HomeMy WebLinkAboutCT 2017-0002; TYLER STREET RESIDENCES; 3337 TYLER STREET NOISE ASSESSMENT IN CARLSBAD CA; 2017-04-03Ldn Consultlng, rnc:.
42428 Chisolm Trail, Murrieta CA 92562
www.ldnconsulting.net
April 3, 2017
Elizabeth Lagrua
Tyler Street Development, LLC
4459 Hackett Avenue
Lakewood, CA 90713
phone 760-473-1253
fax 760-689-4943
APR 1 3 2017
CITY o:~ C ·:l.' /·O
Subject: 3337 Tyler Street Noise Assessment in Carlsbad CA
The firm of Ldn Consulting, Inc. is pleased to submit the following noise impact analysis for
the proposed 3337 Tyler Street residential development in the City of Carlsbad. The purpose
of the survey is to determine the estimated exterior and interior noise levels within the
outdoor areas of the project site and within the residential structures and recommend
mitigation measures for compliance with the California Code of Regulations Title 24 and the
City of Carlsbad guidelines and requirements for noise.
PROJECT LOCATION/DESCRIPTION
The proposed site is located on approximately 0.34 acres and consists of eight (8) multi-family
residential dwelling units in two three-story buildings. The proposed project is located at 3337
Tyler Street, west of Interstate 5 in the City of Carlsbad, CA.
The primary noise source that affects the site is the San Diego Northern Railway (SDNR) located
approximately 205 feet east of the site as can be seen in Figure 1. The project site
configuration is provided in Figure 2 below.
ACOUSTICAL FUNDAMENTALS
Noise is defined as unwanted or annoying sound which interferes with or disrupts normal
activities. Exposure to high noise levels has been demonstrated to cause hearing loss. The
individual human response to environmental noise is based on the sensitivity of that individual,
the type of noise that occurs and when the noise occurs.
4/3/2017 1 1657-05 3337 Tyler Street Noise Report
Elizabeth Lagrua
Tyler Street Development, LLC
4459 Hackett Avenue
Lakewood, CA 90713
4/3/2017
Figure 1: Project Site Location
2
Ldn ConMJ/t/1111, Inc.
42428 Chisolm Trail
Murrieta CA 92562
phone 760-473-1253
1657-05 3337 Tyler Street Noise Report
Elizabeth Lagrua
Tyler Street Development, LLC
4459 Hackett Avenue
Lakewood, CA 90713
Ldn CoMu/111111, Inc.
42428 Chisolm Trail
Murrieta CA 92562
phone 760-473-1253
Figure 2: Proposed Project Site Plan
4/3/2017
1 r I f I~
i .. ll
-.. ' •
' i i
I
I
' I t j
: • l : I I I
I j I
I · I
1 I 1 I 11
I ii I •
I kl I 1
3
'-. R F f,' 'f'
I'
' •
1657-05 3337 Tyler Street Noise Report
Elizabeth Lagrua
Tyler Street Development, LLC
4459 Hackett Avenue
Lakewood, CA 90713
Ldn CoMult/1111, Int:.
42428 Chisolm Trail
Murrieta CA 92562
phone 760-473-1253
Sound is measured on a logarithmic scale consisting of sound pressure levels known as a
decibel (dB). The sounds heard by humans typically do not consist of a single frequency but of
a broadband of frequencies having different sound pressure levels. The method for evaluating
all the frequencies of the sound is to apply an A-weighting to reflect how the human ear
responds to the different sound levels at different frequencies. The A-weighted sound level
adequately describes the instantaneous noise whereas the equivalent sound level depicted as
Leq represents a steady sound level containing the same total acoustical energy as the actual
fluctuating sound level over a given time interval.
The Community Noise Equivalent Level (CNEL) is the 24 hour A-weighted average for sound,
with corrections for evening and nighttime hours. The corrections require an addition of 5
decibels to sound levels in the evening hours between 7 p.m. and 10 p.m. and an addition of
10 decibels to sound levels at nighttime hours between 10 p.m. and 7 a.m. These additions
are made to account for the increased sensitivity during the evening and nighttime hours
when sound appears louder. CNEL values do not represent the actual sound level heard at any
particular time, but rather represents the total sound exposure.
