DESIGN REPORT FOR
SEGMENTAL BLOCK RETAINING WALLS
ANCHOR VERTICA® BLOCKS
Buena Vista 11 Subdivision
APN 156-200-01,02, and 15
Carlsbad, California
Prepared for:
HOMELAND ENGINEERING
11337 Moreno Avenue
Lakeside, CA 92040
September 24, 2014
Project No. 14220
ABI Engineering Consultants, Inc.
1701 E. Edinger Avenue, #A9
Santa Ana, Califomia 92705
Tel.: (888) 220-5596
Fax: (714) 866-4171
Buena Vista 11 Subdivision, Carlsbad, CA
Anchor Walls Design
TABLE OF CONTENTS
INTRODUCTION
PROPOSED WALL DESCRIPTION
DESIGN METHODOLOGY
SEISMIC DESIGN METHOD
DESIGN PARAMETERS
Soils Parameters
Wall Parameters
ANALYSIS 2
Static Analysis 2
Seismic Analysis 2
RECOMMENDATIONS 2
REFERENCES 3
ABI Engineering Consultants, Inc.
Buena Vista 11 Subdivision, Carlsbad, CA
Anchor Walls Design
INTRODUCTION
This report presents the design parameters, design methodology, and calculations performed to
design proposed segmental block retaining walls utilizing Anchor Vertica® Blocks for Buena Vista
11 Subdivision, APN 156-200-01, 02, and 15, City ofCarlsbad, California.
PROPOSED WALL DESCRIPTION
Based on our review of the referenced Grading Plan for this project, two (2) segmental retaining
walls are proposed for site development. The maximum height of the walls is 10 feet.
DESIGN METHODOLOGY
The computer code Anchor Wall® Version 6.0 developed by Anchor Retaining Wall systems is used
to complete the analysis. The computer code is based on the methods presented in National Concrete
Masonry Association guidelines (NCMA 2010). The National Concrete Masonry (NCMA) 3"*
edition method of design of segmental block walls uses Coulomb Earth Pressure theory. Anchor
Wall 6.0 program customized for use with Anchor's blocks, allows specifying choice of block types
and geogrids reinforcement. The results of the analysis are included as Appendix A.
The seismic intemal stability of the Anchor segmental walls was explored using Anchor Wall® 6.0,
which incorporates pseudo-static rigid body approach that adopts the Mononobe-Okabe method to
calculate dynamic forces (NCMA 2010).
SEISMIC DESIGN METHOD
The seismic intemal stability of the Anchor segmental walls was explored using Anchor Wall® 6.0,
which incorporates pseudo-static rigid body approach that adopts the Mononobe-Okabe method to
calculate dynamic forces (NCMA 3rd Edition). Based on the recommendations provided by Project
Geotechnical Engineer (Inland Engineering Technologies) an acceleration of 0.27 g is used in the
seismic analysis.
DESIGN PARAMETERS
Soils Parameters
Based on the geotechnical recommendations received from Project Geotechnical Engineer, we have
used the following design strength parameters. It is our recommendation that these parameters be
checked by the Soils Engineer and select fill material with minimum parameters indicated below is
used for the reinforced zone backfill.
Reinforced Fill Retained Soil Foundation Soil
Internal Friction Angle, (|)° 34 30 32
Cohesion, C (psf) 0 0 0
Soil Unit Weight, Y(pcf) 125 125 125
Wall Parameters
Walls are designed using 12-inch deep Anchor Vertica® segmental block units. The design
considered a batter of 4 degrees to the vertical. Surcharge from the slope above the wall is applied,
where applicable. The embedment of the wall at the base is set to a niinimum of 0.5'or 10% of
exposed wall height. The embedment depth is also adjusted to achieve minimum 5 feet day light
ABI Engineering Consultants, Inc.
Buena Vista 11 Subdivision, Carlsbad, CA
MSE Walls Design
distance from the bottom of wall. The wall embedment is incorporated in the wall elevation
presented on the wall plans.
