HomeMy WebLinkAbout1109 OAK AVE; ; CB150485; Permit< I
City of Carlsbad
1635 Faraday Av Carlsbad, CA 92008
04-10-2015 Cogeneration Permit Permit No:CB150485
Building Inspection Request Line (760) 602-2725
Job Address:
Permit Type:
Parcel No:
Valuation:
Occupancy Group:
1109 OAK AV CBAD
COGEN
2050205400
$5,600.00
Sub Type: PHOTO
Lot#: 0
Constuction Type: NEW
Reference #:
Status: ISSUED
Applied: 02/13/2015
Entered By: LSM
Plan Approved: 04/10/2015
Issued: 04/10/2015
Inspect Area:
Plan Check #:
Project Title: DELUDE RES -INSTALL ROOF MNT
PV SYSTEM 14 MODULES/ NO PANEL UPGRADE/4.2 KW/ FLUSH MNT
Applicant:
DELUDE CHAD
P O BOX 235344
ENCINITAS CA 92023
760-216-0988
Building Permit
Add'I Building Permit Fee
Plan Check
Add'I Plan Check Fee
Plan Check Discount
Strong Motion Fee
Green Bldg Stands (SB1473) Fee
$78.91
$0.00
$55.24
$132.26
$0.00
$1.00
$1.00
Owner:
DELUDE CHAD
P O BOX 235344
ENCINITAS CA 92023
PLUMBING TOTAL
ELECTRICAL TOTAL
MECHANICAL TOTAL
Additional Fees
TOTAL PERMIT FEES
Total Fees: $268.41 Total Payments To Date: $268.41 Balance Due:
Inspector: Aa-:-Clearance:
$0.00
$0.00
$0.00
$0.00
$268.41
$0.00
NOTICE: Please take NOTICE that approval of your project includes the "Imposition" of fees, dedications, reservations, or other exactions hereafter collectively
referred to as "fees/exactions." You have 90 days from the date this permit was issued to protest imposition of these fees/exactions. If you protest them, you must
follow the protest procedures set forth in Government Code Section 66020(a), and file the protest and any other required information with the City Manager for
processing in accordance with Carlsbad Municipal Code Section 3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attack,
review, set aside, void, or annul their imposition.
You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection fees and capacity
changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this project. NOR DOES IT APPLY to any
fees/exactions of which ou have reviousl been iven a NOTICE similar to this or as to which the statute of limitations has revious otherwise e ired.
THE FOLLOWING APPROVALS REQUIRED PRIOR TO PERMIT ISSUANCE: 0PLANNING D ENGINEERING Q BUILDING OFIRE 0HEALTH D HAZMATIAPCD .
C cityof Building Permit Application Plan Check No. C,8 \5'0\.f!b
1635 Faraday Ave., Carlsbad, CA 92008 Est. Value
Carlsbad Ph: 760-602-271 9 Fax: 760-602-8558 Plan Ck. Deposit email: building@ carlsbadca.gov
www.carlsbadca.gov Date .;>.A 1~ I 1~ ISWPPP
JOB ADDRESS SUITEt/SPACEt/UNITI r PN //09 OAK" At/c C/J~tSEAO 20.S -020 -5¥ -00
CT/PROJECT# 'LOT# I PHASE# I # uF UNI 1:; I# BEDnvvMS # BATHROOMS I TENANT BUSINESS NAME I CONSTR. TYPE I occ. GROUP
DESCRIPTION OF WORK: Include Square Feet of Affected Area(s)
//1/ .srAu 19 rlt:>N OF "/ZOO lrvv fol A/{. r~s-77:?M / ~,:;o F
fl?Ct/lVTeb .
14 tneduA ~.s }JO f,'+1.J ~ U /> 3ro.d.e.
EXISTING USE FIREPLACE I PROPOSED USE I GARAGE (SF) PATIOS (SF) I DECKS (SF)
YES O
I AIR CONDITIONING I FIRE SPRINKLERS
No[] vEs O NoD vEsO NoD
APPLICANT NAME [HAO .rJ£t1,,0E PROPERTY OWNER NAME 5'/l/l4£ PrlllarvCon••,..
ADDRESS 11a, o/Jk A~E ADDRESS
CITY C ARt.f/3,AO STATE C/J ZIP 9ze;of-CITY STATE ZIP
PHONE I FAX PHONE IFAX , 6C ::Jl6 o't Fr
EMAIL EMAIL C /3'/.)et. vOE C9 G' /n/JI L. 1:0 /YJ
DESIGN PROFESSIONAL CONTRACTOR BUS. NAME
ADDRESS / ADDRESS /
CITY STAT/ ZIP CITY STA/ ZIP
PHONE ~ PHONE AAX
EMAIL / EMAIL /
I STATE UC.# STATE UC.# I CLASS I CITY BUS. UC.#
(Sec. 7031.5 Business and Professions Code: Any City or County which requires a permit to construct, alter, improve, demolish or repair any structure, prior to its issuance, also requires the applicant for such permit to file a signed statement that he is licensed pursuant to the provisions of the Contractor's License Law [Chapter 9, commending with Section 7000 of Division 3 of the Business and Professions Code) or that he is exempt therefrom, and the basis for the alleged exemption. Any violation of Section 7031.5 by any applicant for a permit subjects the applicant to a civil penalty of not more than five hundred dollars ($500)).
