WATER SYSTEM ANALYSIS
FOR
POINSETTIA COMMONS
March 23, 2007
Prepared By:
Dexter Wilson Engineering, Inc.
2234 Faraday Avenue
Carlsbad, CA 92008
(760) 438-4422
Job No: 852-001
Oz
X
Oill
X
O
DEXTER WILSON ENGINEERING, INC.
March 23, 2007
DEXTER S. WILSON, P.E.
ANDREW M. OVEN, P.E.
STEPHEN M. NIELSEN, P.E.
DIANE H. SHAUGHNESSY, P.E.
852-001
Tramwell Crow Residential
949 South Coast Drive, Suite 400
Costa Mesa, CA 92626
Attention: Brad Perozzi, Managing Director
Subject: Water System Analysis for Poinsettia Commons
This letter summarizes our analysis and recommendations for providing potable and
recycled water service to the Poinsettia Commons development. The proposed
development consists of thirteen buildings comprised of commercial and multifamily
residential units. The project is located at the intersection of Avenida Encinas and
Embarcadero Lane. The project is located within the Carlsbad Municipal Water District's
318 Water Pressure Zone for potable water service and 385 Zone for recycled water
service.
Existing potable water service lines within the vicinity of the project include a 12-inch
water line in Avenida Encinas and an 8-inch water line in Embarcadero Lane. We
recommend that water service connections be made to the existing 318 Zone water
pipeline in Embarcadero Lane to serve the project. Based on pad elevations ranging from
56 to 58 feet, maximum static pressures for the project will range from 112 to 113 psi.
Water Demands
The two demands used to design the system are domestic demands from the buildings and
fire flow demands. Table 1 summarizes the projected fixture units for the project based
on information provided by the building architect. Using this information and
2234 FARADAY AVENUE • CARLSBAD, CA 92OO8 • (760)438-4422 • FAX (76O) 438-O173
Brad Perozzi
March 23, 2007
extrapolating Chart A-2 from the Uniform Plumbing Code, the total project fixture unit
count of 2,139 was determined to have an estimated peak water demand of 340 gpm.
Appendix A provides a detailed fixture unit count breakdown for the building plan and
provides Chart A-2 from the Uniform Plumbing Code.
TABLE 1
POINSETTIA COMMONS
WATER FIXTURE UNIT COUNT SUMMARY
221.5
343
167.5
134
134
167.5
167.5
167.5
167.5
10 134
11 134
12 100.5
13 100.5
DEXTER WILSON ENGINEERING, INC.PAGE 2
Brad Perozzi
March 23, 2007
Table 2 summarizes the maximum number of Water Fixture Units that can be served by
a given pipe diameter based on a maximum pipeline velocity of 8.0 feet per second. This
table was used to size recommended building service laterals.
TABLE 2
SIZE OF PRIVATE DOMESTIC SYSTEM PIPING
BASED ON NUMBER OF WATER FIXTURE
UNITS SERVED
0- 14 3/4-inch
15-29 1-inch
30-53 P/4 -inch
54 - 105 11/2-inch
106 - 270 2-inch
271 - 500 21/2-inch
501 - 780 3-inch
781 - 1,920 4-inch
1,921 - 3,575 5-inch
3,576-6,175 6-inch
A design fire flowrate of 4,000 gpm for commercial developments and 3,000 gpm for
multifamily developments were used in the fire system analysis, based on the 2003
Carlsbad Municipal Water District Water Master Plan. Fire sprinkler pipe sizing and
design are not considered in this water system analysis and will be provided by others.
DEXTER WILSON ENGINEERING, INC.PAGE 3
Brad Perozzi
March 23, 2007
Proposed Domestic Water System
Based on pad elevations ranging from 56 to 58 feet, the maximum static pressure within
the 318 Zone will range from 112 to 113 psi. Domestic water service connections for each
of the proposed buildings will be made to the existing 8-inch water line in Embarcadero
Lane. Each of the connection points will have a cluster of water master meters and
associated reduced pressure principle backflow preventers. The sizing and quantity of
water meters in a cluster is not considered in this water analysis and will be determined
by others. Table 3 provides the recommended water connection lateral sizes for each
building. Figure 1 displays the existing and recommended water system layout for the
project.
TABLES
RECOMMENDED WATER CONNECTION
LATERAL SIZES
i '••< " {«' ''•-:'?' Wx%sfelflt-;h X'.^' 4/-r--)l-
1
2
3
4
5
6
7
8
9
10
11
12
13
2"
2" (each)1
2"
2"
2"
2"
2"
2"
2"
2"
2"
ll/2"
1W
!There are two service laterals for this building.
DEXTER WILSON ENGINEERING, INC.PAGE 4
Brad Perozzi
March 23, 2007
Model Development. Analysis using the KYPIPE computer software developed by the
University of Kentucky determined residual pressures throughout the fire protection
system. This computer software utilizes the Hazen-Williams equation for determining
headless in pipes. The Hazen-Williams "C" value used for all pipe sizes in our analysis is
120.
The fire protection system was modeled with an estimated hydraulic grade line of 288 feet
at the existing 12-inch water main in Avenida Encinas. The fire protection system has
been designed to provide a minimum residual pressure greater than 20 psi under a fire
flow scenario at all locations within the proposed project development. For the project, a
fire flowrate of 3,000 gpm was modeled at nodes 28 and 40. A fire flowrate of 4,000 gpm
was also modeled at nodes 8 and 28.