Mirafi geogrid manufactured by TenCate are used for soil reinforcement in the design ofthe walls.
Geogrids of other manufactures are acceptable substitutes, upon our approval. Typical cross-section
of the wall, general notes for wall constmction, geogrids reinforcement schedule and design
parameters are included on the drawings.
The design ofthe retaining wall assumes no build-up of hydrostatic pressures within the reinforced
fill zone ofthe wall. Therefore, constmction of an effective subdrain system behind the reinforced
soil zone and area drain system to drain surface water away from the wall is critical to the
performance of the walls.
ANALYSIS
The wall design is based on the following factor of safety (FS) for stability analysis of the wall. The
factors of safety are for static loading conditions are indicated below and are based on the current
standard of practice.
Static Analysis
FS Ba,seSliding= 1-5, FS Bearing Capacity^ 2.0, FS overturning^ 2.0, FS pull-out= 1-5 and FS uncertainties^ 1-5
Seismic Analysis
FS sliding^ l-li FS bearing— 1-5, FS overturning— l-l^ pull-out— l-l; and FS uncertainties— l-l-
The summary calculations present the data and results for each section of the wall.
RECOMMENDATIONS
The wall shall be constmcted per the details and geogrid reinforcement schedule based on the design
calculations provided in this report, typical section, reinforcement schedule, and construction notes
presented on drawings. The Anchor wall shall be constmcted per the manufacturer's recommended
procedures. No substitution shall be allowed for blocks type or for the unit fill required within the
units and behind the blocks. Special inspections shall be implemented during construction for wall
elements and earthwork.
The foundation, retained, and backfill soils shall have the minimum shear strength properties as used
for design in this report. All backfill shall be placed in loose lifts not exceeding 8 inches; moisture
conditioned, and compacted to a minimum of 90% of the maximum dry density determined by
Modified Proctor compaction test (ASTM D1557).
The project geotechnical engineer is responsible to verify the foundation soil, retained soil, and
backfill soils and their strength are consistent with their geotechnical report findings and as used in
the design of the wall. The compaction tests shall be performed on backfill soils for meeting the
minimum densities recommended. Any changes to foundation, retained and backfill soil properties
and loading conditions on the wall should be brought to our attention. The temporary excavation
ABI Engineering Consultants, Inc.
Buena Vista 11 Subdivision, Carlsbad, CA
MSE Walls Design
back-cut, grading, ground improvement, fill settlement control, and sub-drain, and surface-drainage
system for the Anchor wall shall be per the Project Soils and Civil Engineer's recommendations.
Any changes to grading plans that affects the wall heights and loading conditions shall be brought to
our attention to verily the wall design is applicable and to verify that no design changes are
necessary.
REFERENCES
1. Anchor Retaining Wall Systems, Anchor Wall Version 6.0 Software Documentation,
Issued in 2012.
2. ICC Evaluation Service, Inc., ES Report No. ESR-1959 for Anchor Wall Retaining Wall
Systems, Reissued June 1, 2013.
3. GeoSoils, Inc., Preliminary Geotechnical Evaluation, Buena Vista 11 Subdivision, APN
156-200-01, 02, and 15, City ofCarlsbad, California, Dated March 13, 2013.
4. Lundstrom Engineering and Surveying, Inc., Grading Plan for Buena Vista 11, Carlsbad,
Califomia, Dated September 4, 2014.
5. NCMA 2010, Design Manual for Segmental Retaining Walls, Third Edition, 2010.
ABI Engineering Consultants, Inc.
