HomeMy WebLinkAbout1165 MAGNOLIA AVE; ; CB910804; PermitBUILDING. P'ERMIT
06/28/91 14:51
Page lof I
'Job Address: 1165 MAGNOLIA AV Str:
Permit Type: RESIDENTAL ADD/ALT (OVER S10K)
Parcel No: 205-280-34-00
Valuation: 60,897
Construction Type: VN
Occupancy Group: R3 Class Code:
Description: 410 SF DECK + 786 SF LIVING
Appl/Ownr : FRIETZE, ROBERT
1165 MAGNOLIA AVENUE
rirr r nr
Permit No: CB910804
Project No: A9100976
Development No
Fl: Ste:
3233 06/28/91 0001 01 02
C-F'RMT 575-00
Status: ISSUED
Applied: 05/22/91
Apr/Issue: 06/28/91
Validated By; DC
619 729-5674
Fees Required Fees ollected & Credits'
Fees: 84.00-( \r /2 . Adjustments: / .oh) .00
Total Fees: /840.00 Toted Paynlents:\ 265.00
Baan- be:\ 575.00
\•' , Fee description / i / %VVIAlUn 1ts
Stron
\ 'Eec/Unit Ext fee Data
Building Permit '164.00
Plan Check n 302..00
-------- ---- ---------
- * BUILDING TOTAL L _ /I )f".f\S..1 772.00
' I If• 't: "A I. I. I Enter I for Plumbing Issue Iee' > illll LL_';II 7.50 1
Each Plumbing Fixture or Tr.p /J gyJ Uç4)// 2.50! 10.00
Each Building Sewe\ \ /I / 6.50 6.50
* PLUMBING TOTAL \ II ti\
/ 24.00 ." - I(OOOO6'IO _ Enter IU for Electric Isse Fee ) os / . 5.00 1
Enter 1' for Temporary SerceXJ? / 10.00 1
* ELECTRICAL TOTAL ($1U\Minii11uIi)i),.. F. 15.00
Enter 'I' forMechanicaNIsz UtFee .0
' •/' 15.00 1
Install Furn/Ducts "• 9.00 - 9.00
V Each, Ins tall/Reloc Appl i ance ent>
--
-L 4.50 4.50
* MECHANICAL TOTAL
.. .
29.00
I FINAL APPROVAL -
INSP. 1EL DATE'4
ELEARANE
CflY OF CARLSBAD
2075 Las Palmas Dr., Carlsbad CA 92009 (619) 438-1161
Of:- t193
PERMIT APPLICATION
City of Carlsbad Building Department
2075 Las Palmas Dr., Carlsbad, CA 92009 (619) 438-1161
1. PERMIT TYPE I
A - U COMMERCIAL UNEW OTENANT IMPROVEMENT
B - 0 INDUSTRIAL [-]NEW UTENANT IMPROVEMENT
C CfeOESIDENTIAL DAPARTMENT DCONDO DSINGLE FAMILY DWELLING ,-DITION/ALTERATION
DOUPLEX DOEMOLITION DRELOCATION DMOBIIE HOME DELECTRICAL DPLUMBING
DMECHANICAL DPOOL DSPA
-
D RETAINING WALL DSOLAR DOR,.
EST. VAL
PLAN CE DEPOSIT
VALID. BY
DATE
JDi ..;Lf,.1 f
CZ .---1 d
PROJECT INFO TION PLAN
Address /UMl or
Nearest Cross Streets
GAL DESCRIPTION No. Suivi5
i.iitlj. btLt Sr 300II
02 Energy Catcs ''2 Structural Calcs 02 Soils Report Di Addressed Envelope
ASSESSORS PARCEL .._/,icf_ EXISTING USE 5//vLE P.4ttL.f PROPOSED USE /AJ('/. EA
DESCRIPTION OF WORK,
dlit
,,
BLDG. SQ. FIG. 7SZ # OF STORIES
'3.. CONTACT PER,ON
NAME 4Z-i- ADDRESS '70/ k 7L S.
CITY 5._€)it2L. STATE l4. ZIP CODE ?ZJ$'.z- DAY TELEPHONE
SIGNATURE
APPLICANT DCONTRACTOR 0 AGENT FOR CONTRACTOR 1,tTWER DAGENT FOR OWNER
NAME ADDRESS
CITY STATE ZIP CODE -72 DAY TELEPHONE _Si--5-70 7
PROPERTY OWNER OWNER DLESSEE OTENANT
NAME .:3/1/Ae '4tPivvit ADDRESS
CITY STATE ZIP CODE DAYTELEPHONE
CONTRACTOR
NAME ADDRESS
CITY STATE ZIP CODE DAY TELEPHONE
STATE LIC. N LICENSE CLASS CITY BUSINESS LIC. N
SIGNATURE TITLE DATE
DESIGNER NAME ADDRESS
CITY STATE ZIP CODE DAY TELEPHONE STATE LIC. #
WORKERS' COMPENSATION
Workers Compensation Declaration: I hereby affirm that I have a certificate of consent to self-insure issued by the Director of Industrial Relations,
or a certificate of Workers' Compensation Insurance by an admitted insurer, or an exact copy or duplicate thereof certified by the Director of the
insurer thereof filed with the Building Inspection Department (Section 3800, Lab. C).
INSURANCE COMPANY POLICY NO. EXPIRATION DATE
Certificate of Exemption: I certify that in the performance of the work for which this permit is issued, I shall not employ any person in any manner
so as to become subject to the Workers' Compensation Laws of California.
SIGNATURE DATE
OWNER-BUILDER DECLARATION
Owner-Builder Declaration: I hereby affirm that I am exempt from the Contractor's License Law for the following reason:
0 I as owner of the property or my employees with wages as their sole compensation, will do the work and the structure is not intended or offered for sale
(Sec. 7044, Business and Professions Cede: The Contractor's License Law does not apply to an owner of property who builds or improves thereon,, and who
does such work himself or through his own employees, provided that such improvements are not intended or offered for sale. If, however, the building
or improvement is sold within one year of completion, the owner-builder will have the burden of proving that he did not build or improve for the purpose
of sale.).
0 I, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec. 7044, Business and Professions Code:
The Contractor's License Law does not apply to an owner of property who builds or improves thereon, and contracts for such projects with contractor(s)
licensed pursuant to the Contractor's License Law).