The results of the computer analysis indicate that adequate water pressures are provided
to the Poinsettia Commons project. Furthermore, fire flow requirements are being met
with greater than 20 psi residual pressure at all locations within the project. Appendix B
provides the computer modeling output and Exhibit A provides the corresponding node
and pipe diagram.
Recycled Water
There is some potential for the use of recycled water on the site to irrigate the common
landscaped areas within the project. This is proposed to be accomplished by making a
single connection to the existing 12-inch recycled water line in Avenida Encinas. Figure 1
provides the approximate location of the existing recycled water line and proposed service
connection.
The 12-inch recycled water line is part of the City's 385 Zone recycled water system. With
service from this zone, maximum static pressures on the project are expected to range
from 142 to 143 psi.
DEXTER WILSON ENGINEERING, INC. PAGE 5
EX. 12" RECYCLED
WATER UNE
(385 ZONE)
EX. 12" WATER UNE.
318 PRESSURE ZONE
EX. 12" WATER UNE,
318 PRESSURE ZONE
PROJECT
BOUNDARY
EX 8" WATER UNE,—i
318 PRESSURE ZONE
EMBARCADERO LANE
BLOG
10
•PROPOSED
RECYCLED
WATER METER
LEGEND
- EXISTING PUBUC WATER UNES
EXISTING RECYCLED WATER UNE
PROPOSED DOMESTIC SERVICE
PROPOSED FIRE PROTECTION SYSTEM
txxi PROPOSED FIRE HYDRANT
FIGURE 1
POINSETTIA COMMONS
WATER SYSTEM LAYOUT
\\PACIFIC\DWG\852001\FIGURE-1.DWG 03-23-07 09:49:48 LAYOUT: FIGURE
Brad Perozzi
March 23, 2007
Conclusions and Recommendations
1. The recommended potable and recycled water facilities for the Poinsettia
Commons project are shown on Figure 1.
2. We recommend that building water service lateral sizes of P/2 inches to 21A
inches be used to connect to the existing 8-inch water transmission line in
Embarcadero Lane.
3. The location and sizing of the water meters and backflow preventers are not
considered in this water analysis and will be determined by others.
4. All fire hydrants on the project will be connected to the existing 8-inch water
line in Embarcadero Lane.
5. Individual pressure regulators should be installed on all potable water services
to maintain maximum water service pressures to the buildings at 80 psi.
6. Recycled water can be provided to the project by connecting to the existing 12-
inch recycled water line in Avenida Encinas.
Thank you for the opportunity to work on your project. If you have any questions or
require additional information, please let us know.
Dexter Wilson Engineering, Inc.
Stephen M. Nielsen
SMN:sbr
DEXTER WILSON ENGINEERING. INC. PAGE 7
APPENDIX A
WATER FIXTURE UNIT DATA
PLUMBING CODE DATA
i i it t t i t t i i i i t i i I J II ii ii i *
Water FU
Project Name Poinsettia Commons
Job Number 852-001
Date 8/4/2006
Water Supply Fixture Units
The basis for the Water Fixture Units is "Private" per the 2001 California Plumbing Code
DESCRIPTION:
Clothes Washer
Tub/Shower
Shower
Urinal
Kitchen Sink
Dishwasher
