HomeMy WebLinkAboutCT 04-09; La Costa Greens Neighborhood 1.17; Water System Analysis; 2004-09-03DEXTER WILSON ENGINEERING, INC.
WATER • WASTEWATER • ENVIRONMENTAL
CONSULTING ENGINEERS
WATER SYSTEM ANALYSIS
FOR LA COSTA GREENS
NEIGHBORHOOD 1.17
September 3, 2004
HAR 1 7 2005
ENGINEERING
DEPARTMENT
703 PALOMAR AIRPORT ROAD, SUITE 300 • CARLSBAD, CA 92009 • (760) 438-4422
s ftCTor-01-/
^ , ,-, -J
PL
WATER SYSTEM ANALYSIS
FOR LA COSTA GREENS
NEIGHBORHOOD 1.17
September 3, 2004
Dexter Wilson Engineering, Inc.
703 Palomar Airport Road
Suite 300
Carlsbad, CA 92009
(760) 438-4422
Job Number: 681-024
DEXTER WILSON ENGINEERING, INC.
September 3, 2004
DEXTER S. WILSON, P.E.
ANDREW M. OVEN, P.E.
STEPHEN M. NIELSEN, P.E.
MICHAEL J. FILECCIA, P.E.
DIANE H. SHAUGHNESSY, P.E.
681-024
Morrow Development
1903 Wright Place, Suite 180
Carlsbad, CA 92008
Attention: Tim O'Grady, Vice President
Subject: Water System Analysis for La Costa Greens Neighborhood 1.17
Introduction
This letter-report provides a water system analysis for Neighborhood 1.17 of the La
Costa Greens project. This report determines the required water line sizes to meet
domestic and fire flow requirements for the project and identifies connections to the
existing water system that will occur in the vicinity of the project.
The portion of La Costa Greens covered by this study is located south of Poinsettia
Lane, east of El Camino Real, on the west side of the La Costa Greens project. The
neighborhood analyzed in this study is identified on Figure 1.
Neighborhood 1.17 of the La Costa Greens project is within the 318 and 375 Zones of
the Carlsbad Municipal Water District (CMWD) for water service. The project will
obtain water service by connecting to a 16-inch 375 Zone water line in Poinsettia Lane
and to an 8-inch 318 Zone water line at the south end of the project. The water system
improvements internal to the project will be completed concurrent with required street
improvements for the project.
703 PALOMAR AIRPORT ROAD, SUITE 3OO CARLSBAD, CA 92009 • (760)438-4422 • FAX (76O) 438-0173
Tim O'Grady
September 3, 2004
Page 2
The portion of La Costa Greens analyzed herein proposes single family residential
development. Figure 1 provides the proposed development layout for the project.
Water System Design Criteria
The basic design criteria utilized in sizing the water distribution system piping
includes a minimum residual pressure of 40 psi under peak hour flow conditions, and
a residual pressure of at least 20 psi under maximum day demand plus fire flow
conditions.
The peaking factors used in analyzing various demand scenarios are 1.65 for average
day to maximum day demands, and 2.9 for average day to peak hour demands.
A computer analysis (KYPIPE Program, University of Kentucky) was used to
determine residual pressures throughout the distribution system model. This
computer program utilizes the Hazen-Williams equation for determining headloss with
a "C" value of 120 used for all pipes.
Fire Flows
The fire flow requirement from the March 2003 CMWD Water Master Plan Update is
1,500 gpm for single family residential development. This fire flow was modeled at a
single hydrant location.
Projected Water Demand
The projected water demand for the La Costa Greens project was estimated by using
water duty factors from the March 2003 CMWD Water Master Plan Update. Table 1
Tim O'Grady
September 3, 2004
PageS
summarizes the development, water duty factors, and projected water demand for the
project by service zone.
TABLE 1
LA COSTA GREENS PROJECTED WATER DEMANDS
Existing Water System Facilities
Neighborhood 1.17 of the La Costa Greens project is located within the 318 and 375
Water Service Zones of the CMWD. This area of the District's system is supplied by
a 16-inch 375 Zone line in Poinsettia Lane and an 8-inch 318 Zone water line that was
constructed by the neighborhood south of Neighborhood 1.17. The location of these
facilities are provided on Figure 1.
