HomeMy WebLinkAboutCT 2018-0003; MAGNOLIA BRADY; STRUCTURAL CALCULATIONS FOR RETAINING WALL; 2019-05-08IMAGINE -INNOVATE -INTEGRATE
Structural Calculations
For
Design Retaining Wall
1534 Magnolia Avenue, Carlsbad CA 92008
Asthon 3, LLC Rancho Mission Viejo
Submitted: 05/08/2019
City reference numbers:
CT2018-0003
GR2019-0021
DWG515-3 LAND ).::Vr-: <., · • ,E._NT ---,} '\I) r:: . -Prepared For:
Civil Landworks
110 Copperwood Way, Suite P
Oceanside, CA 92058
760.908.8745
Prepared By:
...._, ..JJ."' ___ ......... Jt\,jG
SMR-ISD Consulting Structural Engineers, Inc.
1495 Pacific Highway, Suite 400
San Diego, CA 92101
619.294.6600
Design Engineer: Dmytro Karpenko
Principal Engineer: Farzad Heidari , S.E.
SMR-ISD Project No.: 2019-005
IMAGINE • INNOVATE • INTEGRATE
Magnolia Retaining Wall
Project
Structural Calculations
Subject
Table of Contents
201 9-005
Project No.
DK
By
1495 Pacific Hwy, Suite 400
San Diego, CA 92101
smrconsultinggroup.com
05/08/2019
Date
P 619.294.6600
F 619.294.6800
I Page: 2 I Of: 14
Table of Contents ............................................................................................................................................................ 2
PROJECT DESCRIPTION .................................................................................................................................................... 3
Scope of work .............................................................................................................................................................. 3
Gravity Load Res isting System ..................................................................................................................................... 3
Lateral Load Resisting System ..................................................................................................................................... 3
Basis of Design ............................................................................................................................................................. 5
Codes ....................................................................................................................................................................... 5
Loads ........................................................................................................................................................................ 5
Foundations ............................................................................................................................................................. 5
Materials .................................................................................................................................................................. 5
Lateral Load Cases ........................................................................................................................................................... 6
Seismic Parameters ..................................................................................................................................................... 6
Seismic Forces -Non-Structural Elements ................................................................................................................... 9
Retaining Wall Design .................................................................................................................................................... 10
Wall Dead Loads ........................................................................................................................................................ 10
Seismic Loads ............................................................................................................................................................. 10
Surcharge Loads ......................................................................................................................................................... 10
Final Design Drawing ................................................................................................................................................. 14
IMAGINE · INNOVATE · INTEGRATE
Magnolia Retaining Wall
Project
Structural Calculations
Subject
PROJECT DESCRIPTION
Scope of work
Retaining Wall Package:
2019-005
Project No.
DK
By
1495 Pacific Hwy, Suite 400
San Diego, CA 92101
smrconsultinggroup.com
05/08/2019
Date
P 619.294.6600
F 619.294.6800
I Page: 3 I Of: 14
The scope of this calculation package includes the design of one type retaining walls for a property in Carlsbad
based on the Civil Engineering drawings dated 01/13/2019 issued by Civil Landworks. Height for this wall with
approximately 4.0 ft. retaining height.
Gravity Load Resisting System
Foundation System:
The foundation system consists of a standard continuous footing to resist earth pressure.
Wall:
The retaining wall section will be designed using reinforced CMU.
Lateral Load Resisting System
Lateral Resisting System:
The lateral loads caused by seismic forces and soil pressures will be resisted by the retaining wall, and
subsequent overturning forces will be resisted by the footing. Sliding forces will be resisted by the foundation
key.
S1'J R~
IMAGINE •INNOVATE • INTEGRATE
Magnolia Retaining Wall
Project
Structural Calculations
Subject
Civil ll!landworks
11DCOH'f:IIWOODW,tV l!Ul'T£• OC0.'1310f CAIIIM'
-l'IO'J01114•~--
2019-005
Project No.
DK
By
1495 Pacific Hwy, Suite 400 P 619.294.6600
San Diego, CA 92101 F 619.294.6800
smrconsultinggroup.com
05/08/2019 I Page: 4 I Of: 14
Date
Location Retaining Wall on the plan of Civil Engineering Drawings
.,
f, 1,s.t:·1•,•, ,.,.
..
