HomeMy WebLinkAboutCT 12-05; LA COSTA RESIDENTIAL; ROUGH GRADE COMPACTION REPORT; 2014-09-09:STRATA-TEC H,I N C. 714-521-5611
GEDCDNEULTANTE FAX 714-521-2552
7372 Walnut Avenue, Unit F,Buena Park, California 90620
September 9, 2014 W.O. 263810
Tony Sfreddo
D.S. Products, Inc.
24 Amberleaf
Irvine, California, 92614
Subject: Rough Grade Compaction Report for
Proposed Multi Family Residential
Development, 7500 Jerez Court, Carlsbad,
California
Reference:
STRATA-TECH, INC., Geotechnical Engineering Investigation of Proposed Multi Family
Residential Development, 391 Tamarack Avenue, Carlsbad, California., Dated October 4, 2011
Gentlemen:
Submitted herewith is the Rough Grade Compaction Report for the subject site. The grading
operation was conducted between April7, 2014 and September8, 2014, utilizing the
recommendations of the referenced report. Observations of the grading were provided by
STRATA-TECH, Inc.
PLACEMENT OF STRUCTURAL FILL
Compacted fill was placed on the subject site to provide adequate support for the proposed 2-
story Multi Family Residential Development
OBSERVATIONS DURING GRADING
Preparation for placement of a compacted fill included overexcavation to approximately 3 feet
below existing grade, and 5-feet beyond the building foundation to provide a minimum, of 2-foot of
compacted fill under the footings of the proposed building. Prior to placement of fill, the bottom
was made level, scarified, watered and tamped smooth.
Subsequent fills were placed in 6 to 8 inch loose lifts and compacted to a minimum of 90
percent. The pads were raised approximately 3 feet in the back to allow for drainage toward
Jerez court. The driveway portion of the site was left low to allow for placement of footing
excavation soil.
STRATA - TECH,INC.
GE 0 CON S U LTA NT S
D.S. Products, Inc. 2 W.O. 263810
Rough Grade Compaction Report September 9, 2014
Final rough finish grade is approximately 6 inches below the finish floor grade in order to allow
placement of sand and concrete for the slab-on-grade building. Approximate limits of grading
for the pad area is shown on Plate A.
TESTING
Maximum density optimum moisture relationship determinations were performed for each soil
type encountered during grading operations. Test results were as follows:
Laboratory Standard: (ASTM: D-1557-91)
4 inch dia. mold; 1/30 cu.ft.vol.;
5 layers-25 blows per layer;
10 lb. hammer dropped 18 inches
Soil Type Classification Optimum Moisture % Max. Dry Density lbs/fl
Light Brown Fine clayey 12 128.0 Sand
Import, Brown clay Sand 10 132.0 wlrock chips
Compaction tests were performed a minimum of every 2 feet and/or 500 cubic yards of compacted
fill soils placed. These tests were performed in accordance with ASTM: D-2922-91 (nuclear
gauge) or ASTM: D-1557-04 (sand cone) test methods. The test results are summarized in Table I.
The approximate test locations are shown on Plate A.
Areas not tested were probed to show adequate compaction.
FOUNDATIONS ON COMPACTED FILL
The proposed building may be supported by continuous spread footings placed a minimum depth
of 18 inches below lowest adjacent finish grade utilizing an allowable bearing value of
1,500 pounds per square foot. This value is for dead plus live load and may be increased 1/3 for
total including seismic and wind loads where allowed by code.
Type
Minimum
Depth
(inches)
Minimum
Width
(inches)
Bearing
Value
(psf)
Increase Maximum
(ps) Width Depth
(pstill) (psi/fl)
Continuous 18 12 2000 180 440 3500
It is recommended that all footings be reinforced with a minimum of four No. 4 bars (2 top and 2
bottom). The structural engineer's reinforcing requirements supersede if more stringent.
STRATA - TECH,INC.
G EDCON S U LTANTS
D.S. Products, Inc. 3 W.O.263810
Rough Grade Compaction Report September 9, 2014
Footing excavations shall be observed by a representative of STRATA-TECH, Inc. prior to
placement of steel or concrete to verify competent soil conditions. If unacceptable soil
conditions are exposed mitigation will be recommended.