Water System Analysis
Appendix A contains the computer analyses performed for the project. Exhibit "A"
presents the node and pipe diagram for the onsite computer model and shows the
recommended water system sizes for the piping within the project. The modeling
performed for the project includes maximum day demand plus fire flow scenarios, as
well as average day demand and peak hour demand scenarios.
Tim O'Grady
September 3, 2004
Page 4
Proposed Water System
Figure 1 provides the proposed potable water system for Neighborhood 1.17 of the La
Costa Greens project. The project will be supplied by connecting to the proposed 16-
inch water line in Poinsettia Lane, connecting to an existing 8-inch water line to the
south, and constructing onsite 8-inch water lines.
The computer output in Appendix A verifies that construction of the improvements on
Figure 1 will provide adequate domestic and fire protection service to La Costa Greens
Neighborhood 1.17. Table 2 summarizes the expected lot elevation and static pressure
ranges for the project.
TABLE 2
WATER SERVICE ZONE SUMMARY
* """.' i **' "• '-" ' ' • -,„••,—
375
318
169
117
261
167
49
65
89
87
NORMALLY CLOSED
VALVE
\
LEGEND
-EXISTING 375 ZONE WATER
PROPOSED 375 ZONE WATER
EXISTING 318 ZONE WATER
PROPOSED 318 ZONE WATER
FIRE HYDRANT
FIGURE 1
LA COSTA GREENS
PA 1.17
PROPOSED WATER LAYOUTNOTE: ALL PIPES ARE 8" UNLESS OTHERWISE NOTED
CS2U:\681024\LA-COSTA-GREENS\FIGURE-1,DWG 09-02-04 10:33:41
Tim O'Grady
September 3, 2004
Page 6
Conclusions and Recommendations
The following is a summary of our conclusions and recommendations based on our
study:
1. The recommended potable water system configuration and sizes for
pipelines to serve La Costa Greens Neighborhood 1.17 are shown on
Figure 1.
2. Water service to the project will be provided by the CMWD 318 and 375
Zone Water System. Two connections to the 16-inch water line in
Poinsettia Lane, and a connection to the existing 8-inch line to the south
are recommended.
3. Individual pressure regulating valves should be installed on all lots that
are expected to have water service pressures of greater than 80 psi.
4. As summarized in Table 2, some of the upper lots within the project will
receive marginally low static pressures of less than 60 psi. The computer
modeling verifies that adequate fire protection service can be provided to
all lots on the project.
Tim O'Grady
September 3, 2004
Page 7
Thank you for the opportunity to assist you with the water system planning for this
project. If you have any questions regarding the contents of this report, please do not
hesitate to call. We are available to discuss this report with you at your convenience.
Dexter Wilson Engineering, Inc.
Stephen M. Nielsen
SMN:jbk
Attachments
APPENDIX A
COMPUTER OUTPUT
The following conditions were modeled:
1. Average Day Demands
2. Maximum Day Demands
3. Maximum Day Demands plus 1,500 gpm Fire Flow at Node 6
4. Maximum Day Demands plus 1,500 gpm Fire Flow at Node 26
5. Maximum Day Demands plus 1,500 gpm Fire Flow at Node 28
6. Maximum Day Demands plus 1,500 gpm Fire Flow at Node 52
7. Peak Hour Demands
FLOWRATE IS EXPRESSED IN GPM AND PRESSURE IN PSIG
A SUMMARY OF THE ORIGINAL DATA FOLLOWS
PIPE NO. NODE NOS.
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
51
53
55
LINE 55
JUNCTION
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
50
52
0
2
4
6
8
8
2
12
14
14
16
20
16
22
24
24
30
20
0
50
52
2
4
6
8
10
12
12
14
10
16
20
18
22
24
26
28
28
30
50
52
30
LENGTH
(FEET)
650
680
320
60
450
480
250
430
250
380
380
190
280
420
90
250
200
300
450
290
130
.0
.0
.0
.0
.0
.0
.0
.0
.0
.0
.0
.0
.0
.0
.0
.0
.0
.0
.0
.0
.0
DIAMETER
(INCHES)
16.0
16.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
ROUGHNESS MINOR LOSS K FIXED GRADE
120.
120.
120.
