HomeMy WebLinkAboutCT 04-10A; POINSETTIA PLACE; LABORATORY REPORT; 2012-05-10c-ro'4-.gO
LABORATORY REPORT
Telephone (619) 425-1993 Fax 425-7917 Established 1928
CLARKSON LABORATORY AND SUPPLY INC.
350 Trousdale Dr. Chula Vista, Ca. 91910 www.clarksonlab.com
ANALYTICAL AND CONSULTING CHEMISTS
Date: May 10, 2012
Purchase Order Number: 5807 JOB#11095 -
Sales Order Number: 10769
Account Number: SCHC
To:
* -------------------------------------------------
Schilling Corporation
697 Greenfield Dr
El Cajon, CA 92021
Atten: Jay Sager
Laboratory Number: B3949 Customers Phone: 579-6500
Fax: 579-3733
Sample Designation:
* -------------------------------------------------
Eight water samples received on 05/08/12 at 1:35pm,
taken on 05/08/12 from 11:20 to 12:20pm by Clarkson Laboratory
taken from Vitalia marked as follows:
ANALYSIS: Per EPA Drinking Water, National Primary Drinking Water
Regulations.
Test Method Colilert (MMO-MUG)
Plate Count per APHA 18th Ed. 1992 Test Method No.9215B
Pour Plate Method @ 35 C/48hr Plate Count Agar
Fecal Plate
Total Coliform Count
Coliform (E-Coli) CFU/ml
#1 End of Line ST 9+92 ABSENT ABSENT <1
#2 Source South Side t7S 7- ABSENT ABSENT ? C52
#3 2" W/S ST 10+00 . ABSENT ABSENT <1
#4 2" W/S ST 13+65 ABSENT ABSENT 1
115 FH ST .15+42 ABSENT ABSENT <1
#6 FH Genoa Ln ABSENT ABSENT 25
417 2" W/S ST 19+16 ABSENT ABSENT 3
#8 End of Line North End ST 23+05 ABSENT ABSENT 8
The results indicate that these water samples are
niicrobiologically safe for drinking.
Note: CFU = Colony Forming Units.
I < Is the symbol for less than. . .
Elf
Rosa M. Bernal
RMB/mlv
LABORATORY REPORT
Telephone (619) 425-1993 Fax 425-7917 Established 1928
CLARKSON LABORATORY AND SUPPLY INC.
350 Trousdale Dr. Chula Vista, Ca. 91910 www.clarksonlab.com
ANALYTICAL AND CONSULTING CHEMISTS
toe_ F_
------------------------------------------------ *
a_4
Schilling Corporation
697 Greenfield Dr
El Cajon, CA 92021
Atten: Jay Sager
Laboratory Number: B3924 Customers Phone: 579-6500
Fax: 579-3733
Sample. Designation:
* -------------------------------------------------
Six water samples received on 01ii27at 12:05Pm,
taken on 05/01/12 from 9:30 to 10:20am by Clarkson
Laboratory, taken from Vitalia marked as follows:
ANALYSIS: Per EPA Drinking Water, National Primary Drinking Water
Regulations.
Test Method Colilert (MMO-MUG)
Plate Count per APHA 18th Ed. 1992 Test Method No.9215B
Pour Plate Method 0 35 C/48hr Plate Count Agar
Fecal Plate
Total Coliform Count
Coliform (E-Coli) CFU/ml
#1 NE Tie in ST 23+10 ABSENT ABSENT 527'00
#2 FH ST 18+57 ABSENT ABSENT 70
#3 SE Tie in ST 10+20 ABSENT ABSENT i7L00J
#4 Fire Service ST 13+65 ABSENT ABSENT 57io:0
#5 FH ST 11+54 ABSENT ABSENT 5t7:001
#6 S Tie Pt St 8+75 ABSENT ABSENT
The results indicate that these water samples are not
microbiologically safe for drinking.
Note: CFU = Colony Forming Units.
< Is the symbol for less than.
Rosa M. Bernal
RMB / a r r
Date: May 3, 2012
Purchase Order Number: 5645 JOB#11095
Sales Order Number: 10658
Account Number: SCHC
LABORATORY REPORT
Telephone (619) 425-1993 Fax 425-7917 Established 1928
CLARKSON LABORATORY AND SUPPLY INC.
350 Trousdale Dr. Chula Vista, Ca. 91910 www.clarksonlab.com
ANALYTICAL AND CONSULTING CHEMISTS
Date: May 2, 2012
Purchase Order Number: 5645 JOB#11095
Sales Order Number: 10658
Account Number: SCHC
To:
* -------------------------------------------------
Schilling Corporation
697 Greenfield Dr
El Cajórz, CA 92021
Atten: Jay Sager
Laboratory Number: B3917 Customers Phone: 579-6500
Fax: 579-3733
Sample Designation:
* -------------------------------------------------
Six water samples received on (0/30j) at 11:00am,
taken on 04/30/12 from 9:40 to 10:30am by Clarkson
Laboratory, taken from Vitalia marked as follows:
tCAJ
ANALYSIS: Per EPA Drinking Water, National Primary Drinking Water
Regulations.