Profile with section Retaining Wall
1495 Pacific Hwy, Suite 400
San Diego, CA 92101
smrconsultinggroup.com
P 619.294.6600
F 619.294.6800
lt.lAGIME • INNOVATE • INTEGRATE
Magnolia Retaining Wall
Project
Structural Calculations
Subject
Basis of Design
Codes
2016 California Building Code
Loads
GRAVITY LOADS:
a) Dead & Soil Loads
b) Surcharge Loads
LATERAL LOADS:
SEISMIC:
Risk Category:
Method:
Latitude:
Longitude:
Ss
S1
2019-005
Project No.
DK
By
Foundations
Soils report by:
Date:
GEOCONINCORPORATED
January 17, 2018
Project No.: J.N.: G2192-52-01
*Loads may be increased by 1 /3 for short term loading.
Active soil pressure:
Additional active soil pressure for 2: 1 (H:V) sloping backfill:
Passive soil pressure:
Coefficient of Friction:
Materials
CONCRETE:
Design compressive strength at 28 days shall be as follows:
Footings:
MASONRY:
8" Medium-weight CMU
REINFORCING STEEL:
(ASTM A615 Grade 60)
05/08/2019 I Page: 5 I Of: 14
Date
See the following pages
See the following pages
II
Non-Structural Elements
33.1581 degrees
-117.3310 degrees
1.127 g
0.433 g
35 pcf
50 pcf
350 pcf
0.35
fc' = 3,000 psi
fm' = 1,900 psi
fy = 60 ksi
IMAGI NE • INNO VATE • INTE GRATE
Magnolia Retaining Wall
Project
Structural Calculations
Subject
Lateral Load Cases
Seismic Parameters
f.!.C?.m.~.C?.i.l .. R~P.C?.!1.:.
2019-005
Project No.
DK
By
1495 Pacific Hwy, Suite 400
San Diego, CA 92101
smrconsultinggroup.com
05/08/2019
Date
P 619.294.6600
F 619.294.6800
I Page: 6 I Of: 14
TABLE 7.5.1
2016 CBC SEISMIC DESIGN PARAMETERS
Parameter Value 2016 CBC Reference
Site Class C Section 1613.3.2
MCER Ground Motion Spectral 1.127g Figure 1613.3.1(1) Response Acceleration -Class B (short), Ss
MCER Ground Motion Spectral 0.433g Figure 1613.3.1(2) Response Acceleration -Class B ( I sec), S,
Site Coefficient, F" 1.000 Table 1613 .3.3(1)
Site Coefficient, Fv 1.367 Table 1613.3.3(2)
Site Class Modified MCER Spectral 1.127g Section 1613.3.3 (Eqn 16-3 7) Response Acceleration (short), SMs
Site Class Modified MCER Spectral 0.592g Section 1613.3.3 (Eqn 16-38) Response Acceleration ( I sec), SM,
5% Damped Design Spectral 0.751g Section 1613.3.4 (Eqn 16-39) Response Acceleration (short), Sos
5% Damped Design Spectral 0.395g Section 1613.3.4 (Eqn 16-40) Response Acceleration ( 1 sec), So,
1495 Pacific Hwy, Suite 400
San Diego, CA 92101
smrconsultinggroup.com
P 619.294.6600
F 619.294.6800
IMAGINE • INNOVATE · INTEGRATE
Magnolia Retaining Wall 2019-005
Project
Structural Calculations
Project No.
DK 05/08/2019 I Page: 7
Subject
Address:
1534 Magnolia Ave
Carlsbad, California
92008
Wind
Results:
Wind Speed:
10-year MRI
25-year MRI
50-year MRI
100-year MRI
Data Source:
Date Accessed:
By Date
ASCE 7 Hazards Report
Standard: ASCE/SEI 7·10
Risk Category: 11
Soil Class: C -Very Dense
Soil and Soft Rock
110Vmph
72 Vmph
79 Vmph
85 Vmph
91 Vmph
Elevation: 149.73 ft (NAVO 88)
Latitude: 33.158145
Longitude: -117.331043
' r
ASCE/SEI 7-10, Fig. 26.5-lA and Figs. CC-1-CC-4, incorporating errata of
March 12, 2014
Mon Jan 21 2019
Value provided is 3-second gust wind speeds at 33 ft above ground for Exposure C Category, based on linear
interpolation between contours. Wind speeds are interpolated in accordance with the 7-1 O Standard. Wind speeds
correspond to approximately a 7% probability of exceedance in 50 years (annual exceedance probability :
0.00143, MRI • 700 years).