120.
120.
120.
120.
120.
120.
120.
120.
120.
120.
120.
120.
120.
120.
120.
120.
120.
120.
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
.00 375.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00 318.00
.00
.00
IS CLOSED
NUMBER DEMAND
1
2
2
2
2
2
1
3
1
1
1
1
2
.00
.00
.61
.95
.95
.68
.14
.68
.07
. 80
.48
. 61
.07
.34
.80
.07
.14
ELEVATION
.00
.00 •'
255.30
255.30
242.30
231.20
218.50
203.10
185.70
183 .00
218.00
214.80
214.50
177 .80
169.30
137.90
163.50
CONNECTING
1
3
5
7
9
11
15
19
23
21
25
27
29
31
33
51
53
3
5
7
9
17
13
17
21
23
27
29
33
35
53
55
PIPES
13
11
15
19
25
35
31
55
OUTPUT SELECTION: ALL RESULTS ARE OUTPUT EACH PERIOD
3 VALUES ARE OUTPUT FOR MAXIMUM AND MINIMUM PRESSURES
THIS SYSTEM HAS 21 PIPES WITH 17 JUNCTIONS , 3 LOOPS AND 2 FGNS
THE RESULTS ARE OBTAINED AFTER 8 TRIALS WITH AN ACCURACY = .00175
681024.OUT Page 1 of 10
WATER ANAYLSIS
LA COSTA GREENS P.A. 1.17
AVERAGE DAILY DEMAND
681-024
PIPE NO.
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
51
53
LINE 55
NODE NOS.
0
2
4
6
8
8
2
12
14
14
16
20
16
22
24
24
30
20
0
50
IS
2
4
6
8
10
12
12
14
10
16
20
18
22
24
26
28
28
30
50
52
CLOSED
FLOWRATE
25.18
11.21
11.21
9.60
8.24
-1.58
13.97
9.70
-5.29
12.85
4.51
1.07
5.66
2.18
1.07
-.50
1.84
2.64
3.21
2.14
HEAD LOSS
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
PUMP HEAD
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
MINOR LOSS
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
VELOCITY
.04
.02
.07
.06
.05
-.01
.09
.06
-.03
.08
.03
.01
.04
.01
.01
.00
.01
.02
.02
.01
HL/1000
.00
.00
.01
.00
.00
.00
.01
.00
.00
.01
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
JUNCTION NUMBER
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
50
52
DEMAND
.00
1
2
2
2
2
2
1
3
1
1
1
1
2
.00
.61
.95
.95
.68
.14
.68
.07
.80
.48
.61
.07
.34
.80
.07
.14
GRADE
375
375
375
375
375
375
375
374
374
374
374
374
374
374
374
318
318
LINE
.00
.00
.00
.00
.00
.00
.00
.99
.99
.99
.99
.99
.99
.99
.99
.00
.00
ELEVATION PRESSUR:
255
255
242
231
218
203
185
183
218
214
214
177
169
137
163
.30
.30
.30
.20
.50
. 10
.70
.00
.00
.80
.50
.80
.30
. 90
.50
51
51
57
62
67
74
82
83
68
69
69
85
89
78
66
.87
.87
.50
.31
.81
.49
.03
.20
.03
.42
.55
.45
. 13
. 04
.95
30
28
20
8
6
10
MAXIMUM PRESSURES
.80 374.99 169.30
1.34 374.99 177.80
.80 374.99 183.00
MINIMUM PRESSURES
2.95 375.00 255.30
1.61 375.00 255.30
2.95 375.00 242.30
89.13
85.45
83 .20
51.87
51.87
57.50
THE NET SYSTEM DEMAND = 28.39
SUMMARY OF INFLOWS(+} AND OUTFLOWS(-) FROM FIXED GRADE NODES
PIPE NUMBER
1
FLOWRATE
25.18
681024.OUT Page 2 of 10
51 3.21
THE NET FLOW INTO THE SYSTEM FROM FIXED GRADE NODES = 28.39
THE NET FLOW OUT OF THE SYSTEM INTO FIXED GRADE NODES = .00
A SUMMARY OF CONDITIONS SPECIFIED FOR THE NEXT SIMULATION FOLLOWS
THE DEMANDS ARE CHANGED FROM ORIGINAL VALUES BY A FACTOR = 1.65
THE RESULTS ARE OBTAINED AFTER 2 TRIALS WITH AN ACCURACY = .00000
MAXIMUM DAILY DEMAND
PIPE NO. NODE NOS.