Additionally, Sound Transmission Class (or STC) is an integer rating of how well airborne
sound is attenuated by a building partition. STC is widely used to rate interior partitions,
ceilings/floors, doors, windows and exterior wall configurations (see ASTM International
Classification E413 and E90). The STC number is derived from tested sound attenuation values
found at the 1/3 octave band frequencies. These transmission-loss (TL) values are then
plotted and compared to a standard reference contour. Acoustical engineers fit these values to
the appropriate TL Curve to determine a single STC value found at 500 Hertz. STC is roughly
the decibel reduction in noise a partition can provide, abbreviated 'dB'.
If an 85 dB sound on one side of a wall is reduced to 50 dB on the other side, that partition is
said to have an STC of 35. This number does not apply across the range of frequencies
because the STC value is derived from a curve-fit from the tested 1/3 octave band
frequencies. Any partition will have less TL at lower frequencies. For example, a wall with an
STC of 35 may provide over 40 dB of attenuation at 3000 Hz but only 15 dB of attenuation at
125 Hz.
4/3/2017 4 1657-05 3337 Tyler Street Noise Report
Elizabeth Lagrua
Tyler Street Development, LLC
4459 Hackett Avenue
Lakewood, CA 90713
NOISE STANDARDS
City of Carlsbad Noise Standards
Ldn Conllult/1111, me.
42428 Chisolm Trail
Murrieta CA 92562
phone 760-473-1253
The City of Carlsbad's General Plan Noise Element requires that all exterior sensitive areas
shall limit noise exposure. For noise sensitive residential land uses, the City has adopted a
policy which has established a "normally acceptable" exterior noise level goal of 60 dBA CNEL
for the outdoor areas and an interior noise level of less than 45 dBA CNEL. However, the City
has also established a "conditionally acceptable" policy goal of up to 65 dBA CNEL for
residential land uses. For residential properties identified as requiring a noise study, a study
shall be prepared by an acoustical professional. This study shall document the projected
maximum exterior noise level and mitigate the projected exterior noise level to a maximum
allowable noise level.
Interior noise levels should be mitigated to a maximum of 45 dBA CNEL in all habitual rooms
when the exterior of the residence are exposed to levels of 60 dBA CNEL or more. If windows
and doors are required to be closed to meet the interior noise standard, then mechanical
ventilation shall be provided per City requirements.
California's Title 24 Noise Standards
The California Commission on Housing and Community Development adopted noise insulation
standards for multi-family residential buildings (Title 24, Part 2, California Code of Regulations
or CCR). CCR Title 24 establishes standards, based on the U.S. Department of Housing and
Urban Development (HUD) requirements, for interior room noise (attributable to outside noise
sources).
The regulations also specify that acoustical studies must be prepared whenever a multi-family
residential or motel/hotel building or structure is proposed to be located near an existing or
adopted freeway route, expressway, parkway, major street, thoroughfare, rail line, rapid
transit line, or industrial noise source, and where such noise sources create an exterior CNEL
(or Ldn) of 60 dBA or greater. Such acoustical analysis must demonstrate that the residence
has been designed to limit intruding noise to an interior CNEL (or Ldn) of at least 45 dBA.
4/3/2017 5 1657-05 3337 Tyler Street Noise Report
Elizabeth Lagrua
Tyler Street Development, LLC
4459 Hackett Avenue
Lakewood, CA 90713
ANALYSIS PROCEDURES
Exterior Noise Levels
Ldn eon.ult/1111, Inc.
42428 Chisolm Trail
Murrieta CA 92562
phone 760-473-1253
Noise measurements were taken at the site using a Larson-Davis Model LxT Type 1 precision
sound level meter. The noise level meter was programmed in "slow" mode and set to record
noise levels in "A" weighted form. The sound level meter and microphone were mounted on a
tripod, five feet above the ground and equipped with a windscreen during all measurements.
The sound level meter was calibrated before and after the monitoring using a Larson-Davis
calibrator, Model CAL 200. The site was monitored in 1-minute intervals or increments so the
train activities could be easily identified. The noise measurement was conducted along the
Coastal Rail trail between the rail line and the subject property during a train pass-by to
determine the noise levels from the train activity. The result of the noise level measurement is
presented in Table 1.