Laundry Sink
Lavatory
Water Closet (1.6 GPF)
Hose Bibb
Each Additional Hose Bibb
TOTAL
Commercial
QUANTITY
0
0
0
1
0
0
0
2
3
1
1
8
FIXTURE
UNITS
EACH
4
4
2
2
1.5
1.5
1.5
1
2.5
2.5
1
TOTAL
FIXTURE
UNITS
0
0
0
2
0
0
0
2
7.5
2.5
L 1
15
Daycare
QUANTITY
0
0
0
0
0
0
0
2
2
0
0
4
FIXTURE
UNITS
EACH
4
4
2
2
1.5
1.5
1.5
1
2.5
2.5
1
TOTAL
FIXTURE
UNITS
0
0
0
0
0
0
0
2
5
0
0
7
UnItA-1 ;•:
QUANTITY
1
1
0
0
1
1
0
1
1
0
0
6
FIXTURE
UNITS
EACH
4
4
2
2
1.5
1.5
1.5
1
2.5
2.5
1
TOTAL
FIXTURE
UNITS
4
4
0
0
1.5
1.5
0
1
2.5
0
0
14.5
UnitA-2
QUANTITY
1
1
0
0
1
1
0
1
1
0
0
6
FIXTURE
UNITS
EACH
4
4
2
2
1.5
1.5
1.5
1
2.5
2.5
1
TOTAL
FIXTURE
UNITS
4
4
0
0
1.5
1.5
0
1
2.5
0
0
14.5
DESCRIPTION:
Clothes Washer
Tub/Shower
Shower
Kitchen Sink
Dishwasher
Laundry Sink
Lavatory
Water Closet (1.6 GPF)
Hose Bibb
Each Additional Hose Bibb
Water Fountain
Urinal
TOTAL
UnitA-3
QUANTITY
1
1
0
0
1
1
0
1
1
0
0
0
6
FIXTURE
UNITS
EACH
4
4
2
1.5
1.5
1.5
1
2.5
2.5
1
0.5
2
TOTAL
FIXTURE
UNITS
4
4
0
0
1.5
1.5
0
2.5
2.5
0
0
0
16
Unit A-4
QUANTITY
1
1
0 J
01
1
01
1
0
0
0
6
FIXTURE
UNITS
EACH
4
4
2
1.5
1.5
1.5
1
2.5
2.5
1
0.5
2
TOTAL
FIXTURE
UNITS
4
4
0
0
1.5
1.5
0
2.5
2.5
0
0
0
16
UnitA-5
QUANTITY
1
1
0
0
1
1
0
1
1
0
0
0
6
FIXTURE
UNITS
EACH
4
4
2
1.5
1.5
1.5
1
2.5
2.5
1
0.5
2
TOTAL
FIXTURE
UNITS
4
4
0
0
1.5
1.5
0
2.5
2.5
0
0
0
16
UnitA-6
QUANTITY
1
1
0
0
1
1
0
1
1
0
0
0
6
FIXTURE
UNITS
EACH
4
4
2
1.5
1.5
1.5
1
2.5
2.5
1
0.5
2
TOTAL
FIXTURE
UNITS
4
4
0
0
1.5
1.5
0
2.5
2.5
0
0
0
16
Pagel
ii i i fc i c i i ii i i I i i i ft J t j i i i t
Water FU (2)
Project Name Poinsettia Commons
Job Number 852-001
Date 8/4/2006
Water Supply Fixture Units
The basis for the Water Fixture Units is "Private" per the 2001 California Plumbing Code
DESCRIPTION:
Clothes Washer
Tub/Shower
Shower
Kitchen Sink
Dishwasher
Laundry Sink
Lavatory
Water Closet (1.6 GPF)
Hose Bibb
Each Additional Hose Bibb
TOTAL
; ;" tfciWf '
QUANTITY
1
2
0
1
1
0
3
2
0
0
10
FIXTURE
UNITS
EACH
4
4
2
1.5
1.5
1.5
1
2.5
2.5
1
TOTAL
FIXTURE
UNITS
4
8
0
1.5
1.5
0
3
5
0
0
23
yniB~2
QUANTITY
1
2
0
1
1
0
3
2
0
0
10
FIXTURE
UNITS
EACH
4
4
2
1.5
1.5
1.5
1
2.5
2.5
1
TOTAL
FIXTURE
UNITS
4
8
0
1.5
1.5
0
3
5
0
0
23
UMtB-3
QUANTITY
1
2
0
1
1
0
3
2
0
0
10
FIXTURE
UNITS
EACH
4
4
2
1.5
1.5
1.5
1
2.5
2.5
1
TOTAL
FIXTURE
UNITS
4
8
0
1.5
1.5
0
3
5
0
0
23
-' * ., ywffr^'' -
QUANTITY
1
2
0
1
1
0
3
2
0
0
10
FIXTURE
UNITS
EACH
4
4
2
1.5
1.5
1.5
1
2.5
2.5
1
TOTAL
FIXTURE
UNITS
4
8
0
1.5
1.5
0
3
5
0
0
23
DESCRIPTION:
Clothes Washer
Tub/Shower
Shower
Urinal
Kitchen Sink
Dishwasher
Laundry Sink
Lavatory
Water Closet (1.6 GPF)
Hose Bibb
Each Additional Hose Bibb
Water Fountain
TOTAL
ewtrpt, ; _ .
QUANTITY
1
2
0
0
1
1
0
3
2
0
0
0
10
FIXTURE
UNITS
EACH
4
4
2
2
1.5
1.5 '
1.5
1
2.5
2.5
1
0.5
TOTAL
FIXTURE
UNITS
4
8
0
0
1.5
1.5
0
3
5
0
0
0
23
Unit D-1
QUANTITY
1
2
0
0
1
1
0
3
2
\0
0
0
10
FIXTURE
UNITS
EACH
4
4
2
2
1.5
1.5
1.5
1
2.5
2.5
1
0.5
TOTAL
FIXTURE
UNITS
4
8
0
0
1.5
1.5
0
3
5
0
0
0
23
Retail
QUANTITY
0
0
0
4
1
1
0
.43•r1
0
18
FIXTURE
UNITS
EACH
4 .