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
51
53
LINE
0
2
4
6
8
8
2
12
14
14
16
20
16
22
24
24
30
20
0
50
55 IS
2
4
6
8
10
12
12
14
10
16
20
18
22
24
26
28
28
30
50
52
CLOSED
FLOWRATE HEAD LOSS PUMP HEAD MINOR LOSS
41
18
18
15
13
-2
23
16
-8
21
7
1
9
3
1
-
3
4
5
3
.55 .
.50
.50
.84
.59
.61
.05
.01
.72
.20
.45
.77
.33
.59
.77
.83
.04
.36
.30
.53
.00
.00
.00
.00
.00
.00
.00
.00
.00
.01
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
. 00
. 00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
. 00
.00
.00
.00
.00
VELOCITY HL/1000
.07
.03
.12
.10
.09
-.02
.15
.10
-.06
.14
.05
.01
.06
.02
.01
-.01
.02
.03
.03
.02
.00
.00
.01
.01
.01
.00
.02
.01
.00
.02
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
JUNCTION NUMBER
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
50
52
DEMAND
.00
2
4
4
4
3
4
1
1
5
2
1
2
1
1
3
.00
.66
. 87
.87
.42
.53
.42
.77
.32
.74
.66
.77
.21
.32
.77
.53
GRADE
375
375
374
374
374
374
374
374
374
374
374
374
374
374
374
318
318
LINE
.00
.00
.99
.99
.99
.99
.99
.98
.98
.98
.98
.98
.98
.98
.98
.00
.00
ELEVATION PRESSUR
255
255
242
231
218
203
185
183
218
214
214
177
169
137
163
.30
.30
.30
.20
.50
.10
.70
.00
.00
.80
.50
.80
.30
.90
.50
51
51
57
62
67
74
82
83
68
69
69
85
89
78
66
.87
.87
.50
.31
.81
.48
.02
.19
.03
.41
.54
.45
.13
.04
.95
MAXIMUM PRESSURES
681024.0UT Page 3 of 10
30
28
20
8
6
10
1.32
2.21
1.32
374.98
374.98
374.98
MINIMUM PRESSURES
4.87 374.99
2.66 374.99
4.87 374.99
169.30
177.80
183.00
255.30
255.30
242.30
89.13
85.45
83.19
51.87
51.87
57.50
THE NET SYSTEM DEMAND = 46.84
SUMMARY OF INFLOWS(+) AND OUTFLOWS(-) FROM FIXED GRADE NODES
PIPE NUMBER
1
51
FLOWRATE
41.55
5.30
THE NET FLOW INTO THE SYSTEM FROM FIXED GRADE NODES =
THE NET FLOW OUT OF THE SYSTEM INTO FIXED GRADE NODES
46.84
.00
A SUMMARY OF CONDITIONS SPECIFIED FOR THE NEXT SIMULATION FOLLOWS
THE DEMANDS ARE CHANGED FROM ORIGINAL VALUES BY A FACTOR
THE FOLLOWING SPECIFIC DEMAND CHANGES ARE MADE :
JUNCTION NUMBER DEMAND
6 1502.66
1.65
THE RESULTS ARE OBTAINED AFTER 4 TRIALS WITH AN ACCURACY .00398
MAXIMUM DAILY DEMAND PLUS 1500 GPM FIRE FLOW AT NODE 6
PIPE
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
51
53
LINE
NO. NODE NOS.