West of project facing
Rail right-of-way
Table 1: Measured Train Noise Levels
September 22, 2016 77 .7 92.6 48.2 73.3 51.8 48.8
Due to the proximity of the noise measurement to the railroad the overall sound level was
found to be 77.7 dBA CNEL for a single event lasting less than 2-minutes. Based on existing
train schedules, the peak hourly traffic volume is expected to be four (4) trains per hour. The
statistical indicators Ll0, LS0, and L90, are also given. Based on the L90 data, 90% of the
time the noise level is below 49 dBA due to very low traffic volumes adjacent to and around
the site. The San Diego Northern Railway (SDNR) segment adjacent to the project site is
utilized for both commuter trains (Coaster and Surfliner) and a few freight trains. As can be
seen from the Lmax data, the train horn at a nearby grade crossing was 92.6 dBA. The noise
levels at the site are relatively low but the train noise elevates the overall noise levels above
60 dBA CNEL.
4/3/2017 6 1657-05 3337 Tyler Street Noise Report
Elizabeth Lagrua
Tyler Street Development, LLC
4459 Hackett Avenue
Lakewood, CA 90713
Ldn CoMult/1111, Int:.
42428 Chisolm Trail
Murrieta CA 92562
phone 760-473-1253
The worst-case daily train activity is as follows: 50 commuter train and freight trains (Source:
NTCD, AMTRAK and SANDAG, 2014). By the year 2030, rail operations are assumed to
increase to a total of 98 trains per day due to overall growth, the addition of Metrolink
Commuter Service and planned infrastructure upgrades. This would result in a noise level
increase of 2.9 dBA CNEL, raising the noise levels to approximately 80.6 dBA CNEL.
Hourly noise levels at the proposed building fa~ade would be further reduced due to distance,
duty-cycle, and existing and proposed site features. The noise reduction due to distance and a
duty-cycle of 8 (minutes) is 4.8 dBA CNEL and 8.8 dBA CNEL respectively, for a reduction of
13.6 dBA CNEL.
Additionally, the nearest sensitive outdoor use areas are the proposed ground floor patios facing
the railway. An existing 6-foot block wall, located to the west of the site, would provide
shielding to the proposed ground floor patio areas. To determine the noise level reductions
from the block wall, the Fresnel Barrier Reduction Calculations were utilized. The Fresnel
barrier reduction calculation is provided as an Attachment A. Utilizing the Fresnel Barrier
Reduction calculations it was determined that the 6-foot solid block wall would provide a 7.0
to 8.4 dBA CNEL reduction. Therefore, the ground level areas would be reduced to 60 dBA
CNEL and meet the City of Carlsbad exterior goal of 60 dBA CNEL.
At the upper levels, the existing three-story residential complex to the south would partially
break the line of sight to the rail line providing a minimum 3 dBA CNEL reduction. Therefore,
the worst-case building fa~ade is expected to be as high as 64.0 dBA CNEL. Based upon these
findings and the instantaneous peaks from the train operations, interior noise levels need to
be reduced to meet the CCR litle 24 and City of Carlsbad requirements.
Interior Noise Levels
The methodology used to determine the resultant interior noise levels is based upon the
exterior noise level minus the sound transmission loss as identified in the American Society of
Testing and Materials (ASTM) guidelines: E413 &E90. The exterior noise levels at the proposed
structures calculated in terms of dBA are converted to the six octave band sound pressure
levels between: 125 Hertz -4000 Hertz. Acoustical modeling of the proposed project dwelling
units was performed in accordance with the above guidelines and included combining the
transmission loss for each of the building components that will reduce the interior noise levels.
Building components typically include the windows, exterior doors, and exterior walls. The
total noise reduction is dependent upon the transmission loss of each building component,
4/3/2017 7 1657-05 3337 Tyler Street Noise Report
Elizabeth Lagrua
Tyler Street Development, LLC
4459 Hackett Avenue
Lakewood, CA 90713
Ldn eon.ult/1111, Inc.