0 I am exempt under Section Business and Professions Cede for this reason:
(Sec. 7031.5 Business and Professions Code: Any City or County which requires a permit to construct, alter, improve, demolish, or repair any structure,
prior to its issuance, also requires the applicant for such permit to file a signed statement that he is licensed pursuant to the provisions of the
Contractor's License Law (Chapter 9, commencing with Section 7000 of Division 3 of the Business and Professions Code) or that he is exempt therefrom,
and the basis for the alleged exemption. Any violation of Section 7031.5 by any applicant for a permit subjects the applicant to a civil penalty of not
more than five hundred dollars ($5001).
SIGNATURE DATE
COMPLETE THIS SECTION FOR NON-RESIDENTIAL BUILDING PERMITS ONLY:
Is the applicant or future building occupant required to submit a business plan, acutely hazardous materials registration form or risk management and prevention
program under Sections 25505, 25533 or 25534 of the Presley-Tanner Hazardous Substance Account Act?
DYES ONO
Is the applicant or future building occupant required to obtain a permit from the air pollution control district or air quality management district?
DYES []NO
Is the facility to be constructed within 1,000 feet of the outer boundary of a school site?
DYES E] NO
IF ANY OF THE ANSWERS ARE YES, A FINAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUED AFTER JULY 1, 1989 UNLESS THE APPLICANT HAS MET OR IS MEETING THE REQUIREMENTS
OF THE OFFICE OF EMERGENCY SERVICES AND THE AIR POLLUTION CONTROL DISTRICT.
CONSTRUCTION LENDING AGENCY
I hereby affirm that there is a construction lending agency for the performance of the work for which this permit is issued (Sec 30970) Civil Code).
LENDER'S NAME LENDER'S ADDRESS
APPLICANT'S SIGNATURE
I certify that I have read the application and state that the above information is correct. I agree to comply with all City ordinances and State laws relating
to building construction. I hereby authorize representatives of the City of Carlsbad to enter upon the above mentioned property for inspection purposes. I ALSO
AGREE TO SAVE INDEMNIFY AND KEEP HARMLESS THE CITY OF CARLSBAD AGAINST ALL LIABILITIES, JUDGMENTS, COSTS AND EXPENSES WHICH MAY IN ANY WAY ACCRUE AGAINST SAID
CITY IN CONSEQUENCE OF THE GRANTING OF THIS PERMIT.
Expiration. Every permit issued by the Building Official under the provisions of this Code shall expire by limitation and become null and void if the building
or work authorized by such permit is not commenced within 180 days from the date of such permit or if the building or work authorized by such permit is suspended
or abandoned at any time after the work is commenced for a period of 180 days (Section 303(d) Uniform Building Code).
'S SIGNJtTURE DOWNER 1CONTRACTOR DRY PHONE APPROVED BY:
J _()J/DATI.
WPtflE: FiI& YELLOW: Applicant PINK: Finance
CITY OF CARLSBAD
INSPECTION REQUEST
PERNIT# CB910804 FOR 10/11/91
DESCRIPTION: 410 SF DECK + 786 SF LIVING
TYPE: RADMAJ
JOB ADDRESS: 1165 MAGNOLIA AV
APPLICANT: FRIETZE, ROBERT
CONTRACTOR:
OWNER:
REMARKS: MH/ROBERT/729-5674
SPECIAL INSTRUCT:
PHONE:
PHONE:
INSPECTOR AREA PY
PLANCK# CB910804
0CC GRP R3
CONSTR. TYPE VN
STR: FL: STE:
619 729-5674
PHONE :
INSPECTOR
TOTAL TIME:
CD LVL DESCRIPTION ACT COMMENTS
14 ST Frame/Steel/Bolting/Welding
24 PL Rough/Topout
34 EL Rough Electric
***** INSPECTION HISTORY *****
DATE DESCRIPTION ACT INSP COMMENTS
100891 Final Structural CO PY SEE CORRECTION LIST
100891 Final Plumbing CO PY
100891 Final Electrical CO PY
090991 Interior Lath/Drywall AP PY
090591 Insulation AP PY
090391 Insulation AP PY
082991 Insulation AP PY ND GRG WALL @ LIVING ROOM
082891 Frame/Steel/Bolting/Welding AP PY ND WALL BET GRG & HSE INStJL
082891 Insulation AP PY ND WALL BET GRG & HSE INSUL
082391 Frame/Steel/Bolting/Welding CO PY SEE NOTICE 8/23/91
081691 Rough Electric AP PY
081691 Rough/Topout AP PY
081691 Roof/Reroof AP PY
081691 Shear Panels/HD's AP PY
081591 Shear Panels/HD's AP PY
081591 Roof/Reroof AP PY
071191 Ftg/Foundation/Piers AP PY FTGS FOR COLUMNS ONLY
10/23/91 INSPECTION HISTORY LISTING
FOR PERMIT# CB910804
DATE
10/11/91
10/11/91
10/11/91
io/11/91
10/08/91
10/08/91
10/08/91
10/08/91
10/08/91
10/08/91
09/09/91
09/09/91
09/05/91
09/05/91
09/03/91
08/29/91
08/29/91
08/28/91
08/28/91
08/28/91
08/23/91
08/23/91
08/16/91
08/16/91
08/16/91
08/16/91
08/16/91
08/15/91
08/15/91
08/15/91
08/15/91
07/18/91
07/11/91
07/11/91
INSPECTION TYPE
Frame/Steel/Bolting/Wel
Rough/Top out
Rough Electric
Final Combo
Final Structural
Final Structural
Final Plumbing
Final Plumbing
Final Electrical
Final Electrical
Interior Lath/Drywall
Interior Lath/Drywall
Insulation
Insulation
Insulation
Insulation
Insulation
Frame/Steel/Bolting/Wel
Frame/Steel/Bolting/Wel
Insulation
Frame/Steel/Bolting/Wel
Frame/Steel/Bolting/Wel
Shear Panels/HD's
Roof/Reroof.
Rough/Topout
Rough Electric
Rough Electric
Shear Panels/HD's
Shear Panels/HD's
Roof/Reroof
Roof/Reroof
Ftg/ Foundation/Piers
Ftg/Foundat ion/Piers
Ftg/Foundat ion/Piers
INSP ACT COMMENTS
RI RI NH/ROBERT/729-5674
RI RI MH/ROBERT/729-5674
RI RI MH/ROBERT/729-5674
PY AP
RI RI NH/ROBERT/729-5674
PY CO SEE CORRECTION LIST
RI RI MH/ROBERT/729-5674
PY CO
RI RI MH/ROBERT/729-5674
PY CO
RI RI MH/ROBERT/729-5674
PY AP
RI RI NH/ROBERT
PY AP
PY AP
RI RI MY/ROBERT/729-5674
PY AP ND GRG WALL @ LIVING ROOM
RI RI NH/FRITZ
PY AP ND WALL BET GRG & HSE INSUL
PY AP ND WALL BET GRG & HSE INSUL
RI RI MH/FRIETZE/729-5674
PY CO SEE NOTICE 8/23/91
PY AP
PY AP
PY AP
RI RI NH/WAYNE PM PLEASE
PY AP
RI RI
PY AP
RI RI NH
PY AP
PY AP
RI RI MH/ROBERT/729-5674
PY AP FTGS FOR COLUMNS ONLY
HIT <RETURN> TO CONTINUE...
