HomeMy WebLinkAboutCT 02-14-04; BRESSI RANCH UNIT 4; GEOTECHNICAL RESPONSE RETAINING WALL; 2003-11-07Leighton and Associates, Inc.
A LEIGHTON GROUP COMPANY
To:
November 7, 2003
Lennar Communities
5780 Fleet Street, Suite 320
Carlsbad, California 92009-4700
RECEIVED Project No. 971009-014
NOV i 2 (,003
ENGINEERING
DEPARTMENT
Attention: Ms. Kristine Zortman
Subject: Geotechnical Response to the City of Carlsbad Review Comments Concerning
Retaining Wall Design Parameters and Site Drainage Recommendations,
Planning Areas PA-6 Through PA-12, Bressi Ranch, Carlsbad, California
References: Leighton and Associates, 1997, Preliminary Geotechnical Investigation, Bressi
Ranch, Carlsbad, California, Project No. 4971009-002, dated July 29, 1997
Introduction
----, 2001, Supplemental Geotechnical Investigation for Mass Grading,
Bressi Ranch, Carlsbad, California, Project No. 971009-005, dated March 14,
2001
In accordance with the request of Mr. David Uson of Project Design Consultants, this letter
presents our geotechnical response to the City of Carlsbad review comments concerning retaining
wall design parameters and site drainage recommendations for the residential developments (i.e.
Planning Areas PA-6 through PA-12) at the Bressi Ranch project located in Carlsbad, California.
We understand that the City of Carlsbad review comments included the need to address retaining
wall design parameters, site drainage recommendations and soil bearing values. Our responses to
the review comments are provided in the following sections. . ,
Retaining Wall Design Parameters
Retaining walls should be designed for the lateral earth pressures exerted on them. The magnitude
of these pressures depends on the amount of deformation that the wall can yield under load. If the
wall can yield enough to mobilize the full shear strength of the soil, it can be designed for "active"
N
• 0
Z
~
0 w :c
(.)
z
cC ....
a..
c.-r oz--,4C ~
3934 Murphy Canyon Road, Suite 8205. San Diego, CA92123-44is'
858.292.8030. Fax 858.292.0771 • www.leightongeo.com
,
.i
971009-014
pressure. If the wall cannot yield under the applied load, the shear strength of the soil cannot be
mobilized and the earth pressure will be higher. Such walls should be designed for "at rest"
conditions. If a structure moves toward the soils, the resulting resistance developed by the soil is
the "passive" resistance. The noted passive resistance assumes an appropriate setback from the face
of slopes.
The native backfill soils should be compacted to at least 90 percent relative compaction (based on
American Standard of Testing and Materials [ASTM] Test Method D1557). The walls should be
constructed and backfilled as soon as possible after backcut excavations. Prolonged exposure of
backcut slopes may result in some localized slope instability
• F·oundation Setback Recommendations from Slope Faces
We recommend a minimum horizontal setback distance from the face of descending slopes
or adjacent retaining walls for all structural foundations, footings, and other settlement-
sensitive structures as indicated on Table 1. This distance is measured from the outside
bottom edge of the footing, horizontally to the descending slope face and is based on the
slope height and type of soil. However, the foundation setback distance may be revised by
the geotechnical consultant on a case-by-case basis if the geotechnical conditions are
different than anticipated.
Table 1
Minimum Foundation Setback from Descending Slope Faces
Slope Height Minimum Recommended Foundation
Setback
Less than 5 feet 5 feet
5 to 15 feet 7 feet
15 to 30 feet 10 feet
Greater than 30 feet 20 feet
Please not~ that the soils within the structural setback area possess poor lateral stability, and
improvements (such as retaining wa1ls, sidewalks, fences, pavements, etc.) constructed within
this setback area may be subject to latera1 movement andlor differential settlement. Potential
distress to such improvements may be mitigated by providing a deepened footing or a pier and
grade beam foundation system to support the improvement. The deepened footing should meet
the setback as described above.