Buena Vista 11 Subdivision, Carlsbad, CA
Anchor Walls Design
APPENDIX A - Design Calculations
ABI Engineering Consultants, Inc.
project: 14220 - Buena Vista 11 [Rev. 1] Wall: Wall A
M| ANCHOR'
m^Zi BUILD SOMETHING BEAUTIFUL
Project Information
Client Buena Vista 11
Name Buena Vista 11
Site Carlsbad, CA
Revision 1 Created 8/19/2014
Standard National Concrete Masonry Association 3rd Edition
Number
Designer
IVlodified
14220
JCW
8/19/2014
Selected Wall Unit
Vertica® 4 Degree
Selected Reinforcement Types
3XT - Mirafi Miragrid 3XT
5XT - Mirafi Miragrid 5XT
Licensor: Anchor Wall Systems, Inc.
Supplier: TenCate Geosynthetics - Mirafi
Supplier: TenCate Geosynthetics - Mirafi
AnchorWall® Software Version 6.0 Page 1 Printed 8/19/2014
project: 14220 - Buena Vista 11 [Rev. 1] Wall; Wall A
Panel
Report Date
Design Standard
Design
Unit of Measure
Selected Wall Unit
Seismic PGA
Soil Parameters
Soil
#1 at Station 0.00
August 19, 2014
National Concrete Masonry Association 3rd Edition
Static and Seismic
Imperial
Vertica® 4 Degree
0.27
Angle Cohesion
Reinforced Fill
Retained Soil
Foundation Soil
Minimum Factors of Safety
External
34.00
30.00
30.00
n/a
n/a
0.00
Internal
Base Sliding 1.50/1.10
Overturning 2.00/1.10
Bearing Capacity 2,00/1.10
Reinforcement Parameters
Name Tult
Tensile Overstress
Pullout
Internal Sliding
RFcr RFd
Mirafi Miragrid 3XT 3501.11 1.58 1.10
Weight
125,00
125.00
125.00
1.50/1.10
1.50/1.10
1,50/1.10
RFid
2.0
-flvlirafi Miragric
Facing
Connection Strength 1.50/1.10
Min. Anchorage Length 0.9999
LTDS Ci Cds
1,05 1918.52 0.70 0.70
Panel Details
Panel Height
Setback Angle
Embedded Depth
Analysis Results
External
4,33
4.00
0,66
Back Slope
Toe Slope
26,57
0,00
Base Sliding
Applied bearing pressure
Internal
Layer Elevation
1.72/1.22
703.51/889,94
Overturning
LL Surcharge
DL Surcharge
0.00
0,00
Rein. Type Length
2.00
0,67
Facing
Layer Elevation
Mirafi Miragrid 3XT
Mirafi Miragrid 3XT
Rein. Type
5,00
5,00
Length
2,00
0.67
Mirafi Miragrid 3XT
Mirafi Miragrid 3XT
5.00
5.00
Anchor
Length
1.91
3.00
Anchor
Length
1.91
3.00
4.15/2.50 Bearing Capacity
Tensile
Overstress Pullout
10.80/8.54
Internal
Sliding
22.88/6.62
7.63/3.51
Connection
Strength
7.68/1.57
5.44/1.91
5.92/4.37
3,94/2.97
12.72/2.61
4,62/1,62
Internal Compound Stability
10 Lowest Static
Radius Point Entry Point
1 10
2 10
1 10
1 10
1 10
1 10
10 Lowest Seismic
1 10
2 10
1 10
1 10
1 10
1 10
Exit Point Result
1.44
2.50
2.68
3.12
3.19
3.71
1.35
2.24
2.43
2.70
2.81
3.15
Status
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
AnchorWall® Software Version 6.0 Page 2 Printed 8/19/2014