ESGIL CORPORATION
9320 CHESAPEAKE DR., SUITE 208
SAN DIEGO, CA 92123
(619)560-1468
DATE: 1731 FlAPPLICaNT
URISDICT
JURISDICTION: UPLAN.C'HEe
UFILE COPY PLAN CHECK NO: SET: DUPS
DDESIGNER PROJECT 'ADDRESS:( M bt)Q.iq.T iG
PROJECT NAME: .
WJi The plans transmitted herewith have been corrected where
tZ necessary and substantially comply with the jurisdiction's
building codes.
The plans transmitted herewith will substantially comply
with the jurisdiction's building codes when minor deficien-
cies identified are resolved and
: checked by building department staff.
, , The plans transmitted herewith have significant deficiencies
identified on the enclOsed 'check list and should be corrected
and resubmitted for a complete recheck.
The check list transmitted 'herewith is for your information.
The plans are being held at Esgil Corp. until corrected
plans are submitted 'for recheck.
The applicant's copy of the check list is enclosed for the
jurisdiction to return to, the applicant-contact person.
'Theapplicant's copy of the check list ,has been sent'to:
Esgil staff did not advise the applicant contact person that
plan check has been completed.
'Esgil staff did advise applicant that the plan check has
been completed. Person contacted:
Date contacted: ' Telephone # '
REMARKS:
0 L S
By:J1 1 ' Enclosures:?LJ.s
E'SGIL CORPORATION
11 GA .E AA 0 RN 0 DM 6110
ESGIL CORPORATION
9320 CHESAPEAKE DR., SUITE 208
SAN DIEGO, CA 92123
(619) 560-1468
DATE: 2- APPLI
-flJURISDICTI
JURISDICTION: CARLSBAD TPL.N
DFILE COPY ?LAN CHECK NO: \_Q4 SET:jups
(--.DESIGNER PROJECT ADDRESS: IVA kar(f,L)0LI A
PROJECT NAME: .M' 4. o -
The plans transmitted herewith have been corrected where
necessary and substantially comply with the jurisdiction's
building codes.
The plans transmitted herewith will substantially comply
with tne jurisdiction's -builang codes when minor deficien-
cies identified are resolved and checked by building department staff.
The plans transmitted herewith have significant deficiencies D identified on the enclosed check list and should be corrected
and resubmitted for a complete recheck.
Fj The check list transmitted herewith is for your information.
I//A The plans are being held at Esgil Corp. until corrected
plans are submitted for recheck.
The applicant's copy of the check list is enclosed for the
jurisdiction to return to the applicant contact person.
The applicant's copy of the check list has been sent to:
10 1 E r Sri
Oc C,°zo4
Esgil staff did not advise the applicant contact person that
plan check has been completed ,o rH43
J Esgil staff did advise applicant that the plan check has
been completed. Person contacted:
Date contacted: Telephone
REMARKS:
I- ? (o
By: M Enclosures(?. CO L Lt ESGIL CORPORATION i1D
11Gk D E] RN (3 DM
FOREWORD: PLEASE READ
JURISDICTION: CITY OF CARLSBAD
TO:
() p*a4 (Z3
(i(D' M+CUOLt P, ftX'
to 4-
HI: -
Plan check is limited to technical requirements
contained in the Uniform Building Code, Uniform
Plumbing Code, Uniform Mechanical Code, National
Electrical Code and state, laws regulating energy
conservation, noise attenuation and access for the
handicapped. The plan check is based on
regulations enforced by the Building Inspection
Department. You may have other corrections based
on laws and ordinances by the Planning Department,
Engineering Department or other departments.
Present California law mandates that residential
construction comply with Title 24 and the following
model codes:
1988 UBC (eff. 1/1/90)
1988 UPC (eff. 1/1/90)
197 NEC (eff. 10/28/87)
1988 UMC (eff. 1/1/90)
The above regulations apply to residential
construction, regardless of the code editions
adopted by ordinance.
The circled items listed need clarification,
modification or change. All items have to be
satisfied before the plans will be in conformance
with the cited codes and regulations. Per Sec.
303(c), 1988 Uniform Building Code, the approval of
the plans does not permit the violation of any
state, county or city law.
To Sneed um the recheck process, note on this list
(or a copy) _where each correction _itemhasbeen
addressed i.e.. plan sheet, specification, etc. Be
sure to enclose the marked up list when you submit
the revised plans .
PLAN CORRECTION SEM
CITY OF CARLSBAD
SINGLE FAMILY AND DUPLEX DWELLINGS
Date plans received by jurisdiction:
Date plans received by Esgil Corporation:
'E (i
Date initial plan check completed:
By: IM
Applicant contact person:
'So 5,4,N Telephone:
NOTE: PAGE NINBS ARE NOT IN SFX(Th7CE AS PAGES HAVING NO I'fl1S NEEDING CORRECTIONS WE D.Vl).
List No. 12, Carlsbad Single Family DweliTiid Duplex With1Tpplements. (1988
PLANS Show on the title sheet all structures, pools,
j walls, etc. included under this application.
1. Please make all corrections on the original Q 7 Any portion of the project shown on the site 4 tracings and submit two new sets of prints, and / plan that is not included with the building L any original plan sets that nay have been / permit application filed should be clearly
returned to you by the jurisdiction, to: identified as "not included."
Esgil Corporation, 9320 Chesapeake Drive, / Clearly show if the lower level is a basement
Suite 1/208, San Diego, California 92123, or a story, based on the definitions in
1 (619) 560-168. Sections 403 and 420. Plot the finish grade
(as defined) on the elevations and dimension
2 Please make all corrections on the original the distance to the floor above, for story
tracings and submit two new sets of prints, , determination.
and any original plan sets that may have been / returned to you by the jurisdiction, to: l/. On the cover sheet of the plans, specify any
/ items requiring special inspection, by way of
The jurisdiction's building department. the following:
() Indicate on the Title Sheet of the plans, the REQUIRED SPECIAL INSTRUCTIONS name of the l egal c"rner ai-d-- name of person In addition to the'regular inspections, the
responsible for the preparation of the plans. following checked items will also require Section 302(a)7. Special Inspection in accordance with Sec 306
of the Uniform Building Code.