LATERAL DESIGN
An allowable lateral bearing value against the sides of footings of 250 pounds per square foot,
per foot of depth, to a maximum of 2,000 pounds per square foot may be used, provided there is
positive contact between the vertical bearing surface and compacted fill.
Friction between the base of the footings and/or floor slabs and the underlying material may be
assumed as 0.35 times the dead load. Friction and lateral pressure may be combined, provided
either value is limited to two-thirds of the allowable. The above values may be increased by
one-third for short durations of seismic and wind loads.
FLOOR SLABS
The surface soils have a medium expansive potential. Slabs on grade shall be supported on
engineered fill compacted to a minimum of 90 percent relative compaction. Slabs should be
reinforced with at least No. 4 bars 18 inches on center both ways.
The soil should be kept moist prior to casting the slab. However, if the soils at grade become
disturbed during construction, they should be brought to approximately optimum moisture
content and rolled to a firm, unyielding condition prior to placing concrete.
In areas where a moisture sensitive floor covering will be used, a vapor barrier consisting of a
plastic film (6 ml polyvinyl chloride or equivalent) should be used. The vapor barrier should be
properly lapped and sealed. Since the vapor barrier will prevent moisture from draining from
fresh concrete, a better concrete finish can usually be obtained if at least 2 inches of wet sand is
spread over the vapor barrier prior to placement of concrete.
HARDSCAPE AND SLABS
Hardscape and slab subgrade areas shall exhibit a minimum of 90 percent relative compaction to
a depth of at least 1 foot. Deeper removal and recompaction may be required if unacceptable
conditions are encountered. These areas require testing just prior to placing concrete.
STRATA - TECH,INC.
G ED CD NB U LTA NT S
D.S. Products, Inc. 4 W.O. 263810
Rough Grade Compaction Report September 9, 2014
POST-GRADING SERVICES
During construction of the residence, it is recommended, and at times required by the regulatory
agency that the following be observed and/or tested by the geotechnical engineer:
Excavations of footings
Backfill of interior slab areas
Backfill of interior trenches
Backfill of exterior utility trenches
Hardscape, and pavement subgrade
It is the responsibility of the developer to schedule the required observations and testing.
REGULATORY COMPLIANCE
All cuts, fills or processing of original ground under the purview of this report have been
completed under the observation of and with selective testing by STRATA-TECH, Inc., and found
to be in compliance with the Grading Code of the City of Carlsbad. The completed work has been
observed by STRATA-TECH, Inc., and is considered adequate for the development. Our findings
were made and recommendations prepared in accordance with generally accepted professional
engineering practices, and no further warranty is implied nor made.
This report is subject to review by the controlling authorities for this project.
We appreciate this opportunity to be of service to you.
Respectfully submitted:
STRATA-TECH, Inc.
Roland Acufia Larry Finley
Principal RCE 46606
Enclosures: Compaction Test Results
Plate A - Compaction Test Map
714-521-5611 S T R A T A - T E C H , I NC. 562-427-8099
B E D - C 0 N S U L T A N T 8 FAX 714-521-2552
7372 Walnut Avenue, Unit F,Buena Park, California 90620
COMPACTION TEST RESULTS
Test Location
Below
Proposed
i!(iL/( (/1)
-
Moisture
Content
%
--
Dry lull
lJcic.'/Ii Soil
(lbs/I)
'ii, RL'hllfl''
Compaction Date
1 Building Pad 5 12.3 116.9 I 91% 4/7/14
2 Building Pad 3 11.8 116.7 I 90%
3 Building Pad 5 12.8 116.9 I 90% 4/8/14
4 Building Pad 3 12.1 117.3 I 91%
5 Building Pad 2 12.2 117.6 I 91%
6 Building Pad 2.5 12.4 118.1 90% 4/9/14
7 Building Pad 2 12.1 117.9 I 90%
8 Building Pad 3 11.5 118.3 I 91%
g Building Pad 2 11.6 118.5 I 91%
io Building Pad PG 10.2 119.8 I 91% 4/11/14
ii Building Pad PG 10.3 119.6 I 91%
12 Building Pad 3 12.1 120.2 II 4/17/14
13 Building Pad 2.5 12.1 119.3 II 92%
14 Building Pad 1 13.5 122.2 II 93%
15 Building Pad 1 9.9 122.7 II 93°1
16 Building Pad PG 10.1 123.5 II 4/25/14
17 Building Pad PG 10.2 122.2 II 92%
18 Sewer 4 9.7 119.8 II 92%
19 Sewer 2 8.9 120.5 II 92 7/11/14
20 Electric 2 8.6 121.0 II 91
21 Building Pad* P.G 8.2 121.4 Il 92% 1 9/8/14
22 Building Pad * P.G 8.5 121.5 II 92% 1
PG= Pad Grade
*reteSt
- \\
. -
blockraff 1H•-'I- 6
721
privo C3.2 _' 1520.