42428 Chisolm Trail
Murrieta CA 92562
phone 760-473-1253
their subsequent surface area, quality of the building/construction materials, a building fac;;:ade
and angle correction.
The interior noise level is also dependent on the acoustical energy absorbed within the room
based upon the Noise Reduction Coefficients (NRC). NRC is a scalar representation of the
amount of sound energy absorbed upon striking a particular surface and the arithmetic value
average of sound absorption coefficients indicating a material's ability to absorb sound. The
absorption coefficients for individual surface areas such as carpet, drywall and furnishings are
used to calculate the interior room effects. The calculated building noise reduction includes
both the room absorption characteristics and the transmission loss from the exterior wall
assembly.
The interior noise reduction calculations were performed using Ldn's interior noise model. The
model converts the exterior sound level to octave band frequencies and accounts for the
transmission loss, correction factors and room absorption. The floor plans used for this analysis
were provided by TRE Architects received January 2017. The following construction details were
utilized for each of the building assemblies to determine the noise reduction characteristics:
Exterior walls and roof assemblies must have a Sound Transmission Class (STC) rating of 46 or
better. Exterior walls with this rating consist of 2"x4" studs or larger, spaced 16" o.c. with R-13
insulation minimum and an exterior surface of 7/8" cement plaster (stucco). Interior wall and
ceiling surfaces shall be at least 1/2" thick gypsum or plaster. Roof assemblies should have a
minimum of ½" sheathing, R-30 insulation and sealed to prevent noise leaks. Glass assemblies
should be dual-glazed and acoustical sealant applied around the exterior edges. The window
assemblies are generally the weakest noise reducing component but are the most convenient
and cost effective elements to change if additional attenuation is needed. The STC ratings for
the glass assemblies was calculated in the interior noise model and provided in the findings
below.
Bathrooms, kitchens, closets and corridors are not required to meet the 45 dBA CNEL standard
and therefore were not modeled. The sensitive rooms were considered to have tile or hardwood
flooring. These rooms were modeled to determine the interior noise reductions. If the modeled
interior noise levels were found to be higher than 45 dBA CNEL in the habitual areas with the
minimum assembly requirements described above additional modeling was performed to
determine the minimum STC rating for the glass assemblies to further reduce interior noise levels
below the acceptable interior threshold of 45 dBA CNEL.
4/3/2017 8 1657-05 3337 Tyler Street Noise Report
Elizabeth Lagrua
Tyler Street Development, LLC
4459 Hackett Avenue
Lakewood, CA 90713
FINDINGS
Ldn eon.ult/1111, Int:.
42428 Chisolm Trail
Murrieta CA 92562
phone 760-473-1253
The worst-case building fa<;ade noise levels were determined to be 60 dBA CNEL for the first floor
areas and 64 dBA CNEL for the upper floor levels. Basic calculations show that a windows open
condition will only reduce the interior noise levels 12-15 dBA CNEL and not provide adequate
interior noise mitigation. To meet the 45 dBA CNEL interior noise standard, an overall minimum
interior noise level reduction of 19 dBA CNEL is needed for the proposed project. Therefore, a
closed window condition is required to reduce interior noise levels to comply with CCR Title 24
and City of Carlsbad requirements. The windows closed condition requires that mechanical
ventilation is installed to move air within the structure and control temperatures. The mechanical
ventilation must meet the jurisdictional requirements for these dwelling units.
The building fa<;ade noise level of 64 dBA CNEL was utilized for all proposed sensitive rooms to
determine the minimum STC ratings of the assemblies. It should be noted though; maximum
sound levels due to rail operations could reach instantaneous peaks of up to 90 dBA due to
signaling and warning devices. Although these peak noise levels may only occur for 1-2
seconds, operation of such devices during evening or nighttime hours could result in a
nuisance to sensitive receptors.
The necessary Sound Transmission Class and transmission losses for all glass assemblies are
provided in Table 2. To meet the minimum requirements, all glass assemblies facing or having
a direct line of site to the railroad tracks should be dual-paned and acoustical sealant applied
around the exterior edges having an STC 28 rating. The modeled results with an anticipated
interior noise level of 45 dBA CNEL or less are provided as an Attachment Bto this report.