4
2
2
1.5
1.5
1.5
1
2.5
2.5
1
0.5
TOTAL
FIXTURE
UNITS
0
0
0
8
1.5
1.5
0
4
15
2.5
1
0
33.5
Ur*^f
QUANTITY
1
2
1
0
1
1
1
4
3
1
1
0
16
FIXTURE
UNITS
EACH
4
4
2
2
1.5
1.5
1.5
1
2.5
2.5
1
0.5
TOTAL
FIXTURE
UNITS
4
8
2
0
1.5
1.5
1.5
4
7.5
2.5
1
0
33.5
Page 2
Water FU (3)
Project Name
Job Number
Date
Poinsettia Commons
852-001
8/4/2006
Water Supply Fixture Units
The basis for the Water Fixture Units is "Private" per the 2001 California Plumbing Code
DESCRIPTION:
Clothes Washer
Tub/Shower
Shower
Kitchen Sink
Dishwasher
Laundry Sink
Lavatory
Water Closet (1.6 GPF)
Hose Bibb
Each Additional Hose Bibb
TOTAL
r fhit-E2 ' ,;;;J
QUANTITY
1
2
1
1
1
1
4
3
1
1
16
FIXTURE
UNITS
EACH
4
4
2
1.5
1.5
1.5
1
2.5
2.5
1
TOTAL
FIXTURE
UNITS
4
8
2
1.5
1.5
1.5
4
7.5
2.5
1
33.5
UnilE-3
QUANTITY
1
2
1
1
1
1
4
3
1
1
16
FIXTURE
UNITS
EACH
4
4
2
1.5
1.5
1.5
1
2.5
2.5
1
TOTAL
FIXTURE
UNITS
4
8
2
1.5
1.5
1.5
4
7.5
2.5
1
33.5
UnitF-t Jj
QUANTITY
1
2
1
1
1
1
4
3
1
1
16
FIXTURE
UNITS
EACH
4
4
2
1.5
1.5
1.5
1
2.5
2.5
1
TOTAL
FIXTURE
UNITS
4
8
2
1.5
1.5
1.5
4
7.5
2.5
1
33.5
?\ UNfefe^ , :
QUANTITY
1
2
1
1
1
1
4
3
1
1
16
FIXTURE
UNITS
EACH
4
4
2
1.5
1.5
1.5
1
2.5
2.5
1
TOTAL
FIXTURE
UNITS
4
8
2
1.5
1.5
1.5
4
7.5
2.5
1
33.5
DESCRIPTION:
Clothes Washer
Tub/Shower
Shower
Kitchen Sink
Dishwasher
Laundry Sink
Lavatory
Water Closet (1.6 GPF)
Hose Bibb
Each Additional Hose Bibb
Water Fountain
Urinal
TOTAL
t "\fc\\b F* O
QUANTITY
1
2
1
1
1
1
4
3
1
1
0
0
16
FIXTURE
UNITS
EACH
4
4
2
1.5
1.5
1.5
1
2.5
2.5
1
0.5
2
TOTAL
FIXTURE
UNITS
4
8
2
1.5
1.5
1.5
4
7.5
2.5
1
0
0
33.5
• ''. 0nitF-4
QUANTITY
1
2
1
1
1
1
4
3
1
1
0
0
16
FIXTURE
UNITS
EACH
4
4
2
1.5
1.5
1.5
1
2.5
2.5
1
0.5
2
TOTAL
FIXTURE
UNITS
4
8
2
1.5
1.5
1.5
4
7.5
2.5
1
0
0
33.5
Unit G-1
QUANTITY
1
2
1
1
1
1
4
3
1
1
0
0
16
FIXTURE
UNITS
EACH
4
4
2
1.5
1.5
1.5
1
2.5
2.5
1
0.5
2
TOTAL
FIXTURE
UNITS
4
8
2
1.5
1.5
1.5
4
7.5
2.5
1
0
0
33.5
UnitG-2
QUANTITY
1
2
1
1
1
1
4
3
1
1
0
0
16
FIXTURE
UNITS
EACH
4
4
2
1.5
1.5
1.5
1
2.5
2.5
1
0.5
2
TOTAL
FIXTURE
UNITS
4
8
2
1.5
1.5
1.5
4
7.5
2.5
1
0
0
33.5
PageS
t i I i I i
Water FU (4)
Project Name
Job Number
Date
Poinsettia Commons
852-001
8/4/2006
Water Supply Fixture Units
The basis for the Water Fixture Units is "Private" per the 2001 California Plumbing Code
DESCRIPTION:
Commercial
Daycare
Unit A-1
UnitA-2
Unit A-3
Unit A-4
UnitA-5
UnitA-6
TOTAL
Building 1
QUANTITY
2
1
2
3
1
2
3
1
15
FIXTURE
UNITS
EACH
15
7
14.5
14.5
16
16
16
16
TOTAL
FIXTURE
UNITS
30
7
29
43.5
16
32
48
16
221.5
DESCRIPTION:
Retail
Unit B-1
Unit B-2
Unit B-3
Unit B-4
Unit C-1
Unit D-1
TOTAL
Building 2
QUANTITY
2
1
2
3
1
2
3
14
FIXTURE
UNITS
EACH
33.5
23
23
23
23
23
23
TOTAL
FIXTURE
UNITS
67
23
46
69
23
46
69
343
DESCRIPTION:
Unit E-3
Unit F-1
TOTAL
Building 3
QUANTITY
3
2
5
FIXTURE
UNITS
EACH
33.5
33.5
TOTAL
FIXTURE
UNITS
100.5
67
167.5
DESCRIPTION:
Unit E-2
Unit F-3
Unit G-2
TOTAL
Building 4
QUANTITY
2
1
1
4
FIXTURE
UNITS
EACH
33.5
33.5
33.5
TOTAL
FIXTURE
UNITS
67
33.5
33.5
134
DESCRIPTION:
Unit E-2
Unit F-3
Unit G-2
TOTAL
Buildings
QUANTITY
2
1
1
4
FIXTURE
UNITS
EACH
33.5
33.5
33.5
TOTAL
FIXTURE
UNITS
67
33.5
33.5
134
DESCRIPTION:
Unit E-1
Unit F-1
Unit F-2
Unit G-1
TOTAL
Buildings
QUANTITY
2
1
1
1
5
FIXTURE
UNITS
EACH
33.5
33.5
33.5
33.5
TOTAL
FIXTURE
UNITS
67
33.5
33.5
33.5
167.5
Page 1
II li li 1 i li I i I i I i li i i i i I I i
Water FU (5)
Project Name Poinsettia Commons
Job Number 852-001
Date 8/4/2006
Water Supply Fixture Units
The basis for the Water Fixture Units is "Private" per the 2001 California Plumbing Code
DESCRIPTION:
Unit E-1
Unit F-1
Unit F-2
Unit G-1
TOTAL
Building?