G All sheets of plans must be signed by the
j person responsible for their preparation. 11Th REQ. IF REMARKS / (California Business and Professions Code). CHECKED
SOILS COMPLIANCE ® Plans, specifications and calculations shall be PRIOR TO
j signed by the California state licensed FOUNDATION INS?. /1 engineer or architect responsible for their
preparation, for plans deviating from STRUCTURAL CONCRETE
conventional wood frame construction. Specify OVER 2500 PSI
expiration date of license. (California
Business and Professions Code). PRESTRESSED STEEL
Specify on the Title Sheet of the plans the FIELD %'ELDING
gross floor area of each element of this
project including dwelling, garage, carport, HIGH STRENGTH BOLTS
patio, deck and balcony. Section 302(d).
EXPANSION ANCHORS 7. Provide a statement on the Title Sheet of the
j plans that this project shall comply with Title SPECIAL MASONRY
7 24 and 1988 UBC, UMC and UPC and 1987 NEC.
/ SPRAYED ON FIRE
Submit fully dimensioned plot plan drawn to PROOFING
scale showing location, size, and use of all
existing and proposed structures on the lot. PILES/CAISSONS
Identify property lines and show lot dimensions
and all easements. Show location of all cut or DESIGNER-SPECIFIED fill slopes. Show finish floor elevations and
show elevations of adjacent finish grade. OTHER Show drainage patterns with minimum slopes.
Section 302(d).
f FIRE PROIEX:TION 7. Indicate distance from property lines to r proposed building. Section 302(d). 1$. Exterior walls closer than 3 feet to property
/ lines shall be one-hour rated construction and
have no openings. Table 5-A.
L
12/11/89 2
1~_
Exterior walls closer than 3 feet to a property 23 Openable window area in habitable rooms must
line shall have 30 inch parapets when the floor 't' be 1/20 of the floor area and a minimum of S area per floor exceeds 1,000 square feet.! square feet. In bathrooms, laundry rooms and Section 1709. similar rooms 1/20 of area is required and
minimum is 1.5 sq. ft. Section 1205 (a). Projections, including eaves, may not extend
more than 12 inches into the 3 foot setback
from the property line. Section 1710.
Eaves over required windows shall be not less
than 30 inches from the side and rear property
lines. Section 504. i
Plastic skylights shall not be installed wi4ifl1
that portion of a roof located withif a
distance to property line where opening in
exterior walls are prohibited or required tb be
protected. Section 5207 (a) 7. (p
Projections, including eaves, shall be onnee hour fire-resistive construction, heavy timber
or of noncombustible material if they project
into the 3' setback area from the property line. Section 1710.
Show location of permanently wired smoke
detector:
Centrally located in corridor or area
giving access to sleeping rooms.
On each story.
C. In the basement.
When sleeping rooms are upstairs, at the
upper level in close proximity to the
stair.
In rooms adjacent to hallways serving
bedrooms, when such rooms have a ceiling
height 24 inches or more above the ceiling
height in the hallway.
NOTE: Detectors shall sound an alarm audible in
j sleeping areas of the unit. Section 1210
When the valuation of a room addition or repair
exceeds $1,000, or when sleeping rooms are
created, smoke detectors shall be provided at
existing bedrooms per item 19 above. Section
1210.
/ Habitable rooms, other than kitchens, shall
contain at least 70 square feet of floor area.
At least one room shall have not less than 120
square feet of floor area. Section 1207 (b).
Window area must be at least 1/10 of the floor
area and a minimum of 10 square feet per
Section 1205 (a). Appears to be deficient in
A AM
1. At least 1/2 of the common wall must be open
' and have an opening not less than 25 sq. ft.
nor one tenth of the floor area of the
1 interior room if light and ventilation is
being supplied from an adjacent room. Section
_J 1205 (a).
2 . Required windows shall not open into a roofed
. porch unless the ceiling height is at least 7
) feet, the longer side is at least 6591. open, [ and the porch abuts a street, yard or court.
Section 1205 (a).
21. Provide mechanical ventilation capable of
/ providing five air changes per hour in
bathrooms, water closet compartments, laundry
rooms and similar rooms if required openable
windows are not provided. Section 1205 (c).
Show discharge point for exhaust air to be at
I least 5 feet from any mechanical ventilating
intake. Section 1205(c).
Ductless fans cannot be used in bathrooms if a
/ tub or shower is present. Section 1205(c).
7. No habitable room, other than a kitchen, shall C be less than 71 0" in any dimension. Section 1207 (c).
4. Show that ceiling height for habitable rooms
I is a minimum of 7'61'. Section 1207 (a).
3J' Show ceiling height for laundry rooms,
/ hallways, corridors, and bathrooms is a
minimum of 7'011. Section 1207 (a).
Dimension on the plans the 30" clear width for
/ water closet compartments and 24" clearance in
front-of water closet. Section 511 (a).
3 Specify safety glazing for glazing in
/ hazardous locations such as glass doors,
glazing adjacent to doors and glazing adjacent
to walking surfaces. Section 5406.
3/ Glazing, in the same wall plane as a door,
/ must be safety glazing if within 12" of the
door and less than 60" above the walking
surface, unless the glazing is leaded or
faceted glass. Section 5406 (d) 6.
3~ Glazing in shower and tub enclosures shall be
tempered, laminated or approved plastic
(including windows within 5 feet of tub or
shower floor). Section 5406 (d) 5.
ei:,i;7,
(CL11P-ç ( i%JC4
2/12 /90 3
L-_ o -iijc-- (
,\ -O VA S TRVkT'ii2 i
36. Sleeping rooms shall have a window or exterior
door for emergency exit. Sill height shall not
exceed 44" above the floor. The window must
have an openable area of at least 5.7 square
feet with the minimum openable width 20" and
the minimum openable height 24". Section 1204.
Basements in dwelling units shall comly with
/ the above (even if not designated as sleeping
rooms). Section 1204.
31. Walls and floors separating units in a duplex
I shall be of one-hour fire-resistive
'construction. Section 1202(b).
3j A mezzanine is an intermediate floor and may
/ not have a floor area exceeding 33 1/3 percent
of the total floor area in the room below. The
mezzanine floor must have a clear height of 7
'feet, above and below, and must have the long
side open to the room below except for posts
and protective walls or railings not exceeding
42" in height. Section 1716.
4j The loft you show does not comply as a
I mezzanine floor and is, by Uniform Building
Code definition, a story. Section 1716.