Table 2: Minimum Sound Transmission Class Ratings
STC Octave Band Transmission Loss (Hz)
Assembly Rating1
125 250 500 1000 2000 4000
Windows 28 19 20 22 32 37 38
Fixed Windows 28 21 15 25 35 41 28
Glass Doors 28 19 17 26 33 39 29
1 STC Ratings used in Model
Although, STC 28 rated window and glass assemblies are needed to meet the 45 dBA CNEL
standard. Due to the ra il operations, it is recommended that interior noise reduction methods
4/3/2017 9 1657-05 3337 Tyler Street Noise Report
Elizabeth Lagrua
Tyler Street Development, LLC
4459 Hackett Avenue
Lakewood, CA 90713
Ldn Conallt/1111, Int:.
42428 Chisolm Trail
Murrieta CA 92562
phone 760-473-1253
(i.e., dual-paned glass treatments) for the window and glass assemblies installed having line
of sight to the rail alignment be increased to a minimum sound transmission classification
(STC) rating of 31. This would assist in remediating instantaneous noise levels from the train
activities. If you have any questions, please do not hesitate to contact me directly at (760)
473-1253 .
Jeremy Louden, Principal
Attachments: A -Fresnel Barrier Calculations
B -Interior Noise Model Calculations
4/3/2017 10 1657-05 3337 Tyler Street Noise Report
TYLER-1
Incoherent Line Source
Source to Receiver Horizontal Distance (ft)=
Source to Barrier Horizontal Distance (ft)=
Barrier to Receiver Horizontal Distance (ft)=
Source Height (ft) = 5.00
Receiver Height (ft)= 4.00
Barrier Height (ft) = 6 .00
210.00
200.00
10.00
Distance Source to Receptor (ft) d =
Distance Source to Barrier top (ft) dl =
Distance Barrier top to Receiver (ft) d2 =
210.00
200.00
10 .20
Frequency (Hz) = 8000 Attenuation (db) = 13.3 Fresnel
Frequency (Hz) = 4000 Attenuation (db) = 11.6 Fresnel
Frequency (Hz) = 2000 Attenuation (db) = 9.9 Fresnel
Frequency (Hz) = 1000 Attenuation (db) = 8.4 Fresnel
Frequency (Hz) = 500 Attenuation (db) = 7.0 Fresnel
Page 1
N = 2.813
N = 1.407
N = 0.703
N = 0.352
N = 0.176
INTERIOR NOISE CALCULATIONS
Project Name:
Building (s)
Floor Level
Arch Plan:
Room Type:
3337 Tyler Street
All
1
All
Den
Exterior Noise Levels
Exterior
Assembly
Stucco
Windows
Fixed Window
Glass Doors
Exterior Door
Source
NBS W-50-71
Milgard
Milgard
Milgard
NBS Monograph 77
Room Absorption {RA)
Interior
Characteristics Source
Carpet Army TM 5-805-4
Furnishings Army TM 5-805-4
Drywall Netwell
Overall Absorption Factor (Furnished Room)
Noise Reduction
Area
261
so
0
40
20
Noise Reduction from Absorption based upon Floor Area
Noise Level Increase for Defects and Exposed Surface Area
STC
46
28
28
28
26
NRC
0.28
0.45
0.07
0.8
Overall Reduction from Tranmission Loss + Room Absorption -Surfa
Building Fa<;ade Noise Level (dBA CNEL)
125 250
27 42
19 20
21 15
19 17
16 14
125 250
0.15 0.17
0.32 0.29
0.09 0.08
0.56 0.54
125 250
-20.6 -20.6
18.5 18.5
ce Exposure
Ldn Consulting, Inc.
Date: 1/23/17
Project # 16-57
Transmission Loss {dB}
Frequency {Hz.}
500 1000 2000 4000
44 46 49 54
22 32 37 38
25 35 41 28
26 33 39 29
23 30 36 26
Absorption Coefficients
Frequency {Hz.}
500 1000 2000 4000
0.12 0.32 0.52 0.30
0.42 0.58 0.60 0.48
0.05 0.03 0.06 0.09
0.59 0.93 1.18 0.87
500 1000 2000 4000
-20.6 -20.6 -20.6 -20.6
18.5 18.5 18.5 18.5
17.1
62.0
Resultant Interior Noise Level (dBA CNEL) 45
* Corrections for Fa~ade Level was accounted for In the modeling.