0
2
4
6
8
8
2
12
14
14
16
20
16
22
24
24
30
20
0
50
55 IS
2
4
6
8
10
12
12
14
10
16
20
18
22
24
26
28
28
30
50
52
CLOSED
FLOWRATE
1541.55
843.48
843.48
-659.18
-248.87
-415. 17
698.07
278.47
253.74
21.20
7.45
1.77
9.33
3.59
1.77
-.83
3.04
4.36
5.30
3.53
HEAD LOSS
1.05
.36
4.95
-.59
- .73
-2.00
2.72
.85
.42
.01
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
PUMP HEAD
.00
.00
.00
.00
. 00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
MINOR LOSS
.00
.00
.00
.00
.00
. 00
. 00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
VELOCITY
2.46
1.35
5.38
-4.21
-1.59
-2 . 65
4.46
1.78
1.62
.14
.05
.01
.06
.02
.01
-.01
.02
.03
.03
.02
HL/1000
1.61
.53
15.46
-9.79
-1.61
-4 . 16
10.89
1.99
1.67
.02
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
JUNCTION NUMBER DEMAND GRADE LINE ELEVATION PRESSURE
681024.OUT Page 4 of 10
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
50
52
.00
.00
1502.66
4.87
4.87
4.42
3.53
4.42
1.77
1.32
5.74
2.66
1.77
2.21
1.32
1.77
3.53
373.95
373.59
368.64
369.23
369.96
371.23
370.37
370.37
370.37
370.37
370.37
370.37
370.37
370.37
370.37
318.00
318.00
255.30
255.30
242.30
231.20
218.50
203.10
185.70
183.00
218.00
214.80
214.50
177.80
169.30
137.90
163.50
49.12
49.37
55.32
60.68
65.81
72.48
80.02
81.19
66.03
67.41
67.54
83.45
87.13
78.04
66.95
30
28
20
6
8
10
MAXIMUM PRESSURES
1.32 370.37 169.30
2.21 370.37 177.80
1.32 370.37 183.00
MINIMUM PRESSURES
1502.66 368.64 255.30
4.87 369.23 255.30
4.87 369.96 242.30
87.13
83.45
81.19
49.12
49.37
55.32
THE NET SYSTEM DEMAND = 1546.85
SUMMARY OF INFLOWS(+) AND OUTFLOWS(-) FROM FIXED GRADE NODES
PIPE NUMBER
1
51
FLOWRATE
1541.55
5.30
THE NET FLOW INTO THE SYSTEM FROM FIXED GRADE NODES = 1546.85
THE NET FLOW OUT OF THE SYSTEM INTO FIXED GRADE NODES = .00
A SUMMARY OF CONDITIONS SPECIFIED FOR THE NEXT SIMULATION FOLLOWS
THE DEMANDS ARE CHANGED FROM ORIGINAL VALUES BY A FACTOR = 1.65
THE FOLLOWING SPECIFIC DEMAND CHANGES ARE MADE :
JUNCTION NUMBER DEMAND
26 1501.77
THE RESULTS ARE OBTAINED AFTER 3 TRIALS WITH AN ACCURACY = .00065
MAXIMUM DAILY DEMAND PLUS 1500 GPM FIRE FLOW AT NODE 26
PIPE NO. NODE NOS. FLOWRATE HEAD LOSS PUMP HEAD MINOR LOSS VELOCITY HL/1000
0
2
4
6
8
2
4
6
8
10
1541.55
672.06
672.06
669.40
665.74
1.05
.24
3.25
.60
4.49
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
2.46
1.07
4.29
4.27
4.25
1.61
.35
10.15
10.08
9.97
681024.OUT Page 5 of 10
11
13
15
17
19
21
23
25
27
29
31
33
35
51
53
LINE
8
2
12
14
14
16
20
16
22
24
24
30
20
0
50
55 IS
12
12
14
10
16
20
18
22
24
26
28
28
30
50
52
CLOSED
-1
869
863
-660
1521
661
1
855
849
1501
-654
656
658
5
3
.21
.49
.86
.88
.21
.11
.77
.68
.93
.77
.49
.70
.02
.30
.53
4
6
-2
17
3
4
6
4
-2
1
2
.00
.09
.95
.46
.51
.74
.00
.44
.58
.05
.42
.94
.93
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
-
5
5
-4
9
4
5
5
9
-4
4
4
.01
.55
.51
.22
.71
.22
.01
.46
.42
.58
.18
.19
.20
.03
.02
.00
16.35
16.16
-9.84
46.08
9.85
.00
15.87
15.68
44.99
-9.66
9.72
9.76
.00
.00
JUNCTION NUMBER DEMAND
2 .00
4
6
8
10
12
14
16
18
20
22
24
26
28
30
50
52
.
2.
4.
4.
4 .