project: 14220 - Buena Vista 11 [Rev, 1] Wall: Wall A
Panel
Report Date
Design Standard
Design
Unit of Measure
Selected Wall Unit
Seismic PGA
Soil Parameters
Soil
#2 at Station 6.00
August 19, 2014
National Concrete Masonry Association 3rd Edition
Static and Seismic
Imperial
Vertica® 4 Degree
0.27
Angle Cohesion Weight
Reinforced Fill
Retained Soil
Foundation Soil
Minimum Factors of Safety
External
34.00
30.00
30,00
n/a
n/a
0.00
125.00
125.00
125.00
Internal
2,0
irafi Miragrid
'Vlirafi Miragrid :
Miragrid i
Facing
Base Sliding
Overturning
Bearing Capacity
1,50/1,10
2.00/1.10
2.00/1.10
Tensile Overstress
Pullout
Internal Sliding
Reinforcement Parameters
Name Tult RFcr RFd
1.50/1.10
1.50/1.10
1.50/1,10
RFid
Connection Strength 1.50/1.10
Min. Anchorage Length 0 9999
LTDS Ci Cds
Mirafi Miragrid 3XT 3501.11 1.58 1.10 1,05 1918.52 0.70 0.70
Mirafi Miragrid 5XT 4701.49 1.58 1.10 1,05 2576.30 0.70 0.70
Panel Details
Panel Height
Setback Angle
Embedded Depth
Analysis Results
External
7.00
4.00
0.66
Back Slope
Toe Slope
26.57
0.00
LL Surcharge
DL Surcharge
0.00
0,00
Base Sliding 1.58/1,22 Overturning 3.35/2,35 Bearing Capacity 7.52/6
Applied bearing pressure 1.251.74/1,529,68
Internal Anchor Tensile Internal
Layer Elevation Rein. Type Length Length Overstress Pullout Sliding
3 4.67 Mirafi Miragrid 3XT 7.00 1.74 16,81/5.55 7,02/1.67 4,47/3.49
2 2.67 Mirafi Miragrid 3XT 7.00 3.37 6.86/2.88 7.71/2.42 3.07/2.46
1 0.67 Mirafi Miragrid 5XT 7.00 5.00 4.79/2.35 7.61/2.88 2.34/1.90
Facing Anchor Connection
Layer Elevation Rein. Type Length Length Strength
3 4.67 Mirafi Miragrid 3XT 7.00 1.74 9.35/2.22
2 2.67 Mirafi Miragrid 3XT 7.00 3.37 4.33/1.36
1 0.67 Mirafi Miragrid 5XT 7.00 5.00 3.07/1.16
Internal Compound Stability
10 Lowest Static
Radius Point Entry Point Exit Point Result Status
1 10 1 1,41 Pass
2 10 3 1.68 Pass
1 10 4 1.86 Pass
2 10 6 1.87 Pass
1 10 7 2.03 Pass
4 10 2 2.07 Pass
1 10 9 2.21 Pass
5 10 5 2.31 Pass
1 10 10 2.38 Pass
1 10 8 2.85 Pass
10 Lowest Seismic
1 10 1 1.34 Pass
2 10 3 1.55 Pass
2 10 6 1.67 Pass
AnchorWall® Software Version 6.0 Page 3 Printed 8/19/2014
PVoject: 14220 - Buena Vista 11 [Rev. 1] Wall: Wall A
1 10 4 1.70 Pass
1 10 7 1,80 Pass
1 10 9 1,92 Pass
1 10 2 1.95 Pass
1 10 10 2.04 Pass
1 10 5 2.13 Pass
1 10 8 2.47 Pass
AnchorWall® Software Version 6.0 Page 4 Printed 8/19/2014
Project: 14220 - Buena Vista 11 [Rev. 1] Wall: Wall A
Panel
Report Date
Design Standard
Design
Unit of Measure
Selected Wall Unit
Seismic PGA
Soil Parameters
Soil
#3 at Station 12.00
August 19, 2014
National Concrete Masonry Association 3rd Edition
Static and Seismic