INTERIOR NOISE CALCULATIONS
Project Name:
Building (s)
Floor Level
Arch Plan:
Room Type:
3337 Tyler Street
All
2
All
Family/Dining
Exterior Noise Levels
Exterior
Assembly
Stucco
Windows
Fixed Window
Glass Doors
Exterior Door
Source
NBS W-50-71
Milgard
Milgard
Milgard
NBS Monograph 77
Room Absorption {RA}
Interior
Characteristics Source
Carpet Army TM 5-805-4
Furnishings Army TM 5-805-4
Drywall Netwell
Overall Absorption Factor (Furnished Room)
Noise Reduction
Area
819
144
0
96
0
Noise Reduction from Absorption based upon Floor Area
Noise Level Increase for Defects and Exposed Surface Area
STC
46
28
28
28
26
NRC
0.28
0.45
0.07
0.8
Overall Reduction from Tranmission Loss + Room Absorption -Surfa
Building Fac;ade Noise Level (dBA CNEL)
125 250
27 42
19 20
21 15
19 17
16 14
125 250
0.15 0.17
0.32 0.29
0.09 0.08
0.56 0.54
125 250
-26.9 -26.9
18.5 18.5
ce Exposure
Ldn Consulting, Inc.
Date: 1/23/17
Project # 16-57
Transmission Loss {dB}
Frequency {Hz.}
500 1000 2000 4000
44 46 49 54
22 32 37 38
25 35 41 28
26 33 39 29
23 30 36 26
Absorption Coefficients
Frequency {Hz.}
500 1000 2000 4000
0.12 0.32 0.52 0.30
0.42 0.58 0.60 0.48
0.05 0.03 0.06 0.09
0.59 0.93 1.18 0.87
500 1000 2000 4000
-26.9 -26.9 -26.9 -26.9
18.5 18.5 18.5 18.5
20.7
62.0
Resultant Interior Noise Level (dBA CNEL) 41
* Corrections for Fa~ade Level was accounted for in the modeling.
INTERIOR NOISE CALCULATIONS
Project Name:
Building (s)
Floor Level
Arch Plan:
Room Type:
3337 Tyler Street
All
3
All
Master Bedroom
Exterior Noise Levels
Exterior
Assembly
Stucco
Windows
Fixed Window
Glass Doors
Exterior Door
Source
NBS W-50-71
Milgard
Milgard
Milgard
NBS Monograph 77
Room Absorption {RA}
Interior
Characteristics Source
Carpet Army TM 5-805-4
Furnishings Army TM 5-805-4
Drywall Netwell
Overall Absorption Factor {Furnished Room)
Noise Reduction
Area
243
24
0
40
0
Noise Reduction from Absorption based upon Floor Area
Noise Level Increase for Defects and Exposed Surface Area
STC
46
28
28
28
26
NRC
0.28
0.45
0.07
0.8
Overall Reduction from Tranmission Loss + Room Absorption -Surfa
Building Fa<;ade Noise Level (dBA CNEL)
125 250
27 42
19 20
21 15
19 17
16 14
125 250
0.15 0.17
0.32 0.29
0.09 0.08
0.56 0.54
125 250
-21.2 -21.2
17.3 17.3
ce Exposure
Ldn Consulting, Inc.
Date: 1/23/17
Project # 16-57
Transmission Loss {dB}
Frequency {Hz.}
500 1000 2000 4000
44 46 49 54
22 32 37 38
25 35 41 28
26 33 39 29
23 30 36 26
Absorption Coefficients
Frequency {Hz.}
500 1000 2000 4000
0.12 0.32 0.52 0.30
0.42 0.58 0.60 0.48
0.05 0.03 0.06 0.09
0.59 0.93 1.18 0.87
500 1000 2000 4000
-21.2 -21.2 -21.2 -21.2
17.3 17.3 17.3 17.3
20.5
62.0
Resultant Interior Noise Level (dBA CNEL) 41
* Corrections for Fa~ade Level was accounted for in the modeling.