QUANTITY
2
1
1
1
5
FIXTURE
UNITS
EACH
33.5
33.5
33.5
33.5
TOTAL
FIXTURE
UNITS
67
33.5
33.5
33.5
167.5
DESCRIPTION:
Unit E-2
Unit F-3
Unit F-4
Unit G-1
TOTAL
Building 8
QUANTITY
2
1
1
1
5
FIXTURE
UNITS
EACH
33.5
33.5
33.5
33.5
TOTAL
FIXTURE
UNITS
67
33.5
33.5
33.5
167.5
DESCRIPTION:
Unit E-2
Unit F-3
Unit F-4
Unit G-1
TOTAL
Building 9
QUANTITY
2
1
1
1
5
FIXTURE
UNITS
EACH
33.5
33.5
33.5
33.5
TOTAL
FIXTURE
UNITS
67
33.5
33.5
33.5
167.5
DESCRIPTION:
Unit E-1
Unit F-1
Unit F-2
Unit G-1
TOTAL
:.-'. ^Building 10
QUANTITY
2
1
1
1
5
FIXTURE
UNITS
EACH
33.5
33.5
33.5
33.5
TOTAL
FIXTURE
UNITS
67
33.5
33.5
134
DESCRIPTION:
Unit E-1
Unit F-1
Unit F-2
Unit G-1
TOTAL
Building 1.1
QUANTITY
2
1
1
1
5
FIXTURE
UNITS
EACH
33.5
33.5
33.5
33.5
TOTAL
FIXTURE
UNITS
67
33.5
33.5
134
DESCRIPTION:
Unit E-2
Unit F-3
Unit F-4
TOTAL
Building 12
QUANTITY
2
1
1
4
FIXTURE
UNITS
EACH
33.5
33.5
33.5
TOTAL
FIXTURE
UNITS
67
33.5
100.5
DESCRIPTION:
Unit E-2
Unit F-3
Unit F-4
TOTAL
. Building 13
QUANTITY
2
1
1
4
FIXTURE
UNITS
EACH
33.5
33.5
33.5
TOTAL
FIXTURE
UNITS
67
33.5
100.5
Page 2
SIZING WATER SYSTEMS Appendix A
CHART A-3
Enlarged Scale Demand Load
&'3i
XII
I
20 40 60 80 100 120 140 160 180 200 220 240
Fixture Units
CHART A-3 (Metric)
Enlarged Scale Demand Load
20 40 60 80 100 120 140 160 180 200 220 240
Fixture Units
191
ti t i ii ti li I J i
7oo
CHA
Estimate Curves
500 [Hill || in 1 1 1 1 1 1 MM 1 1| inn
400
S 300
a.
3 • -»i :::::::::::::::::::::::::;!.:
O -ft....
II 1 1 1 1 1 llfjJrfT 1 1 1 1 1 II 1 1 1 1 1 1 II
inn -'.'.li'i'.rz-.: ^0- 1 for system pre<
, ' . . Mo. 2 for system prw
J !::: i "":::":::::::: :
2001 CALIFORNIA PLUMBING
RTA-2
for Demand Load
.s^
^s^j*f^
.f^
_ . _ i. _ __ -^^^
: : ::: : : : ::: : : : : : : : ; : : :: : : : j 55!
(i. t
---- -^.i.-..
: ;:";?!: : • • : : ;!!""""j * * ..-- -*
lominantly for flushometer valves
tominantly for flush tanks : : : :
CODE
\
^--^
^
-"
0 500 1000 1500 2000 2500 3000 35*0 •*>«> *sw> s«-. ss*o t-. tsis> 7oot>
Fixture Units
APPENDIX B
WATER SYSTEM ANALYSIS
The following conditions were modeled:
1. Average day demands
2. Maximum day demands plus fire flow demand of 4,000 gpm at node 8 and
28
3. Maximum day demands plus fire flow demand of 3,000 gpm at node 28
and 40
4. Peak hour demands
Foinsettia Commons
Water System Analysis
Project No.: 852-001
File Name: point
August 17,2006
FLOWRATE IS EXPRESSED IN GPM AND PRESSURE IN PSIG
(SCENARIO :
PIPE NO
AVERAGE DAY DEMANDl
. NODE NOS. LENGTH
(FEET)
3
7
11
15
19
21
23
27
31
35
39
43
47
51
55
59
63
67
0
4
8
12
16
20
22
24
28
32
36
40
44
48
52
56
60
64
64
8
12
16
20
22
24
28
32
36
40
44
48
52
56
60
64
4
JUNCTION NUMBER
4
8
12
16
20
22
24
28
32
36
40
44
48
52
56
60
64
DEMAND
.00
2.53
.93
.93
.93
2.53
.93
.93
.93
.93
.93
.93
.93
.93
.93
.00
.00
120
150
120
30
70
50
50
50
60
60
130
50
50
20
30
500
950
250
.0
.0
.0
.0
.0
.0
.0
.0
.0
.0
.0
.0
.0
.0
.0
.0
.0
.0
DIAMETER
(INCHES)
12.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
12.0
12.0
ELEVATION
56.00
58.00
58.00
58.00
57.00
56.00
57.00
57.00
56.00
56.00
56.00
56.00
56.00
57.00
57.00
57.00
57.00
ROUGHNESS MINOR LOSS K FIXED GRADE
120.
