Loading...
HomeMy WebLinkAbout3583; Cannon Road Lift Station; Kelly Ranch Lift Station Hydrogen Sulfide Rep; 2002-12-01HYDROGEN SULFIDE REPORT KELLY RANCH LIFT STATION LOCATION: ADJACENT TO CANTERBURY DEVELOPMENT DECEMBER 2002 PREPARED BY: DHK ENGINEERS, INC. (760) 747-9553 V7 HYDROGEN SULFIDE REPORT Kelfy Ranch Lift Station December 2002 1.INTRODUCTION As part of the Camion Road Lift Station (CRLS) design development, residents within the project area have voiced their concerns over the "existing" odors from the Kelly Ranch Lift Station (KRLS) located adjacent to the Canterbury Community (formerly Kelly Ranch). The City requested that DHK Engineers, Inc. (DHK) conduct this hydrogen sulfide study at KRLS to determine if and when hydrogen sulfide was present in the KRLS area. 2.HYDROGEN SULFIDE SURVEY METHODOLOGY A hydrogen sulfide survey was conducted around the KRLS from October 26 through November 8, 2002 to document existing hydrogen sulfide concentrations. The access hatch was partially sealed with adhesive tape to provide one opening for the lift station to breathe. Each time the lift station "draws and fills" a portion of the air within the lift station is discharged through the opening. A container (five-gallon bucket) was placed above the opening to allow instrument installation and simulate "calm wind conditions". Several holes were drilled in the bucket to allow nature air dissipation. Each day, the data was electronically downloaded and the access hatch seal verified. Figure 1 illustrates the testing configuration. H2S Meter A Drager PAC III Hydrogen Sulfide Meter, with 0 to 100 parts per million (ppm), was used to monitor hydrogen sulfide. Measurements were automatically taken each minute for the entire sampling period. Equipment information (PAC III) is provided in Appendix A. DHK ENGINEERS, INC HYDROGEN SULFIDE REPORT Kelfy Ranch Lift Station December 2002 3. HYDROGEN SULFIDE SURVEY RESULTS Figure 2 provides a graphical summary of the monitoring sessions and is provided in Appendix B. The electronic data base for the entire sampling period in one-minute intervals is provided in Appendix C. 4. CONCLUSIONS The monitoring results indicated that the majority of the time (approximately 99%), the lift station has no hydrogen sulfide venting from the station. On occasions, a peak flow of waste water enters the wet well and displaces the air through the vent. Under calm or light wind conditions, the displaced puff of vented air may travel toward the Canterbury Development prior to adequate dispersion and dissipation. If the new Cannon Road Lift Station is delayed beyond summer of 2003, it may be warranted to install a passive carbon system to minimize the impacts of the "puff' release from the wet well. DHK ENGINEERS, INC HYDROGEN SULFTOE REPORT Kelfy Ranch Lift Station December 2002 APPENDIX A PAC III HYDROGEN SULFIDE MONITOR DHK ENGINEERS, INC DragerPACIII Single Gas Monitors Hydrogen Sulfide (H2S), Ammonia (NH3), Sulfur Dioxide (502) • User-selectable alarm levels for ACGIH or TRGS 402 • RF shielded For personnel monitoring under the most demanding hazardous gas conditions, including offshore oil rigs and underground mines, this little instrument is tough to beat for reliability and simplicity. Using Drager sensor technology, the Pac III provides fast and accurate response to hazardous gas levels, with an attention-getting 95 dB alarm. Alarm levels can be set for TWA and STEL. Gas concentration is continuously shown on the high intensity LED. A datalogging kit is an optional rental item. It provides graphic or spread sheet analysis of exposure at TWA, STEL or ceiling values. AgiTEAD RENTALS ' The DRAGER PAC III Single Gas Monitor rents with a Dragertool, extra battery case and operating manual. SPECIFICATIONS Measurement Range Hydrogen Sulfide (H2S) o to 100 ppm at i ppm resolution Ammonia (NH3) o to 300 ppm at i ppm resolution Sulfur Dioxide (SOz) o to 50 ppm at o.oi ppm resolution Approvals UL Class I and II, Division i, Groups A through G CSA Class I, Division i, Groups A through D MSHA permissible single gas monitor Datalogging > 125 hours at i-minute intervals Output RS-232 port Power 9V alkaline battery, 600 hours operation Dimensions 4.3" x 2.6" x 1.3" Weight 7 oz 800-242-39^0 www.ashtead-technology.com HYDROGEN SULFIDE REPORT Kelly Ranch Lift Station December 2002 APPENDIX B SUMMARY FIGURE OF HYDROGEN SULFIDE RESULTS FIGURE 2 IH2S (ppm) 8 8 DHK ENGINEERS, INC HYDROGEN SULFTOE REPORT Kelfy Ranch Lift Station December 2002 APPENDIX C ELECTRONIC FILE OF MONITORING RESULTS DHK ENGINEERS, INC