 139.9 95.7 ND AC 5 AC 8/29/03 Granite Ct 4+25 Village L-2 1st Lift 4.8 139.2 95.2 ND AC 6 AC 8/29/03 Granite Ct 5+20 (North) I Village L-2 1st Lift 5.1 141.2 96.6 ND AC 7 AC L.2./29/03 Granite Ct 5+40 (South) Village L-2 1st Lift 5.3 138.9 95.0 ND AC F AC 8 AC 8/29/03 Granite Ct 2+00 Village L-2 1st Lift 4.8 141.3 96.7 ND NOTE: Gaps in Test No. sequence are due to similar work performed in other areas of the site. LEGNED: AC = Asphlatic Concrete B = Base Grade BG = Base Grade CSG = Curb Subgrade ND = Nuclear Densometer SG = Subgrade SL = Sewer Lateral SM = Sewr Main SW = Sidewalk WL = Water Lateral WM = Water Main Calavera Hills II, LLC Calavera Hills II, Village L-2 File: C:\excel\tables\3400\3459.L2..de.cro GeoSosis, Inc. W.O. 3459.L2.DIE-SC March, 2005 Page 2 3' APPENDIX REFERENCES GeoSoils, Inc., 2003a, Pavement design report, Calavera Hills II, Village L-2 (Granite Court), Carlsbad Tract 01-02, City of Carlsbad, San Diego County, California, W.O. 3459-E-SC, dated June 30. 2003b, Report of rough grading, Calavera Hills, Village L-2, Lots 1 through 14, Carlsbad Tract 01-01, City of Carlsbad, San Diego County, California, W.O. 3459-B1-SC, dated June 24. 2003c, Memorandum, "General discussion of fill quality, Calavera Hills II, Carlsbad, California," W.O. 3459-132-SC, dated May 20. 2002, Review of grading and trench backfill recommendations, Calavera Hills II, Carlsbad Tract 00-02, Drawing 390-90, City of Carlsbad, San Diego County, California, W.O. 2863-A-SC, August 16. 1999, Update of geotechnical report, Calavera Hill, Village L-2, City of Carlsbad, California," W.O. 2748-A-SC, dated October 15. 1 998a, Lack of paleontological resources, Carlsbad Tract nos. 83-19, PUD 56, and 83-32, PUD 62, Carlsbad, San Diego County, California, W.O. 2393-B-SC, dated January 21. 1998b, Preliminary review of slope stability, Calavera Hills, Villages "Q" and "1", City of Carlsbad, California, W.O. 2393-B-SC, dated February 16. 1998c, Review of slope stability, Calavera Hills, Villages "Q" and "1," City of Carlsbad, California, W.O. 2393-B-SC, dated June 24. O'Day Consultants, 2002, Improvement plans for Calavera Hills Village L-2, Project No. C.T. -01-01, Drawing No. 403-6, dated October 17. GeoSoils, Inc.