3.
4 .
1.
1.
5.
2.
1501.
2.
1.
1.
3.
00
66
87
87
42
53
42
77
32
74
66
77
21
32
77
53
GRADE
373
373
370
369
365
369
362
345
341
341
340
334
330
336
338
318
318
LINE
.95
.71
.47
.86
.37
.86
.91
.41
.66
.66
.96
.38
.33
.79
.74
.00
.00
ELEVATION PRESSUR]
255
255
242
231
218
203
185
183
218
214
214
177
169
137
163
.30
.30
.30
.20
.50
.10
.70
.00
.00
.80
.50
.80
.30
.90
.50
49
49
53
60
62
61
67
68
53
51
50
68
73
78
66
.91
.64
.33
.09
.58
.67
.58
.75
.28
.82
.19
.90
.42
.04
.95
50
30
28
8
6
26
MAXIMUM PRESSURES
1.77 318.00 137.90
1.32 338.74 169.30
2.21 336.79 177.80
MINIMUM PRESSURES
4.87 369.86 255.30
2.66 370.47 255.30
1501.77 330.33 214.50
78 .04
73.42
68.90
49.64
49.91
50. 19
THE NET SYSTEM DEMAND = 1546.85
SUMMARY OF INFLOWS(+) AND OUTFLOWS(-) FROM FIXED GRADE NODES
PIPE NUMBER
1
51
FLOWRATE
1541.55
5.30
THE NET FLOW INTO THE SYSTEM FROM FIXED GRADE NODES = 1546.85
THE NET FLOW OUT OF THE SYSTEM INTO FIXED GRADE NODES = .00
A SUMMARY OF CONDITIONS SPECIFIED FOR THE NEXT SIMULATION FOLLOWS
THE DEMANDS ARE CHANGED FROM ORIGINAL VALUES BY A FACTOR = 1.65
681024.0UT Page 6 of 10
THE FOLLOWING SPECIFIC DEMAND CHANGES ARE MADE
JUNCTION NUMBER DEMAND
28 1502.21
THE RESULTS ARE OBTAINED AFTER 3 TRIALS WITH AN ACCURACY = .00008
MAXIMUM DAILY DEMAND PLUS 1500 GPM FIRE FLOW AT NODE 28
PIPE NO. NODE NOS.
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
51
53
LINE
0
2
4
6
8
8
2
12
14
14
16
20
16
22
24
24
30
20
0
50
55 IS
2
4
6
8
10
12
12
14
10
16
20
18
22
24
26
28
28
30
50
52
CLOSED
FLOWRATE
1541
672
672
669
665
-1
869
863
-660
1521
772
1
744
738
1
734
768
769
5
3
.55
.06
.06
.40
.74
.21
.49
.86
.87
.20
.41
.77
.37
.63
.77
.21
.00
.32
.30
.53
HEAD
1
3
4
4
6
-2
17
4
3
5
2
2
3
LOSS PUMP HEAD MINOR LOSS VELOCITY
.05
.24
.25
.60
.49
.00
.09
.95
.46
.51
.99
.00
.43
.08
.00
.99
.60
.91
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
2
1
4
4
4
-
5
5
-4
9
4
4
4
4
4
4
.46
.07
.29
.27
.25
.01
.55
.51
.22
.71
.93
.01
.75
.71
.01
.69
.90
.91
.03
.02
HL/1000
1.61
.35
10.15
10.07
9.97
.00
16.35
16.16
-9.84
46.08
13.13
.00
12.26
12.09
.00
11.96
12.99
13 .04
.00
.00
JUNCTION NUMBER DEMAND
2 . 00
4
6
8
10
12
14
16
18
20
22
24
26
28
30
50
52
2
4
4
4
3
4
1
1
5
2
1
1502
1
1
3
.00
.66
.87
.87
.42
.53
.42
.77
.32
.74
.66
.77
.21
.32
.77
.53
GRADE
373
373
370
369
365
369
362
345
340
340
341
336
336
333
336
318
318
LINE
. 95
.71
.47
.86
.37
.86
.91
.41
.41
.41
.97
.89
.89
.91
.50
.00
.00
ELEVATION PRESSUR:
255
255
242
231
218
203
185
183
218
214
214
177
169
137
163
.30
.30
.30
.20
.50
.10
.70
.00
.00
.80
.50
.80
.30
.90
.50
49
49
53
60
62
61
67
68
53
52
53
67
72
78
66
.91
.64
.33
.09
.58
. 67
. 04
.21
.72
.91
.04
.65
.46
.04
.95
50
30
20
MAXIMUM PRESSURES
1.77 318.00 137.90
1.32 336.50 169.30
1.32 340.41 183.00
78.04
72.46
68.21
8
6
24
MINIMUM PRESSURES
4.87 369.86 255.30