INTERIOR NOISE CALCULATIONS
Project Name:
Building (s)
Floor Level
Arch Plan:
Room Type:
3337 Tyler Street
All
3
All
Bedroom 2
Exterior Noise Levels
Exterior
Assembly
Stucco
Windows
Fixed Window
Glass Doors
Exterior Door
Source
NBS W-50-71
Milgard
Milgard
Milgard
NBS Monograph 77
Room Absorption {RA}
Interior
Characteristics Source
Carpet Army TM 5-805-4
Furnishings Army TM 5-805-4
Drywall Netwell
Overall Absorption Factor (Furnished Room)
Noise Reduction
Area
198
28
0
0
0
Noise Reduction from Absorption based upon Floor Area
Noise Level Increase for Defects and Exposed Surface Area
STC
46
28
28
28
26
NRC
0.28
0.45
0.07
0.8
Overall Reduction from Tranmission Loss + Room Absorption -Surfa
Building Fac;ade Noise Level (dBA CNEL)
125 250
27 42
19 20
21 15
19 17
16 14
125 250
0.15 0.17
0.32 0.29
0.09 0.08
0.56 0.54
125 250
-19.7 -19.7
15.7 15.7
ce Exposure
Ldn Consulting, Inc.
Date: 1/23/17
Project # 16-57
Transmission Loss {dB}
Frequency {Hz.}
500 1000 2000 4000
44 46 49 54
22 32 37 38
25 35 41 28
26 33 39 29
23 30 36 26
Absorption Coefficients
Frequency {Hz.}
500 1000 2000 4000
0.12 0.32 0.52 0.30
0.42 0.58 0.60 0.48
0.05 0.03 0.06 0.09
0.59 0.93 1.18 0.87
500 1000 2000 4000
-19.7 -19.7 -19.7 -19.7
15.7 15.7 15.7 15.7
23.0
62.0
Resultant Interior Noise Level (dBA CNEL) 39
• Corrections for Fa~ade Level was accounted for in the modeling.
\
INTERIOR NOISE CALCULATIONS
Project Name:
Building (s)
Floor Level
Arch Plan:
Room Type:
3337 Tyler Street
All
3
All
Bedroom 3
Exterior Noise Levels
Exterior
Assembly
Stucco
Windows
Fixed Window
Glass Doors
Exterior Door
Source
NBS W-50-71
Milgard
Milgard
Milgard
NBS Monograph 77
Room Absorption {RA)
Interior
Characteristics Source
Carpet Army TM 5-805-4
Furnishings Army TM 5-805-4
Drywall Netwell
Overall Absorption Factor (Furnished Room)
Noise Reduction
Area
279
52
0
0
0
Noise Reduction from Absorption based upon Floor Area
Noise Level Increase for Defects and Exposed Surface Area
STC
46
28
28
28
26
NRC
0.28
0.45
0.07
0.8
Overall Reduction from Tranmission Loss + Room Absorption -Surfa
Building Fa91de Noise Level (dBA CNEL)
125 250
27 42
19 20
21 15
19 17
16 14
125 250
0.15 0.17
0.32 0.29
0.09 0.08
0.56 0.54
125 250
-20.7 -20.7
16.2 16.2
ce Exposure
Ldn Consulting, Inc.
Date: 1/23/17
Project # 16-57
Transmission Loss {dB}
Frequency {Hz.}
500 1000 2000 4000
44 46 49 54
22 32 37 38
25 35 41 28
26 33 39 29
23 30 36 26
Absorption Coefficients
Frequency {Hz.}
500 1000 2000 4000
0.12 0.32 0.52 0.30
0.42 0.58 0.60 0.48
0.05 0.03 0.06 0.09
0.59 0.93 1.18 0.87
500 1000 2000 4000
-20.7 -20.7 -20.7 -20.7
16.2 16.2 16.2 16.2
21.6
62.0
Resultant Interior Noise Level (dBA CNEL) 40
* Corrections for Fac;ade Level was accounted for In the modeling.