Wor11en' Compenntlon Declaration: I hereby aff,rm under penafty of perjury one of the following declarations:
D I have and will maintain a certificate of consent to self-Insure for workers' compensation as provided by Section 3700 of the Labor Code. for the performance of the wor11 for which this permit is issued. D I have and wlll maintain wor11ers' compensation, as required by Section 3700 of the labor Code, for the performance of the wor11 for which this permit is issued. My wor11ers' compensation insurance carrier and policy
number are: Insurance Co. Policy No. Expiration Date---------
~ section need not be completed ~ the permit is for one hundred dollars ($100) or less. LJ Certificate of Exemption: I certify that in the performance of the wor11 for which this permit is issued, I shall not employ any person in any manner so as to become subject to the Workers' Compensation Laws of
California. WARNING: Failure to secure wor11ers' compensation coverage Is unlawful, and shall subject an employer to criminal penalties and civil fines up to one hundred thousand dollars (&100,000), In
addition to the cost of compensation, damages as provided for In Section 3706 of the Labor code, lnlerest and attorney's fees.
~ CONTRACTOR SIGNATIJRE O AGENT DATE
D
D
, as owner of the property or my employees with wages as their sole compensation, will do the wor11 and the structure is not intended or offered for sale (Sec. 7044, Business and Professions Code: The Contractor's
License Law does not apply to an owner of property who builds or improves thereon, and who does such work himseff or through his own employees, provided that such improvements are not intended or offered for
sale. If, however, the building or improvement is sold within one year of completion, the owner-builder will have the burden of proving that he did not build or Improve for the purpose of sale).
I, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec. 7044, Business and Professions Code: The Contracto(s License Law does not apply to an owner of
property who builds or improves thereon, and contracts for such projects with contractor(s) licensed pursuant to the Contracto(s License Law).
I am exempt under Section Business and Professions Code for this reason:
1. I personally plan to provide the major labor and materials for construction of the proposed property Improvement. D Y es D o
2. I (have I have not) signed m application for a building permit for the proposed work.
3. I have contracted with the following person (firm) to provide the proposed construction (include name address I phone I contractors' license number):
4. I plan to provide portions of the work, but I have hired the following person to coordinate, supervise and provide the major work (include name I address I phone I contractors' license number):
5. I wiU provide some of the wor11, but I have contracted · J the following persons to provide the work indicated (include name I address I phone I type of work):
R$ PROPERTY OWNER SIGNATIJRE 0AGENT
,,.. ·-
I COMPLETE THIS SECTION FOR NON-RESIDENTIAL BUILDING PERMITS ONLY
Is the applicant or future building occupant required kl submit a business plan, acutely hazardous materials registration form or risk management and prevention program under Sections 25505, 25533 or 25534 of the
Presley-Tanner Hazardous Substance Account Act? CJ Yes CJ No
Is the applicant or future building occupant required to obtain a permit from the air pollution control district or air quality management district? CJ Yes CJ No
Is the facility to be constructed within 1,000 feet of the outer boundary of a school site? CJ Yes CJ No
IF ANY OF THE ANSWERS ARE YES, A FINAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUED UNLESS THE APPLICANT HAS MET OR IS MEETING THE REQUIREMENTS OF THE OFFICE OF
EMERGENCY SERVICES AND THE AIR POLLUTION CONTROL DISTRICT.
I certify that I haYe read the appllcatlon and state that the abolle lnfonnation ls correct and that the infonnation on the plans Is accurate. I agree to comply with all Cilyordlnanoesand State laws relating to bulldlngconstruction.
I hereby aulhorize represenlative of Ille City of Ca1sbad to enler upon the above mentioned property for inspection purposes. I ALSO AGREE TO SAVE, INDEM'llFY AND KEEP HARt.USS THE CrTY OF CARLSBAD
AGAINST All LIABILITIES, JUDGt.ENTS, COSTS AND EXPENSES WHICH MAY IN ANY WAY ACCRUE AGAINST SAID CrTY IN CONSEQUENCE OF THE GRANTING OF THIS PERMIT.