120.
120.
120.
120.
120.
120.
120.
120.
120.
120.
120.
120.
120.
120.
120.
120.
120.
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
CONNECTING
7
7
11
15
19
21
23
27
31
35
39
43
47
51
55
59
3
67
11
15
19
21
23
27
31
35
39
43
47
51
55
59
63
63
.00 288.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
PIPES
67
OUTPUT SELECTION: ALL RESULTS ARE OUTPUT EACH PERIOD
3 VALUES ARE OUTPUT FOR MAXIMUM AND MINIMUM PRESSURES
THIS SYSTEM HAS 18 PIPES WITH 17 JUNCTIONS, 1 LOOPS AND 1 FGNS
THE RESULTS ARE OBTAINED AFTER 9 TRIALS WITH AN ACCURACY = .00114
Dexter Wilson Engineering Page 1 of 9
Poinsettia Commons
Water System Analysis
Project No.: 852-001
File Name: point
August 17,2006
PIPE NO.
3
7
11
15
19
21
23
27
31
35
39
43
47
51
55
59
63
67
JUNCTION
4
8
12
16
20
22
24
28
32
36
40
44
48
52
56
60
64
4
48
44
16
12
8
NODE
0
4
8
12
16
20
22
24
28
32
36
40
44
48
52
56
60
64
NOS.
64
8
12
16
20
22
24
28
32
36
40
44
48
52
56
60
64
4
NUMBER
FLOWRATE HEAD
16.22
9.90
7.37
6.44
5.51
4.58
2.05
1.12
.19
-.74
-1.67
-2.60
-3.53
-4.46
-5.39
-6.32
-6.32
9.90
DEMAND
.00
2.53
.93
.93
.93
2.53
.93
.93
.93
.93
.93
.93
.93
.93
.93
.00
.00
MAXIMUM
.00
.93
.93
MINIMUM
.93
.93
2.53
GRADE
288
288
288
288
288
288
288
288
288
288
288
288
288
288
288
288
288
LOSS PUMP HEAD MINOR LOSS VELOCITY HL/1000
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
LINE
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
ELEVATION
56.00
58.00
58.00
58.00
57.00
56.00
57.00
57.00
56.00
56.00
56.00
56.00
56.00
57.00
57.00
57.00
57.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.05
.06
.05
.04
.04
.03
.01
.01
.00
.00
-.01
-.02
-.02
-.03
-.03
-.04
-.02
.03
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
PRESSURE
100.
99.
99.
99.
100.
100.
100.
100.
100.
100.
100.
100.
100.
100.
100.
100.
100.
53
67
67
67
10
53
10
10
53
53
53
53
53
10
10
10
10
PRESSURES
288
288
288
.00
.00
.00
56.00
56.00
56.00
100.
100.
100.
53
53
53
PRESSURES
288
288
288
.00
.00
.00
58.00
58.00
58.00
99.
99.
99.
67
67
67
THE NET SYSTEM DEMAND =16.22
Dexter Wilson Engineering Page 2 of 9
Poinsettia Commons Project No.: 852-001
Water System Analysis File Name: point
August 17,2006
SUMMARY OF INFLOWS (+) AND OUTFLOWS (-) FROM FIXED GRADE NODES
PIPE NUMBER FLOWRATE
3 16.22
THE NET FLOW INTO THE SYSTEM FROM FIXED GRADE NODES = 16.22
THE NET FLOW OUT OF THE SYSTEM INTO FIXED GRADE NODES = .00
Dexter Wilson Engineering Page 3 of 9
Poinsettia Commons
Water System Analysis
Project No.: 852-001
File Name: point
August 17, 2006
A SUMMARY OF CONDITIONS SPECIFIED FOR THE NEXT SIMULATION FOLLOWS
THE DEMANDS ARE CHANGED FROM ORIGINAL VALUES BY A FACTOR = 1.65
THE FOLLOWING SPECIFIC DEMAND CHANGES ARE MADE:
JUNCTION NUMBER DEMAND
8 2002.53
28 2002.53
THE RESULTS ARE OBTAINED AFTER 3 TRIALS WITH AN ACCURACY = .00006
[SCENARIO: FIRE FLOW DEMAND OF 4,000
PIPE NO. NODE
3
7
11
15
19
21
23
27
31
35
39
43
47
51
55
59
63
67
0
4
8
12
16
20
22
24
28
32
36
40
44
48
52
56
60
64
NOS.
64
8
12
16
20
22
24
28
32
36
40
44
48
52
56
60
64
4
JUNCTION NUMBER
4
8
12
16
20
22
24
28
32
36
40
44
48
52
FLOWRATE
4026.11
2803.94
801.41
799.88
798.35
796.81
792.64
791.10
-1211.43
-1212.96
-1214.50
-1216.03
-1217.57
-1219.10
-1220.64
-1222.17
-1222.17
2803.94
DEMAND
.00
2002.53
1.53
1.53
1.53
4.17
1.53
2002.53
1.53
1.53
1.53
1.53
1.53
1.53
HEAD
4.