2.66 370.47 255.30
2.66 336.89 214.80
49.64
49.91
52 .91
681024.OUT Page 7 of 10
THE NET SYSTEM DEMAND = 1546.84
SUMMARY OF INFLOWS(+) AND OUTFLOWS(-) FROM FIXED GRADE NODES
PIPE NUMBER
1
51
FLOWRATE
1541.55
5.30
THE NET FLOW INTO THE SYSTEM FROM FIXED GRADE NODES = 1546.84
THE NET FLOW OUT OF THE SYSTEM INTO FIXED GRADE NODES = .00
A SUMMARY OF CONDITIONS SPECIFIED FOR THE NEXT SIMULATION FOLLOWS
THE DEMANDS ARE CHANGED FROM ORIGINAL VALUES BY A FACTOR = 1.65
THE FOLLOWING SPECIFIC DEMAND CHANGES ARE MADE :
JUNCTION NUMBER DEMAND
52 1502.21
THE RESULTS ARE OBTAINED AFTER 2 TRIALS WITH AN ACCURACY = .00156
MAXIMUM DAILY DEMAND PLUS 1500 GPM FIRE FLOW AT NODE 52
PIPE NO.
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
51
53
LINE 55
JUNCTION
2
4
6
8
10
12
14
16
NODE NOS.
0
2
4
6
8
8
2
12
14
14
16
20
16
22
24
24
30
20
0
50
IS
2
4
6
8
10
12
12
14
10
16
20
18
22
24
26
28
28
30
50
52
CLOSED
NUMBER
FLOWRATE
41.55
18.50
18.50
15.84
13 .59
-2 .62
23 .05
16.01
-8.72
21.20
7.46
1.77
9.32
3.58
1.77
-.84
3.05
4.37
1503.98
1502.21
DEMAND
.00
.00
2.66
4.87
4.87
4.42
3.53
4.42
HEAD LOSS
.00
.00
.00
.00
.00
.00
.00
.00
.00
.01
.00
.00
.00
.00
.00
.00
.00
.00
20.30
13.05
GRADE LINE
375.00
375.00
374.99
374.99
374.99
374.99
374.99
374.98
PUMP HEAD MINOR LOSS VELOCITY
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
. 00
. 00
.00
.00
.00
.00
.00
.00
ELEVATION
255.30
255.30
242.30
231.20
218.50
203 .10
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
. 00
. 00
.00
.00
.00
.00
.00
.00
PRESSURE
51.87
51.87
57.50
62.31
67.81
74.48
.07
.03
.12
.10
.09
-.02
.15
.10
-.06
.14
.05
.01
.06
. 02
.01
-.01
.02
.03
9.60
9.59
HL/1000
.00
.00
.01
.01
.01
.00
.02
.01
.00
.02
.00
.00
.00
.00
.00
.00
.00
.00
45.12
45.02
681024.OUT Page 8 of 10
18
20
22
24
26
28
30
50
52
30
28
20
8
6
52
1.77
1.32
5.74
2.66
1.77
2.21
1.32
1.77
1502.21
374.98
374.98
374.98
374.98
374.98
374.98
374.98
297.70
284.64
185.70
183.00
218.00
214.80
214.50
177.80
169.30
137.90
163.50
82.02
83.19
68.03
69.41
69.54
85.45
89.13
69.25
52.50
MAXIMUM PRESSURES
1.32 374.98 169.30
2.21 374.98 177.80
1.32 374.98 183.00
MINIMUM PRESSURES
4.87 374.99 255.30
2.66 374.99 255.30
1502.21 284.64 163.50
89.13
85.45
83.19
51.87
51.87
52.50
THE NET SYSTEM DEMAND = 1545.52
SUMMARY OF INFLOWS(+) AND OUTFLOWS(-) FROM FIXED GRADE NODES
PIPE NUMBER
1
51
FLOWRATE
41.55
1503.98
THE NET FLOW INTO THE SYSTEM FROM FIXED GRADE NODES =
THE NET FLOW OUT OF THE SYSTEM INTO FIXED GRADE NODES
1545.52
.00
A SUMMARY OF CONDITIONS SPECIFIED FOR THE NEXT SIMULATION FOLLOWS
THE DEMANDS ARE CHANGED FROM ORIGINAL VALUES BY A FACTOR = 2.90
THE RESULTS ARE OBTAINED AFTER 2 TRIALS WITH AN ACCURACY = .00012
PEAK HOUR
PIPE NO. NODE
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
0
2
4
6
8
8
2
12
14
14
16
20
16
22
24
24
30
NOS.