Site Is not In a hurricane-prone region as defined in ASCE/SEI 7·10 Section 26.2.
Mountainous terrain, gorges, ocean promontories, and special wind regions should be examined for unusual wind
conditions.
I Of: 14
IMAGINE · INNOVATE -INTEGRATE
Magnolia Retaining Wall
Project
Structural Calculations
Subject
ASCE.
Seismic
2019-005
Project No.
DK
By
1495 Pacific Hwy, Suite 400
San Diego, CA 92101
smrconsultinggroup.com
05/08/2019
Date
Site Soll Class: C -Very Dense Soil and Soft Rock
Results:
Ss :
s,:
F. :
F. :
SMs
SMt :
1.128
0.433
1.367
1.128
0.592
Seismic Design Category D
1.2
r!
10 t
MCER Response Spectrum
Sos :
So, :
T, :
PGA :
PGA u:
FroA
1.
06
0.7 ., • 06 ♦
0.752
0.395
8
0.443
0.443
1
Design Response Spectrum
::. \
02 '-
P 619.294.6600
F 619.294.6800
I Page: 8 Im 14
~~ ~. --------0.1 ---------~~~~~ o ~
0 2 ~ 4 Sa (g) VS T(s)
Data Accessed:
Date Source:
0
Mon Jan 21 2019
0 ~
0 2 ~ 4 Sa (g) VS T(s) 6
USGS Seismic Design Maps based on ASCE/SEI 7-10, incorporating
Supplement 1 and errata ol March 31, 2013, and ASCE/SEI 7-1 0 Table 1.5-2.
Additional data for site-specilic ground motion procedures in accordance with
ASCE/SEI 7-10 Ch. 21 are available from USGS.
0
S,'J R~ 1495 Pacific Hwy, Suite 400 P 619.294.6600
San Diego, CA 92101 F 619.294.6800
smrconsultinggroup.com
IMAGI NE • INNOVATE · INTEGRATE
Magnolia Retaining Wall 2019-005
Project Project No.
Structural Calculations DK 05/08/2019 I Page: 9 lof: 14
Subject By Date
Seismic Forces -Non-Structural Elements
Short period spectral acceleration;
Component seismic importance factor;
Sos= 0.751 ; g;
Ip= 1.0; Section 11 .5.1 /Table 1.5-2;
Seismic Demands on Non-Structural Components
Seismic Design Force:
Fp_component = 0.4aoSosWp • [1 + 2(z/h)];
(Rp/lp);
Need not exceed:
Fp_oomponent_max = 1 .6*S□s*lp = 1.20; Wp;
Shall not be less than:
F p_oomponent_min = 0.3*S□s*lp = 0.23; Wp;
Where:;
ap = Component Amplification Factor;
Rp = Component Response Modification Factor;
Z = Height in structure at point of attachment of component;
h = Average roof height of structure relative to the base elevation;
Wp = Wall weight/ Component operating weight;
Element.Analyzed: ............................................. Site .Retainin.9. Wall
Component Amplification Factor:;
Component Response Modification Factor:;
Component Height:;
Structure Height:;
Fp = (0.4 *ap*S□s*(1 +2*(z/h)))/(Rp/lp)=0.12; W p;
ap = 1.0;
Rp = 2.5;
z = O;
h =1 ;
Fp= min(Fp_component_max,max(Fp,Fp_component_min)) = 0.23;
Section 13.3.1 ;
Tables 13.5-1 & 13.6-1 ;
Tables 13.5-1 & 13.6-1 ;
IMAGINE • INNOVATE • INTEGRATE
Magnolia Retaining Wall
Project
Structural Calculations
Subject
Retaining Wall Design
2019-005
Project No.
DK
By
1495 Pacific Hwy, Suite 400
San Diego, CA 92101
smrconsulti nggrou p. com
05/08/2019
Date
P 619.294.6600
F 619.294.6800
I Page: 10 I Of 14
The acceptance criteria for Sliding and Overturning safety factors under seismic load is 1.1 per CBC section 1807.2.3.
Per soils report recommendation, additional active soil pressure of 50 pcf is added to account for the 2: 1 (H :V) sloping backfi ll;
therefore, the backfill slope is entered as O in the Retain Pro analysis.