OSHA: An OSHA pennl is requied b' excavations over 5'0' deep and demJlition or conslruction of sb'UcWres over 3 slories 11 height
EXPIRATION: Every pemit issued by Ille Building Official under the pl'O'lisions of this Code shal eicpre by linitation and become nul and void l the building or wol1I aulhorized by such pemit is not corrrnenced \\ithn
180 days fi"om the date of such pemitorif the buiding or · by such perm~ is suspended or abandoned ata:,y tine after the wol1I is corrrneoced for a peood of 180 days (Section 106.4.4 Uniform Building Code).
A$ APPLICANT'S SIGNATURE DATE
Inspection ist
Permit#: CB150485 Type: COGEN PHOTO DELUDE RES -INSTALL ROOF MNT
PV SYSTEM 14 MODULES/ NO PANEL UP
Date ~lr:i_~ection Item Inspector Act Comments
04/20/2016 35 Photo Voltaic (PV) AEK AP
04/20/2016 39 Final Electrical AEK Fl
04/18/2016 35 Photo Voltaic (PV) PD NS
04/12/2016 35 Photo Voltaic (PV) PD co
Thursday, May 05, 2016 Page 1 of 1
Carlsbad 15-0485
04/6/2015
EsGil Corporation
In <Partnersfiip witfi (}overnment for (J3ui{aing Safety
DATE: 04/6/2015
JURISDICTION: Carlsbad
PLAN CHECK NO.: 15-0485
PROJECT ADDRESS: 1109 Oak Ave
SET: II
PROJECT NAME: Delude 3.8KW rooftop PV system
D APPLICANT
D JURIS.
D PLAN REVIEWER
D FILE
~ The plans transmitted herewith have been corrected where necessary and substantially
comply with the jurisdiction's building codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's building
codes when minor deficiencies identified below are resolved and checked by building
department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed
check list and should be corrected and resubmitted for a complete recheck.
D The check list transmitted herewith is for your information. The plans are being held at
Esgil Corporation until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the
applicant contact person.
D The applicant's copy of the check list has been sent to:
~ EsGil Corporation staff did not advise the applicant that the plan check has been
completed.
D EsGil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted:
Date contacted: (by:
Telephone #:
) Email:
Mail Telephone Fax In Person
D REMARKS:
By: Morteza Beheshti
EsGil Corporation
D GA D EJ D MB D PC 3/31
Fax#:
Enclosures:
EsGil Corporation
In (J!artnersliip witli <]overnment for (}Jui{aing Safety
DATE: 02/25/2015
JURISDICTION: Carlsbad
PLAN CHECK NO.: 15-0485
PROJECT ADDRESS: 1109 Oak Ave
SET: I
PROJECT NAME: Delude 3.SKW rooftop PV system
D APPLICANT
/JURIS.
D PLAN REVIEWER
D FILE
D The plans transmitted herewith have been corrected where necessary and substantially
comply with the jurisdiction's building codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's building
codes when minor deficiencies identified below are resolved and checked by building
department staff.
~ The plans transmitted herewith have significant deficiencies identified on the enclosed
check list and should be corrected and resubmitted for a complete recheck.
D The check list transmitted herewith is for your information. The plans are being held at
Esgil Corporation until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the
applicant contact person.
D The applicant's copy of the check list has been sent to:
D EsGil Corporation staff did not advise the applicant that the plan check has been
completed.
~ EsGil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Chad Delude Telephone#: 760.216.0988
J?_ate contacted: vns (by~ Email: cbdelude@gmail.com Fax #:
"17~ail Te"hone ·--,tax In Person
C8J REMARKS: • ~ ·/
By: Morteza Beheshti
EsGil Corporation
D GA D EJ D MB D PC
Enclosures:
2/18
GENERAL PLAN CORRECTION LIST
JURISDICTION: Carlsbad
PROJECT ADDRESS: 1109 Oak Ave
DATE PLAN RECEIVED BY
ESGIL CORPORATION: 2/18
REVIEWED BY: Morteza Beheshti
FOREWORD (PLEASE READ):
PLAN CHECK NO.: 15-0485
DATE REVIEW COMPLETED:
02/25/2015
This plan review is limited to the technical requirements contained in the International Building
Code, Uniform Plumbing Code, Uniform Mechanical Code, National Electrical Code and state
laws regulating energy conservation, noise attenuation and disabled access. This plan review
is based on regulations enforced by the Building Department. You may have other corrections
based on laws and ordinances enforced by the Planning Department, Engineering Department
or other departments.
The following items listed need clarification, modification or change. All items must be satisfied
before the plans will be in conformance with the cited codes and regulations. The approval of
the plans does not permit the violation of any state, county or city law.
• Please make all corrections and submit two new complete sets of prints to:
ESGIL CORPORATION.
• To facilitate rechecking, please identify, next to each item, the sheet of the plans upon
which each correction on this sheet has been made and return this sheet with the
revised plans.
• Please indicate here if any changes have been made to the plans that are not a result of
corrections from this list. If there are other changes, please briefly describe them and where
they are located on the plans. Have changes been made not resulting from this list?
