· WATERSTUDY
FOR
QUARRY CREEK PLANNING AREA R-3
City of Carlsbad, CA
PREPARED FOR:
PRESIDIO CORNERSTONE QC, LLC
4365 EXECUTIVE DRIVE, SUITE 600
SAN DIEGO, CA 92121
PREPARED BY:
SB&O, INC.
3990 RUFFIN ROAD, SUITE 120
SAN DIEGO, CA 92123
(858) 560-1141
SB&O JOB NO. 71470.60
Aaron Parker PE 6854 7
Exp: 9/30/2017
OCTOBER 20,2015 OCT 2 '1 2015
Corporate Office: 3990 Ruffin Road, Suite 120 • San Diego, California 92123 • Phone 858.560.1141 Fax 858.560.8157
41689 Enterprise Circle North, Suite 126 • Temecula, CA 92590 • Phone 951.695.8900 Fax 951.695.8901
' _j
. u
2
PLANNING ENGINEERING SURVEYING
TABLE OF CONTENTS
1. INTRODUCTION ...................................................................................................................... 1
2. DESCRIPTION OF WATER SYSTEMS .................................................................................. 1
2.1 Existing Condition ................................................................................................................ 1
2.2 Proposed Private Water System ............................................................................................ 1
3. HYDRAULIC ANALYSIS ........................................................................................................ 2
3.1 EPANET ............................................................................................................................... 2
3.2 Residual Demand Analysis ................................................................................................... 2
3.3 Results .................................................................................................................................... 2
4. WATER METER SIZING .......................................................................................................... 3
4.1 UPC Demands ...................................................................................................................... 3
4.2 Meter Sizes ............................................................................................................................ 3
5. RECOMMENDATIONS ............................................................................................................. 3
5.1 Pipelines ................................................................................................................................ 3
5.2 Pressure Regulation .............................................................................................................. 3
5.3 Meters ................................................................................................................................... 3
EXHIBITS
Exhibit A: Vicinity Map
Exhibit B: EPANET Results I Site Map
D:\71472 Quarry Creek\Reports\Water\20150514, QC-R3, WATER STUDY.xlsx.docx
. u z
PLANNING ENGINEERING SURVEYING
1. Introduction
The Quarry Creek project is located in the City of Carlsbad (City), but is bordered to the east by
the City of Oceanside. The project is situated west of College Boulevard, east of Interstate 5 and
south of Haymar Drive. The property is divided north and south by the Buena Vista Creek which
runs east to west across the middle of the site.
Planning Area 3 (R-3) is located in the southeastern portion of the site, and consists of 88 two-
story townhomes. R-3 is bound by the Buena Vista Creek to the north, Creekside Street to the
west and Marron Road to the south.
This report summarizes our analysis of the proposed domestic water system within R-3, for
sizing of facilities and verifying adequate working pressures. This report is preliminary and may
be revised due to changes that occur in the final design stage of the project.
2. Description of Water Systems
2.1 Existing Condition
A water system analysis for the Quarry Creek Master Plan was prepared by Dexter Wilson
Engineering, dated March 2012. The Quarry Creek water system is connected to the 580
pressure zone near the intersection of Tamarack A venue and Simsbury Court. A pressure
reducing station reduces all the Quarry Creek main lines to 330 pressure zone.
2.2 Proposed Private Water System
The R-3 area contains private streets, private sewer, and a private water system. The internal 6"
PVC private main lines are looped through the site, and connected at two locations with master
public water meters and backflow devices. The layout of the domestic water system and the
Points of Connection (POCs) are illustrated in Exhibit A. Each building shall receive a single
water service and each unit shall be individually sub-metered. No irrigation, fire hydrants or
sprinkler systems shall be connected to the private potable water system.
A parallel private 8" PVC private fire system shall be provided in a joint trench to provide
service to fire hydrants and to building fire suppression systems. The private fire system shall
also be looped through the site and be connected to an 8" Double Check Detector Assembly
(DCDA) at the public right-of-way, at each of the two POCs.
D:\71472 Quarry Creek\Reports\Water\20150514, QC-R3, WATER STUDY.xlsx.docx 1
. u z
PLANNING ENGINEERING SURVEYING
3. Hydraulic Analysis
3.1 EPANET
EPANET (v2.00.12) is a computer program that performs extended period simulation of
hydraulic and water quality behavior within pressurized pipe networks. EP ANET can be used
for many different kinds of applications in distribution systems analyses. A network consists of
pipes, nodes (pipe junctions), pumps, valves, and storage tanks or reservoirs. EPANET tracks the
flow of water in each pipe, the pressure at each node, and the height of water in each tank,
throughout the network during the simulation period comprised of multiple time steps.
3.2 Residual Demand Analysis
In accordance with the City's Design Requirements, Section 3 .2.1, the following demand profiles
shall apply to the hydraulic analysis of the 88 residential multi-family units:
Average Daily Demand (ADD)= 22,000 gallons per day (gpd) = 15 gallons per minute (gpm)
Maximum Daily Demand (MDD) = 36,300 gpd = 25 gpm
Peak Hour Demand (PHD)= 63,800 gpd = 43.5 gpm
Per City's Design Requirements, Section 2.3, the minimum residual pressure shall meet the
following criteria:
A. 40 PSI at PHD
B. 20 PSI at design fire flow plus MDD
The private fire system is independent of the potable water system and therefore only scenario
"A" (PHD) is hydraulically modeled.