7.10 Retaining Walls
7.10.1 Rc1aining walls not restrained at 1he top and having a level backfill surface should be
designed for an active soil pressure equivalent to the pressure exerted by a nuid with a
density of 35 pounds per cubic foot (pcf). Whcr.: the backfill will Ix inciin.:tl at nu steeper
than 211: IV. an acti\'e soil pressure of 50 pcf is rccommcmlcd. These soil pressures assume
that the backfill materials within an area bounded by the wall and a I: I plane extending
upward fro m the base of the wall possess an expansion index of 50 or less.
Wall Dead Loads
Wall Thickness;
Weight of Wall (CMU 8'');
Height of Wall;
Total Weight of Retaining Wall;
Fp from Stem Self Weight;
Seismic Loads (Self-Weight);
Seismic Loads
t = 8.0 in;
Wp.Wall = 78.0 psf;
H = 4.67 ft;
Wp = Wp,Wall • H = 364.3 plf;
Fp = 0.23;
Fp,Wall = Fp • WoL.w = 17 .9 psf;
Per soils report wall is exempt from seismic earth pressures because retained height is less than 6'-0".
7, 10.3 The structural engineer should dctcnninc the seismic design category for the project. If the
project possesses a seismic design category of D, E, or F. the proposed retaining walls
should be designed with seismic lateral pressure. A ·eismic load of 16H p f hould be used
for design of walls that uppon m re than 6 li:e1 of backfill in accordance with
ection I 03.5 I:! of the 2016 DC. The seismic loud is dependent on the retained height
Surcharge Loads
Assumed height existing CMU 8" retaining Wall;
Assumed height existing concrete footing;
Assumed width existing concrete footing;
Applied width line loads;
Loads from adjacent free-standing existing retaining wall;
Distance back of stem to centre line of existing wall ;
Assumed footing base below retained height;
Hw = 8.0 ft;
t=1.5ft;
b = 2.5 ft;
w = 1.0 ft;
q = (Wp,Wall * Hw + t * b * 150 pcf) * w = 1187 lb;
e = 1.55 ft;
h = 2.16 ft;
Use 8" Solid Grouted CMU wall w/ #4@16" O.C. Vertical & #4@24 O.C. Horizontal -w/ 4'-0" wide Continuous
Footing w/ #4@16" O.C. Top & Bottom [see.RETAIN.PRO Output Below for Desi_gn}
IMAGINE ·INNOVATE · INTEGRATE
Magnolia Retaining Wall
Project
Structural Calculations
Subject
Pp= 1148.44#
2019-005
Project No.
DK
By
1495 Pacific Hwy, Suite 400
San Diego, CA 92101
smrconsultinggroup.com
05/08/2019
Date
Adj Ftg Load =1187#
Ecc.=8" from CL
Wall Loading
P 619.294.6600
F 619.294.6800
/Page: 11 jot: 14
786# 59#
IMAGINE • IN NOVATE • INTEGRATE
Magnolia Retaining Wall
Project
Structural Calculations
Subject
2019-005
Project No.
DK
By
1495 Pacific Hwy, Suite 400
San Diego, CA 92101
smrconsultinggroup.com
05/08/2019
Date
P 619.294.6600
F 619.294.6800
I Page: 12 I Of: 14
~1~~~~:',0~-1,!~~;:• Build 11·18·06.3° Cantilevered Retaining Wall
License To : SMR CONSUL TING GROUP Code: IBC 2015.ACI 318-14,ACI 530-13
..,I c.r.it.e.ri_a _________ l I Soil Data I
Retained Height = 4.00ft
Wall height above soil = 0.67 ft
Slope Behind Wall = 0.00
Height of Soil over Toe = 12.00 In
Water height over heel = o.o ft
I Surcharge Loads
Surcharge Over Heel = 0.0 psf
Used To Resist Sliding & Overturning
Surcharge Over Toe = 0.0
Used for Sliding & Overturning I Axial Load Applied to Stem
Axial Dead Load • 0 0 lbs
Axial Live Load = 0.0 lbs
Axial Load Eccentrlcily = 0.0 In
I Stem Weight Seismic Load
Allow Soll Bearing = 2,000.0 psf
Equivalent Fluid Pressure Method
Active Heel Pressure = 50.0 psfin
Passive Pressure
Soil Density, Heel
Soil Density, Toe
FoolingllSoil Friction
Soll height to Ignore
for passive pressure
= 350.0 psflft
= 110.00 pd
• 110.00 pcf
= 0.350
= 12.00 In
I
• I Lateral Load Applied to Stem • I Adjacent Footing Load
■
Lateral Load
... Height to Top
... Height to Bottom
Load Type
O.O#lft
0.00 ft
0.00ft
• Seismic (E)
(Service Level)
Wind on ExPOsed Stem =
(Sttength Level)
0.0 psf
I Fp / WP Weight Multiplier = 0.230 g
ACJacent ~oollng Load
Footing Width
Eccentricity
Wall to Fig CL Dist
Footing Type
Base Above/Below Soil
at Back of Wall
Poisson's Ratio
Added seismic base force
I Design Summary
Wall Stability Ratios
Overturning • I Stem Construction • Bottom
Stem OK
Sliding
Total Bearing Load
... resultant ecc.