Imperial
Vertica® 4 Degree
0.27
Angle Cohesion Weight
Reinforced Fill
Retained Soil
Foundation Soil
Minimum Factors of Safety
External
34.00
30.00
30.00
n/a
n/a
0.00
125,00
125.00
125.00
Internal
2.0
Facing
Base Sliding
Overturning
Bearing Capacity
1.50/1.10
2.00/1.10
2.00/1,10
Tensile Overstress
Pullout
Internal Sliding
Reinforcement Parameters
Name Tult RFcr RFd
1.50/1,10
1.50/1.10
1.50/1.10
RFid
Connection Strength 1.50/1.10
Min. Anchorage Length 0.9999
LTDS Ci Cds
Mirafi Miragrid 3XT
Mirafi Miragrid 5XT
3501,11
4701.49
1.58
1.58
1.10
1.10
1,05
1.05
1918,52
2576.30
0.70
0.70
0,70
0.70
Panel Details
Panel Height
Setback Angle
Embedded Depth
Analysis Results
External
7.67
4.00
0.66
Back Slope
Toe Slope
26.57
0.00
LL Surcharge
DL Surcharge
0,00
0.00
Base Sliding 1.61/1.20
Applied bearing pressure 1,382,27/1,781.95
Overturning 3.20/2.14 Bearing Capacity 6.70/5.20
Internal Anchor Tensile Internal
Layer Elevation Rein. Type Length Length Overstress Pullout Sliding
4 5.34 Mirafi Miragrid 3XT 7.00 1.20 22,88/7,69 6.82/1,65 4.79/3.50
3 4.00 Mirafi Miragrid 3XT 7.00 2.29 9.69/4.16 6.88/2.22 3.68/2.76
2 2.00 Mirafi Miragrid 3XT 7.00 3.91 6,10/2.60 9.65/3.09 2,72/2,09
1 0.67 Mirafi Miragrid 5XT 7.00 5.00 4.85/2.41 8.43/3,25 2.32/1.80
Facing Anchor Connection
Layer Elevation Rein. Type Length Length Strength
4 5.34 Mirafi Miragrid 3XT 7,00 1,20 12.72/3.08
3 4.00 Mirafi Miragrid 3XT 7.00 2.29 5.87/1,89
2 2.00 Mirafi Miragrid 3XT 7.00 3.91 4.16/1.33
1 0.67 Mirafi Miragrid 5XT 7.00 5.00 3.21/1.24
Internal Compound Stability
10 Lowest Static
Radius Point Entry Point Exit Point Result Status
1 10 1 1.33 Pass
10 5 1.65 Pass
1 10 3 1.66 Pass
1 10 6 1.77 Pass
1 10 8 1.89 Pass
10 4 1,94 Pass
1 10 2 1,94 Pass
1 10 10 2.08 Pass
1 10 11 2.21 Pass
1 10 7 2.30 Pass
10 Lowest Seismic
1 10 1 1.28 Pass
AnchorWall® Software Version 6.0 Page 5 Printed 8/19/2014
F*roject: 14220 - Buena Vista 11 [Rev. 1] Wall: Wall A
10 5 1.51 Pass
10 3 1.55 Pass
10 6 1.61 Pass
10 8 1.68 Pass
10 10 1.80 Pass
10 2 1.81 Pass
10 4 1.88 Pass
10 11 1.90 Pass
10 7 2,05 Pass
AnchorWall® Software Version 6.0 Page 6 Printed 8/19/2014
Project: 14220 - Buena Vista 11 [Rev. 1] Wall: Wall B
Ml ANCHOR'
JD^m BUILD SOMETHING BEAUTIFUL
Project information
Client
Name
Site
Revision
Buena Vista 11
Buena Vista 11
Carlsbad, CA
1 Created 8/19/2014
Number
Designer
Modified
14220
JCW
9/24/2014
standard National Concrete Masonry Association 3rd Edition
Selected Wall Unit
Vertica® 4 Degree
Selected Reinforcement Types
5XT - Mirafi Miragrid 5XT
3XT - Mirafi Miragrid 3XT
Licensor: Anchor Wall Systems, Inc,