D Yes D No
Carlsbad 15-0485
02/25/2015
ELECTRICAL and ENERGY COMMENTS
PLAN REVIEWER: Morteza Beheshti
ELECTRICAL (2013 CALIFORNIA ELECTRICAL CODE)
1. Provide a Title sheet and provide typical and general information including site plan of
the project.
2. Please provide a statement on the Title Sheet of the plans to show compliance with the
current Codes. The following are the correct current Codes:
a. The 2013 edition of the California Building Code (CBC) adopts the 2012
International Building Code (IBC) and the 2012 International Residential Code
(IRC).
b. The 2013 edition of the California Electrical Code (CEC) adopts the 2011 National
Electrical Code (NEC) and the 2012 California Amendments.
c. The 2013 edition of the California Mechanical Code (CMG) adopts the 2012
Uniform Mechanical Code (UMC) and the 2012 California Amendments.
d. The 2013 edition of the California Plumbing Code (CPC) adopts the 2012 Uniform
Plumbing Code (UPC) and the 2012 California Amendments.
e. The 2010 edition of the California Energy Efficiency Standards
3. Please structural calculations for the module addition on the existing roof.
4. Please provide a module roof layout plan. Section plan for railing and module
installation. Indicate a minimum of 5" from roof surface to under the module to comply
with UL 1703 Fire testing.
5. Clearly dimension the maximum height of the array at the highest point above the
surface of the roof. Where any part of the array exceeds 24 inches above the roof
surface, provide calculations from a CA State Licensed PE for uplift forces on the PV
system, showing that all PV rack components and the roof structure and connections are
adequately designed. Provide plans, details, and sections necessary to show all
structural components and connections. The structural calculations, plans and details
shall be sealed and signed by the P.E.
6. The following design loads shall be clearly indicated on the construction documents.
Wind load. The following information should be provided:
*Basic Wind speed (3-second gust), 110 mph (123 in Palm Springs)
*Wind exposure shall be determined by the engineer.
7. Please demonstrate compliance with the fire access and pathways setback requirements
under section 3111.4 of the 2013 residential CBC. Show setback dimensions on plans.
There should be a minimum of 36" clear from the roof ridge. A, minimum of 36" clear
from two, 36" pathways from the eave to the ridge. Also, there should be at least 18"
. . '
Carlsbad 15-0485
02/25/2015
from edge of the modules to any roof edge/ valley or hip. When there is modules on
both sides of the valley then 18" clear should be provided on both sides of the valley to
the edge of the nearest module. Do not install junction boxes or any obstacles in the
above clear fire department passageways.
8. Provide the required separate ground electrode for the "photovoltaic rack assembly" per
690.47 (D) or connect to the building electrode system. If the electrode conductor is
routed through electrical equipment (disconnects, panels, meter enclosures, etc) then
provide a detail on the plans describing compliance with CEC 250.64(C). (Conductor
splices only allowed with compression connectors or exothermic welding.) Size the
ground electrode conductor per 250.166, not smaller than #8.
*Note: The rack electrode system is described in the 201 O CEC 690.47(0) and the
upcoming 2016 CEC 690.47(0). It was mistakenly deleted from the 2013 CEC.
9. Please show exact location of the items shown on single line in lieu of general circled
area. Provide an AC disconnect within sight of the inverter. CEC 690.14(0)(2)
1 O. Include typical labeling details for the solar PV addition throughout the system.
Note: If you have any questions regarding this Electrical and Energy plan review list please
contact Morteza Beheshti at (858) 560-1468. To speed the review process, note on this
list (or a copy) where the corrected items have been addressed on the plans.
Carlsbad 15-0485
02/25/2015
[DO NOT PAY -THIS IS NOT AN INVOICE]
VALUATION AND PLAN CHECK FEE
JURISDICTION: Carlsbad PLAN CHECK NO.: 15-0485
PREPARED BY: Morteza Beheshti
BUILDING ADDRESS: 1109 Oak Ave
BUILDING OCCUPANCY:
BUILDING AREA
PORTION ( Sq. Ft.)
Air Conditioning
Fire Sprinklers
TOTAL VALUE
Jurisdiction Code cb
~-~·-~-~-----=-i
~dg. Permit Fee by Ordinanc_<:_~
Plan Check Fee by Ordinance
Valuation
Multiplier
By Ordinance
Type of Review: D Complete Review
D Repetitive Fee --_ "".'J Repeats
* Based on hourly rate
Comments: 1.5 hour plan review.
D Other
0 Hourly
EsGil Fee
DATE: 02/25/2015
TYPE OF CONSTRUCTION:
Reg. VALUE
Mod.
D Structural Only
____ 1_.s--11 Hrs.@•
$100.00_
($)
$187.501
$1so.001
Sheet 1 of 1
macvalue.doc +