2.33 OK
2.09 OK
1,762 lbs
6.56 In
Design Height Above Ftg
Wall Material Above "HI"
Design Molhod
Thickness
RebarS,ze
Rebar Spacing
Rebar Placed Ill
ft= 0.00
= Masonry
= LRFD = 8.00
= II 4
= 16.00
= Center
1, 1ar.0 lbs
2.50 ft
8.00 In
1.55 ft
Line Load
-2.2 ft
0.300
58.6 lbs
I
Soil Pressure @ Toe • 974 psi OK
Soil Pressure @ Hool = 32 psi OK Design Data -------------------------
Allowable = 2,000 psi
Soll Pressure Less Than Allowable
ACI Fact0<ed @Toe = 1.364 psi
ACI Fact0<ed @ Heel = 45 psf
Footing Shear @ Toe =
Footing Shear @ Heel =
Allowable =
Sliding Cales
La1eral Sliding Force =
less 100% Passive Force =
less 100% Friction Force =
Added Force Req'd =
... .for 1.5 Stability =
7.7 psi OK
2.5 psi OK
82.2 psi
844.6 lbs
1.148.4 lbs
616.8 lbs
0.0 lbs OK
0.0 lbs OK
Vertical 00<nponent of active lateral soil pressure IS NOT
considered in the calculation of soil bearing pressures.
Load Factors ------------
Building Code
Dead Load
Live Load
Earth,H
Wind, W
Seismic, E
IBC 2015,ACI
1.200
1.600
1.600
1.000
1.000
fb/FB + fa/Fa
Total Force@ Section
Service Level
Strength Level
Moment .... Actual
Service Level
Strength Level
Moment. .... Allowable
Shear ..... Actual
Service Level
Slrenglh Level
Shear ..... Allowable
Anet (Masonry)
Rebar Depth 'd'
= 0.491
lbs=
lbs• 843.8
n-#•
n-# = 1.151.9
= 2,346.2
psi=
psi= 9.2
psi" 78.5
ln2= 91.50
In= 3.75
Masonry Data -------------------------
r m
Fy
Solid Grouting
Modular Ratio 'n'
Wall Weight
Equiv. Solid Thick.
Masonry Block Type
Masonry Design Method
psi=
psi=
" =
psi=
in=
=
=
1.900
60,000
Yes
16.96
78.0
7.60
Medium Weight
LRFD
Concrete Data ------------------------re psi=
Fy psi=
Sl',R~ 1495 Pacific Hwy, Suite 400 P 619.294.6600
San Diego, CA 92101 F 619.294.6800
smrconsultinggroup.com
IMAGINE • INNOVATE • INTEGRATE
Magnolia Retaining Wall 2019-005
Project Project No.