E)CITS, STAIRWAYS, AND RAILINGS
Floors above the second story shall have not
f less than 2 'exits. Exceptions: 1. Occupied
roofs may have one exit if such occupied areas
are less than 500 square feet and located no
higher than immediately above the second story.
2. When the third floor within a unit does not
exceed 500 sq. ft., only one exit need be
provided. Section 3303(a).
Required exit doorways shall be not less than
/ 36" in width and not less than 6'8" in height,
and shall be capable of opening at least 90
degrees. Section 3304 (f).
/3. Provide 36" high protective railing for
porches, balconies, and open sides of stair
landings. Openings between railings shall be
less than 6". Section 1711.
Show how guardrail connection details are
/ adequate to support 20 pounds'per lineal foot
at a right angle to the top rail. Table 23-B.
4 . Provide stairway and landing details. Section
/ 3306 (b), (c) and (p).
Maximum rise is 7" and minimum run is
11". When the stairs serves less than 10
occupants, or serves an unoccupied roof,
rise may be 8" maximum and run 9"
minimum.
Minimum headroom is 61 -811.
Minimum width is 36".
46. All handrails per Section 3306 (.j), shall
satisfy the following:
() Provide handrail for stairways with 4 or
more risers.
b Handrail shall be 34" to 38" above the
nosing of treads.
The handgrip portion of handrail shall be
not less than 1 1/2", nor more than 2" in
cross-sectional dimension.
Every stairway landing shall have a dimension,
/ measured in the direction of travel, at least
equal to the stairway width. Such dimension
need not exceed 36 inches. Section 3306 (g),
3304 (j).
An interior door may open inward at the top
7 step of a stairway provided the top step is
not more than 7 1/2" lower than the floor
level. Section 3304 (i).
Provide details of winding stairway complying
/ with Section 3306 (d):
Minimum tread is 6 inches at any point
and minimum 9 inches at a point 12 inches
from where the treads are narrowest.
Maximum rise is 8 inches.
C. Minimum width is 36 inches.
5/10/90 4
Provide spiral stairway details, per Section / 3306 (f):
Minimum run is 7-1/2 inches measured at a
point 12 inches from where the treads are
the narrowest.
Maximum rise is 9 1/2 inches. Maximum
clear opening between risers is 6 inches.
C. Minimum headroom is 6 feet 8 inches
d. The tread must provide a clear walking
area measuring at least 26 inches from the
outer edge of the supporting column to the
inner edge of the handrail.
Spiral stairways may not be used for required I exits when the area served is greater than 400
sq. ft. Section 3306 (f).
57( Provide I.C.B.0. Research Report and number for I metal stairway, or submit plans and
calculations and approved fabricator registered
with the building department or note that the
stairway fabrication plans shall be submitted
to and approved by the building official prior
/ to installation.
5/. Exterior stairways shall not project into the 3
/ foot setback from the property lines. Section
/ 3306 (n).
5/. The walls and soffits of the enclosed usable
/ space under interior stairs shall be protected
on the enclosed side as required for one-hour
fire-resistive construction. Section 3306 (m).
5/. Within units, show that corridors have a / minimum width of 36 inches. Section 3305 (b).
ROOF)
5 Specify roof slope.
0'. Roof slope is not adequate for roof type
specified. Table 32-B,C,D and E.
sl. Specify roof material and application. Chapter
I 32.
51. Specify I.C.B.0. or U.L. approval number for
roof materials not covered in U.B.C., e.g.,
tile, etc. Section 107.
,Ø. Specify minimum 1/4 inch per foot roof slope
for drainage or design to support accumulated
water. Section 3207 (a) and Section 2305 (f).
Show roof drains and overflows. Section 3207.
Provide skylight details to show compliance
( with Sections 3401 and 5207 or provide
I.C.B.0. approval number.
/3. Plastic skylights must be separated from each
other by at least 4 feet. Section 5.07 (a) 6.
Show attic ventilation. Minimum vent area is
/ 1/150 of attic area or 1/300 of attic area if
at least 50% of the required vent is at least
3 feet above eave vents or cornice vents.
Show required area and area provided.
Section 3205 (c).
MASONRY
çI5. Provide fireplace construction details or note
/ construction to be per attached fireplace
standard drawing. Chapter 37.
Show anchored veneer support and connections
/ attached to wood in Seismic Zones 3 and 4,
comply with Section 3006 (d)l and Section 2515
(a). Show ties and #9 wire in horizontal
joints.
6/. Show height and construction details of all
masonry walls. Chapter 24.
6 Show floor and roof connections to masonry
/ walls. Connection shall resist 200 pounds per
lineal foot or the actual design load,
whichever is greater. Cross grain tension or
bending in wood ledgers is not permitted.
/ Section 2310.
61. Show a minimum 2" air space and flashing
between planter and building walls.
Section 2516 (c) 7.
GARAGE AND CARPORTS
Garage requires one-hour fire protection on
the garage side of walls and ceiling common to
the dwelling. Table 5-B, Section 503 (d).
All elements supporting floor above garage,
including walls supporting floor joists, must
have one-hour fire-resistive protection on the
garage side. Section 503 (b)
Show 1 3/8" solid core self-closing door for
openings between garage and dwelling. Section
503 (d).
Garages are not permitted to open into a room f used for sleeping purposes. Section 1104.
GD
12/18/90 S
9,1. If required, show size, imbedment and location
of hold down anchors on foundation plan.
Section 302 (d).
If hold downs are required, note on plan that
hold down anchors must be tied in place prior
to foundation inspection. Section 305 (e) 1.
24. Show adequate footings under all bearing walls
and shear walls. Section 2907 (b).
/s. Show on the plans stepped footings for slopes
steeper than 1:10. Section 2907 (c).
94. Show minimum 18" clearance from grade to bottom
/ of floor joists and minimum 12" clearance to
bottom of girders. Section 2516 (c).2.
Show pier size, spacing and depth into
undisturbed soil. Table 29-A.
Show minimum underfloor access of 18" x 24".
Section 2516 (c).
/99. Show minimum underfloor ventilation equal to 1
sq. ft. for each 150 sq. ft. of underfloor
area. Openings shall be as close to corners as
practicable and shall provide cross ventilation
on at least two approximately opposite sides.
Section 2516 (c) 6.
/wall
1Show wall bracing. Every exterior wood stud
and main cross-stud partition shall be
braced at each end at least every 25 feet of
length with 1 x 4 diagonal let-in braces or
/ equivalent. Section 2517 (g) 3, Table 25-V.