- 2 -
Leighton
971009-014
• Lateral Earth Pressures
The recommended lateral pressures for the onsite soil or granular~soil and level or sloping
backfill are presented on Table 2. '
Table 2
Lateral Earth Pressures
Equivalent Fluid Weight (pet)
Conditions Expansion Index Less than Expansion Index Greater
50 than 50
Level 2:1 Slope Level 2:1 Slope
Active 35 55 60 70
At-Rest 55 65 70 80
Passive 350 150 350 150
To design an unrestrained wall, such as cantilever wall, the active earth pressure may be
used. For a restrained retaining wall, such as a basement wall, the at-rest pressure should be
used. Further, for sliding resistance, the friction coefficient of 0.35 may be used at the
concrete and soil interface. In combining the total lateral resistance, the passive pressure or
the frictional resistance should be reduced by 50 percent. Wall footings may be designed in
accordance with structural considerations. The passive resistance value may be increased by
one-third when considering loads of short duration including wind or seismic loads. The
horizontal distance between foundation elements providing passive resistance should be a
minimum of three times the depth of the elements to allow full development of the passive
pressure. The total depth of retained earth for design of cantilever walls should be the vertical
distance below the ground surface measured at the wall face for stem design or measured at
the heel of the footing for overturning .and sliding. All retaining structures should be provided .
with a back drain and appropriately waterproofed. Typical wall drainage is presented on
Figure 1. Surcharge loading effects from adjacent structures should be evaluated by the
geotechnical and structural engineers.
• Soil Bearing Value and Minimum Foundation Embedment Depth
Foundations for retaining walls in competent formational soils or properly compacted fill
should be embedded at least 18 inches below lowest adjacent grade. At this depth, an allowable
bearing capacity of 2,000 psfmay be assumed.
- 3 -Leighton
971009-014
Control of Surface Water and Drainage
Surface drainage should be carefully taken into consideration during precise grading, landscaping,
and building construction. Positive drainage (e.g., roof gutters, downspouts, area drain, etc.) should
be provided to direct surface water away from structures and towards the street or suitable drainage
devices. Ponding of water adjacent to structures should be avoided. The adjacent grade next to
structures should have a minimum fall of 2 percent for a distance of at least 5 feet. Roof gutters,
downspouts, and area drains should be aligned so as to transport surface water to a minimum
distance of 5 feet away from structures. The. performance of structural foundations is dependent
upon maintaining adequate surface drainage away from structures.
Water should be transported off the site in approved drainage devices or unobstructed swales. We
recommend that the minimum flow gradient for the drainage be 1 percent for area drains and
drainage swales. In places where the prospect of maintaining the minimum recommended gradient
for the drainage swales and the construction of additional area drains is not feasible, provisions for
specific recommendations to the homeowners may be necessary, outlining the importance of
maintaining positive drainage to streets.
• Side-yard Drainage Recommendation Alternative
We understand that some of the residential structures of the tract may be located
approximately 5 feet from the side-yard property line. Consequently, the recommended
surface drainage design (e.g. positive drainage away from the residential structure [at a
gradient of at least 2 percent] for a distance of at least 5 feet) cannot be met on some of the
lots.
As an alternative, we recommend that surface drainage adjacent to the residential structures
be accomplished with a gradient of at least 3-1/2 percent away from the structure for a
minimum horizontal distance of 3 feet. Drainage should be further maintained by a swale or
drainage path at a gradient of at least I-percent to a suitable collection device (Le. area drain,
street gutter, etc.). We also recommend that the footings less than 5 feet from the drainage
swale be deepened so the bottom of the footing is at least 12 inches below the flow-line of
the drainage swale. "..
Where necessary, drainage paths may be shortened by the use of area drains and tightline
collector pipes. It is very important that these gradients be maintained throughout the life of the
structure. Eave gutters with properly connected downspouts that drain precipitation away from
the residential structure and reduce water infiltration into the sub grade soils may also be utilized.
The impact of heavy irrigation or inadequate runoff gradient can create perched water conditions,
resulting in seepage or shallow groundwater conditions where previously none existed.
Maintaining adequate surface drainage and controlled irrigation will significantly reduce the
potential for nuisance-type moisture problems. To reduce differential earth movements (such as
heaving and shrinkage due to the change in moisture content of foundation soils, which may cause
-4-
Leighton
971009-014
distress to a residential structure and improvements), the moisture content of the soils surrounding
the structure should be kept as relatively constant as possible.
All area drain inlets should be maintained and kept clear of debris in order to function properly. In
addition, yard landscaping should not cause any obstruction to the yard drainage. Rerouting of yard
drainage pattern and/or installation of area drains should be performed, if necessary. A qualified
civil engineer or a landscape architect should be consulted prior to rerouting of drainage.