Structural Calculations DK 05/08/2019 I Page: 13 !or 14
Subject By Date
RetafnPro (c) 1987-2018, Build 11.18.06.30
LlcanH : KW.()6056873
License To : SMR CONSUL TING GROUP
Cantilevered Retaining Wall Code: IBC 2015.ACI 318-14,ACI 530-13
I Footing Dimensions & Strengths
Toe Width
Heel Width
Total Footing Width
Footing Thickness
Key Width
Key Depth
Key Distance from Toe
2.17ft
1.33
3.50
15.00in
12.00 In
6.00 in
0.00ft
re " 3,000 psi Fy = 60,000 psi
150.00 pcf
0.0018
Footing Concrete Density
Min.As ¾
Cover@Top 2.00 @ Btm.= 3.00 In
t Footing Design Results I
Toe Heel
Factored Pressure 1,364 45 psf
Mu' : Upward = 2,570 29 fl-#
Mu' : Downward 970 251 ft-#
Mu: Design 1,600 222 ft-#
Actual 1-Way Shear 7.71 2.49 psi
Allow 1-Way Shear 43.82 43.82 psi
Toe Reinforcing # 4@ 16.00 in
Heel Reinforcing # 4 @ 16.00 in
Key Reinforcing None Spec'd
Other Acceptable Sizes & Spacings
Toe: Not req'd: Mu< phi•5•1ambda'sqrt(fc)"Sm
Heel: Not req"d: Mu< phi•5•1ambda"sqrt(fc)"Sm
Key: Not req'd: Mu < phi.5'1ambda'sqrt(fc)'Sm
Min footing T&S rein! Area 1.13 in2
0.32 ln2 ,ft Min rooting T&S reinf Area per foot
If one layer of horizontal bars:
#4@ 7.41 in
#5@ 11.48 in
#6@ 16.30 In
If two layers of horizontal bars:
#4@ 14.81 in
#5@22.96 in
#6@32.59 In
I Summarv of Overturnina & Resistina Forces & Moments
Item
Heel Active Pressure
Surcharge over Heel
Surcharge Over Toe
Adjacent Footing Load
Added Lateral Load =
Load @ Stem Above Soil =-
Seismic Stem Self Wt
Total
Reslstlng/Overtumlng Rallo
..... OVERTURNING .....
Force Distance Momeni
lbs ft ft-#
689.1
96.9
58.6
844.6
1.75
1.80
3.59
O.T.M.
1,205.9
174.4
210.2
1,590.5
Vertical Loads used for Soil Pressure ~
2.33
1.762.2 lbs
Soll Over Heel
Sloped Soil Over Heel
Surcharge Over Heel
Adjacent Footing Load
Axial Dead Load on Stem =
• Axial Live Load on Stem
Soil Over Toe
Surcharge Over Toe
Stem Weight(s) =
Earth @ Stem Transitions"
Footing Weight
Key Weight =
Vert. Component
..... RESISTING .....
Force Distance
lbs ft
293.2 3.17
134.3 3.17
238.7 1.09
364.3 2.50
656.8 1.75
75.0 0.50
Moment
ft-#
929.4
425.7
259.0
91 1.9
1,150.4
37.5
Total = 1,762.2 lbs R.M." 3,713.8
If seismic is included, the OTM and sliding ratios
be 1.1 per section 1807.2.3 of IBC 2009 or IBC 201
Vertical component of active lateral soil pressure IS NOT considered in
the calculation of Sliding Resistanoe.
Vertical component of active lateral soil pressure IS NOT considered in
the calculation of Overturning Resistance.
I Tilt I
• Axial live load NOT included in total displayed, or used for overturning
resistance, but is included for soil pressure ca1culation.
Horizontal Deflect;on at Top of wan due to settlement of son
(Denection due to wall bending not considered)
Soll Spring Reaction Modulus
Horizontal Defi @ Top of Wall (approximate only)
250.0 pcl
0.036 in
The above calculation is nol valid if the heel soil bearing pressure exceeds that of the toe
because the wall would then tend to rotate Into the retained soil.
I
IMAGINE· IN NOVATE · INTEGRATE
Magnolia Retaining Wall
Project
Structural Calculations
Subject
Final Design Drawing
1495 Pacific Hwy, Suite 400
San Diego, CA 92101
smrconsultinggroup.com
2019-005
Project No.
DK
By
#4@24•0.c.
(HORIZ.)
#4@16"0.C.
(VERT.)
8" CMU WALL FULLY i GROUTED
FINISHED PAVING 5' ..,.
PROPERTY LINE
EXISTING SITE
WALL
2'-0"
1'-~·
EQ.
05/08/2019
Date
I
I
I
I
11 I
I
I
I
I
I
RETAINING WALL
DRAIN SYSTEM PER
GEOTECH REPORT
#4@12"0.C.
3" 3"
CLR. 1'-0" CLR.
3'-6'
Retaining Wall Detail
P 619.294.6600
F 619.294.6800
!Page: 14 lot: 14