Supplier: TenCate Geosynthetics - Mirafi
Supplier: TenCate Geosynthetics - Mirafi
AnchorWall® Software Version 6.0 Page 1 Printed 9/24/2014
Project: 14220 - Buena Vista 11 [Rev. 1] Wall: Wall B
Panel
Report Date
Design Standard
Design
Unit of Measure
Selected Wall Unit
Seismic PGA
Soil Parameters
Soil
#1 at Station 0.00
September 24, 2014
National Concrete Masonry Association 3rd Edition
Static and Seismic
Imperial
Vertica® 4 Degree
0.27
Angle Cohesion
Reinforced Fill
Retained Soil
Foundation Soil
Minimum Factors of Safety
External
34.00
30.00
30.00
n/a
n/a
0.00
Internal
Base Sliding 1.50/1,10
Overturning 2.00/1.10
Bearing Capacity 2.00/1.10
Reinforcement Parameters
Name Tult
Tensile Overstress
Pullout
Internal Sliding
RFcr RFd
Weight
125,00
125.00
125.00
rrrr — —- 2H
{Mjfafi Miragrid 3XT}8.00
{rjfrafi Miragrid 3Xr;8.00
{jjiirafi Miragrid 3XT} 5.00
'.lirafi Miragrid 3XT} 8,0C
Facing
1.50/1.10
1.50/1.10
1.50/1,10
RFid
Connection Strength 1.50/1.10
Min. Anchorage Length 1.0000
LTDS Ci
Mirafi Miragrid 3XT 3501.11 1.58 1.10 1.05 1918.52 0.70
Cds
0.70
Panel Details
Panel Height
Setback Angle
Embedded Depth
Analysis Results
External
8,33
4.00
2.50
Back Slope
Toe Slope
26.60
0,00
LL Surcharge
DL Surcharge
0.00
500.00
Base Sliding 1.94/2.30
Applied bearing pressure 1,721.52/1,172.38
Overturning 5.25/6,56 Bearing Capacity 9.49/13.94
Internal Anchor Tensile Internal
Layer Elevation Rein. Type Length Length Overstress Pullout Sliding
4 6.67 Mirafi Miragrid 3XT 8.00 2.94 6.54/6.13 4.19/2.67 4.19/5.96
3 5,33 Mirafi Miragrid 3XT 8.00 3.77 5,74/5,47 6.49/4.58 3.55/4.82
2 3.33 Mirafi Miragrid 3XT 8.00 5.01 3.77/3,63 7.91/5.95 2.93/3.73
1 1.33 Mirafi Miragrid 3XT 8.00 6.26 2.59/2.51 8.37/6.63 2.52/3.03
Facing Anchor Connection
Layer Elevation Rein. Type Length Length Strength
4 6.67 Mirafi Miragrid 3XT 8.00 2.94 18,17/2.32
3 5.33 Mirafi Miragrid 3XT 8.00 3,77 8.39/2.46
2 3.33 Mirafi Miragrid 3XT 8.00 5.01 4.77/1.93
1 1.33 Mirafi Miragrid 3XT 8.00 6.26 3.10/1.55
Internal Compound Stability
10 Lowest Static
Radius Point Entry Point Exit Point Result Status
1 10 1 1.47 Pass
3 9 3 1.67 Pass
6 9 2 1.83 Pass
1 10 4 1.83 Pass
5 8 6 1.88 Pass
1 8 7 2.04 Pass
10 9 5 2.16 Pass
1 7 9 2.33 Pass
1 10 8 2.65 Pass
1 7 11 2.87 Pass
10 Lowest Seismic
1 10 1 1.38 Pass
3 9 3 1.55 Pass
AnchorWall® Software Version 6.0 Page 2 Printed 9/24/2014
I^roject: 14220 - Buena Vista 11 [Rev. 1] Wall: Wall B
1 10 4 1,68 Pass
3 7 6 1.71 Pass
6 9 2 1.83 Pass
1 8 7 1,83 Pass
1 7 9 2.05 Pass
1 10 5 2.10 Pass
1 10 8 2.36 Pass
1 6 11 2.47 Pass
AnchorWall® Software Version 6.0 Page 3 Printed 9/24/2014