Test Method Colilert (MMO-MUG)
Plate Count per APHA 18th Ed. 1992 Test Method No.9215B
Pour Plate Method @ 35 C/48hr Plate Count Agar
Fecal Plate
Total Coliform Count
Coliform (E-Coli) CFU/ml'
#1 NE Tie in ST 23+10 ABSENT
--------------------------------------------
ABSENT
#2 FH ST 18+57 ABSENT ABSENT >'5-7'00
#3 SE Tie in ST 10+20 ABSENT ABSENT
#4 Fire Service ST 13+65 ABSENT ABSENT 5:7010)
#5 FH ST 11+54 ABSENT ABSENT
#6 S Tie Pt St 8+75 ABSENT ABSENT
The results indicate that the water sample #6 is
microbiologically safe for drinking.
Note CFU = Colony Forming Units.
> = Is the symbol for greater than.
~ f' i-Vi 0 - T4 , =V r
Rosa M. Bernal
RMB/arr
LABORATORY REPORT
Telephone (619) 425-1993 Fax 425-7917 Established 1928
CLARKSON LABORATORY AND SUPPLY INC.
350 Trousdale Dr. Chula Vista, Ca. 91910 www.clarksonlab.com
ANALYTICAL AND CONSULTING CHEMISTS
Date: April 26, 2012 cç 04 - cC') Purchase Order Number: 5613 JOB#11095
Sales Order Number: 10594
Account Number: SCHC
To:
---------------------- ------------ -------------* p Schilling Corporation
697 Greenfield Dr
El Cajon, CA 92021
Atten: Jay Sager
Laboratory Number: B3907 Customers Phone: 579-6500
Fax: 579-3733
Sample Designation:
Eight water samples received onCO--4—/--2-4-/-1-2 at 2:30p'm, I taken on 04/24/12 from 12:10pm to 1:30pm by Clarkson
Laboratory, taken from Vitalia marked as follows:
ANALYSIS: Per EPA Drinking Water, National Primary Drinking Water
Regulations.
Test Method Colilert (MMO-MUG)
Plate Count per APHA 18th Ed. 1992 Test Method No.9215B
Pour Plate Method @ 35 C/48hr Plate Count Agar
Fecal Plate
Total Coliform Count
I. Coliform (E-Coli) --------------------------------------------- CFU/ml
#1 NE Tie in St. 23+10 ABSENT ABSENT 6
F.H. St 18+57 ABSENT ABSENT 570
SE Tie in St. 10+20 ABSENT ABSENT 290
#4 Fire Service St. 12+85 ABSENT ABSENT <1
#5 F.H. St, 11+54 ABSENT ABSENT 1200
#6 5 Tie Pt. St. 8+75 . ABSENT ABSENT 37
T7West Side St. 176+89 ABSE f ABSENT
4fi2 #8 St. 179+89 ABSENT ABSENT 120
The results indicate that the water samples #2 and #5 are not
microbiologically safe for drinking.
Note: CFU = Colony Forming Units.
< Is the symbol for less than.
Em
Rosa M. Bernal
RNB / arr
LABORATORY REPORT
Telephone (619) 425-1993 Fax 425-7917 Established 1928
CL'ARKSON LABORATORY AND SUPPLY INC.
350 Trousdale Dr. Chula Vista, Ca. 91910 www.c1arksonlab.com
ANALYTICAL AND CONSULTING CREMISTS
Date: April 25, 2012
Purchase Order Number: Job#11109 c:C.— CA')
Sales Order Number: 10594
Account Number: SCBC
To:
* --------------------------------------------------*.
Schilling Corporation
697 Greenfield Dr
El Cajon, CA 92021
Atten: Jay Sager
Laboratory Number: 33899 Customers Phone: 579-6500
Fax: 579-3733
Sample Designation:
Right water samples received onCO:~_123/_11
taken on 04/23/12 from 11:30am to 1:06pm by Clarkson
Laboratory from Vitalia marked as follows:
ANALYSIS: Per EPA Drinking Water, National Primary Drinking Water
Regulations.
Teat Method Colilert (MMO-MUG)
Plate Count per APHA 18th Ed. 1992 Test Method No.92153
Pour Plate Method @ 35 C/48hr Plate Count Agar
#1 NE Tie in St. 23+10
#2 P.R. St 18+57
*3 SE Tie in St. 10+20
H A Fire Service St. 12+85 AMN F.H. St, 11+54
#6 S Tie Pt. St. 8+75
Focal • Plate
Total Colifozm Count
Coliform (E-Co3.i) CPU/ml
ABSENT
--------------------------------------------
ABSENT 4
ABSENT 87
ABSENT ABSENT 33
ABSENT ABSENT J30
ABSENT ABSENT CI7OO
ABSENT ABSENT 4
#7 West Side St. 176+87. ABSENT ABSENT <1
#8 St. 179+89 • -, ABSENT ABSENT <1
The results indicate water sample #5 is not
microbiologically safe for drinking.
Note: CPU = Colony Forming Units.
< Is the symbol for less than.
Rosa M. Bernal
RMB/mlv