Al. In 2-story buildings, shear panels at the first Z story (at least 48 inches in width) shall be
located at each end or as near thereto as
possible and comprise at least 25 percent of
the linear length of the wall, or provide
design. Section 2517(g)3, Table 25-V.
1/2. Note cross bridging or blocking. Floor joists
/ and rafters 12" or more in depth shall be
supported laterally by bridging at intervals
not exceeding 8 feet, unless both edges are
held inline. Sec. 2506 (h), 2517 (d) 6.
43. Show blocking at ends and at supports of floor L joists, rafters and trusses at exterior walls.
/ Section 2517 (d) 3, 2517 (h) 6.
lot. Bearing partitions, perpendicular to joists, J shall not be offset from supporting girders,
beams, walls or partitions, more than the depth
of the joist. Section 2517 (d) 5.
Show rafter ties. Rafter ties shall be spaced
not more than 4 feet on center and be just
above the ceiling joists, where rafters and
ceiling joists are not parallel. Section 2517
/ (h) 4.
1/6. Show rafter purlin braces to be not less than
' 65 degrees to the horizontal.
Section 2517 (h) 5.
i/i. Show double top plate with minimum 48" lap
( splice. Section 2517 (g) 2.
]4'8. Show nailing will be in compliance with Table
' 25-Q.
y 9. Show or note fire stops at the following
locations per Section 2516 (f):
In concealed spaces of stud walls and
partitions, including furred spaces, at
the ceiling and floor levels and at 10
foot intervals along the length of the
wall;
At all interconnections between concealed
vertical and horizontal spaces such as
occur at soffits, drop ceilings and cove
ceilings;
C. In concealed spaces between stair
stringers at the top and bottom of the
run and between studs along and inline
with the run of stairs if the walls under
the stairs are unfinished; and
d. In openings around vents, pipes, ducts,
chimneys, fireplaces and similar openings
which afford a passage for fire at
ceiling and floor levels, with
noncombustible materials.
1 . In duplexes, draft stops shall be provided in
floor-ceiling assemblies and attics in line
with walls separating units and separating
units from common areas.
Show stud size and spacing. Maximum allowable
/ stud heights: Bearing wall: 2 x4 and 2 x 6
max. 101 ; Non-bearing: 2 x 4 max. 141 , 2 x 6
max. 20'. Table 25-R-3.
1. Studs supporting two floors, a roof and
ceiling must be 3 x 4 or 2 x 6 at 16" o.c.
Table 25-R-3.
(i Note on A.I.T.C. Certificate of Compliance for
'>-' glued laminated wood members shall be given to
/ the building inspector prior to installation.
Section 2505.
2/12/90 7
16/Show . that water heater is adequately braced to
resist seismic forces, when not connected by
) rigid pipe. UMC Section 504(d).
l. Show shower stall can accommodate a 30" circle
/ and has a minimum floor area of 1,024 sq. in.
UPC 909 (d).
l. Provide clothes washer hook-up for each unit.
/
/.floor/ceiling
Title 24, Part 3.
NOISE INSULATION (DUPLEKES)
1Show details of duplex common (party) walls
assemblies to achieve a Sound
Transmission Class (SIC) rating in walls of 50
decibels and 'an Impact Insulation Class (IIC)
/ rating on floor/ceiling of 50 decibels.
/ Title 24.
Show how penetrations of assemblies for piping,
electrical devices, recessed cabinets,
bathtubs, soffits, or heating ventilating, or
exhaust ducts shall be sealed, lined, or
insulated to maintain required sound
/ transmission rating. Title 24.
Provide insulation in walls and ceiling to
/ achieve' STC of 50 between garage and living
area if garage use is not controlled by
resident. Title 24.
1'. Provide plans, calculations and worksheets to
/ show compliance with current energy standards.
The regulations require a properly completed
and properly signed Form CF-1R to be either
imprinted on the plans, taped to the plans or
"sticky backed" on the plans, to allow the
building inspector to readily compare the
actual construction with the requirements of
/ the approved energy design.
frl'O. All energy items shown on the plans must be in ' agreement with the information shown on the
properly completed Form CF-1R.
17 . Specify on the building plans all of the
mandatory energy conservation requirements as
listed on the enclosure titled, "Mandatory
Energy Conservation Requirements".
. Show the make, model and efficiency of the //2
space heating (or cooling) system and provide
heat loss calculations if the output exceeds
45,000 BTU/Hr.
For room additions, show that the glazing area
' of the addition does not exceed 16% of the
/ newly-conditioned floor area, plus glazing
/ removed or relocated due to the addition.
/4- Provide fluorescent general lighting in
kitchen(s) per CAC, Title 24, 2-5352(3).
/ CARLSBAD S.F.D. & DUPLEX SUPPW(ENT
17/. Energy conservation design should be for Zone
7.
l7. Floor drains must have auto-prime (city
policy).
1/7. Note exhaust fans cannot be ductless type
/ (city policy).
'L78. New residential units must be pre-plumbed for
future solar water heating. Note "two roof
jacks must be installed" where the water
heater is in the one story garage and directly
below the most south facing roof (City
/ Ordinance No. 8093).
Note "two 3/4" copper pipes must be installed
" to the most convenient future solar panel
location when the water heater is not in a one
story garage and is not directly below the
most south facing roof. (City Ordinance No.
8093).
All piping for present or future solar water
I heating must be insulated when in areas that
are not heated or cooled by mechanical means
(city policy).
)41. Incorporate the waterproofing details, on the
attached Policy 80-8, where interior living
space occurs below grade at the masonry
wall(s).
18 Show on the Title Sheet on the plans, the
information required by the attached
Developmental Services Sheet 112383.
10. All new residential buildings, including
/ additions, require a soils report. Please
/ submit two copies. Exception: If a room
addition is limited to one story and 1000 sq.
ft. in area, then a soils report is not
required. Esgil Corporation will advise the
City to place their soils notice stamp on the
plans.
Heavy timber framing, minimum 6" x 10" beams
/ and minimum 8" x 8" post, for the structural
/ beam and column supporting the fire separation
1 between the garage and living area above, is
acceptable if shown on the plans. (city
policy).
2/26/90 10
18/All structures require a Class B roof covering, Enclosures:
except room additions. If a room addition
covers all of the existing building (2nd story 1.
addition), then the above exception doesn't
/ apply.
2.
l.
I
City Ordinance 9792 requires two parking
spaces/unit with clear area of 201 x20' i.e. no
/ washing machines, etc. Show compliance. 3.
