May 31, 1973
, Subject: Project No. 73-3-16BC
Gentlemen:
Review of Pre I iminary Grading Plan
Spanish Village Units 1 and 2
Rancho La Costa
Carlsbad, Cal ifornia
TEI,EPHONE (714) 565·1955
In ac:cordance with the request made by Mr. Sam Gaines of Rick Engineering in San Diego,
California, a review was made of the preliminary grading plem prepared by Rick Engineering
of San Diego and dated April 2, 1973 with a revision on May 23, 1973. The preHminarygrad-
ing plan shows a total of 129 lots easterly of Borings 4 and 11 described in our report da'ted
May 10, 1973.
Generally ,the proposed cut and fill slopes shown on the grading plari are feqsible ,from slope
stabiLity poirH of view except the proposed 2 horizontal to 1 vertical cut slope southerly of
So ~~!.1b.!,.e.r.ge.<;?!,~d~~~,QY~Qllqrl."w.iI Ls_':!tlb.'.2J.!eh.2..p-t~s I~I id~g.~~ in
the_tc:e ar~a of.,,!b~.lope. It l~.J.,~~§.~tTJe_C:Rromended:"that-t.bfoLp.tQP"Q'§'~ ,~ut slo~e i~ !?! area
be cJian9!S!..~!:S9LltQLta.L.v..eI.tl.cJ;1J_Q!'.it~~ltte r •
;In lieu of this, th~P-tmo~~~~lid~.qEm~t,!llg)!.l?~_Q.Y..eJ:excavg.ted .... to.,Q,"d.ist,ance . .equ.(.v.alent to
the ~-o,f-Gu.t-er-9r.e.oter inside th@..P...me.g§ed ... .£il.I"'slg~_s<~,C_e and then re.compacted to a 2
horizontal to ]_v.e.r.tJ&~ql..!!'(lbil ized fill slQpes. Th is area should be carefu J1y ~xamjned Py an
engin~ering geologist during .... g(c;d"Tn'9·in C;;der to determine the ·Iateral extent and geometric
configuration of the landslided zone. Detailed slope stobilHy analysis based on the geometric
configuration of the landsl-ided mass should be performed to determine the 'required thickness of
the stabilized fills and the necessity of a shear key for the fill slope. The recommended thickness
of overex~avation may have te be adjusted in accordance with the findings of the slope stability
analysis.
Respectfully submitted,
BENTON ENGINEERING, INC.
Fsviewed ~,~