21.
1.
.
.
_ 1
-1.
-3.
-1.
-1.
-.
-15.
-4.
4.
GRADE
278.
256.
255.
254.
253.
253.
252.
251.
253.
255.
259.
260.
262.
263.
GPM SPLIT BETWEEN NODES 8 AND 28
LOSS PUMP HEAD MINOR LOSS VELOCITY HL/1000
66
45
69
42
98
70
69
69
81
82
95
52
53
61
92
36
05
96
LINE
38
93
24
82
85
15
46
78
59
41
35
88
40
01
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
ELEVATION
56.
58.
58.
58.
57.
56.
57.
57.
56.
56.
56.
56.
56.
57.
00
00
00
00
00
00
00
00
00
00
00
00
00
00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
11.42
17.90
5.11
5.11
5.10
5.09
5.06
5.05
-7.73
-7.74
-7.75
-7.76
-7.77
-7.78
-7.79
-7.80
-3.47
7.95
38
143
14
14
13
13
13
13
-30
-30
-30
-30
-30
-30
-30
-30
-4
19
.79
.00
.06
.01
.96
.91
.78
.73
.22
.29
.37
.44
.51
.58
.65
.72
.26
.85
PRESSURE
96
86
85
85
85
85
84
84
85
86
88
88
89
89
.37
.20
.47
.29
.30
.43
.70
.40
.62
.41
.12
.78
.44
.27
Dexter Wilson Engineering Page 4 of 9
Poinsettia Commons
Water System Analysis
64
4
60
28
24
16
MAXIMUM PRESSURES
.00 283.34
.00 278.38
.00 279.29
MINIMUM PRESSURES
2002.53 251.78
1.53 252.46
1.53 254.82
57.00
56.00
57.00
57.00
57.00
58.00
Project No.: 852-001
File Name: point
August 17,2006
56
60
64
1.53
.00
.00
263.93
279.29
283.34
57.00
57.00
57.00
89.67
96.33
98.08
98.08
96.37
96.33
84.40
84.70
85.29
THE NET SYSTEM DEMAND = 4026.11
SUMMARY OF INFLOWS (+) AND OUTFLOWS (-) FROM FIXED GRADE NODES
PIPE NUMBER
3
FLOWRATE
4026.11
THE NET FLOW INTO THE SYSTEM FROM FIXED GRADE NODES = 4026.11
THE NET FLOW OUT OF THE SYSTEM INTO FIXED GRADE NODES = .00
Dexter Wilson Engineering Page 5 of 9
Poinsettia Commons
Water System Analysis
Project No.: 852-001
File Name: point
August 17,2006
A SUMMARY OF CONDITIONS SPECIFIED FOR THE NEXT SIMULATION FOLLOWS
THE DEMANDS ARE CHANGED FROM ORIGINAL VALUES BY A FACTOR = 1.65
THE FOLLOWING SPECIFIC DEMAND CHANGES ARE MADE:
JUNCTION NUMBER DEMAND
28 1502.53
40 1500.93
THE RESULTS ARE OBTAINED AFTER 2 TRIALS WITH AN ACCURACY = .00156
SCENARIO :
PIPE NO.
3
7
11
15
19
21
23
27
31
35
39
43
47
51
55
59
63
67
JUNCTION
4
8
12
16
20
22
24
28
32
36
40
44
48
52
FIRE FLOW DEMAND OF 3,000
NODE NOS.
0
4
8
12
16
20
22
24
28
32
36
40
44
48
52
56
60
64
NUMBER
64
8
12
16
20
22
24
28
32
36
40
44
48
52
56
60
64
4
FLOWRATE
3027.15
1653.68
1649.50
1647.97
1646.44
1644.90
1640.73
1639.19
1 136.66
135.13
133.59
-1367.34
-1368.87
-1370.41
-1371.94
-1373.48
-1373.48
1653.68
DEMAND
.00
4.17
1.53
1.53
1.53
4.17
1.53
1502.53
1.53
1.53
1500. 93
1.53
1.53
1.53
HEAD
2.
8.
6.
1.
3.
2.
2.
2.
.
.
-1.
-1.
-.
-1.
-19.
-5.
1.
GRADE
283.
275.
268.
267.
263.
260.
258.
255.
255.
255.
255.
257.
259.
260.
GPM SPLIT BETWEEN NODES 28 AND 40
LOSS PUMP HEAD MINOR LOSS VELOCITY HL/1000
75
07
42
60
73
66
65
65
03
03
07
89
89
76
14
07
03
87
LINE
39
32
90
29
56
90
25
60
57
54
47
36
26
02
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
ELEVATION
56.
58.
58.
58.
57.
56.
57.
57.
56.
56.
56.
56.
56.
57.
00
00
00
00
00
00
00
00
00 -
00
00
00
00
00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
8.59
10.55
10.53
10.52
10.51
10.50
10.47
10.46
.87
.86
.85
-8.73
-8.74
-8.75
-8.76
-8.77
-3.90
4.69
22.88
53.78
53.53
53.44
53.35
53.26
53.01
52.91
.53
.52
.51
-37.82
-37.90
-37.98
-38.06
-38.13
-5.29
7.47
PRESSURE
98.
94.
91.
90.
89.
88.
87.
86.
86.
86.
86.
87.