1j7. All chimneys attached to any appliance or I fireplace that burns solid fuel shall be
equipped with an approved spark arrester. The
net free area of the spark arrester shall be
not less than four times the net free ara of
the outlet of the chimney. The spark arrester
screen shall have heat and corrosion resistance
equivalent to 12 gauge wire, 19 gauge
galvanized wire or 24 gauge stainless steel.
Openings shall not permit the passage of
spheres having a diameter larger than 1/2-inch
and shall, not block the passage of spheres
having a diameter of less than 3/8-inch.
MISELLANJS
Please see additional corrections, or remarks,
on the following page.
j l To speed up the recheck process, note on this
list (or a copy) where each correction item has 4 been addressed, i.e., plan sheet, note or
/ detail number, calculation page, etc.
190 Please indicate here if any changes have been
made to the plans that are not a result of
corrections from this list. If there are other
changes, please briefly describe them and where
they are located in the plans.
Have changes been made to the plans not
-resulting from this correction list? Please
check.
No
The City of Carlsbad has contracted with Esgil
Corporation located at .9320 chesapeake Drive, Suite
208, San Diego, California 92123; telephone number
619/560-1468, to perform the plan check for your
project. If you have any questions regarding these
plan check items, please contact__________________
at Esgil Corporation. If you have any questions
regarding City Building permit procedures, please
contact Carter Darnell at the City of Carlsbad, 2075 Las Palmas Dr., telephone 619/438-1161.
Thank you.
rt- L5 tô—rr 2.I 'S
2/14/90
Date il19 I q( Jurisdiction CARLSBAD
Prepared byt
—rc) VALUATION AND PLAN CHECK FEE
Bldg. Dept.
Esgil
PLAN CHECK NO. \-
BUILDING ADDRESS
APPLICANT/CONTACT -Sj S to, \) PHONE NO.
-
BUILDING OCCUPANCY -3 DESIGNER PHONE______________
TYPE OF CONSTRUCTION .._V-_ CONTRACTOR PHONE
BUILDING PORTION BUILDING ARak VALUATION
MULTIPLIER
VALUE
-po L-1UjL)6 -ioo ='a
___ 1• _________ ot_
I
4o'5
_
Air Condjtionjnz
Commercial S
-
Residential
Res. or Comm.
-
Fire Sprinklers -
I S
-
TotalValue
Buildirid Permit Fee. $_ 4'_4 00
Plan Check Fee S 3 (O $
COMHCNTS S
.
S
S
SHEET OF 12/87
3.
I O'12.OW.
BUILDING PLANCHECK
ENGINEERING CHECKLIST
DATE: 2%AAlc3I
PLANCHECK NO. 9 1 - OO4
H 1 2 3 1105 MiNGL 14 \/F-
S N R
T D D 205-20-34
ITEM COMPLETE
ITEM INCOMPLETE
NEEDS YOUR ACTION
ITEM SELECTED
ic C C
H H H
E E E
LIE
PROJECT ID:
LEGALREQUIREMENTS
SitePlan
1. Provide a fully dimensioned site plan drawn to scale.
Show: north arrow, property lines, easements, existing and
proposed structures, streets, existing street improvements,
right-of-way width and dimension setbacks.
Show on site plan: Finish floor elevations, pad
elevations, elevations of finish grade adjacent to
building, existing topographical lines, existing and
proposed slopes, driveway with percent (%) grade and
drainage patterns.
cQ:-r Provide legal description and Assessors Parcel Number.
DiscretionaryApprovalCompliance
No Discretionary approvals were required.
Project complies with all Engineering Conditions of
Approval for Project No.________________
Project does not comply with the following Engineering
Conditions of Approval for Project No.___________________
Conditions complied with by: Date:
FieldReview
Field review completed. No issues raised.
VO F-~ Field review completed. The following issues or
discrepancies with the site 'plan were found,:
E E A. Site lacks adequate public improvements
E E E B. Existing drainage improvements not shown or in
conflict with site plan.
E E C. Site is served by overhead power lines.
P:\D0CS\M1SF0RMS\FRM0010.DH REV. 02/27/91
D. Grading is required to access site, create pad or
provide for ultimate street improvement.
El E. Site access visibility problems exist. Provide onsite
turnaround or engineered solution to problem.
El El El F. Other:_____________________________________________
Dedication Requirements
El 9. No dedication required.
El El El 10. Dedication required. Please have a registered Civil
Engineer or Land Surveyor prepare the appropriate legal
description together with an 8½" x 11" plat map and submit
with a title report and the required processing fee. All
easement documents must be approved and signed by owner(s)
prior to issuance of Building Permit. The description of
the dedication is as follows:___________________________
Dedication completed, Date By:_______
Improvement Requirements
El El El 11. No public improvements required. SPECIAL NOTE: Damaged or
defective improvements found adjacent to building site must
be repaired to the satisfaction of the City inspector prior
to occupancy.
El El 12. Public improvements required. This project requires
construction of public improvements pursuant to Section
18.40 of the City Code.
51 StIEJIv /Lc* fJtJTLE
Improvement plans signed, Date: by:
P:\D0CS\MISF0RI4S\FRM0010.DH REV. 02/27/91
IJbOL!tJD1'J OF OJ€DS4E40 011U11S (JL? 13. Improvements are required. Construction of the public
improvements may be deferred in accordance with Section
18.40 of the City Code. Please submit a letter requesting
deferral of the required improvements together with a
recent title report on the property and the appropriate
processing fee so we may prepare the necessary Future
Improvement Agreement. The Future Improvement Agreement
must be signed, notarized and approved by the City prior to
issuance of a Building Permit.
Future Improvement Agreement completed, Date:
By:_______________________
E E E 13a. Inadequate information available on site plan to make a
determination on grading requirements. Please provide more
detailed proposed and existing elevations and contours.
Include accurate estimates of the grading quantities (cut,
fill, import, export).
E/0 0 14. No grading required as determined by the information
provided on the site plan.
E D 0 15. Grading Permit required. A separate grading plan prepared
by a registered Civil Engineer must be submitted for
separate plan check and approval through the Engineering
Department. NOTE: The Grading Permit must be issued and
aradina substantially complete and found acceptable to the
City Inspector prior to issuance of Building Permits.
Grading Inspector sign off. Date: by:
Miscellaneous Permits
Right-of-Way Permit not required.
PQ Right-of-Way Permit required. A separate Right-of-Way
Permit issued by the Engineering Department is reguired for_ the following: CO 1JJT1OILJ
9MM 18. Sewer Permit is not required.
E E E 19. Sewer Permit is required. A sewer Permit is required
concurrent with Building Permit issuance. The fee required
is noted below in the fees section.
