LABORATORY NUMBER SD38-3723 DATE November 22, 1983
Job No. 1763
(Graham T FaIor_A:trport RDad
Carlsbad, California 92008
Attention: Mr. Mike Loban
Project: Graham International II
2111 Palomar Airport Road -
Carlsbad, California
Subject: Material sampled by Testing Engineers-San Diego personnel
- and submitted to the laboratory on 11/17/83, identified • as: Class II Aggregate Base Course; Secured from: jobsite
• South Coast Asphalt.
Procedure: Moisture density relations of soil, tested in accordance
with ASIM D-1557, Method C.
Results: M/D No. 1
Dry weight per cubic foot
Percent moisture
Maximum dry density, lbs./cu. ft.
Optimum moisture content, %
#1 #2 #3
132.2 135.6 131.7
5.4 7.2 9.3
135.8
6.7%
TESTING ENGINEERS-SAN DIEGO
Reviewed by:
[eII
(1) Graham International
(1) Hope Consulting Group
(1) Atkinson, Johnson & Spurner
(1) N.H. Golden Construction Co.
(1) City of Carlsbad Bldg. Inspec. Dept.
r J Testing Engineers—San Diego
_____ 3467 Kurtz St., P0. Box 80985, San Diego, Ca. 92138 (619) 225-9641
( j 2948 Industry Street, Suite B, Oceanside, Ca. 92054 (619) 758m37310
~/ vm5 -
I m
DAILY RESULTS- IN PLACE DENSITY TESTS
DATE OF TEST 11/17/83 . LOCATION Prkfi11 E" Wrr Tine Trpn'h
FILE No. 1763 . PROJECT GrahamInternationalII -
LAB. No._SD38-3724 DATE OF REPàRT —CONTRACTOR M.H.Golden Construction
TEST
NO. L 0 C A T I 0 N
IN
PLACE
MOIST.
OPTIMUM
MOIST.
IN PLACE
DRY
DENSITY
MAX. DRY
DENSITY
PERCENT
REL. COMP.
REQUIRED
PERCENT
RELATIVE
COMP.
REMARKS
1
At the parking lot north of new struc-
ture,20'southofnorthwestcorner 7.8 6..7 140.6 135.,8 95 100 Complies
•
_2
At the parking lot north of new struc-
ture, 100' south of northwest corner 7.4 6.7 140.9. 135.8 95
-
100 Complies
• . 1
THE ABOVE TEST RESULTS AND CALCULATIONS CONSTITUTE THE REPORTING OF FACTUAL DATA DERIVED FROM
TESTS MADE BY TESTING ENGINEERS. SAN DIEGO. FOLLOWING ASTM STANDARDS OR SPECIFIED PROCEDURES. -
THESE RESULTS SHOULD NOT BE INTERPRETED AS ENGINEERING OPINION OR JOB CONTROL.
(1) Graham International . TESTING ENGINEERS-SAN DIEGO
(1) Hope Consulting Group REVIEWED BY
(1) Atkinson, Johnson & Spurner
(1) M.H. Golden Construction Co.
(1) City of Carlsbad Bldg. Inspec. Dept.