3.3 Results
The results of the analyses are summarized in the table below and Exhibit A. Please note that the
initial reservoir numbers used in the study take into account a loss of approximately 7' of head
from each meter and backflow device. (320ft H20)-(7ft Headloss) =323ft H20.
SIMULATION ALLOWABLE
Max. Velocity (FPS) 1.8 8
Hazen-Williams Roughness Coef. "C" 120 -
Max. Residual Pressure (PSI) 87.9 -
Min. Pressure (PSI) 78.7 40
D:\71472 Quarry Creek\Reports\Water\20150514, QC-R3, WATER STUDY.xlsx.docx 2
_j
B&D~
PLANNING ENGINEERING SURVEYING
4. Water Meter Sizing
4.1 UPC Demands
The demands for each unit and building were calculated based upon the amount of fixture units
in each. Using chart A-2 (Appendix B) of the UPC, the fixture units are converted to flow
demand in gpm.
88 TOTAL NO. OF UNITS
33 ASSUMED FIXTURE UNITS PER DWELLING UNIT
2,904 TOTAL FIXTURE UNITS
. 420 TOTAL DEMAND (GPM)
4.2 Meter Sizes
The private water system is looped to two points of connection with a demand of 210 gpm at
each. A 3" water meter has a capacity of320 gpm and a 2" meter has capacity of 160 gpm for a
total capacity of 480 gmp.
5. Recommendations
5 .1 Pipelines
The on-site main lines within the project should be constructed with 6" PVC (C900 CL. 150)
pipe or equivalent, and in accordance with the City's Water Design & Construction Manual.
5.2 Pressure Regulation
This water system does not require any pressure regulators or reducers for the on·-site public
water system. The individual buildings will require pressure reducers, to be determined by the
building plumbing engineer.
5.3 Meters
The domestic water system shall be looped and connected at two POCs with a 3" and a 2" public
water meter at each location. Each on-site unit shall be sub-metered to track individual water
usage.
D:\71472 Quarry Creek\Reports\Water\20150514, QC-R3, WATER STUDY.xlsx.docx 3
Exhibit A: Vicinity Map
£L CAMINO
COUNTRY CLUB
VICINITY lt{AP
NOT TO SCALE
THOMAS BROTHERS PG. 1107, GRID A-2
2006 EDmON
D:\71472 Quarry Creek\Reports\Water\20150514, QC-R3, WATER STIJDY.xlsx.docx
Exhibit B: EPANET Results & Site Map
, ____ 1
D:\71472 Quarry Creek\Reports\Water\20150514, QC-RJ, WATER STUDY.xlsx.docx
__ j
Page 1
PM
10/19/2015 6:31:03
**********************************************************************
* E P A N E T
*
* Hydraulic and Water Quality
*
* Analysis for Pipe Networks
*
* Version 2.0
*
**********************************************************************
Input File: R3 Domestic EPANET, UPC.net
Link -Node Table:
Link
ID
P1
P2
P3
P4
P5
P6
P8
P7
P9
Node
Node
ID
J1
J2
J3
J4
J5
J7
J6
POC2
POC1
Results:
Start
Node
J5
J1
J2
J3
J4
POC2
J7
JS
J6
Demand
GPM
21.00
5.00
8.00
12.00
42.00
0.00
0.00
-39.68
-48.32
End
Node
J1
J2
J3
J4
J1
J7
J2
J6
POC1
Head
ft
322.68
322.69
322.68
322.68
322.68
322.73
322.77
323.00
323.00
1
Pressure
psi
81.76
79.16
80.02
80.46
83.06
78,. 74
87.86
0.00
0.00
Length Diameter
ft in
265 6
175 6
240 6
185 6
280 6
43 3
155 6
275 6
25 3
Quality
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00 Reservoir
0.00 Reservoir
'
Link Results:
Link
ID
P1
P2
P3
P4
P5
P6
P8
Flow VelocityUnit Headloss Status
GPM fps ft/Kft
6.32 0.07 0.01 Open
-19.18 0.22 0.06 Open
15.50 0.18 0.04 Open
7.50 0.09 0.01 Open
-4.50 0.05 0.00 Open
39.68 1. 80 6.39 Open
39.68 0.45 0.22 Open
2
Page 2
Link Results: (continued)
Link
ID
P7
P9
Flow
GPM
-48.32
-48.32
VelocityUnit Headloss
fps ft/Kft
0.55
2.19
3
0.31
9.20
Status
Open
Open
I
I
I
a
I
~
• • .....
lEGEND
P.O. C.
@
PRIVATE DOAIESTIC WATER (4• P.V.C. MAIN)
PRIVATE FIR£ (s• P. V.C. MAIN)
PUBUC MAIN (12• P.V.C.)
INDIC4TES POINT OF CONNECTION
INDIC4TES JUNCTION
w .,,.. \
~
(j
d ~
(PUBliC) ( ) .. ~
' • I
'
~ c: .2
~
i .;.;. ....
~ ~
ti' t'lj
~
~ .... ~ ~
t " ~ ~ ~
~
WATEREXHBITFOR BB&JDU ~ ~ 10-20 1s OUARRY CREEK PLANNNG AREA R-3 i: ~ PLANNING ENGINEERING SURVEYING ~ " 71.illl7~An
I PRESSURE ZONE = JJO I