20. Industrial Waste Permit is not required.
P:\D0CS\MISF0RMS\FRM0010.DH REV. 02/27/91
.Ei E 21. Industrial Waste Permit is required. Applicant must
complete Industrial Waste Permit Application Form and
submit for City approval prior to issuance of a Building
Permits. Permits must be issued prior to occupancy.
Industrial Waster Permit accepted -
- Date: By:
Fees Required
N/ 27. Park-in-Lieu Fee
Quadrant: Fee per Unit:
Total Fees:_____
O N/A 23. Traffic Impact Fee
Fee Per Unit:_________________
NIA 24. Bridge and Thorough fare Fee
Fee Per Unit:______________
Total Fee:
Total Fee:
oJJA 25.
o N/A 26.
DWIA 27.
Public Facilities Fee required.
Facilities Management Fee Zone: Fee:
Sewer Fees Permit No. EDU's
Benefit Area:______________ Fee:
0 i.s.1/V 28. Sewer Lateral Required:
Fee:__________________
29. REMARKS: =200bF COP'( O17- VESI&A DEED SO
trnE T-MPeDVEMffAJr 44!EMiur C,Qt') BE
2v
P.EPAQZb
Eg2S lFcfiaD -fW) TSrJ AQO
BEfr-( M TEt2Sb'J CUQYr AWIIJR.c, PRffE aPi'
OP TITLE Pt1C' oO.- V1F&T&)9 OFE() V)iMI FiFT7..E
As Jr O AJ J CALL O t )t 0 AJ SiTE Ptf'.J
ENGINEERING AUTHORIZATION TO ISSUE PERMIT
cO,3S3u)S,''COUCUTI S4DSWAUX P.- 9hb,S.12.D.
G-1 'Mrfl-J % S.t...oP
BY: DATE:
P:\D0CS\MISF0RMS\FRM0010.DH REV. 02/27/91
NJOBETD C F[21ETZE.
ppM ELI;FE-raE.
PLANNING CHECKLIST
Plan Check No. 97- A O Y Address 1165- "-ii it..ou,ij ,4
Planner (JpJ 4v" &'L Phone 438-1161 ext.
(Name)
I APN:
40 W Type of Project and Use /,vóur ,2-. 4ØØi,'o"
Zone (2-( 7S2& Facilities Management Zone
CIA P^ Legen
40 5U U Item Complete
CL CL CL
Item Incomplete - Needs your action
1, 2, 3 Number in circle indicates plancheck number where deficiency was
identified
0 0 Environmental Review Required: YES N0 TYPE
DATE OF COMPLETION:
Compliance with conditions of approval? If not, state conditions which require action.
Conditions of Approval
0 Discretionary Action Required: YES - NO TYPE
APPROVALJRESO. NO. DATE:
PROJECT NO.
OTHER RELATED CASES:
Compliance with conditions of approval? If not, state conditions which require action.
Conditions of Approval
e I M/ California Coastal Commission Permit Required: YES ..& NO -
DATE OF APPROVAL:
San Diego Coast District, 1333 Camino Del Rio South, Suite 125, San Diego, CA. 92108-3520
(619) 297-9740
Compliance with conditions of approval? If not, state conditions which require action.
Conditions of Approval
E Landscape Plan Required: YES ___- NO (
See attached submittal requirements for landscape. plans
Site Plan:
Provide a fully dimensioned site plan drawn to scale. Show: North
arrow, property lines, easements, existing and proposed structures,
streets, existing street improvements, right-of-way width and
dimensioned setbacks.
Show on Site Plan: Finish floor elevations, elevations of finish grade
adjacent to building, existing topographical lines, existing and proposed
slopes and driveway.
3.
'6n 4.
Zoning:
1. Setbacks:
Front:
Int.tide:
Street Side:
Rear:
Lot coverage:
Height:
Parking:
Required 20 Shown
Required 2z Shown
Required A Shown Ø
Required / ','. 1 Shown 23'
Required Shown 2r%
Required _____ Shown
Spaces Required 2_— Shown •-
Guest Spaces Required _____ Shown
4
Provide legal description of property.
Provide assessor's parcel number.
0 0 Additional Comments
OK TO ISSUE AND ENTERED APPROVAL INTO COMPUTER /1 DATE 6- w-
PLNCK. FRM
' CERTIFICATION OF COMPLIANCE
CITY OF CARLSBAD Plan Check No.
DEVELOPMENT PROCESSING SERVICES DIVISION
2075 LAS PALMAS CARLSBAD, CA 92009
(619) 438-1161
This form shall be used to determine the amount of school fees for a project and to verify
that the project aplicant has complied with the school fee requirements. No building
permits for the projects shall be issued until the certification is signed by the
appropriate school district and returned to the City of Carlsbad Building Department.
CH RICT:
- Carlsbad Unified - San Marcos Unified
Carlsbad, CA 92009 (434-0610)
801 Pine Avenue IUAA1)i 1210 West San Marcos Blvd.
San Marcos, CA 92069 (744-4776)
Encinitas Union Elementary San Dieguito Union High School
189 Union Street 710 Encinitas Boulevard
Encinitas, CA 92024 (944-4306) Encinitas, CA 92024 (753-6491)
Project Applicant: AP
Project Address: II ( '~ /'l'1'49
RESIDENTIAL: SQ. FT. of living area Number of dwelling units
SQ. FT. of covered area SQ. FT. of garage area
COMMERCIAL! IN SQ. FT. AREA
Prepared By Date
FEE CERTIFICATION
(To be completed by the School District)
Applicant has complied with fee requirement under Government Code 53080
Project is subject to an existing fee agreement
Project is exempt from Government Code 53080
Final Map approval and construction started before September 1, 1986.
(other school fees paid)
Other
Residential Fee Levied: based on sq. ft.@
Comic! ndust Fee Levied: $____________ based on sq. ft.@
Scho1 District Official tle
A ('~ .3~jk . a
i
(
Da
AB 2926 and SB 201 fees are capped at $1.58 per square foot for residential.
AB 2926 is capped at $.26 per square foot for commercial/industrial.
City of Carlsbad
.]ilIi.IuII1I([3yzJriT.I.,rjpI1
SCHOOL FEES
Please fill out the enclosed form and take it to the appropriate
school district.
Once you have paid the school fee, a school official has signed
the school fee form, and all other plan; check requirements have
been met, a building permit can be issued. The City of Carlsbad
will not issue any building permit without a completed school fee
form.
* I I
BUILDING DEPARTMENT
dc -
enc.
2075 Las Palmas Drive-Carlsbad, CaIiforn'. 92009-4859o(619) 438-1161