2
4
6
8
10
12
12
14
10
16
20
18
22
24
26
28
28
FLOWRATE HEAD LOSS PUMP HEAD MINOR LOSS
73
32
32
27
23
-4
40
28
-15
37
13
3
16
6
3
-1
5
.02
.52
.52
.85
.88
.59
.50
.14
.33
.27
.09
.10
.40
.31
.10
.46
.35
.00
.00
.01
.00
.01
.00
.01
.01
.00
.02
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
VELOCITY
.12
.05
.21
.18
.15
-.03
.26
.18
-.10
.24
.08
.02
.10
.04
.02
-.01
.03
HL/1000
.01
.00
.04
.03
.02
.00
.06
.03
-.01
.05
.01
.00
.01
.00
.00
.00
.00
681024.OUT Page 9 of 10
35 20 30
51 0 50
53 50 52
LINE 55 IS CLOSED
JUNCTION NUMBER
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
50
52
30
28
20
8
6
10
7.67
9.31
6.21
DEMAND
.00
.00
4.67
8.56
8.56
7.77
6.21
7.77
3.10
2.32
10.09
4.67
3.10
3.89
2.32
3.10
6.21
MAXIMUM
2.32
3.89
2.32
MINIMUM
8.56
4.67
8.56
.00
.00
.00
GRADE LINE
375.00
375.00
374.98
374.98
374.97
374.98
374.97
374.95
374.95
374.95
374.95
374.95
374.95
374.95
374.95
318.00
318.00
PRESSURES
374.95
374.95
374.95
PRESSURES
374.98
374.98
374.97
.00
.00
.00
ELEVATION
255.30
255.30
242.30
231.20
218.50
203.10
185.70
183.00
218.00
214.80
214.50
177.80
169.30
137.90
163.50
169.30
177.80
183.00
255.30
255.30
242.30
.00
.00
.00
PRESSURE
51.86
51.86
57.49
62.31
67.80
74.47
82.01
83 .18
68.01
69.40
69.53
85.43
89.11
78.04
66.95
89.11
85.43
83.18
51.86
51.86
57.49
.05
.06
.04
.00
.00
.00
THE NET SYSTEM DEMAND = 82.33
SUMMARY OP INFLOWS(+) AND OUTFLOWS(-) FROM FIXED GRADE NODES
PIPE NUMBER
1
51
FLOWRATE
73.02
9.31
THE NET FLOW INTO THE SYSTEM FROM FIXED GRADE NODES =
THE NET FLOW OUT OF THE SYSTEM INTO FIXED GRADE NODES =
82.33
.00
681024.OUT Page 10 of 10
I
ll
II
I
V
NORMALLY CLOSED
VALVE
LEGEND
EXISTING 375 ZONE WATER
PROPOSED 375 ZONE WATER
EXISTING 318 ZONE WATER
PROPOSED 318 ZONE WATER
2J COMPUTER MODEL NODE NO,
LJ COMPUTER MODEL PIPE NO.
» FIRE HYDRANT
NOTE: ALL PIPES ARE 8" UNLESS OTHERWISE NOTED
EXHIBIT A
LA COSTA GREENS
P.A. 1.17
NODE AND PIPE DIAGRAM
CS2U:\681024\LA-COSTA-GREENS\EXHiB!T~A,DWG 09-02-04 10:30:35