If you have any questions regarding this letter, please contact this office. We appreciate this
opportunity to be of service.
Respectfully submitted,
LEIGHTON AND ASSOCIATES, INC.
lVft-o.CJL
William D. Olson, RCE 45283
Senior Project Engineer
till1.~~~612
Director of Geology
Attachment: Figure 1 -Retaining Wall Backfill and Drainage Detail
Distribution: (2) Addressee
(1 ) Lennar Communities, Attention: Lisa Galloway
(1) Lennar Communities, Attention: Jim Urbina
(12) Project Design Consultants, Attention: David Uson
-5-
-
Leighton
RETAINING WALL BACKFILL AND
DRAINAGE DETAIL
OPTION 2: GRAVEL WRAPPED
IN FILTER FABRIC
For Maximum a-Foot High Walls with
On-Site Soils Having Very Low to Low
Expansion Potentials (i.e. on Expansion
Index of 50 or Less)
SLOPE OR LEvEL
OPTION 1: PIPE SURROUNDED WITH
CLASS 2 PERMEABLE MATERIAL
WATERPROOFING --1---1
(SEE GENERAL NOTES)
14 TO 1 ~ INCH SIZE
GRAVEL WRAPPED IN FILTER FABRIC
SLOPE
OR LEVEL
,
LEVEL OR
SLOPE
WATERPROOFING
(SEE GENERAL NOTES)
Class 2 Filter Permeable Water/al Gradation
Pef Caltrans Specifications
GENERAL NOTES:
12-NINIMUM
ClASS 2 PERMEABLE FILTER MATERIAL
(SEE GRADATION)
-4 INCH DIAMETER
PERFORATED PIPE
(SEE NOTE 3)
Sieve Size
1-
3/4-
3/8-
No.4
No.8
No. 30
No. 50
No. 200
'" Waterproofing should be provided where moisture nuisance problem through the wall is und8sirobl8
'" Wat8r proofing of th8 walls is not under purview of the geotechnical engin88r
'" All droins should have a gradient of 1 percent minImum
Percent Pgsslng
100
90-100
40-100
25-40
18-33
5-15
0-7
0-3
'" Outlet port/on of th8 subdroin should have a 4-inch diamet8r solid pipe discharged into a suitabl8 disposal area d8signed
by the project 8ngin88r. The subdrain pipe should be accessible far maintenance (rodding)
'" Other subdrain backfill options are subject to the review by the geotechnical, 8ngin88r and modification of design
porometers
~:
1) Sand should hav8 a sand equivalent of JO or great8r and may be densified by water jetting
2) 1 Cu. ft. per ft. of 1/4-to 1 112-inch size grovel wropped in filt8r fabric
J) Pipe iyptI shauld be ASTM 01527 Acrylanitril8 Butadiene StyrenfJ (ASS) SORJ5 or ASTM 01785 Polyvinyl Chlaridll plastic
(P\IC). Schedule 40. Armco A200D ~ or approved equIvalent PipfJ should bll installed with perforotions down. Perfoiatlons
should be JI8 inch in diometer placed at thfJ ends of a 120-dBgrBfJ arc in two rows at J-Inch on C8nter (staggfJred)
4) FIlter fabric should be Miran 140NC or approved equivalent
5) W88pholfJ should be J-Inch minimum diameter and provIded at 10-foot maximum intervals. If exposure is permitted.
w88pho/es should be located 12 inchfJs above finished grodfJ. If exposure is not permitted such as for a wall adjacfJnt to a
sldllwalklcurb. a pipe under thfJ sid8walk to be discharged through thfJ curb face or equivalfJnt should bfJ provided. For a
basement-iyptI wall, a proper subdrain outlet system should be provided
6) Retaining wall plans should be reviewed and approved by thfJ geotechnical fJngln88r
7) Walls over six f8fJt in heIght are subject to a special revIew by the geotechnical fJngin88r and modifications to the
abovil reqUirements
RETAINING WALL BACKFILL
AND SUBDRAIN DETAIL
(rev. June 2000)
PROJECT NO. 971009-014
PROJECT NAME 8,.. .. 1 Ranch
Carl.bad. CalifornIa
Leighton and Associates, Inc.
A LEIGHTON GROUP COMPANY Figure No.1