WZI
-
I
6 101510-S
Proposed P 10
tU . Building 2 at
11 12 ' ..
- - - -. o#o •- - 10.0001 1701 -
' Proposed ......S
- I - r,
. . - -- .
.0
Soil rolls
priso
390 0? 5 pol o BuIlding
- - 'S
p0000.00
Od
-..
high
-,
- S -• --
W.I,fofllso 4510 - . - S
. -: -
.-
- . /
- - - - - - -- S .000000. lon000000 '000.1.__5 • "O-/' - - - .
0"41 I 00 0 poltl 9 009
9.
I 900020 0 A
prl of. 0400,30
of
__________ / _______________ I.-
.? -
•-• . Jerez Court
WAflOO
-------------------------------
I 1005009040 -- 042.0,00
r.E0l6•04WW .01.110 0 fll9h 104250011 10190050 00060u, .01.9 6 nt 42 015 5poApol0S.6 bOcOwdi 1060 .01
0101001
La Costa Vista
VF.' --'- 7-unit Residental Condominium Project
kL2 Site Plan: 1.1 7000JE00000URT,CARLSOADSCA APN:296.200.O8
Split r
proInt data
640-atone P04010 Planned T0nt0tIV0Tl0ot1 hIt Floor Am,
100 dM0. 0040091000 soto8, 10r0, No.5,
PAnA(9.0odrro): 2-41001.0,400040-. 2,4600415 P1400 (0-Sd or): a-onto 1.1,403.q.0- • 2,988.q. genevel lotOrnietlen Intl. CII) of C011.bod, County 010,0, Pion C (0-409 no): 0410501.1,002 044.. 3,070 ,q,lt,
do 00000W.IIOSCOS10bOAMOI00POIWOS000AOIOI 000.0. tlron09 0,009 09.
-
TMtPMENT 32 SYLVA IRVINE, CA 00000
0.6.03 00000.d'l0005tal010 (7 7-sON) 0040)03 Proposed: 17950409.0,0(7.4041.) P00000.0 0011d160 01007 Ar_S
• 090.001.0900 0oI.6ng 5000 00.01 400.01 01070.00 0lslld)0rg 1: 7,750 .q.tt
• -
001411005 BEGOVICII+i4AUGARCH005CTS 01000ud 1.0050 UO.17.CO0dol0J142I4 0040 Und.o.iop.010 .10. 60 00 not 00p9.0b14 00Sd 0'902, 4102 09(5 ToSs 14014040
LONG OEACH,CA00600 4090100. 17,6750411(40010) - P014lrrgr.qo104dl - 000.080,1174 Landscape0,..1 0,10400-3-120') 2.0 0p000010,rll. 7 • 14.0 - 00 .000 01011 onDIASgno.r: ULTANTS Lot USonolo LAO Coo.,aO. 0(00.001 (0,08000.0- .60% 0000090 0109000d1 6,00409(5 • 0.3 900.1 60042011000 • 0.1000000
- LEWIS ST. #101 012377 olol.p.o.. r.qoio.d • 10.0(17)000.0. GARDEN GROVE,CA 02460 P4000. P.9000.. Requited:.lVor4i(odn) p.40000,00)d.d 714.740.6040 - 011v.t.P.40 4100 P1000.0501 117.001.3000(01540400)
Ooosp.nor.930w42r
)
5oroo0(0V 00441040 .900SUnit • 14,0 000400
GALA6SCAPE lola ROMPER AVE o.prink0o,IAA4rro42!oopl1nk0r. 10991560 0100 SAMOA AMA, CA 02700 714.000.6000 ,00l00090l009lzp000loo W000101.t000:I1l0105lIl10r000l0rIlOt0r00M00400t01m0I01 totOl 0000.010410.0 . 179.p.on