88.
87.
53
17
39
69
51
79
21
06
48
47
44
26
08
97
Dexter Wilson Engineering Page 6 of 9
Poinsettia Commons
Water System Analysis
Project No.: 852-001
File Name: point
August 17,2006
56
60
64
1.53
.00
.00
261.16
280.23
285.25
57.00
57.00
57.00
88.47
96.73
98.91
64
4
60
MAXIMUM PRESSURES
.00 285.25
.00 283.39
.00 280.23
57.00
56.00
57.00
98.91
98.53
96.73
28
40
36
MINIMUM PRESSURES
1502.53 255.60
1500.93 255.47
1.53 255.54
57.00
56.00
56.00
86.06
86.44
86.47
THE NET SYSTEM DEMAND =3027.15
SUMMARY OF INFLOWS (+) AND OUTFLOWS (-) FROM FIXED GRADE NODES
PIPE NUMBER
3
FLOWRATE
3027.15
THE NET FLOW INTO THE SYSTEM FROM FIXED GRADE NODES = 3027.15
THE NET FLOW OUT OF THE SYSTEM INTO FIXED GRADE NODES = .00
Dexter Wilson Engineering Page 7 of 9
Poinsettia Commons
Water System Analysis
Project No.: 852-001
File Name: point
August 17, 2006
A SUMMARY OF CONDITIONS SPECIFIED FOR THE NEXT SIMULATION FOLLOWS
THE DEMANDS ARE CHANGED FROM ORIGINAL VALUES BY A FACTOR = 2.90
THE RESULTS ARE OBTAINED AFTER 3 TRIALS WITH AN ACCURACY = .00013
SCENARIO :
PIPE NO.
3
7
11
15
19
21
23
27
31
35
39
43
47
51
55
59
63
67
JUNCTION
4
8
12
16
20
22
24
28
32
36
40
44
48
52
56
60
64
PEAK HOUR
NODE
0
4
8
12
16
20
22
24
28
32
36
40
44
48
52
56
60
64
NOS.
64
8
12
16
20
22
24
28
32
36
40
44
48
52
56
60
64
4
NUMBER
DEMAND)
FLOWRATE
47.04
28.70
21.36
18.67
15.97
13.27
5.94
3.24
.54
-2.16
-4.85
-7.55
-10.25
-12.94
-15.64
-18.34
-18.34
28.70
DEMAND
.00
7.34
2.70
2.70
2.70
7.34
2.70
2.70
2.70
2.70
2.70
2.70
2.70
2.70
2.70
.00
.00
HEAD
-
GRADE
288
287
287
287
287
287
287
287
287
287
287
287
287
287
287
288
288
LOSS PUMP HEAD MINOR LOSS VELOCITY
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.01
.00
.00
LINE
.00
.99
.99
.99
.99
.99
.99
.99
.99
.99
.99
.99
.99
.99
.99
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
ELEVATION
56.00
58.00
58.00
58.00
57.00
56.00
57.00
57.00
56.00
56.00
56.00
56.00
56.00
57.00
57.00
57.00
57.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.00
.13
.18
.14
.12
.10
.08
.04
.02
.00
-.01
-.03
-.05
-.07
-.08
-.10
-.12
-.05
.08
HL/1000
.01
.03
.02
.01
.01
.01
.00
.00
.00
.00
.00
.00
.00
-.01
-.01
-.01
.00
.00
PRESSURE
100.
99.
99.
99.
100.
100.
100.
100.
100.
100.
100.
100.
100.
100.
100.
100.
100.
53
66
66
66
10
53
10
10
53
53
53
53
53
10
10
10
10
Dexter Wilson Engineering Page 8 of 9
Poinsettia Commons
Water System Analysis
Project No.: 852-001
File Name: point
August 17,2006
MAXIMUM PRESSURES
4
48
44
.00
2.70
2.70
288.00
287.99
287.99
56.00
56.00
56.00
100.53
100.53
100.53
16
12
8
MINIMUM PRESSURES
2.70 287.99
2.70 287.99
7.34 287.99
58.00
58.00
58.00
99.66
99.66
99.66
THE NET SYSTEM DEMAND = 47.04
SUMMARY OF INFLOWS (+) AND OUTFLOWS (-) FROM FIXED GRADE NODES
PIPE NUMBER
3
FLOWRATE
47.04
THE NET FLOW INTO THE SYSTEM FROM FIXED GRADE NODES =
THE NET FLOW OUT OF THE SYSTEM INTO FIXED GRADE NODES =
47.04
.00
Dexter Wilson Engineering Page 9 of 9
i f
I
EX. 12" WATER UNE,
318 PRESSURE ZONE
EX. 8" WATER UNE,
318 PRESSURE ZONE
EMBARCADERO LANE
/. "• JEX. 12" WATER LINE,
318 PRESSURE ZONE
LEGEND
EXISTING PUBLIC WATER LINES
PROPOSED DOMESTIC SERVICE
PROPOSED FIRE HYDRANT
COMPUTER MODEL PIPE NUMBER
COMPUTER MODEL NODE NUMBER
PROJECT
BOUNDARY
EXHIBIT A
POINSETTIA COMMONS
NODE AND PIPE DIAGRAM
\\PACIFIC\DWG\852001\EXHIBIT-A.DWG 08-17-06 13:36:31 LAYOUT: EXHIBIT